Schneider R9D87832, R9D87840, R9D87820, R9D87806, R9D87816 Installation Instructions

Resi9 RCBO 1P-Ns
en
R9D878pp
Installation
1
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
b Install this product in accordance with National Wiring Regulation. b Check compatibility with earthing system. Do not use this product on installations
which require double pole switching eg. IT or TT systems.
Failure to follow these instructions will result in death or serious injury.
All electrical equipment protected by Resi9 RCBO must be effectively earthed. Maximum, permissible earthing resistance is as follows:
Device Ue
230 Va 100 Ω
Click!
2
Maximum Earthing Resistance
1
Connection
2
NOTICE
INOPERABLE EQUIPMENT
b Do not bind the neutral cable for installation.
b Install the neutral cable straight between the Resi9 RCBO and
the main neutral terminal block.
Failure to follow these instructions can result in equipment damage.
Lin
1
Lin
FE
Nin
Nout Lout
5
4
Nout Lout
Testing
3
The installation, or part of it, is protected by devices which automatically switch off the supply if earth default develops. These devices should be tested periodically according to the local regulations, by pressing on the button marked "T".
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Test once a month each device by pressing on the button marked "T".
Failure to follow these instructions will result in death or serious injury.
The devices should switch off the supply immediately, and should then be switched on to restore the supply. If the devices do not switch off the supply when the button is pressed, seek expert advice.
NOTICE
HAZARD OF IMPROPER OPERATION
Do not use Test Button to switch OFF RCBO.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
N
2
3
FE
Main Neutral terminal block
Main Earth terminal block
Schneider Electric Industries SAS
35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex www.schneider-electric.com
HRB11382-00 1/1
Nin
2
Load
neutral
L
Load
phase
Periodic test:
In the absence of any regulation, Schneider Electric recommends the test should be carried out once a month.
Megger test:
Resi9 RCBO must be disconnected before any dielectric tests are carried out.
This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.
© 07-2013 Schneider Electric - All rights reserved.