While every precaution has been taken in the preparation of this document,
Schneider Electric SA assumes no liability for any omissions or errors i t may contain,
nor for any damages resulting from the application or use of the information herein.
The products and options descr ibed in th is document may be changed or modifi ed at
any time, either from a technical point of view or in the way they are operated.
Their description can in no way be considered contractual.
Before you begin_____________________________________________________________________________________________ 4
Documentation structure_______________________________________________________________________________________ 5
Introduction_________________________________________________________________________________________________ 6
Receipt _________________________________________________________________________________________________ 7
Installing the card in the drive________________________________________________________________________________ 7
Connection to the bus______________________________________________________________________________________ 8
Recommendations ________________________________________________________________________________________ 9
Controlling the address and speed of the bus __________________________________________________________________ 18
LEDs__________________________________________________________________________________________________ 18
Control-signal diagnostics__________________________________________________________________________________ 19
Communication faults_____________________________________________________________________________________ 22
Card fault ______________________________________________________________________________________________ 22
Software setup using PL7_____________________________________________________________________________________ 28
1755873 11/20093
Before you begin
Read and understand these instructions before performing any procedure with thi s drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand this manual before installing or operating the drive. Installation, adjustment, repair, and
maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts in this variable speed drive, including printed wiring boards, operate at line voltage. DO NOT TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA and PC or across the DC bus capacitors.
• Install and close all covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive:
- Disconnect all power
- Place a "DO NOT TURN ON" label on the variable speed drive disconnect
- Lock the disconnect in the open position
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15
MINUTES for the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure given
in the Installation Manual to verify that the DC voltage is less than 45 Vdc. The drive LEDs are not accurate indicators
of the absence of DC bus voltage.
Electric shock will result in death or serious injury
CAUTION
DAMAGED EQUIPMENT
Do not operate or install any drive that appears damaged.
Failure to follow this instruction can result in equipment damage.
41755873 11/2009
Documentation structure
Installation manual
This manual describes:
• How to assemble the drive
• How to connect the drive
Programming manual
This manual describes:
• The functions
• The parameters
• How to use the drive display terminal (integrated display terminal and graphic display terminal)
Communication parameters manual
This manual describes:
• The drive parameters with specific information (addresses, formats, etc.) for use via a bus or communication network
• The operating modes specific to communication (status chart)
• The interaction between communication and local control
• Configuration of the communication-specific parameters via the integrated display terminal or the graphic display terminal
• Diagnostics
• Software setup
• The communication services specific to the protocol
ATV58-58F/ATV71 compatibility manual
This manual describes the differences between the Altivar 71 and the Altivar 58/58F.
It explains how to replace an Altivar 58 or 58F, including how to replace drives communicating on a bus or network.
1755873 11/20095
Introduction
Presentation
The Profibus DP communication card (catalog number VW3 A3 307) is used to connect an Altivar 61 / 71 drive to a Profibus DP bus.
Data is exchanged in order to make use of all the Altivar 61 / 71 functions:
• Configuring functions
• Uploading adjustment parameters
• Control-signaling
• Monitoring
• Diagnostics
The card has a 9-pin female SUB-D connector for connection to the Profibus DP bus.
The connector and cable for connection to the Profibus DP bus must be ordered separately.
Notation
Drive terminal displays
The graphic display terminal menus are shown in square brackets.
Example:
The integrated 7-segment display terminal menus are shown in round brackets.
Example: (COM-).
[1.9 COMMUNICATION].
Parameter names are displayed on the graphic display terminal in square brackets.
Example:
Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.
Example: (LFF).
[Fallback speed]
Formats
In this manual, hexadecimal values are written as follows: 16#.
61755873 11/2009
Hardware setup
LEDs1
2
Addressing switches, also used to adjust
the drive process data exchange mode
3 9-pin female SUB-D connector
Receipt
• Check that the card catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damaged in transit.
Presentation
Installing the card in the drive
See the Installation Manual.
1755873 11/20097
Hardware setup
Pin 5
Pin 1
Pin 6Pin 9
9-pin female SUB-D
Profibus DP communication module: TSX-PBY100
TSX PREMIUM PLC
Altivar 61 / 71Altivar 61 / 71
Connector with line
terminator
490 NAD 911 03
Profibus DP connection cable
TSX PBS CA
p00
(100 or 400 m)
Intermediate
connectors
490 NAD 911 04
Connection to the bus
Connector pinout
The transmission interface conforms to the RS 485 standard and is electrically isolated from the drive.
DescriptionUsedCatalog number
ConnectorsWith line terminator490 NAD 911 03
Intermediate connection490 NAD 911 04
Intermediate connection and
connector port
Profibus DP bus connection cables
DescriptionLengthCatalog number
Profibus DP connection cables100 mTSX PBS CA 100
400 mTSX PBS CA 400
Example of connection:
490 NAD 911 05
81755873 11/2009
Hardware setup
Recommendations
• The user can select the data rate from a range of 9.6 kbps to 12 Mbps. Thi s select ion, made when s tarting up t he network, applies to all
the bus subscribers.
• The maximum segment length is in inverse proportion to the data rate.
Data rate (kbps)9.619.293.75187.550015003000600012000
Distance/segment (m)1200120012001000400200100100100
Repeaters can be used to cover greater distances.
• The bus ends with a line terminator at each end of the segment.
• Do not connect more than 32 stations per segment without a repeater, or more than 127 with a repeater.
• Keep the bus away from the power cables (clearance of at least 30 cm).
• If it is necessary for power cables to cross each other, be sure they cross at right angles.
1755873 11/20099
Configuration
Configuring the switches
Note:
A new configuration of the switches (address and mode) will only be appli ed after the next power on of the drive.
Selecting the operating mode
The switch furthest to the left is used to determine the type of cyclic exchanges performed by the drive:
• Switch 0 (OFF): Altivar 61 / 71 mode
• Switch 1 (ON): Altivar 58 compatibility mode
This manual only describes Altivar 61 / 71 mode. To find out about Altiva r 58 compat ib il ity mode , ref er to the ATV58 -5 8F/ATV7 1 migration
manual.
101755873 11/2009
Configuration
Coding the drive address
An Altivar 61 / 71 is identified on the bus by its address, coded between 0 and 126.
The address corresponds to the binary number given by position 0 (up/OFF) or 1 (down/ON) of the 7 switches on the right of the card.
The least significant bits are on the right.
The table below indicates the positions of the switches for all configurable addresses:
• Addresses 0 and 1 are usually reserved for the Profibus DP masters and must not be used to configure the Profibus DP address on an
Altivar 61 / 71.
• It is not advised to use address 126, which is incompatible with SSA service (Set Slave Address) and with some network configuration
softwares (Sycon, ...).
Examples:
Address 23
Address 89
The address can be checked via the display terminal (see Diagnostics section).
1755873 11/200911
Configuration
Control-signal configuration
There are a number of possible configurations. For more information, refer to the programmi ng and communication parameters manuals.
The configurations below are just some of the possibilities available.
Control via Profibus DP in I/O profile
The command and the target come from Profibus DP.
Control is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the command word.
Target 1 configurationNetwork card The target comes from Profibus DP.
Command 1 configurationNetwork card The command comes from Profibus DP.
Configuration via the graphic display terminal or the integrated display terminal:
Control via Profibus DP or via the terminals in I/O profile
The command and the target both come from Profibus DP or the terminal s. Input LI5 at the terminal s is used to switch between Pr ofibus DP
and the terminals.
Control is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the command word.
Target 1 configurationNetwork cardTarget 1 comes from Profibus DP.
Target 1B configurationAnalog input 1 on the terminals Target 1B comes from input AI1 on the terminals.
Target switchingInput LI5Input LI5 switches the target (1
Command 1 configurationNetwork cardCommand 1 comes from Profibus DP.
Command 2 configurationTerminalsCommand 2 comes from th e terminals.
Command switchingInput LI5Input LI5 switches the command.
Target 1B is connected to the functions (summing, PID, etc.) that remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
Control via Profibus DP or the terminals in Drivecom profile
The command and the target both come from Profibus DP or the terminals. Input LI5 at the terminals is used to switch between
Profibus DP and the terminals.
Control is in Drivecom profile.
from the same channel.
Configure the following parameters:
ParameterValueComment
ProfileCombined Drivecom profileThe run commands are in Drivecom profile, the command and t he target
Target 1 configurationNetwork cardTarget 1 comes from Profibus DP.
Target 2 configurationAnalog input 1 on the terminalsTarget 2 comes from input AI1 on the terminals.
Target switchingInput LI5Input LI5 switches the target (1
Configuration via the graphic display terminal or the integrated display terminal:
Control in Drivecom profile via Profibus DP and target switching at the terminals
The command comes from Profibus DP.
The target comes either from Profibus DP or from the termi nals. Input LI5 at the termina ls is used to switc h the target between Profibus DP
and the terminals.
Control is in Drivecom profile.
Configure the following parameters:
ParameterValueComment
ProfileSeparate Drivecom profileThe run commands are in Drivecom profile, the command and the target
Target 1 configurationNetwork cardTarget 1 comes from Profibus DP.
Target 1B configurationAnalog input 1 on the terminals Target 1B comes from input AI1 on the terminals.
Target switchingInput LI5Input LI5 switches the target (1
Command 1 configurationNetwork cardCommand 1 comes from Profi bus DP.
Command switchingChannel 1Channel 1 is the command channel.
Target 1B is connected to the functions (summing, PID, etc.) that remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
PZDs are configured by configuring the communication scanner.
The 8 periodic output variables are assigned by means of parameters nCA1 to nCA8. They are confi gured using the graphic display te rminal
[1.9 - COMMUNICATION] (COM-) menu and [COM. SCANNER OUTPUT] (OCS-) submenu.
via the
Note:
[COM. SCANNER OUTPUT] (OCS-) submenu defines the data (parameters nCA1 to nCA8) from the PLC to the drive.
p parameter with a value of zero does not designate any parameter in the drive. These 8 words are described in the table below:
An nCA
Parameter nameProfibus variableDefault assignment
[Scan. Out1 address] (nCA1) PZD1Command word (CMD)
[Scan. Out2 address] (nCA2) PZD2Speed target (LFRD)
[Scan. Out3 address] (nCA3) PZD3Not used
[Scan. Out4 address] (nCA4) PZD4Not used
[Scan. Out5 address] (nCA5) PZD5Not used
[Scan. Out6 address] (nCA6) PZD6Not used
[Scan. Out7 address] (nCA7) PZD7Not used
[Scan. Out8 address] (nCA8) PZD8Not used
The 8 periodic input variables are assigned by me ans of parameters nMA1 to nMA8. They a re configured u sing the graphic di splay terminal
[1.9 - COMMUNICATION] (COM-) menu and [COM. SCANNER INPUT] (ICS-) submenu.
via the
Note:
[COM. SCANNER INPUT] (ICS-) submenu defines the data (parameters nMA1 to nMA8) from the drive to the PLC.
An nMA
p parameter with a value of zero does not designate any parameter in the drive. These 8 words are described in the table below:
Parameter nameProfibus variableDefault assignment
[Scan. In1 address] (nMA1)PZD1Status word (ETA)
[Scan. In2 address] (nMA2)PZD2Output speed (RFRD)
[Scan. In3 address] (nMA3)PZD3Not used
[Scan. In4 address] (nMA4)PZD4Not used
[Scan. In5 address] (nMA5)PZD5Not used
[Scan. In6 address] (nMA6)PZD6Not used
[Scan. In7 address] (nMA7)PZD7Not used
[Scan. In8 address] (nMA8)PZD8Not used
Example of configuring PZDs via the graphic display terminal:
All modifications to parameters nMA1 ... nMA8 or nCA1 ... nCA8 must be made with the motor stopped.
The master PLC program should be updated to take account of this modification.
1755873 11/200915
Configuration
Configuring communication fault management
The response of the drive in the event of a Profibus DP communication fault can be configured.
RDYNET+0.00Hz0A
COM. FAULT MANAGEMENT
Configuration can be performed using the graphic display terminal or
the integrated display terminal via the
parameter in the
[COM. FAULT MANAGEMENT] (CLL- ) submenu).
(
The values of the [Network fault mgt](CLL) parameter, which trigger a drive fault [Com. network] (CnF), are:
ValueMeaning
[1.8 - FAULT MANAGEMENT] (FLt-) menu
[Network fault mgt] (CLL)
[Freewheel] (YES): Freewheel stop (factory setting).
[Ramp stop] (rMP):Stop on ramp.
[Fast stop] (FSt): Fast stop.
[DC injection] (dCI): DC inje c ti o n sto p.
[Network fault mgt] (CLL) parameter, which do not trigger a drive fault, are:
[Ignore] (nO) : Fault ignored.
[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt).
[fallback spd] (LFF):
[Spd maint.] (rLS) :
The fallback speed can be configured in the
parameter.
Change to fallback speed, maintained as long as the fault persists and the run command has not been
removed.
The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run
command has not been removed.
[1.8 – FAULT MANAGEMENT] (FLt-) menu using the [Fallback speed] (LFF)
161755873 11/2009
Configuration
Configuring monitored parameters
Up to 4 parameters can be selected and their value displayed in the [1.2 - MONITORING] menu on the graphic display terminal.
The selection is made via the
Each parameter in the range
[Address 4 select]
address. An address at zero is used to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCR): Logic address 3204;
signed decimal format
• Parameter 2 = Motor torque (OTR): Logic address W3205; signed
decimal format
• Parameter 3 = Last fault (LFT): Logic address W7121; hexadecimal
format
• Disabled parameter: Address W0; default format: Hexadecimal
format
One of the three display formats below can be assigned to each monitored word:
6.3 CONFIG. COMM. MAP.
Address 1 select: 3204
Format address 1: Signed
Address 2 select: 3205
Format address 2: Signed
Address 3 select: 7121
CodeQuick
Format address 3: Hex
Address 4 select: 0
Format address 4: Hex
Note: If a monitored parameter:
- has been assigned to an unknown address (e.g., 3200)
- has been assigned to a protected parameter
- has not been assigned
the value displayed in the
[COMMUNICATION MAP] screen will be "-----" (see "Diagnostics" section).
1755873 11/200917
Diagnostics
1.1
1.2
1.3
1.4
1.5
2.1
2.2
2.3
2.4
2.5
ST
DX
Controlling the address and speed of the bus
From the terminal, select the [1.9 - COMMUNICATION](COM-) menu ([PROFIBUS DP](PbS-) submenu) to display both
parameters:
[Address] (Adrc): Drive address on the bus configured on the switches
-
[Bit rate] (bdr): Bus speed imposed by the Profibus DP master
-
These parameters cannot be modified.
LEDs
The Profibus DP card has two LEDs, ST and DX, visible through the window on the cover of the Altivar 61 / 71:
• The status of the Profibus DP card is indicated by the red ST (status) LED: LED 2.1.
• The status of the Profibus DP communication link is indicated by the gr een DX (data exchange) LED: LED 2.2.
The table below gives the meaning of the various states of these two LEDs:
Red ST
LED
(LED 2.1)
Green DX
LED
(LED 2.2)
MeaningCorrective actions in the event of malfunction
The card has been configured and its
parameters set correctly by the master.
The card is in Idle state, awaiting
configuration.
The card is in Wait_Prm or Wait_Cfg state.Check the connection to the Profibus DP bus,
The card is in ILF fault mode.Check the connection between the Profibus DP card and the drive.
The card is in the "data exchange" state,
and error-free data exchange is taking place.
No communication on the bus,
no data is being exchanged.
Enter a value between 1 and 126 using the switches on the option
card.
start up the PLC and, if the drive has a communication card fault
(CnF), reset it.
Check the connection to the Profibus DP bus, start up the PLC.
LED states
LED offSlow flashing (0.5 s)
LED onQuick flashing (0.1 s)
181755873 11/2009
Diagnostics
Control-signal diagnostics
On the graphic display terminal, the [1.2 - MONITORING] menu ([COMMUNICATION MAP] submenu) can be used to display
control-signal diagnostic information between the Altivar 61 / 71 drive and the Profibus DP master:
• Active command channel
• Value of the command word (CMD) from the active command channel
• Active target channel
• Value of the target from the active target channel
• Value of the status word
• Values of four parameters selected by the user
•In the
•In the
•In the
•In the
Example of the display of communication diagnostic information
[COM. SCANNER INPUT MAP] submenu: PZD input values
[COM SCANNER OUTPUT MAP] submenu: PZD output values
[CMD. WORD IMAGE] submenu: Command words from all channels
[FREQ. REF. WORD MAP] submenu: Frequency targets from all channels
RUNNET+50.00Hz80A
COMMUNICATION MAP
Command channel: Com. card
Cmd value: 000F
Channel ref. active: Com. card
Frequency ref: 500.0
Status word: 8627
CodeQuick
W3204: 53
W3205: 725
W7132: 0000
W0: ----COM. SCANNER INPUT MAP
COM SCANNER OUTPUT MAP
CMD. WORD IMAGE
FREQ. REF. WORD
The [Status word] parameter indicates the value of the status word (ETA).
[Com card cmd.]
Displaying parameters selected by the user
The four [W····] parameters indicate the value of the four words select ed by the user.
The address and display format of these parameters can be configured in the
[6.3 - CONFIG. COMM. MAP] submenu) (see "Configuration" section on page 10).
(
The value of a monitored word equals "
- Monitoring has not been activated (address equals W0)
- The parameter is protected
- The parameter is not known (e.g., W3200)
-----" if:
[6 - MONITORING CONFIG.] menu
201755873 11/2009
Diagnostics
Displaying PZDs (communication scanner)
In the [1.2 - MONITORING](SUP-) menu:
[COM. SCANNER INPUT MAP] (ISA-) submenu is used to display the value of the 8 input PZDs (communication scanner
- The
input parameters NM1 to NM8).
[COM SCANNER OUTPUT MAP] (OSA-) submenu is used to display the value of the 8 output PZDs (communication
- The
scanner output parameters NC1 to NC8).
Configuration of these periodic parameters is described in the "Conf iguration" section.
Example of displaying PZDs on the graphic display terminal:
RUNNET+50.00Hz80ARUNNET+50.00Hz80A
COM. SCANNER INPUT MAP COM SCANNER OUTPUT MAP
Com Scan In1 val.: 34359Com Scan Out1 val.: 15
Com Scan In2 val.: 600Com Scan Out2 val.: 598
Com Scan In3 val.: 0Com Scan Out3 val.: 0
Com Scan In4 val.: 0Com Scan Out4 val.: 0
Com Scan In5 val.: 0Com Scan Out5 val.: 0
CodeQuickCodeQuick
Com Scan In6 val.: 0Com Scan Out6 val.: 0
Com Scan In7 val.: 0Com Scan Out7 val.: 0
Com Scan In8 val.: 0Com Scan Out8 val.: 0
In this example, only the first two parameters have been configured (default assignment).
Drivecom status "Operation enabled",
reverse operation, speed reached.
600 rpm
"Enable operation" (Run) command
598 rpm
1755873 11/200921
Diagnostics
Communication faults
Profibus DP communication faults are displayed by the red RD indicator of the Profibus DP card.
In factory settings, a Profibus DP communication fault triggers a re-settable drive fault
The response of the drive in the event of a Profibus DP communication fault can be changed (see "Configuring communication fault
management"):
-Drive fault
- No drive fault (stop, maintain, fallback).
The fault management is described in the user’s manual "Communication parameters", chapter "Communication monitoring":
• After initialization (power up), the drive checks that at least one of the command or target parameters has been written once via Profib us
DP.
• Then, if a Profibus DP communication fault occurs, the drive reacts according to the configuration (stop, maintain, fallback ...).
The origin of the last Profibus DP communication fault can be displayed by the parameter
ValueDescription of the values of the para m e te r[Com. network] (CnF)
The parameter
FAULT INFO] (AFI-) submenu.
[Com. network] (CnF) (freewheel stop, stop on ramp, fast stop or DC injection stop).
0No faultt
1
2Identification error between the Profibus DP card of the drive and the Profibus DP master.
3Identification error of the Profibus DP card of the drive (hardware problem).
Time out on the reception of the periodic variables addressed to the drive. This time out is adjustable by the network
configuration software..
[Com. network] (CnF) is displayed on the display terminal (graphic only): [1.10 DIAGNOSTICS] (DGT-) menu, [MORE
[Com. network] (CnF) and a freewheel stop.
[Com. network] (CnF) :
Card fault
The [Option int link](ILF) fault appears when there are serious problems:
- Hardware problem on the Profibus DP card itself.
- Dialog faults between the option card and the drive.
It is not possible to configure the behavior of the drive i n the event of a [Option int link](ILF) fault, the drive stops in freewheel.
This type of fault cannot be reset.
Two parameters display the origin of the last [Option int link](ILF) faults :
• [Internal link fault 1](ILF1) displays the error that occurred on option card no. 1 (directly mounted on the drive),
• [Internal link fault 2](ILF2) displays the error that occurred on option card no. 2 (mounted on the option card no. 1),
The parameter [Intern al link fault 1](ILF1) and [Internal link fault 2](ILF2) are displayed on the display terminal (graphic only): [1.10
ValueDescription of the values of the para m e te r Internal link fault 1](ILF1) and [Internal link fault 2](ILF2)
0No fault
1Loss of internal communication with the drive
2Hardware malfunction detected
3Error in the EEPROM checksum
4Faulty EEPROM
5Faulty Flash memory
6Faulty RAM memory
7Faulty NVRAM memory
8Faulty analog input
9Faulty analog output
10Faulty logic input
11Faulty logic output
101Unk no wn ca rd
102Dialog faults between the option card and the drive
103Dialog time out between the option card and the drive
221755873 11/2009
Software setup
Profibus DP protocol
Data is exchanged according to the master-slave principle.
Only the master can initialize communication. The slaves behave like servers responding to requests from masters.
Several masters can coexist on the same bus. In this case, the slave I/O can be read by all the masters. However, a s ingle master has write
access to the outputs. The number of data items exchanged is defined at the time of configuration.
A GSD file contains the configuration information for t he Altivar 61 / 71 with Profibus DP. This f ile is used by the PLC during the configurat ion
phases.
The GSD file is unique to the whole Altivar 61 / 71 range. It does not describe the drive parameters, just the communication information.
This file appears on the CD-ROM supplied with the drive.
The Profibus DP card for Altivar 61 / 71 drives only supports Type 5 (Byte-String 28) cyclic frames in PPO (Parameter-Process Data-Object)
format.
Type 5 PPO cyclic frames feature 14 periodic variables that are used for 2 types of service:
- I/O exchanges (PZD)
- Aperiodic exchanges (PKW) for parameter setting, configuration and diagnostics
PKW aperiodic exchanges are included in the cyclic frames and do not require special frames. An aperiodic exchange is used to read or
write a parameter. The Altivar 61 / 71 PKW service does not conform to Profidrive.
1755873 11/200923
Software setup
Output PZDs
The first eight bytes contain an aperiodic request (PKW) to write or read a parameter.
The remaining 20 bytes contain the output PZDs (written from the Profibus master), of which only PZD1 to PZD8 are significant.
1234567891011121314
PKWPZD1PZD2PZD3
PKE0R/W PWENC1NC2NC3
1516171819202122232425262728
PZD4PZD5PZD6PZD7PZD8PZD9PZD10
NC4NC5NC6NC7NC8Not usedNot used
PKW request:
PKEParameter logic address
RIWRequest code
PWEFor a read request: Not used
0: No request
1: Read
2: Write
For a write request: Parameter value
Cyclic control and adjustment parameters:
PZD1: Communication scanner output word 1 (NC1)
PZD2: Communication scanner output word 2 (NC2)
PZD3: Communication scanner output word 3 (NC3)
PZD4: Communication scanner output word 4 (NC4)
PZD5: Communication scanner output word 5 (NC5)
PZD6: Communication scanner output word 6 (NC6)
PZD7: Communication scanner output word 7 (NC7)
PZD8: Communication scanner output word 8 (NC8)
The default assignment of the periodic output data is:
• PZD1 = Command word
• PZD2 = Speed target
• PZD 3 to PZD 10 = Not used
12 3 4 567891011121314
PKWPZD1PZD2PZD3
PKE0R/WPWECommand wordSpeed targetNot used
1516171819202122232425262728
PZD4PZD5PZD6PZD7PZD8PZD9PZD10
Not usedNot usedNot usedNot usedNot usedNot usedNot used
The assignment of PZDs is described in the Configuration section.
How to display the value of the PZDs is described in the "Diagnostics" sectio n.
241755873 11/2009
Software setup
Input PZDs
The first eight bytes contain the response (PKW) to the aperiodic re ad/write request.
The remaining 20 bytes contain the input PZDs (read mode), of which only PZD1 to PZD8 are signi ficant.
Cyclic monitoring parameters:
PZD1: Communication scanner input word 1 (NM1)
PZD2: Communication scanner input word 2 (NM2)
PZD3: Communication scanner input word 3 (NM3)
PZD4: Communication scanner input word 4 (NM4)
PZD5: Communication scanner input word 5 (NM5)
PZD6: Communication scanner input word 6 (NM6)
PZD7: Communication scanner input word 7 (NM7)
PZD8: Communication scanner input word 8 (NM8)
The default assignment of the periodic input data is :
• PZD1 = Status word (ETA)
• PZD2 = Output speed (RFRD)
• PZD 3 to PZD 10 = Not used
1234567891011121314
PKWPZD1PZD2PZD3
PKE0R/WPWEStatus wordOutput speedNot used
1516171819202122232425262728
PZD4PZD5PZD6PZD7PZD8PZD9PZD10
Not usedNot usedNot usedNot usedNot usedNot usedNot used
The assignment of PZDs is described in the Configuration section on page 11
How to display the value of the PZDs is described in the "Diagnostics" sectio n.
1755873 11/200925
.
Software setup
PKW aperiodic service
The PKW service, consisting of PKE, R/W, R/W/N, and PWE, enables aperiodic access to Altivar 71 parameters in read and write mode.
Output PKWs
PKE
Parameter logic address
R/W
0: No request
1: Read
2: Write
One-off read and write requests can be triggered continuously while R/W equals 1 or 2.
Note:
Values other than 0, 1 and 2 should not be used. In particular, the values 16#0052 and 16#0057 must not be used, as these are reserved
for compatibility with the Altivar 58/58F.
PWE
If write: Value to be written
Input PKWs
PKE
Copies the output PKE value
R/W/N
0: No request
1: Correct read operation
2: Correct write operation
7: Read or write error
PWE
• If correct read operation: Parameter value. This can be limited by the drive if the maximum value is exceeded by the write operation.
• If correct write operation: Value of the write PWE
• If there is an error:
0: Incorrect address
1: Write operation refused
Note:
The parameters in the output PZDs should not be changed by the PKW service.
Parameters linked to output PZDs should not be changed by the PKW service.
Example: The speed target and the frequency target.
261755873 11/2009
Software setup
Examples of PKW aperiodic exchanges
Example of aperiodic write operation: Acceleration time ACC (address 9001) = 10 s, unit 0,1s (values in hexadecimal format).
12345678etc.
2329000200000064etc.
ACC = 10 s
Write request
Address 9001 = 2329h
The positive response is identical to the write request, aperiodic part (bytes 1 to 8).
Example of negative response:
12345678
232900070000000
etc.
etc.
0 (incorrect address)
Negative response
1755873 11/200927
Software setup using PL7
Correspondence between cyclic data and PL7 PRO words
In PL7, cyclic exchanges between the Profibus DP master (e.g., TSX Premium PLC + TSX PBY100 module) and the Altivar 61 / 71 take
the form of input words %IWxy.0.k and output word s %QWxy.0.k, where "x" = number o f the PLC rack and "y" = location of t he Profibus DP
module in the PLC rack.
PWE%QWxy.0.3PWE%IWxy.0.3
PZD1%QWxy.0.4Command word (CMD)PZD1%IWxy.0.4Status word (ETA)
PZD2%QWxy.0.5Speed target (LFRD)PZD2%IWxy.0.5Output speed (RFRD)
PZD3%QWxy.0.6Not usedPZD3%IWxy.0.6Not used
PZD4%QWxy.0.7Not usedPZD4%IWxy.0.7Not used
PZD5%QWxy.0.8Not usedPZD5%IWxy.0.8Not used
PZD6%QWxy.0.9Not usedPZD6%IWxy.0.9Not used
PZD7%QWxy.0.10 Not usedPZD7%IWxy.0.10Not used
PZD8%QWxy.0.11 Not usedPZD8%IWxy.0.11Not used
PZD9%QWxy.0.12 Not usedPZD9%IWxy.0.12Not used
PZD10%QWxy.0.13 Not usedPZD10%IWxy.0.13Not used
PL7 output
word
%QWxy.0.2Not
Altivar 61 / 71
parameter
Not used%IWxy.0.2Not used
Not used
Altivar 61 / 71 parameterProfibus
ProfibusPL7 input word
PZD9%IWxy.0.12
used
PL7 input
word
%IWxy.0.2
Altivar 61 / 71 parameter
Altivar 71
parameter
Not used
281755873 11/2009
AT V61/71_Profibus_EN_1755873_03
1755873 11/2009
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.