Motor Circuit Breakers and Manual Motor
Protectors
User Guide
03/2020
DOCA0161EN-01
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical character
istics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this
document on any medium whatsoever without permission of Schneider Electric, given in writing. You also
agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the document or its content, except for a
non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, service, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
DOCA0161EN-01 03/20205
6DOCA0161EN-01 03/2020
At a Glance
Document Scope
Validity Note
Online Information
About the Book
This guide provides users, installers, and maintenance personnel with technical information needed to
operate TeSys™ GV5 and TeSys™ GV6 devices in compliance with the IEC/EN and UL/CSA standards:
In IEC/EN standards, TeSys GV5 / GV6 devices are motor circuit breakers.
In UL/CSA standards, TeSys GV5 / GV6 devices are manual motor protectors.
device
In this guide, the term
Motor circuit breakers
Manual motor protectors
This document applies to TeSys GV5 devices and TeSys GV6 devices.
The information contained in this guide is likely to be updated at any time. Schneider Electric strongly
recommends that you have the most recent and up-to-date version available on
electric.com/tesys
.
The technical characteristics of the devices described in the present document also appear online. To
access the information online:
covers:
www.schneider-
Related Documents
StepAction
1Go to the Schneider Electric home page
2In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks (
3If you entered a reference, go to the Product Datasheets search results and click on the
reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click
on the product range that interests you.
4If more than one reference appears in the Products search results, click on the reference that
interests you.
5Depending on the size of your screen, you may need to scroll down to see the datasheet.
6To save or print a datasheet as a .pdf file, click Download XXX product datasheet.
www.schneider-electric.com
The characteristics that are described in the present document should be the same as those character
.
*
).
-
istics that appear online. In line with our policy of constant improvement, we may revise content over time
to improve clarity and accuracy. If you see a difference between the document and online information, use
the online information as your reference.
Title of documentationReference number
TeSys Motor Control and Protection Components CatalogMKTED210011EN
TeSys GV5P - Motor Circuit Breaker (IEC) and Manual Motor Protector
(UL/CSA) - Instruction Sheet
TeSys GV6P - Motor Circuit Breaker (IEC) and Manual Motor Protector
(UL/CSA) - Instruction Sheet
MFR49208
MFR49209
You can download these technical publications and other technical information from our website at
www.schneider-electric.com
Trademark Notice
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
TeSys GV5 / GV6 devices offer current ratings from 150 to 500 A, for AC power systems up to 690 Vac.
TeSys GV5 / GV6 devices are available in the following frame sizes:
TeSys GV5 for current ratings from 150 to 220 A
TeSys GV6 for current ratings from 320 to 500 A
TeSys GV5 / GV6 devices have the following features:
Direct rotary handle
3-pole devices
5, 10 and 20 trip classes
The following accessories are optional and installable on site:
Voltage trip releases
Auxiliary contacts
Insulation accessories
Device Identification
The commercial reference of each device provides information about:
The size of the device
The type of protection the device provides
The current rating of the device
The breaking capacity of the device
For example, the commercial reference of the GV5P 220H device contains the following information:
GV5: The device is a TeSys GV5 device.
P: The device offers protection against overloads and short-circuits.
220: The device has a current rating of 220 A.
H: The breaking capacity of the device is 70 kA at 415 Vac.
Breaking Capacity
Standard Compliance
The following table shows the breaking capacity (Ics = Icu) in kA rms for TeSys GV5 / GV6 devices:
AC power
systems
230 Vac85 kA100 kA85 kA100 kA40 kA100 kA40 kA100 kA
400/415 Vac36 kA70 kA36 kA70 kA36 kA70 kA36 kA70 kA
440Vac35kA65kA35kA65kA30kA65kA30kA65kA
500Vac30kA50kA30kA50kA25kA50kA25kA50kA
660/690 Vac8 kA10 kA8 kA10 kA10 kA10 kA10 kA10 kA
TeSys
GV5PGV5
P 150F
TeSys
GV5PGV5
P 150H
TeSys
GV5PGV5
P 220F
TeSys
GV5PGV5
P 220H
TeSys
GV6PGV6
P 320F
TeSys
GV6PGV6
P 320H
TeSys
GV6PGV6
P 500F
TeSys
GV6PGV6
P 500H
TeSys GV5 / GV6 devices are compliant with the following standards:
IEC/EN 60947-2 and IEC/EN 60947-4-1 for motor protection circuit breakers
UL 60947-4-1 for motor protection circuit breakers
CSA-C22.2 No.60947-4-1 for motor protection circuit breakers
10
DOCA0161EN-01 03/2020
Device Overview
Device Description
TeSys GV5 / GV6 - Introduction
TeSys GV5 / GV6 devices are equipped with direct rotary handles as standard.
The device operating controls, operation indicators, settings, and locking mechanisms for the direct rotary
handle are located on the front of the device.
There are two models of rotary handle:
Black handle for standard applications
Red handle on yellow bezel for machine control applications
TeSys GV5 deviceTeSys GV6 device
A Power connection
B Direct rotary handle
C Device and accessory data labels
D QR code
E Seal for trip unit
F Trip unit
G Push-to-trip button
H Rating plate
QR code
Scan the QR code to get additional information about the device from the Schneider Electric website. To
scan the QR code, use a smartphone that is equipped with a camera and installed with a QR code reader.
DOCA0161EN-01 03/202011
TeSys GV5 / GV6 - Introduction
Devices with Extended Rotary Handle
For devices with an extended rotary handle:
The device operating controls are located on the front cover.
The operation indicators and settings are accessible when the door is open.
The locking mechanisms are located on the front cover (door closed)
There are two models of extended rotary handle:
Black handle for standard applications
Red handle on yellow bezel for machine control applications
Cabinet door open Cabinet door closed
(see page 27)
.
Rating Plate
A Open door shaft operator
B Rating plate
C Push-to-trip button
D Trip unit
E Extended rotary handle
The rating plate on the front of the device identifies the device and its characteristics. The rating plate
depends on the breaking performances.
A Range name
B Type of device
C Commercial reference
D Uimp: rated impulse withstand voltage
E Ui: rated insulation voltage
F Ics: service breaking capacity
G Icu: ultimate breaking capacity
H Ue: rated operational voltage
I Standards
12
DOCA0161EN-01 03/2020
TeSys GV5 Accessories
TeSys GV5 / GV6 - Introduction
LegendAccessoryInstruction sheet reference
ATerminal shield
BInterphase barrier
CInsulating screen (45 mm / 1.8 in)
DSteel connector (1.5–95 mm² / 16-4/0 AWG)
EAluminum connectors for one conductor (25-185 mm² / 4 AWG-350 kcmil)
FAluminum connector for one conductor (120-240 mm² / 250-450 kcmil)
GSpreaders (35-45 mm / 1.4-1.8 in)
HExtended rotary handle
IOpen door shaft operator
JMCC conversion accessory
KSpare direct rotary handle
LOF, SD, or SDE indication contacts
MSDE adapter
NAU (UVR) or AS (SHT) voltage releases
OSDTAM thermal fault module
PCombination kit for contactor
DOCA0161EN-01 03/202013
MFR49208
MFR49208
GHD16344AA
MFR49208
MFR49208
QGH14246
MFR49208
GHD16292AA
EAV78496
GHD16295AA
MFR55037
MFR55023
GHD16303AA
MFR55033
GHD16274AA
1378738
TeSys GV5 / GV6 - Introduction
TeSys GV6 Accessories
14
LegendAccessoryInstruction sheet reference
ATerminal shield (45 mm / 1.77 in)
BTerminal shield (52.5 mm / 2.07 in)
CInterphase barrier
DInsulating screen (70 mm / 2.76 in)
EAluminum connector for one conductor (35-300 mm² / 2 AWG-600 kcmil)
FAluminum connector for two conductors (35-240 mm² / 2 AWG-500 kcmil)
GSpreader (52.5 mm / 2.07 in)
HSpreader (70 mm / 2.76 in)
IExtended rotary handle
JOpen door shaft operator
KMCC conversion accessory
LSpare direct rotary handle
MSDTAM thermal fault module
NOF, SD, or SDE indication contacts
OAU (UVR) or AS (SHT) voltage releases
MFR49209
MFR49209
MFR49209
GHD16344AA
MFR49209
MFR49209
MFR49209
MFR49209
GHD16320AA
EAV78496
GHD16295AA
MFR55039
GHD16274AA
MFR55023
MFR55033
DOCA0161EN-01 03/2020
Sealing Accessories
TeSys GV5 / GV6 - Introduction
Use sealing accessories to prevent device operations.
Seal typeHelps to preventSeal image
Seal for front cover mounting screw
Dismantling the front cover
Accessing the auxiliaries
Dismantling the trip unit
Seal for transparent protective cover
of the trip unit
Seal for mounting screw for terminal
shields
Altering trip unit settings
Accessing the power connection
(protection against direct contact)
For more information about the installation of sealing accessories, consult the instruction sheet on the
Schneider Electric website:
GHD16296AA
.
DOCA0161EN-01 03/202015
TeSys GV5 / GV6 - Introduction
Environmental Conditions
Ambient Temperature
The ambient temperature refers to the temperature of the air immediately surrounding the device.
Operation temperature:
–25 to +70 °C (–13 to +158 °F): Normal operating temperature
–35 to –25 °C (–31 to –13 °F): Commissioning possible
Storage temperature: –50 to +85 °C (–58 to +185 °F)
Extreme Atmospheric Conditions
TeSys GV5 / GV6 devices are designed to operate in industrial atmospheres as defined in IEC/EN 609472 standard for the highest level of pollution (level 3).
They are tested for extreme storage conditions according to the following standards:
StandardTitle
IEC/EN 60068-2-2Dry heat, severity level +85 °C (+185 °F)
IEC/EN 60068-2-1Dry cold, severity level –50 °C (–58 °F)
IEC/EN 60068-2-30Damp heat, cyclic
IEC/EN 60068-2-52Salt-mist test
temperature +55 °C (+131 °F)
relative humidity 95%
Vibration
It is recommended to install the device in a properly ventilated switchboard without excessive dust.
TeSys GV5 / GV6 devices are tested against vibration.
Conformity tests are carried out in accordance with IEC/EN 60068-2-6 standard at the levels of severity
required by the merchant shipping regulatory body (DNV-GL):
2 Hz to 13.2 Hz with an amplitude of +/- 1 mm (+/- 0.04 in)
13.2 Hz to 100 Hz at a constant acceleration of 0.7 g
16
DOCA0161EN-01 03/2020
Electromagnetic Disturbances
TeSys GV5 / GV6 devices are immune to electromagnetic disturbance.
TeSys GV5 / GV6 - Introduction
Overcurrent protection tests are carried out in accordance with the electromagnetic compatibility (EMC)
standard (IEC/EN 60947-2 standard appendixes F and J).
Check for compliance with EMC standard by testing for immunity to:
Overvoltages produced by the operation of electromagnetic switchgear.
Overvoltages produced by atmospheric disturbance that pass through the electrical network (for
example, lightning).
The use of apparatus emitting radio waves (such as radio transmitters, walkie-talkies, or radar).
Electrostatic discharges produced by the operators themselves.
Conformity with EMC standard as described above helps to ensure that:
The device operates correctly in a disturbed environment:
Without nuisance tripping.
In accordance with the trip time.
There is no disturbance to any type of industrial or commercial environment.
DOCA0161EN-01 03/202017
TeSys GV5 / GV6 - Introduction
Altitude
TeSys GV5 / GV6 devices are designed to operate within specification at altitudes of up to 2,000 m
(6,600 ft).
Above 2,000 m (6,600 ft) modifying the characteristics of the surrounding air (dielectric strength, cooling
capacity) causes derating as follows:
Altitude (m/ft)< 2,000 m
(6,600 ft)
Maximum operating voltage (Vac)690690635560
Rated operational current at 40 °C (104 °F)1.000.98 0.960.94
For example, tripping the device with the push-to-trip button can lead to inappropriate fault indications or
corrective actions (such as switching to an alternate power source).
Follow these steps to test the trip mechanism:
StepActionPosition
1Close the device.I(ON)
CAUTION
2Press the push-to-trip button.
The device trips.
3Turn the rotary handle counterclockwise to the O(OFF)
position.
The device is open.
4Turn the rotary handle clockwise from the O(OFF)
position to the I(ON) position.
The device is closed.
Trip
O(OFF)
I(ON)
22
DOCA0161EN-01 03/2020
Locking a Device With Direct Rotary Handle
Handle Locking
Lock handle with up to three padlocks (not supplied).
Handle lockingPadlocks
Padlocking (standard) only in the
O(OFF) position.
TeSys GV5 / GV6 - Operating the Device
Lock handle with up to three padlocks (not
supplied) with shackle diameters of 5–
8 mm (0.2–0.3 in).
NOTE: Locking the rotary handle in the I(ON) position does not disable the device protection functions. If
there is an electrical fault, the device still trips. When unlocked, the handle moves to the Trip position. To
return the device to service, follow the resetting instructions
Door Locking (MCC Function)
Padlocking in the two positions I(ON)
and O (OFF) (optional). This locking
option requires the removal, adaptation,
and reinstallation of the rotary handle.
(see page 20)
Lock handle with up to three padlocks (not
supplied) with shackle diameters of 5–
8 mm (0.2–0.3 in).
.
Locks the door in the closed position
when the device is in the I(ON) position or
in the Trip position.
Helps to prevent the direct rotary handle
from being moved to the I(ON) position
when the door is open.
DOCA0161EN-01 03/202023
TeSys GV5 / GV6 - Operating the Device
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified persons are authorized to disable the door lock.
Failure to follow these instructions will result in death or serious injury.
If the lock has been disabled, the following direct rotary handle functions are inoperative:
Door locking
Preventing the device from being closed when the door is open
DANGER
It is possible to temporarily disable this lock to open
the door when the device is in the I(ON) position.
Disabling this lock requires modifying the rotary
handle.
For more information, refer to
GV5 / GV6 - Rotary Handle MCC Adaptor Plate -
Instruction Sheet
.
GHD16295AA, TeSys
24
DOCA0161EN-01 03/2020
Testing a Device With Extended Rotary Handle
Push-to-Trip Procedure
HAZARD OF NUISANCE TRIPPING
Device tests must only be done by qualified electrical personnel.
Failure to follow these instructions can result in injury or equipment damage.
When testing the trip mechanism take precautions against:
For example, tripping the device with the push-to-trip button can lead to inappropriate fault indications or
corrective actions (such as switching to an alternate power source).
There is no push-to-trip button on the door of a device with an extended rotary handle. To check the trip
mechanism, the door must first be opened.
Follow these steps to test the trip mechanism:
StepActionPosition
1Switch the device to the open O(OFF) position. Open the door. O(OFF)
TeSys GV5 / GV6 - Operating the Device
CAUTION
2Turn the device from the O(OFF) position to the I(ON)
position, using one of the following tools:
An open door shaft operator (LV426937).
A flat wrench, taking care not to damage the extension shaft
or its surface treatment.The extension shaft is a hollow
rectangular tube,15 x 10 mm (0.59 x 0.39 in).
The device is ready for the test.
3Press the push-to-trip button. The device trips.Trip
4Use a special tool (refer to step 2) to turn the extension shaft
counterclockwise and switch the device from the Trip position
to the O(OFF) position.
The device is in the open position.
I(ON)
O(OFF)
DOCA0161EN-01 03/202025
TeSys GV5 / GV6 - Operating the Device
StepActionPosition
5Close the door.–
26
DOCA0161EN-01 03/2020
Locking a Device With Extended Rotary Handle
Handle Locking
The extended rotary handle offers several locking functions to:
Prevent the rotary handle being operated.
Prevent the door being opened.
Some locking functions can be disabled on different adaptations.
The handle can be locked with up to three padlocks (not supplied).
Handle lockingPadlocks
Padlocking (standard) in the O(OFF)
position.
Padlocking the rotary handle in the
O(OFF) position does not prevent the
door from opening.
TeSys GV5 / GV6 - Operating the Device
Lock rotary handle with up to
three padlocks (not supplied) with
shackle diameters of 5–8 mm (0.2–
0.3 in).
NOTE: Locking the rotary handle in the I(ON) position does not disable the device protection functions. If
there is an electrical fault, the device still trips. When unlocked, the rotary handle moves to the Trip position.
To return the device to service, follow the resetting instructions
Door Locking (MCC Function)
Padlocking (after modification to the
rotary handle during installation) in the
two positions I(ON) and O (OFF).
There is a choice of two options when
locking the rotary handle in the I(ON)
position:
Standard with the door opening
locked.
As an option, door is not
interlocked, and locking the rotary
handle does not stop the door from
opening.
The extended rotary handle locks the door in the I(ON) position as standard.
Lock rotary handle with up to
three padlocks (not supplied) with
shackle diameters of 5–8 mm (0.2–
0.3 in).
(see page 20)
.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified persons are authorized to disable the door lock.
Failure to follow these instructions will result in death or serious injury.
DOCA0161EN-01 03/202027
TeSys GV5 / GV6 - Operating the Device
Example: An application includes a device for a switchboard incoming supply and several device protecting
motors with extended rotary handles installed behind the same door. Locking the door with the rotary
handle of the incoming supply device simplifies maintenance work on the switchboard.
Sealing Accessories
The sealing accessories for devices with extended rotary handles are identical to those for devices with
direct rotary handles
It is possible to temporarily disable this lock to open the door when the device is in
the I(ON) position.
Disabling this lock requires modifying the rotary handle.
For more information, refer to:
TeSys GV5 / GV6 devices offer positive contact indication and are suitable for isolation in accordance with
IEC/EN 60947-1 and 2 standards. The O (OFF) position of the actuator is sufficient to isolate the device
concerned.
The following marking on the rating plate label indicates that the device is capable of isolation:
To confirm this capability, IEC/EN 60947-1 and 2 standards require specific shock withstand tests.
TeSys GV5 / GV6 devices can be locked in the O (OFF) position to allow work to be carried out with the
power off in accordance with installation rules. The device can only be locked in the open position if the
device is in the O (OFF) position.
NOTE: Locking a TeSys GV5 / GV6 device in the open position is sufficient to isolate the device.
Maintenance and Servicing Work on Installation
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E or CSA Z462 or local equivalent.
This equipment must only be installed and serviced by qualified electrical personnel.
Turn off all power supplying this equipment before working on or inside equipment.
Always use a properly rated voltage sensing device to confirm that power is off.
Replace all devices, doors, and covers before turning on power to this equipment.
Repair the installation immediately if an insulation fault occurs during operation.
Failure to follow these instructions will result in death or serious injury.
TeSys GV5 / GV6 - Operating the Device
DANGER
Turn off all power supplying the equipment before working on or inside equipment. For a partial powering
down of the installation, the installation and safety rules require clearly labeling and isolating the feed being
worked on.
Maintenance Work Following a Trip on Electrical Fault
HAZARD OF CLOSING ON ELECTRICAL FAULT
Do not close the device again without first inspecting and, if necessary, repairing the downstream
electrical equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The following table describes the procedure to be followed after a trip on electrical fault:
StepAction
1Isolate the feed before inspecting the downstream electrical equipment.
2Look for the cause of the detected fault.
3Inspect and, if necessary, repair the downstream equipment.
4Inspect the equipment in the event of a short-circuit trip.
5Close the device again.
NOTE: The fact that a protection has tripped does not remedy the cause of the fault detected on the
downstream electrical equipment.
WARNING
Checking the Settings
Checking settings does not require any particular precautions. The checks must be carried out by a
qualified person.
DOCA0161EN-01 03/202029
TeSys GV5 / GV6 - Operating the Device
Testing the Device
HAZARD OF NUISANCE TRIPPING
Protection tests must be done by qualified electrical personnel.
Failure to follow these instructions can result in injury or equipment damage.
When testing device trip mechanisms, precautions must be taken:
To avoid disrupting operations.
To avoid inappropriate actions or tripping of alarms.
For example, tripping the device with the push-to-trip button can lead to inappropriate fault indications or
corrective actions (such as switching to a replacement power source).
Setting the Trip Unit
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done by qualified electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
CAUTION
WARNING
Modifying trip unit settings requires a thorough knowledge of the installation and safety rules.
Provide protection for direct-on-line motor-feeders and star-delta motor starters (direct-on-line starting
is the most widely used type of motor-feeder).
Integrate the basic protections (overload, short-circuit, and phase unbalance) for the motor-feeder.
Allow protection and coordination of the motor-feeder components that comply with the requirements of
IEC/EN 60947-2 and IEC/EN 60947-4-1 standards.
Are used to create motor-feeders with two devices.
A TeSys GV5 / GV6 device
B Instantaneous protection
C Overload protection
D Contactor
E SDTAM thermal fault module
Characteristics Defined by IEC/EN 60947-4-1 Standard
A motor-feeder must satisfy the general rules of IEC/EN 60947-4-1 standard, in particular the rules
concerning the protection of contactors and motor-feeders.
In the matter of protection, this standard defines:
Coordination of motor-feeder protections
Trip class setting value
Insulation coordination
32
DOCA0161EN-01 03/2020
Coordination According to IEC/EN 60947-4-1 Standard
Two types of coordination are allowed: type 1 coordination or type 2 coordination.
In type 1 coordination, deterioration of the contactor and relay is accepted under the two following
conditions:
The contactor or starter does not represent a danger to people or installations.
The starter can operate correctly when parts have been repaired or replaced.
In type 2 coordination, some slight welding of the contactor or starter contacts is allowed if, following
type 2 coordination tests:
They are easy to separate.
The control and protection switchgear functions then work without the need for repair.
To ensure type 2 coordination, IEC/EN 60947-4-1 standard lays down three Id fault current tests intended
to check that the equipment behaves correctly in overload and short-circuit conditions.
TeSys GV5 / GV6 - Protection Functions
1 Overload zone Id < 10 In
2 Impedant short-circuit zone 10 In < Id < 50 In
3 Short-circuit zone Id > 50 In
DOCA0161EN-01 03/202033
TeSys GV5 / GV6 - Protection Functions
Motor Operating States
Introduction
TeSys GV5 / GV6 devices consider the application to be operating as soon as the 10% of Ir pickup is
crossed in a positive direction by the motor current.
Two operating states are considered:
Startup state
Steady state
Startup State
The application is considered to be in startup state according to the following criteria:
Start: As soon as the 10% of Ir pickup is crossed in a positive direction by the motor current.
End: As soon as the Id pickup equals 1.5 x Ir and the td time delay equals 10 s (non-adjustable
parameters).
Exceeding the 10 s time delay does not result in tripping.
NOTE: The trip unit filters the subtransient state (first current peak of approximately 20 ms on contactor
closing). This current peak is not therefore taken into account when assessing whether the Id pickup has
been crossed.
Steady State
The application is considered to be in steady state according to the following criteria:
Start: As soon as startup ends.
End: As soon as the 10% of Ir pickup is crossed in a negative direction by the motor current.
Operating Diagram
The following diagrams show the two cases of transition between startup and steady state:
Operating states with current I < Id before end of tdOperating states with current I > Id at end of td
A TeSys GV5 / GV6 devices status (green: ON position)
B Contactor status (green: ON position)
C Current in the motor
D Operating state: startup state (green: active state)
E Operating state: steady state (green: active state)
34
DOCA0161EN-01 03/2020
Trip Unit Description
Introduction
The trip unit is suitable for protecting motor-feeders in standard applications.
The thermal trip curves are calculated for self-ventilated motors.
The adjustment dials and indications are located on the front face.
Description
TeSys GV5 trip unit
TeSys GV6 trip unit
TeSys GV5 / GV6 - Protection Functions
Indication LEDs
A Indication LEDs
B Phase-unbalance
C Seal for setting cover
D Instantaneous protection pickup (Ii)
E Tripping curve
F Adjustment dial for the short-time protection pickup (Isd)
G Trip class setting
H Adjustment dial for the overload or thermal protection pickup (Ir)
Indication LEDs on the front of the trip unit indicate its operational state.
Indication LEDDescription
Green READY LEDBlinks slowly when the electronic trip unit is ready to provide protection.
Red ALARM LEDOverload temperature alarm LED: Shows a steady light when the thermal image of
the motor exceeds 95% of the Ir setting.
The indication LEDs function for device load currents above 30 A.
DOCA0161EN-01 03/202035
TeSys GV5 / GV6 - Protection Functions
Protection Functions
The following figure and table define the protection functions performed by the trip unit:
AIrOverload or thermal protection pickupYes0.4 x InYes
BClassTrip classYes10Yes
CIsdShort-time protection pickupYes13 x IrNo
DtsdShort-time protection time delayNo0.1 sNo
EIiInstantaneous protection pickupNo17 x InNo
–IunbalPhase-unbalance protection pickupNo30%Yes
–tunbalPhase-unbalance protection time delay
during startup
Phase-unbalance protection time delay in
steady state
activation
No0.7 sYes
No4 sYes
Setting the Protection
Reflex Tripping
Each function is reviewed in detail on the following pages.
Set the overload or thermal protection pickup (Ir), the short-time protection pickup (Isd), and trip class
(Class) by using the dials on the device.
The system of reflex protection breaks very high fault currents by mechanically tripping the device with a
piston actuated directly by the pressure produced in the device from a short-circuit. This piston operates
the opening mechanism, resulting in ultra-fast device tripping
(see page 61)
.
36
DOCA0161EN-01 03/2020
Overload or Thermal Protection (ANSI 49)
Introduction
Overload or thermal protection protects all types of motor applications against overload currents.
Operating Principle
Overload or thermal protection is I
It incorporates the motor thermal image function.
It can be configured as the Ir pickup and as the trip class (Class).
Tripping curve:
TeSys GV5 / GV6 - Protection Functions
The long-time protection is set by two dials according to the starting
characteristics of the application.
The pickup setting Ir for trip unit long-time protection is expressed in
amperes:
This value corresponds to the operating current used in the motor
application.
The maximum Ir setting corresponds to the trip unit rating In.
2
t IDMT (Inverse Definite Minimum Time):
Ir Pickup Setting Value
The overload or thermal protection pickup (Ir) is set by using a multi-position dial.
The default Ir pickup setting value is 0.4 x In (minimum dial value).
The overload or thermal protection tripping range is 1.05–1.20 x Ir according to IEC/EN 60947-4-1
standard.
The following table shows the preset values of the adjustment dial Ir in amperes for each current rating In:
ItemParameterDescription
AIrOverload or thermal protection pickup
BClassOverload or thermal protection trip class (according to IEC/EN 60947-4-1 standard)
Trip unit rating In (A)150 A220 A320 A500 A
Pickup Ir (A)70100160250
80120180280
90140200320
100155220350
110170240380
120185260400
130200280440
140210300470
150220320500
DOCA0161EN-01 03/202037
TeSys GV5 / GV6 - Protection Functions
Trip Class Setting Value
The trip class (Class) is set by using an adjustment dial:
Class 5
Class 10 (default value)
Class 20
The trip class corresponds to the value of the tripping time for a current of 7.2 x Ir according to
IEC/EN 60947-4-1 standard.
The following table shows the value of the tripping time depending on the current in the load for all three
classes:
Current in the loadTripping time (in seconds)
1.5 x Ir96-120192-240320-400
6 x Ir5.2-6.510.8-13.520.8-26
7.2 x Ir4-58-1016-20
The precision range is -20%, + 0%
Motor Thermal Image
The model representing heat rise and cooling in a motor load is constructed according to the algorithm for
calculating the thermal demand, taking account of the iron and copper losses.
The following figure represents the limit curves for the iron and copper components calculated for class 20:
Class 5Class 10Class 20
Thermal Memory
A Limit temperature curve for copper
B Limit temperature curve for iron
C Tripping curve (low envelope)
The trip unit uses a thermal memory function to protect the motor from overheating in case of low amplitude
repetitive faults.
Electronic protection without thermal memory function does not protect against repetitive faults because
the duration of each overload above the pickup setting is too short to cause tripping. However, each
overload causes a temperature rise in the installation. The cumulative effect of successive overloads can
overheat the system. The thermal memory function remembers and integrates the thermal heating caused
by each pickup setting overrun. The thermal memory function remembers the thermal heating values for
20 minutes before or after tripping.
Example: Comparison of the heat rise calculation without thermal image (diagram A) and with thermal
image (diagram B):
Diagram ADiagram B
38
0 Load control (cyclical)
1 Motor temperature
2 Thermal level calculated without thermal image (diagram A), with thermal image (diagram B)
3 Overload or thermal protection level
With thermal image, the trip unit adds the thermal effect of successive current pulses. Tripping occurs
based on the actual thermal state of the motor.
DOCA0161EN-01 03/2020
Cooling Fan
TeSys GV5 / GV6 - Protection Functions
The thermal image of the motor is calculated taking account of the fact that the motor is self-cooled (fan
mounted on the shaft end).
DOCA0161EN-01 03/202039
TeSys GV5 / GV6 - Protection Functions
Short-Time Protection (ANSI 51)
Introduction
Short-time protection protects all types of motor applications against short-circuit currents.
Short-time protection lets through motor starting currents but protects cables and motor starter devices and
allows not to oversize them (useful for wide range settings devices).
Operating Principle
Short-time protection is definite time. It can be configured as the Isd pickup.
Tripping curve:
ItemFunctionDescription
AIrOverload or thermal protection pickup
CIsdShort-time protection pickup
DtsdShort-time protection fixed time delay
Isd Pickup Setting Value
StepAction
1Set the long-time protection first: the setting pickup is Ir (A).
2Turn the Isd adjustment dial to the value required. The setting range is 5 to 13 x Ir in steps of Ir.
3Isd is set to Ir (A) x Isd setting.
The precision range is +/-15%.
The short-time protection pickup Isd is set by using a multi-position dial.
The setting value is expressed in multiples of Ir.
tsd Time Delay Value
40
The time delay cannot be adjusted.
The hold time is 20 ms.
The maximum breaking time is 60 ms.
DOCA0161EN-01 03/2020
Instantaneous Protection (ANSI 50)
Introduction
Instantaneous protection protects all types of motor applications against very high intensity short-circuit
currents.
Operating Principle
Instantaneous protection is fixed: the pickup value is determined by the current rating In. Protection is
instantaneous.
Tripping curve:
TeSys GV5 / GV6 - Protection Functions
Ii Pickup Value
ItemParameter Description
EIiInstantaneous protection pickup
The Ii pickup value is 15 x In (trip unit rating In corresponds to the maximum Ir setting).
The precision range is +/-15%.
The maximum breaking time is 30 ms.
DOCA0161EN-01 03/202041
TeSys GV5 / GV6 - Protection Functions
Phase Unbalance Protection (ANSI 46)
Introduction
Unbalances of the motor phase currents lead to significant heat rise and braking torques that can cause
premature deterioration of the motor. These effects are amplified during startup: protection must be almost
immediate.
Description
Phase unbalance protection:
Calculates the current unbalance for each phase, compared to the average current, expressed as a
percentage:
Compares the value of the maximum current unbalance with the Iunbal protection pickup.
The following diagram shows a maximum positive unbalance on phase 2:
If the maximum current unbalance value is higher than the phase unbalance protection Iunbal pickup, the
tunbal time delay is actuated.
Phase unbalance protection cannot be deactivated.
Phase unbalance protection is activated during startup and in steady state.
42
DOCA0161EN-01 03/2020
Operating Principle
TeSys GV5 / GV6 - Protection Functions
The phase unbalance (or phase loss) protection trips if the current unbalance exceeds the 30% fixed
pickup Iunbal during a fixed tunbal time delay. The tunbal time delay differs according to the motor
operating conditions:
Start-up phase: tunbal = 0.7 s
Steady state phase: tunbal = 4 s
Phase loss is an extreme case of phase unbalance and leads to tripping under the same conditions.
During startup:
A: Activation of startup phase.
B: Activation of protection time delay as soon as the pickup is
crossed.
C: Protection tripped at the end of the fixed time delay of 0.7 s.
1M Motor current
1D Maximum unbalance of the motor phase
currents
2A Monitoring by phase unbalance protection
during startup
White: Not active
Green: Active
In steady state:
A: Activation of steady state phase.
B: Activation of protection time delay as soon as the pickup is
crossed.
C: Protection tripped at the end of the fixed time delay of 4 s.
1M Motor current
1D Maximum unbalance of the motor phase
currents
2B Monitoring by phase unbalance protection
in steady state
White: Not active
Green: Active
The phase unbalance protection does not trip if the current unbalance falls below the Iunbal pickup
before the end of the fixed tunbal time delay.
A: Activation of steady state phase.
B: Activation of protection time delay as soon as the pickup is
crossed.
D: Time delay is reset.
1M Motor current
1D Maximum unbalance of the motor phase
currents
2B Monitoring by phase unbalance protection
The following table shows electrical auxiliary devices that can be added to devices. They can be installed
on site. For more information, see the
(see page 7)
Electrical auxiliary deviceUse
OF auxiliary contactView the on/off status of the device remotely.
SD auxiliary contactView the trip status of the device remotely.
SDE auxiliary contactIndicate that the device has tripped on an electrical fault.
AU undervoltage trip release Trip the device when the control voltage drops below a tripping threshold.
AS shunt tripSend an electrical trip command remotely to trip the device.
SDTAM thermal fault module Provide alarm and fault differentiation.
Slots for Electrical Auxiliary Devices on TeSys GV5 Devices
The following table shows the possible slots for electrical auxiliary devices mounted in the case.
.
TeSys Motor Control and Protection Components Catalog
Electrical auxiliary deviceSlot
ABCDE
OF1 auxiliary contact✔––––
OF2 auxiliary contact–––✔–
SD auxiliary contact–✔–––
SDE auxiliary contact (with addition of the optional SDE adapter)––✔––
AU undervoltage trip release––––✔
AS shunt trip––––✔
SDTAM thermal fault module✔–––✔
NOTE: It is not possible to install all the accessories at the same time in one device. For example, SDTAM
thermal fault module uses the same slot as AU undervoltage trip release or AS shunt trip.
46
DOCA0161EN-01 03/2020
Slots for Electrical Auxiliary Devices on TeSys GV6 Devices
The following table shows the possible slots for electrical auxiliary devices mounted in the case.
Electrical auxiliary deviceSlot
OF1 auxiliary contact–✔––––––
OF2 auxiliary contact––✔–––––
OF3 auxiliary contact–––✔––––
OF4 auxiliary contact––––––✔–
SD auxiliary contact––––✔–––
SDE auxiliary contact (with embedded SDE
adapter)
AU undervoltage trip release– ––––––✔
AS shunt trip– ––––––✔
SDTAM thermal fault module✔––––––✔
TeSys GV5 / GV6 - Electrical Auxiliary Devices
ABCDEFGH
–––––✔––
NOTE: It is not possible to install all the accessories at the same time in one device. For example, SDTAM
thermal fault module uses the same slot as AU undervoltage trip release or AS shunt trip.
DOCA0161EN-01 03/202047
TeSys GV5 / GV6 - Electrical Auxiliary Devices
Operation of the Auxiliary Indication Contacts
The following table shows the position of the indication contacts (or outputs) relative to the position of the
actuator and main contacts.
Use indication contacts to view the status of the device remotely.
The indication contact provides either OF, SD, or SDE indication functions, depending on its location in the
device.
Indication contacts are located under the front face of the device, in a compartment isolated from the power
circuits.
Description
NameImageDefinition
OF open/close
indication contact
TeSys GV5 / GV6 - Electrical Auxiliary Devices
The OF contact indicates the position of the main contacts of the device (open
or closed).
Characteristics
SD trip indication
contact
SDE electrical
fault contact
The SD contact indicates that the device has tripped due to:
Operation of the push-to-trip button
Operation of the AU undervoltage trip release or AS shunt trip
Overload or thermal protection
Short-time protection
Instantaneous protection
Phase-unbalance protection
The SDE contact indicates that the device has tripped on an electrical fault due
to:
The following voltage trip release auxiliaries are operated remotely by an electrical trip command:
AU undervoltage trip release
AS shunt trip
NOTE: It is recommended to test the operation of a voltage trip release at regular intervals, such as every
six months.
Voltage trip release auxiliaries are installed in the case under the front face of the device.
Description
NameImageDescription
AU undervoltage trip
release
AS shunt tripAS shunt trip:
TeSys GV5 / GV6 - Electrical Auxiliary Devices
AU undervoltage trip release:
Trips the device when the voltage is less than 0.35 times the rated
voltage of the release.
If the voltage is between 0.35 and 0.7 times the rated voltage of the
release, tripping can occur but is not certain to occur.
If the voltage is above 0.7 times the rated voltage of the release,
tripping cannot occur.
Allows the device to be closed again when the voltage reaches
0.85 times the rated voltage of the release.
Use this type of trip release for failsafe emergency stops.
Trips the device when the voltage exceeds 0.7 times the rated voltage
of the release.
Operates by impulse type control signals maintained for ≥ 20 ms.
Characteristics
Wiring diagram
The characteristics of voltage trip release auxiliaries comply with IEC/EN 60947-2 recommendations.
The diagrams is shown with circuits de-energized, all devices open, connected, and charged, and relays
in normal position.
AU Undervoltage trip release
AS Shunt trip
DOCA0161EN-01 03/202051
TeSys GV5 / GV6 - Electrical Auxiliary Devices
SDTAM Thermal Fault Module
Introduction
Use the SDTAM thermal fault module to manage tripping due to overload.
The SDTAM thermal fault module receives data from the trip unit through an optical link and makes
available two outputs assigned to:
Overload indication
Motor contactor control
Description
A Output terminals
B SDTAM thermal fault module
C Operating mode adjustment dial
Characteristics
Installation
The characteristics of the SDTAM thermal fault module outputs are:
Voltage: 24–415 Vac/Vdc
Current:
Active outputs: 80 mA maximum
Idle outputs: 0.25 mA
The slots used to install the SDTAM thermal fault module depend on the device.
TeSys GV5TeSys GV6
The SDTAM thermal fault module uses the same slot as:
AU undervoltage trip release, AS shunt trip, or OF1 auxiliary contact in a TeSys GV5 device.
AU undervoltage trip release or AS shunt trip in a TeSys GV6 device.
52
DOCA0161EN-01 03/2020
Wiring diagram
TeSys GV5 / GV6 - Electrical Auxiliary Devices
Connect the SDTAM thermal fault module and the two outputs in strict accordance with the wiring diagram.
The diagram is shown with circuits de-energized, all devices open, connected and charged and relays in
normal position.
Output Assignment
Contactor Control
ItemDescription
SD1, SD3Thermal fault module input power supply
SD2Overload fault signal output. This output maintains its state until reset.
Output 2 (SD4/OUT2): normally closed, opens the contactor KM.
Outputs are activated 400 ms before the device trips in the case of:
Overload or thermal protection
Phase-unbalance protection
Contactor control by the output 2 signal (SD4/OUT2) optimizes continuity of service and provides the
following additional benefits:
Lower risk of motor deterioration.
Activation of the output indicates that the application is not working normally. Abnormal operation is not
the result of an anomaly or internal fault in the motor-feeder.
The cause of this abnormal operation can be temporary (for example, a voltage drop causing an overly
long starting time).
When the cause of the overload or unbalance has disappeared, the equipment can be powered up again.
NOTE: To control a contactor with a consumption exceeding 80 mA, it is necessary to provide a control
relay.
DOCA0161EN-01 03/202053
TeSys GV5 / GV6 - Electrical Auxiliary Devices
Operating Modes
To return the outputs to their initial state following activation:
Manual (SDTAM dial in the OFF position) after canceling the module power supply.
Automatic (SDTAM dial on one of the time delay adjustment settings) following a time delay (set
from 1 to 15 minutes to allow for the motor cooling time).
The SDTAM thermal fault module incorporates an auto-reset delay setting dial.
ItemDescription
IMotor current
Output 1SDTAM overload fault signal output
Output 2SDTAM contactor control output
KM1Motor contactor
QTeSys GV5 / GV6 device
54
DOCA0161EN-01 03/2020
TeSys GV5 / GV6
DOCA0161EN-01 03/2020
Appendices
DOCA0161EN-01 03/202055
56DOCA0161EN-01 03/2020
TeSys GV5/ GV6
Tripping and Limitation Curves
DOCA0161EN-01 03/2020
Additional Characterist ics
Appendix A
Additional Characteristics
What Is in This Chapter?
This chapter contains the following topics:
Motor-Feeder Protection58
Reflex Tripping61
Limitation Curves62
TopicPage
DOCA0161EN-01 03/202057
Tripping and Limitation Curves
Motor-Feeder Protection
TeSys GV5P150• and TeSys GV5P220• Tripping Curves
Reflex tripping
58
DOCA0161EN-01 03/2020
TeSys GV6P320• Tripping Curves
Tripping and Limitation Curves
Reflex tripping
DOCA0161EN-01 03/202059
Tripping and Limitation Curves
TeSys GV6P500• Tripping Curves
Reflex tripping
60
DOCA0161EN-01 03/2020
Reflex Tripping
Introduction
Tripping and Limitation Curves
TeSys GV5 / GV6 devices incorporate the exclusive reflex-tripping system.
This system breaks very high fault currents.
The device is mechanically tripped via a “piston” actuated directly by the short-circuit.
For high short-circuits, this system provides a faster break, thereby ensuring discrimination.
Reflex-tripping curves are exclusively a function of the device rating.
DOCA0161EN-01 03/202061
Tripping and Limitation Curves
Limitation Curves
Introduction
The limiting capacity of a device is its aptitude to let through a current, during a short-circuit, that is less
than the prospective short-circuit current.
The exceptional limiting capacity of TeSys GV5 / GV6 devices is due to the rotating double-break
technique (very rapid natural repulsion of contacts and the appearance of two arc voltages in-series with
a very steep wave front).
Ics = 100% Icu
The exceptional limiting capacity of TeSys GV5 / GV6 devices greatly reduces the forces created by faults
in devices.
The result is a major increase in breaking performance.
In particular, the service breaking capacity Ics is equal to 100% of Icu.
The Icu value, defined by IEC/EN 60947-2 standard, is guaranteed by tests comprising the following steps:
Break the circuit three times consecutively with a fault current equal to 100% of Icu
Check that the device continues to function normally, that is:
It conducts the rated current without abnormal temperature rise.
Protection functions perform within the limits specified by the standard.
Suitability for isolation is not impaired.
Longer Service Life of Electrical Installations
Current-limiting devices greatly reduce the negative effects of short-circuits on installations.
Thermal effects: Reduced temperature rise in conductors, therefore longer service life for cables.
Mechanical effects: Reduces electrodynamic forces, therefore less risk of electrical contacts, or busbar
being deformed or broken.
Electromagnetic effects: Reduction in disturbances for measuring devices located near electric circuits.
Economy by Means of Cascading
Cascading is a technique directly derived from current limiting.
Devices with breaking capacities less than the prospective short-circuit current may be installed
downstream of a limiting device.
The breaking capacity is reinforced by the limiting capacity of the upstream device.
It follows that substantial savings can be made on downstream equipment and enclosures.
Current and Energy Limiting Curves
The limiting capacity of a device is expressed by two curves which are a function of the prospective shortcircuit current (the current which would flow if no protection devices were installed):
The actual peak current (limited current)
Thermal stress (A²s), that is, the energy dissipated by the short-circuit in a condition with a resistance
of 1 Ω.
62
DOCA0161EN-01 03/2020
Maximum Permissible Cable Stresses
The table below indicates the maximum permissible thermal stresses for cables depending on their
insulation, conductor (Cu or Al), and their cross-sectional area (CSA). CSA values are given in mm² and
thermal stresses in A²s.
Tripping and Limitation Curves
Current-limiting Curves
The following example shows a current-limiting curve of TeSys GV5 / GV6 devices on 400/440 Vac
networks.
This type of release operates when supplied with current. The shunt (SHT) release provokes circuit
breaker opening when it receives a pulse-type or maintained command.
AU: Undervoltage release
This type of release (UVR) operates when the supply voltage drops below the set minimum.
Auxiliary contact (IEC 60947-1)
Contact included in an auxiliary circuit and mechanically operated by the switching device.
B
Breaking capacity
Value of prospective current that a switching device is capable of breaking at a stated voltage under
prescribed conditions of use and behavior. Reference is generally made to the ultimate breaking capacity
(Icu) and the service breaking capacity (Ics).
C
Circuit breaker (IEC 60947-2)
Mechanical switching device, capable of making, carrying, and breaking currents under normal circuit
conditions and making, carrying for a specified time and breaking currents under specified abnormal circuit
conditions such as those of short-circuits. Circuit breakers are the device of choice for protection against
overloads and short-circuits. Circuit breakers can, as is the case for TeSys GV, be suitable for isolation.
Connection terminal
Flat copper surface, linked to the conducting parts of the device, and to which power connections are made
using bars, connectors or lugs.
Contactor (IEC 60947-1)
Mechanical switching device having only one position of rest, operated otherwise than by hand, capable
of making, carrying and breaking currents under normal circuit conditions including operating overload
conditions. A contactor is provided for frequent opening and closing of circuits under load or slight overload
conditions. It must be combined and coordinated with a protective device against overloads and shortcircuits, such as a circuit breaker.
Contactor utilization categories (IEC 60947-4-1)
The standard defines four utilization categories, AC1, AC2, AC3 and AC4 depending on the load and the
control functions provided by the contactor. The class depends on the current, voltage and power factor,
as well as contactor withstand capacity in terms of frequency of operation and endurance.
D
Degree of protection - IP•• (IEC 60529)
Defines device protection against the penetration of solid objects and liquids, using two digits specified in
IEC 60529 standard. Each digit corresponds to a level of protection, where 0 indicates no protection.
First digit (0 to 6): Protection against penetration of solid foreign objects. 1 corresponds to protection
against objects with a diameter less than 50 mm, 6 corresponds to total protection against dust.
Second digit (0 to 8): Protection against penetration of liquids (water). 1 corresponds to protection
against falling drops of water (condensation), 8 corresponds to continuous immersion.
The enclosure of TeSys GV motor circuit breakers provides a minimum of IP40 (protection against objects
less than 1 mm).
DOCA0161EN-01 03/202065
Glossary
Direct rotary handle
This is a control handle for the circuit breaker. It has the same three positions I (ON), O (OFF) and TRIP
as the toggle control. It provides IP40 and IK07 protections. It maintains suitability for isolation and offers
optional locking using a padlock.
Durability
The term “durability” is used in the standards instead of “endurance” to express the expectancy of the
number of operating cycles which can be performed by the equipment before repair or replacement of
parts. The term “endurance” is used for specifically defined operational performance.
E
Electrical durability
With respect to its resistance to electrical wear, equipment is characterized by the number of on-load
operating cycles, corresponding to the service conditions given in the relevant product standard, which can
be made without replacement.
Electronic trip unit
Trip unit that continuously measures the current flowing through each phase and the neutral if it exists. For
MicroLogic, the measurements are provided by built-in current sensors linked to an analog-digital
converter with a high sampling frequency. The measurement values are continuously compared by the
ASIC to the protection settings. If a setting is overrun, a Mitop release trips the circuit breaker operating
mechanism. This type of trip unit offers much better pick-up and delay setting accuracy than thermalmagnetic trip units. It also provides a wider range of protection functions.
Extented rotary handle
Rotary handle with an extended shaft to control devices installed at the rear of switchboards. It has the
same characteristics as direct rotary handles. It offers multiple locking possibilities using a padlock or a
door interlock.
F
Failsafe remote tripping
Remote tripping is carried out by an opening mechanism using an AU undervoltage release (UVR) in
conjunction with an emergency off button. If power is lost, the protection device opens the circuit breaker.
I
Ics: Service breaking capacity
Expressed as a percentage of Icu, it provides an indication on the robustness of the device under severe
conditions. It is confirmed by a test with one opening and one closing/opening at Ics, followed by a check
that the device operates correctly at its rated current.
Icu: Ultimate breaking capacity
Expressed in kA, it indicates the maximum breaking capacity of the circuit breaker. It is confirmed by a test
with one opening and one closing/opening at Icu, followed by a check that the circuit is properly isolated.
This test ensures user safety.
Ie: Rated operational current
A rated operational current of an equipment is stated by the manufacturer and takes into account the rated
operational voltage, the rated frequency, the rated duty, the utilization category and the type of protective
enclosure, if appropriate.
Ii: Instantaneous protection
This protection supplements Isd. It provokes instantaneous opening of the device. The pick-up may be
adjustable or fixed (built-in). This value is always lower than the contact-repulsion level.
In: Rated current
The rated current corresponds to the current that the device can carry continuously with the contacts
closed and without abnormal temperature rise.
Ir: Oervload or thermal protection
Protection function where the adjustable Ir pick-up determines a protection curve similar to the thermalprotection curve (inverse-time curve I
which corresponds to a theoretically infinite tripping time (asymptote) and of the point at 6 Ir at which the
tripping time depends on the rating.
66
2
t). The curve is generally determined on the basis of the Ir setting
DOCA0161EN-01 03/2020
Isd: Short-time protection with fixed time delay
This protection supplements thermal protection. Short-time protection, but with a fixed time delay. This
function is available on MicroLogic 2M. The short-time pick-up Isd is adjustable from approximately 5 to
13 Ir.
Iunbal: Phase-unbalance or phase-loss protection
This protection function steps in if the current values and/or the unbalance in the three phases supplying
the motor exceeds tolerances. Currents should be equal and displacement should be one third of a period.
Phase-loss is a special case of phase-unbalance.
M
Maximum breaking time
Maximum time after which breaking is effective, which is when the contacts are separated and the current
is completely interrupted.
MCC rotary handle
Handle used for motor control centers and providing IP43 and IK07 protections.
Mechanical durability
With respect to its resistance to mechanical wear, equipment is characterized by the number of no-load
operating cycles which can be effected before it becomes necessary to service or replace any mechanical
parts.
Glossary
P
Power loss / Pole resistance
The flow of current through the circuit breaker poles produces Joule-effect losses caused by the resistance
of the poles.
R
Release (IEC 60947-1)
A device which is mechanically connected to a mechanical switching device (for example a circuit breaker),
which releases the holding means and permits the opening or the closing of the switching device. For
circuit breakers, releases are often integrated in a trip unit.
S
Safety clearances
When installing a circuit breaker, minimum distances (safety clearances) must be maintained between the
device and panels, bars and other protection systems installed nearby. These distances, which depend on
the ultimate breaking capacity, are defined by tests carried out in accordance with IEC 60947-2 standard.
SDTAM thermal fault module
Relay module with two static outputs specifically for the motor-protection MicroLogic 2 M trip units. An
output, linked to the contactor coil, opens the contactor when an overload or other motor fault occurs, thus
avoiding opening of the circuit breaker. The other output stores the opening event in memory.
Spreader
Set of three flat conducting parts made of aluminum. They are screwed to the circuit breaker terminals to
increase the pitch between poles.
Starting current
Start-up of a three-phase, asynchronous motor is characterized by:
A high inrush current, approximately 14 x In for 10 to 15 ms
A starting current, approximately 7.2 x In for 5 to 30 seconds
Return to the rated current after the starting time
Starting time
Time after which the motor ceases to draw the starting current and falls back to the operating current Ir (
≤ In).
Static output
Output of a relay made up of a thyristor or triac electronic component. The low switching capability means
that a power relay is required. This is the case for the SDTAM outputs.
DOCA0161EN-01 03/202067
Glossary
T
Thermal image of the rotor and stator
The thermal image models the thermal behavior of a motor rotor and stator, taking into account
temperature rise caused by overloads or successive starts, and the cooling constants. For each motor
power rating, the algorithm takes into account a theoretical amount of iron and copper which modifies the
cooling constants.
Thermal protection
Protection against over currents following an inverse time curve I
permissible temperature rise for the motor. Tripping occurs after a time delay that decreases with
increasing current.
Trip class (IEC 60947-4-1)
The trip class determines the trip curve of the thermal protection device for a motor feeder. The standard
defines trip classes 5, 10, 20, and 30. These classes are the maximum durations, in seconds, for motor
starting with a starting current of 7.2 x Ir, where Ir is the thermal setting indicated on the motor rating plate.
U
Ue: Rated operational voltage
A value of voltage which, combined with a rated operational current, determines the application of the
equipment and to which the relevant tests and the utilisation categories are referred. For multiple
equipment, it is generally stated as the voltage between phases. This is the maximum continuous voltage
at which the equipment may be used.
Ui: Rated insulation voltage
The rated insulation voltage of an equipment is the value of voltage to which dielectric tests and creepage
distances are referred. In no case shall the maximum value of the rated operational voltage exceed that of
the rated insulation voltage.
Uimp: Rated impulse withstand voltage
The peak value of an impulse voltage of prescribed form and polarity which the equipment is capable of
withstanding without failure under specified conditions of test and to which the values of the clearances are
referred. The rated impulse withstand voltage of an equipment shall be equal to or higher than the values
stated for the transient over voltages occurring in the circuit in which the equipment is fitted.
2
t = constant, which defines the maximum
68
DOCA0161EN-01 03/2020
DOCA0161EN-01
Schneider Electric Industries SAS
35, rue Joseph Monier
CS30323
F - 92506 Rueil Malmaison Cedex
http://www.se.com
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
03/2020
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.