Schneider Electric MGE Galaxy 300, MGE Galaxy 7000 Specifications

Page 1
40002 0x0001 1
40011 0x000A 10
40020 0x0013 19
40028 0x001B 27
40037 0x0024 36
40046 0x002D 45
40051 0x0032 50
40057 0x0038 56
40065 0x0040 64
Not supported by Galaxy 7000 SSC
2
3
4 Not supported by Galaxy 7000 SSC
5 Not supported by Galaxy 7000 SSC
6
7 Galaxy 7000 parallel SSC
8
9
10
11
12
13 Not supported by Galaxy 7000 SSC
14
40066 0x0041 65
Not supported by Galaxy 7000 SSC
0 0 1 - Galaxy 7000 Unitary
Load Alarm Violation Fault
BOOLEAN
1 - Alarm violation present 0 - Alarm violation not present
Alarm/Status Register
1
UINT16
Run in Frequency converter
BOOLEAN
0 - Power converter currently works on auto ranging 1 - Power converter currently works on frequency converter
UPS Temperature Fault
BOOLEAN
1 - UPS temperature fault
Battery to be checked or External battery monitoring fault
BOOLEAN
1 - Battery Replacement need ed
Device ventilation fault
BOOLEAN
1 - System level fan fault exists
UPS overload
BOOLEAN
1 - UPS output overload
Emergency stop
BOOLEAN
1 - Emergency stop in progess
Modbus data Invalid
BOOLEAN
1 - Modbus Data Not valid
Communication fault
BOOLEAN
1 - UPS serial communication fault exists
Battery low warning
BOOLEAN
1 - Low battery
Low battery
BOOLEAN
1 - Ups is in shutdown state
Operation on static switch
BOOLEAN
1 - (In bypass) Bypass AC Input is used as source of power
Internal UPS hardware fault exists
BOOLEAN
1 - An internal UPS hardware fault exists
NA
BOOLEAN
Battery usage status
1 - On battery power in response to an input power problem
Alarm/Status Register
1
UINT16
Load powered (protected or not)
BOOLEAN
0: Output is not powered. 1: Output is powered.
Load Protected (UPS coupled)
BOOLEAN
0: Inverter is not used 1: Inverter is used
Reserved for future use
5
NMC card manufactruing date
6
ASCII
Reserved for future use
8
NMC card serial number
8
ASCII
NMC card hardware revision
9
NMC card firmware revision
9
ASCII
NMC application name
9
ASCII
NMC card model number
9
ASCII
Modbus Register Map: MGE Galaxy 300/ MGE Galaxy 7000
Over all status of the UPS. 0 = Status unknown
Notes:
1. 16-bit registers are transmitted MSB first (i.e. big-endian).
2. UINT16 and UINT32 are most-significant word in n+0, least significant word in n+1 (i.e. big-endian).
3. Function codes 3 and 4 are supported
4. Modbus serial RTU and TCP is supported.
5. Signednumbers are twos-compliment
6. Status bits are atomic within a single Modbusregister. User should not look for consistency across multiple registers, only within a single register.
7. For ASCII strings less than the maximum length, the unused characters are filled with nulls.
8. Single -register reads of reserved or undefined registers will return an error. Block reads which begin with a valid register will return zeros for undefined registers.
9. Strings are two characters per register, first character in high-order byte, second character in low-order byte. Printable ASCII only.
10. Bit #0 is le
11. Data Type column: "INT16"=signed 16-bit integer, "UINT16" = unsigned16-bit integer, "INT32" = signed 32-bit integer, "UINT32" = unsigned 32-bit integer, "ENUM" is a UINT16 value which maps to a defined list of states, "ASCII" = the printable ASCII subset from 0x20 - 0x7E. BOOLEAN= a single bit, 0 or 1.
12. "Absolute Starting Register Address" = 0 (the colu mn heading used in this table) is equivalent to "Register 40001" in Modicon terminology, which is address zero when transmitted over the wire.
13. The number of word by frame should not exceed 26 words.
14. Register 40072 is only to be used in Parallel Configurations and is not supported for Unitary Configurations.
Note 1: For detailed modbus configuration settings please refer to the AP9635 User’sGuide. Note 2: SSC for Static Switch Cabinet.
ast significant bit.
990-4329B-001 06/2021
© 2021 Schneider Electric. All Rights Reserved.
Modicon Standard Register
Number
40001 0
Absolute
Starting
Register
Address,
(Hexadeci
x0000 0
Absolute
Starting
Register Address, (Decimal)
Bit Supported Modules
2 = No alarms present 4 = Warning alarms present 8 = Critical alarms present
0
1
Data Point
Length
# registers
1
Data Type
ENUM
ASCII
BOOLEAN
Multiply
Reading By:
Divide
Reading
By:
Valid Response
990-4329B
15
0
1 - Unitary 3: 3 (Galaxy 7000 & Galaxy 300) 2 - Modular 3: 3 (Galaxy 7000 & Galaxy 300) 3 - Galaxy 7000 parallel
1 2 3
with SSC 4 - Galaxy 7000 SSC 5 - Galaxy 300 unitary 3:1 6 - Galaxy 300 modular 3:1
BOOLEAN
0 1 0 - Galaxy 7000 Modular 0 1 1 - Galaxy 7000 Parallel with SSC 1 0 0 - Galaxy 7000 SSC 0 0 1 - Galaxy 300 Unitary 33 1 0 1 - Galaxy 300 Unitary 31 0 1 0 - Galaxy 300 Redundant 33 1 1 0 - Galaxy 300 Redundant 31
Modus Register Map 1
Page 2
Modicon
4
5
6
7
8
9
Not supported by Galaxy 7000 SSC
Only on G7000
Only on G7000
Only on G7000
14
15
40067 0x0042 66
0
1
2
3
4
5
6
7
8
9
10 Not supported by Galaxy 7000 SSC
11
12
13
14
15 Not supported by Galaxy 7000 SSC
40069 0x0044 68
0
1
2
3 Not supported by Galaxy 300
4
5
6
7
8 Not supported by Galaxy 7000 SSC
9
Not supported by Galaxy 7000 SSC
10
11 Not supported by Galaxy 7000 SSC
12
13
14
15
40070 0x0045 69
0
1
2
3
4
5
6
7
8
9 Only Galaxy 7000 SSC supported
10 Only Galaxy 7000 SSC supported
11 Only Galaxy 7000 SSC supported
12
13
14
15
NA
BOOLEAN
NA
BOOLEAN
NA
K2S switch on/off status
BOOLEAN
1 - K2S swtich on (close)
Overlap transfert on SSC status
BOOLEAN
1 - Overlap transfert fault exists
NA
BOOLEAN
UPS Redundancy status
BOOLEAN
1 - Power modules redundancy is lost
NA
K2S fault status
BOOLEAN
1 - K2S fault exist
NA
BOOLEAN
Status of the input contact 1
BOOLEAN
1 - Input contact 1 fault exist
Status of the input contact 2
BOOLEAN
1 - Input contact 2 fault exist
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Alarm/Status Register
1
UINT16
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
Main AC fuse status
BOOLEAN
1 - Main AC fault (open)
NA
BOOLEAN
Main AC frequency status
BOOLEAN
1 - Main AC frequency out of range
NA
BOOLEAN
NA
BOOLEAN
Main AC voltage status
BOOLEAN
1 - Main AC is not OK/Voltage out of range
Main AC switch status
BOOLEAN
1 - Main AC switch closed
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Battery switch status
BOOLEAN
1 - Battery switch closed
Alarm/Status Register
1
UINT16
NA
Internal battery temperature status
BOOLEAN
1 - The internal battery temperature exceeds the c ritical thresho ld
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Battery test in progress
BOOLEAN
1 - Test in progress
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Battery test result
BOOLEAN
1 - Battery test failed (Done and Error)
NA
BOOLEAN
NA
BOOLEAN
Alarm/Status Register
1
UINT16
Installed battery status
BOOLEAN
1 - Battery presen t
UPS environnement fault
BOOLEAN
0 - No UPS environnental fault 1 - UPS environnemntal fault or ups minor fault
BOOLEAN
0 - UPS not in ECO Mode 1 - UPS is running in ECO Mode
NA
BOOLEAN
Rectifier internal fault status
1 - Re ctifier inte rnal f ault exists
Load protection status in parallel installation
BOOLEAN
0 - Load protection is restored 1 - Load protection is lost due to less number of good power modules
UPS Power Saving Mode status
BOOLEAN
0 - UPS not in Power Saving Mode (Efficiency Booster Mode) 1 - UPS is running in Power Saving Mode (EBM)
Maintenance bypass switch status
BOOLEAN
1 - Maintenance bypass switch closed
NA
BOOLEAN
NA
NA
BOOLEAN
NA
BOOLEAN
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
Absolute
Starting
Register Address, (Decimal)
Le
Bit Supported Modules
Data Point
ngth
# registers
Data Type
Multiply
Reading By:
Divide
Reading
By:
Valid Response
10
11
12
13
ECO mode status
BOOLEAN
BOOLEAN
990-4329B
BOOLEAN
BOOLEAN
Modus Register Map 2
Page 3
Modicon
40071 0x0046 70
0
Galaxy 7000 parallel with SSC
2
3
4
Galaxy 7000 parallel with SSC
Galaxy 7000 parallel with SSC
Galaxy 7000 parallel with SSC
8
Galaxy 7000 parallel with SSC
Galaxy 7000 parallel with SSC
11
12
13
14 Galaxy 7000 parallel with SSC
15
40072 0x0047 71
2
3
4
5
6
7
8
9
10
11
12
13
14
15
40073 0x0048 72
0
1
2
3
4
5
6
7
Not supported by Galaxy 300
Not supported by Galaxy 300
Not supported by Galaxy 300
Not supported by Galaxy 300
12
13
14
15
NA
BOOLEAN
NA
BOOLEAN
Input Contact 4 COSIT
BOOLEAN
1 - Input contact 4 closed 0 - Input contact 4 open
NA
BOOLEAN
NA
Input Contact 1 COSIT
BOOLEAN
1 - Input contact 1 closed 0 - Input contact 1 open
Input Contact 2 COSIT
BOOLEAN
1 - Input contact 2 closed 0 - Input contact 2 open
Input Contact 3 COSIT
BOOLEAN
1 - Input contact 3 closed 0 - Input contact 3 open
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Alarm/Status Register
1
UINT16
Input contact 1 status
BOOLEAN
1 - input contact 1 closed
Input contact 2 status
BOOLEAN
1 - input contact 2 closed
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
Output switch status
BOOLEAN
1 - Output switch closed
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Inverter and AC bypass desynchronisation
BOOLEAN
0 - Ups synchronised with AC bypass, 1 - Ups is not synchronised with the AC bypass
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Alarm/Status Register
1
UINT16
Internal bypass hardware fault exists
BOOLEAN
0 - Hardware fault no longer exist 1 - Hardw are fault due to Bypass internal fau lt (fuse, relay, …)
NA
BOOLEAN
NA
BOOLEAN
Bypass switch status
BOOLEAN
1 - Bypass switch c losed
Bypass frequency status
BOOLEAN
0 - Bypass frequency in range 1 - Bypass frequency out of range
Bypass voltage status
BOOLEAN
0 - Bypass voltage in range 1 - Bypass voltage out of range
NA
NA
BOOLEAN
Bypass overload status
BOOLEAN
0 - Bypass input power not overload 1 - Bypass input power overload
Bypass thermal overload status
BOOLEAN
0 - No thermal overload on bypass input 1 - Thermal overload exists on bypass input
Bypass swtich fault status
BOOLEAN
0 - No fault in bypass swtich 1 - Bypass swtich is in fault condition
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Alarm/Status Register
1
UINT16
NA
BOOLEAN
UPS maintenance bypass status
BOOLEAN
0 - UPS is not in maintenance bypass 1 - UPS is in maintenance bypass
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
Absolute
Starting
Register Address, (Decimal)
Le
h
Bit Supported Modules
Data Point
ngt
# registers
Data Type
Multiply
Reading By:
Divide
Reading
By:
Valid Response
1
5
6
7
9
10
0
Parallel configurations only
1
BOOLEAN
8
9
10
11
990-4329B
BOOLEAN
Modus Register Map 3
Page 4
Modicon
40074 0x0049 73
0 Not present for Galaxy 7000 SSC
1
2
3 Not present for Galaxy 7000 SSC
4
5
6
7
8
9
10
11
12
13
14
15
40075 0x004A 74
0
Only on G7000
1 Only on G7000
2 Only on G7000
3
4
5
6
7
8
9
10
11
12
13
14
15
40076 0x004B 75
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
40077
0x004C 76
0
1 Not present for Galaxy 7000 SSC
2 Not present for Galaxy 7000 SSC
3 Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
6
7
8
9
10
11
12
13
14
15
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
UPS fuse fault
BOOLEAN
0 - No fuse or fuse closed 1 - Fuse open
NA
BOOLEAN
NA
BOOLEAN
Inverter overload status
BOOLEAN
1 - Inverter Overload
Inverter thermal overload status
BOOLEAN
1 - Thermal overload
Inverter limitation status
BOOLEAN
0 - No current limitation 1 - Cu rren t limit ation
Alarm/Status Register
1
UINT16
NA
BOOLEAN
Inverter major fault
BOOLEAN
1 - Failure due to inverter malfunction
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Reserved for future use
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
NA
BOOLEAN
NA
BOOLEAN
ECO Scheduling setting
BOOLEAN
1 - Scheduled EC O mode feature is available
NA
BOOLEAN
NA
BOOLEAN
Alarm/Status Register
1
UINT16
EBM setting
BOOLEAN
1 - Efficienc y Booster Mode feature is available
ECO setting
BOOLEAN
1 - ECO m ode feature is available
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Battery charging status
BOOLEAN
1 - Battery is charging
Alarm/Status Register
1
UINT16
Charger hardware fault exists
BOOLEAN
1- Hardware fault due to charger malfunction
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
Absolute
Starting
Register Address, (Decimal)
Le
Bit Supported Modules
Data Point
ngth
# registers
Data Type
BOOLEAN
BOOLEAN
Multiply
Reading By:
Divide
Reading
By:
Valid Response
990-4329B
4
5
Modus Register Map 4
Page 5
Modicon
40078 0x004D 77
40080 0x004F 79
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
40081 0x0050 80
40225 0x00E0 224 Not present for Galaxy 300
40227 0x00E2 226 Not present for Galaxy 300
40229 0x00E4 228 Not present for Galaxy 300
40231 0x00E6 230 Not present for Galaxy 300
40233
0x00E8 232 Not present for Galaxy 300
40234 0x00E9 233 Not present for Galaxy 300
40235
0x00EA 234 Not present for Galaxy 300
40236 0x00EB 235 Not present for Galaxy 300
40238 0x00ED 237
40241 0x00F0 240 Not present for Galaxy 300
40243 0x00F2 242 Not present for Galaxy 300
40245 0x00F4 244 Not present for Galaxy 300
40247 0x00F6 246 Not present for Galaxy 300
40249 0x00F8 248 Not present for Galaxy 300
40250 0x00F9 249 Not present for Galaxy 300
40251 0x00FA 250 Not present for Galaxy 300
40252 0x00FB 251 Not present for Galaxy 300
40254
0x00FD 253 Not present for Galaxy 300
40255 0x00FE 254
40257
0x0100 256 Not present for Galaxy 7000 SSC
40258
0x0101 257 Not present for Galaxy 7000 SSC
40259
0x0102 258 Not present for Galaxy 7000 SSC
40260
0x0103 259
40263 0x0106 262 Not present for Galaxy 7000 parallel with SSC
40264
0x0107 263 Not present for Galaxy 7000 parallel with SSC
40265 0x0108 264 Not present for Galaxy 7000 parallel with SSC
40266 0x0109 265
40267 0x010A 266 Not present for Galaxy 300 3:1
40268 0x010B 267 Not present for Galaxy 300 3:1
40269 0x010C 268
40271 0x010E 270 Not present for Galaxy 7000 SSC
40272 0x010F 271
40278
0x0115 277 Not present for Galaxy 7000 SSC
40279 0x0116 278 Not present for Galaxy 7000 SSC
40280 0x0117 279 Not present for Galaxy 7000 SSC
40281 0x0118 280
40287 0x011E 286 Not present for Galaxy 7000 parallel with SSC
40288 0x011F 287 Not present for Galaxy 7000 parallel with SSC
40289 0x0120 288 Not present for Galaxy 7000 parallel with SSC
40290 0x0121 289 Not present for Galaxy 7000 parallel with SSC
40291 0x0122 290 Not present for Galaxy 7000 parallel with SSC
40292 0x0123 291 Not present for Galaxy 7000 parallel with SSC
40293 0x0124 292
40294 0x0125 293 Not present for Galaxy 300 3:1
40295 0x0126 294 Not present for Galaxy 300 3:1
40296 0x0127 295 Not present for Galaxy 300 3:1
40297 0x0128 296 Not present for Galaxy 300 3:1
40298 0x0129 297 Not present for Galaxy 300 3:1
40299 0x012A 298
40300 0x012B 299
40301 0x012C 300
40302 0x012D 301 Not present for Galaxy 7000 SSC
40303 0x012E 302
40305 0x0130 304 Not present for Galaxy 300 3:1
40306
0x0131 305 Not present for Galaxy 300 3:1
40307 0x0132 306 Not present for Galaxy 300 3:1
40308 0x0133 307 Not present for Galaxy 300 3:1
Output phase 3 active power
1
UINT16
kW
Output phase 1 apparent power
1
UINT16
kVA
Reserved for future use
2
Output phase 1 active power
1
UINT16
kW
Output phase 2 active power
1
UINT16
kW
UPS Temperature in deg F
1
UINT16
°F
UPS Temperature in deg C
1
UINT16
°C
Battery voltage
1
UINT16
Volts
Output phase 2 to phase 3 voltage
1
UINT16
Volts
Output phase 3 to phase 1 voltage
1
UINT16
Volts
Reserved for future use
1
Output phase 2 to neutral voltage
1
UINT16
Volts
Output phase 3 to neutral voltage
1
Volts
Output phase 1 to phase 2 voltage
1
UINT16
Volts
Bypass input phase 2 to phase 3 voltage
1
UINT16
Volts
Bypass input phase 3 to phase 1 voltage
1
UINT16
Volts
Output phase 1 to neutral voltage
1
UINT16
Volts
Bypass input phase 2 to neutral voltage
1
UINT16
Volts
Bypass input phase 3 to neutral voltage
1
UINT16
Volts
Bypass input phase 1 to phase 2 voltage
1
UINT16
Volts
Mains input phase 3 to phase 1 voltage
1
UINT16
Volts
Reserved for future use
6
Bypass input phase 1 to neutral voltage
1
UINT16
Volts
Reserved for future use
6
Mains input phase 1 to phase 2 voltage
1
UINT16
Volts
Mains input phase 2 to phase 3 voltage
1
UINT16
Volts
Output phase 3 current
1
UINT16
Amps
Reserved for future use
2
Battery curren t
1
INT16
Amps
Bypass input phase 3 current
1
UINT16
Amps
Output phase 1 current
1
Amps
Output phase 2 current
1
UINT16
Amps
Reserved for future use
3
Bypass input phase 1current
1
UINT16
Amps
Bypass input phase 2 current
1
UINT16
Amps
Mains input phase 1 current
1
UINT16
Amps
Mains input phase 2 current
1
UINT16
Amps
Mains input phase 3 current
1
UINT16
Amps
Monthly time in PSM
2
UINT32
Second
Number of G7000 in PSM
1
UINT16
Reserved for future use
2
Percent time spent on PSM since commissionning
1
UINT16
%
Percent time spent on PSM since reset
1
UINT16
%
Number time running in PSM
1
UINT16
Time on PSM since reset
2
UINT32
Second
Time OnLine since commissionning PSM
2
UINT32
Second
Time OnLin e since reset PSM
2
UINT32
Second
Reserved for future use
3
Time on PSM since commissionning
2
UINT32
Second
Number time running in ECO mode
1
UINT16
Monthly time in ECO mode
2
Second
Time OnLin e since reset ECO
2
UINT32
Second
Percent time spent on ECO since commissionning
1
UINT16
%
Percent time spent on ECO since reset
1
UINT16
%
Time on ECO mode since commissionning
2
UINT32
Second
Time on ECO mode since reset
2
UINT32
Second
Time OnLine since commissionning ECO
2
UINT32
Second
NA
BOOLEAN
NA
BOOLEAN
Reserved for future use
48
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
NA
BOOLEAN
Alarm/Status Register
1
UINT16
NA
BOOLEAN
Short circuit on output status
BOOLEAN
1 - Short circuit fault exixts
Reserved for future use
2
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
Absolute
Starting
Register Address, (Decimal)
Le
Bit Supported Modules
Data Point
ngth
# registers
Data Type
BOOLEAN
UINT32
Multiply
Reading By:
Divide
Reading
By:
Valid Response
UINT16
UINT16
990-4329B
Modus Register Map 5
Page 6
Modicon
40309 0x0134 308 Not present for Galaxy 300 3:1
40310 0x0135 309 Not present for Galaxy 300 3:1
40311 0x0136 310
40312 0x0137 311
40313 0x0138 312
40314 0x0139 313
40315 0x013A 314 Peak factor will be in multiples of 100
0x013B 315
Peak factor will be in multiples of 100 (Not present for Galaxy 300 3:1)
0x013C 316
Peak factor will be in multiples of 100 (Not present for Galaxy 300 3:1)
40318 0x013D 317 Power factor will be in multiples of 100 (0 to 100)
0x013E 318
Frequency value will be in multiples of 10 Not present for Galaxy 7000 SSC
40320 0x013F 319
0x0140
320
Frequency value will be in multiples of 10 Not present for Galaxy 7000 parallel with SSC
40322 0x0141 321 Frequency value will be in multiples of 10
40323 0x0142 322 Only on G7000
40324 0x0143 323 Only on G7000
40325 0x0144 324 Only on G7000
40326 0x0145 325
40330 0x0149 329 Not present for Galaxy 7000 SSC
40331
0x014A 330 Not present for Galaxy 7000 SSC
40332 0x014B 331 Not present for Galaxy 7000 SSC
40333
0x014C 332 Not present for Galaxy 7000 SSC
40337 0x0150 336 Not present for Galaxy 7000 SSC
40338 0x0151 337 Not present for Galaxy 7000 SSC
40339
0x0152 338 Not present for Galaxy 7000 SSC
40340 0x0153 339 Not present for Galaxy 7000 SSC
40341 0x0154 340 Not present for Galaxy 7000 SSC
40342 0x0155 341
40343 0x0156 342
40344 0x0157 343
40345 0x0158 344
40346 0x0159 345
40385 0x0180 384
40386 0x0181 385
40387 0x0182 386
40389
0x0184 388
40390 0x0185 389
40392
0x0187 391
40393
0x0188 392
40394
0x0189 393
40396
0x018B 395
40397 0x018C 396
40417 0x01A0 416
40425 0x01A8 424
40433 0x01B0 432
40441 0x01B8 440
40449 0x01C0 448 Only on G7000
40522 0x0209 521
40523 0x020A 522
40530 0x0211 529 Only on G7000
40531
0x0212 530 Not present for Galaxy 7000 SSC
0x0213 531 Not present for Galaxy 7000 SSC
Nominal battery voltage
1
UINT16
Volts Reserved for future use
7
UPS num ber in par allel installatio n
1
UINT16
Nominal Battery Backup time
1
UINT16
minutes
UPS serial num ber
8
ASCII
UPS firmware release
15
ASCII
Nominal output apparent power
1
UINT16
kVA
UPS model number
8
Reserved for future use
20
UPS man ufacturere name
8
ASCII
UPS product name
8
ASCII
UIO sensor port 1 maximum humidity threshold
1
UINT16
%
Reserved for future use
2
UIO sensor port 1 minimum humidity threshold
1
UINT16
%
UIO sensor port 1 minimum temperature threshold in deg C
1
UINT16
°C
Reserved for future use
2
UIO sensor port 1 humidity
1
UINT16
%
UIO sensor port 1 temperature in deg C
1
UINT16
°C
UIO sensor port 1 maximum temperature threshold in deg C
1
UINT16
°C
Reserved for future use
2
UIO sensor port 1 maximum temperature threshold in deg F
1
UINT16
°F
UIO sensor port 1 minimum temperature threshold in deg F
1
UINT16
°F
Reserved for future use
39
Total battery cap acity
1
Amp-Hour
Battery temperatu re in Deg F
1
UINT16
°F
UIO sensor port 1 temperature in deg F
1
UINT16
°F
Mains input phase 2 to neutral voltage
1
UINT16
Volts
Mains input phase 3 to neutral voltage
1
UINT16
Volts
Total number of battaries count
1
UINT16
Battery remaining c apacity
1
UINT16
%
Reserved for future use
4
Mains input phase 1 to neutral voltage
1
UINT16
Volts
Reserved for future use
4
Battery remaining runtime
1
UINT16
minutes
Battery temperatu re
1
UINT16
°C
Output phase 1 power factor
1
UINT16
%
Output phase 2 power factor
1
UINT16
%
Output phase 3 power factor
1
UINT16
%
Reserved for future use
1
Bypass input frequency
1
UINT16
dHz Output frequency
1
UINT16
dHz
Output phase 3 peak factor
1
UINT16
Output power factor
1
UINT16
Mains input frequency
1
UINT16
dHz Total output percent load
1
%
Output phase 1 peak factor
1
UINT16
Output phase 2 peak factor
1
UINT16
Total Output active power
1
UINT16
kW
Total Output apparent power
1
UINT16
kVA
Reserved for future use
1
UINT16
Output phase 2 apparent power
1
UINT16
kVA
Output phase 3 apparent power
1
UINT16
kVA
Standard
Register
Number
40316
40317
40319
40321
Absolute
Starting
Register
Address,
(Hexadeci
Absolute
Starting
Register Address, (Decimal)
Le
h
Bit Supported Modules
Data Point
ngt
# registers
Data Type
UINT16
UINT16
Multiply
Reading By:
Divide
Reading
By:
Valid Response
40532
UINT16
ASCII
990-4329B
Modus Register Map 6
Page 7
Modbus
UPS on
Normal AC
input
UPS in ECO
Mode
UPS in
Power
Saving
M
ode (EBM)
X 1 1
X 0 1
X 0 0
X
0 0
X 0 0
X 0 0 0 X X X X X
41D 0 0 0 0 0
X 1 0
41B 0 0 0 0 0
X 0 1
47B 1 1 1 1 1
X 1 1
X 1 1
46E 1 1 1 1 1
X 1 1
42F 1 1 1 1 1
X
1 1
X 0 0
X 0 0
41A 0 0 0 1 1
X 0 0
X 0 0
4C1 0 0 0 0 0
X 0 0
X 0 0
42A 0 0 0 0 0
X 0 0
X 0 0
40B
0 0 0 0 0
X 0 0
40E 0 0 0 0 0
X 0 0
41C 0 1 1 1 0
X 0 0
40A 0 0 0 0 0
X 0 0
X 0 0
4C2 0 0 0 0 0
X 0 0
X 0 0
44B 0 1 1 1 0
X 0 0
X 0 0
X 0 0
Load Powered
Main AC switch status (Q1 or QM1)
UPS in maintenance position
Global Overview MGE Galaxy 300/ MGE Galaxy 7000
Output switch status (QOP or Q5N)
Breaker status
UPS in Power Saving Mode (EBM)
UPS in ECO mode
Battery Charging
On Bypass
On Manual
Bypass
UPS on
Battery
Low Battery
Warning
End of
battery
runtim
e
Main UPS status
AC bypass Out of tolerance
AC Normal Voltage Out Of Tolerance
AC Normal Frequency Out Of Tolerance
Static switch overload
Inverter Overload
Low Battery Warning
Overload
Environment fault - Orange Led on UPS
UPS Warning
Fan Faillure
Load on inverter
UPS on battery
Emergency Power Off
End of battery runtime
Battery temperature fault
Charger fault
Load on AC Bypass
Inverter fault
Rectifier fault
UPS Internal Communication Fault
Load not protected
Internal UPS fault - Red Led on UPS interface
UPS Fault
Maintenance Bypass switch status (Q3BP)
Battery switch status (QB or QF1)
Bypass switch status (QM2 or Q4S)
Address (word
+ bit) Hexa
format
400 1 1 1 1 1 1
401 1 1 1 0 0 0
404 0 1 1 0 0 0
407 0 0 0 1 1 0
461 0 0 0 0 0 1
493
0
0
0
443 1 1 1 1 1 1
1
1
416 0 0 0 0 0 1
402 0 0 0 1 1 1
1
409 0 0 0 0 0 0 1 0 0
419 0 0 0 0 0 0
0
490 0 0 0 0 0 0
0
406 0 0 0 1 0 0
0
0
Comm lost
990-4329B
405 0 0 1 1 0 0
465 0 0 0 0 0 0
448 0 1 1 1 0 0
467 0 0 0 0 0 0
Characteristics for UPS in Online operation
Characteristics value for the current UPS operational mode
Modus Register Map
0
0
0
0
7