IC2000P+: 15483
New features
The IC2000P+ controls lighting according to brightness AND the time of the day.
IF brightness is less than the set threshold (light sensitive function: IC)
AND IF the time program allows relay closing (time function: IH),
THEN the lighting circuit is activated.
Programmable Light
Sensitive Switch
(2-2100 lux)
and wall-mounted cell
1
Cable
ON override
external contact
(option)
2
max. Ø 4
IH function
Brightness
Threshold
IC function
IC2000P+
output
Status picto.
External input (ON override
The pictograms " ", " " ash during the time
delay phase (switch-on and switch-off).
)
6
displayed
IC2000P+
output
Status picto.
displayed
Power supply 230 V AC +10%, -15%,
1
50/60 Hz
Leaet holder slot
2
Sealed swivel cover
3
Output contact
4
Brightness sensor
5
ON override external command input
6
Back-lit LCD screen
7
Date; Time; Day 1 = Monday,
8 9
10
Day 2 = Tuesday, etc.
Output contact status (On, Off)
11
Viewing ON periods by 1h segment
12
Operating mode: "AUTO", "PROG":
13
programming, " ": time resetting,
"MAN": "HOLIDAY" programming, " ":
adapt conguration
Congure
On energisation or after having reset (see the New Features chapter):
Select the language (FRANÇAIS, ENGLISH, etc.)
b
Set the year, month, day and time
b
Choose between three pre-set time programs in your IC2000P+:
b
"DAYPROG": ON time programming from 7h to 20h V validation of the IC function
v
from 7h to 20
"NIGHTPROG": ON time programming from 5h to 8h and from 18h to 23h V
v
validation of the IC function on these two operating periods
"EMPTYPROG": OFF time programming the entire day V no validation of the IC
v
function.
These programs can be modied by going to the program menu when the
conguration phase is nished (modication of times, operating periods, etc.)
Set your brightness threshold using the "+" and "-" keys, either starting from the
b
previously entered value, or from the measured value (2 lux if there is no mains
supply or sensor).
The following information can be read on the display:
3
15
Validate your choice by pressing "ok".
b
Once this phase is over, your IC2000P+ moves to the "AUTO" mode and
operates with the items dened above (time program and threshold).
If you do not agree with the ashing word or value: scroll down the display
using the "-" and "+" keys.
To conrm the ashing word or value: validate using "ok".
15
If you are lost: press "Menu" to return to the "AUTO" mode without saving the last
change.
If you press no key for 2 minutes: return is automatic to the "AUTO" mode
without saving.
h
The position of the threshold in the range (bargraph)
The brightness range (350-2100)
Brightness above the threshold " ", below the threshold " "
The threshold value (1400 lux)
Operation indication " " ON override,
14
" " holidays
Programming help and status
15
pictogram: " " lighting,
" " switch-off, " " programmed
switch-off,
"AM" morning, "PM" afternoon,
16
"s" seconds, "lx" lux, "min" minutes
"Menu" Selection of operating modes
17
"-", "+" Value setting and navigation
18
keys
"ok" Flashing information validation
19
key.
To reset, press simultaneously on the
3 keys "-", "menu" and "ok", i.e. 17 ,
(-) and 19.
18
Program "PROG"
Access the "PROG" mode by pressing the "Menu" key; the "PROG" mode is used to manage the IH time programs of your IC2000P+,
by means of ve options:
"NEW" to dene a new program (if the "EMPTYPROG" program has been chosen in the "Congure" phase), or add ACTIVE, INACTIVE
b
commands to the two other pre-set time programs: "DAYPROG" and "NIGHTPROG":
"SAVE": to save the new switching operation
v
"COPY": to repeat this switching operation for the other days of the week
v
"CHECK" to view the programs
b
"MODIFY" to change the program already memorised
b
"CLEAR" to delete the program partially or totally (the date, time and language are kept):
b
"SINGLE" deletes programming of the chosen switching operations
v
"ALL OFF" deletes the programming of all the days of the week
v
"FINISH" to leave the "PROG" mode and return to the "AUTO" mode.
b
4

Summer-winter time " "
Modify the time, date, summer/winter time:
Press "Menu", access the mode " " via key "+"
b
Change the time and date
b
Choose summer/winter time:
b
"WOUT S/W": no automatic change
v
"WITH S/W": automatic change according to the chosen zone:
v
Zone Summer time Winter time Comments
EUROPE Last Sunday in
GB/P Last Sunday in
SF/GR/TR Last Sunday in
USA-CAN First Sunday in
5
FREE As per choice As per choice Choice of month,
Adapt the conguration " "
In this mode you can:
1- Modify the brightness threshold of the light sensitive function (IC), setting from
2 to 2100 lux.
To guide you, setting is divided into three ranges:
-
dark: 2 to 50 lux
-
overcast: 60 to 300 lux
-
light: 350 to 2100 lux
2- Set the time delay on switch-on and switch-off, from 20 to 140 sec. (default
setting at 80 sec.). These time delays are used to lter parasitic transient
phenomena, for example lighting of a car at night (switch-off time delay), etc.
3- Change the program: return to the 3 pre-set programs: day, night and empty.
4- Modify the language
5- Modify the time format
6- Modify the date format
7
b
To perform one of these operations you must:
b
Press "Menu", access the mode " " via key "+"
b
"LUX VALUE": to adjust the brightness threshold
b
"DELAY": to set the time delays:
v
"LIGHT ON": switch-on time delay
v
"LIGHT OFF": switch-off time delay
b
"PROGSTART": to choose one of the pre-set programs in the product
b
"LANGUAGE": to choose the language
b
"24h/12h": to modify time display over 24h or 12
b
"DATEFORM": to modify date display D/M/Y, M/D/Y or Y/M/D.
Load table
Output contact permissible power:
b
resistive loads: I max. = 16 A - 250 Va, I min = 100 mA - 12 V
v
motors: 2300 VA.
v
Lighting type/load Max power
resistive load (cos φ = 1) 16 A
inductive load (cos φ = 0.6) 10 A
incandescent lamps (230 V) 2300 W
halogen lamps (230 V) 2300 W
non-corrected/series-corrected uorescent tubes 26 x 36 W, 20 x 58 W, 10 x 100 W
parallel-corrected uorescent tubes with conventional
ballast
dual-mounted uorescent tubes 10 x (2 x 58 W), 5 x (2 x 100 W)
uorescent tubes with electronic ballast 9 x 36 W, 6 x 58 W
dual-mounted uorescent tubes with electronic ballast 5 x (2 x 36 W), 3 x (2 x 58 W)
uo-compact lamps with electronic ballast 9 x 7 W, 7 x 11 W, 7 x 15 W, 7 x 20 W
9
parallel-corrected mercury vapour lamps 1 x 250 W (30 µF)
parallel-corrected sodium vapour lamps 1 x 250 W (37 µF)
For other applications, relay using a CT contactor.
Schneider Electric Industries SAS
35 rue Joseph Monier
CS 30323
F-92506 Rueil Malmaison Cedex (France)
tel : +33 (0)1 41 29 70 00
http://www.schneider-electric.com
March at 2 h
March at 1 h
March at 3 h
April at 2 h
This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
As standards, specications and designs develop from time to time, always ask for conrmation of the information given in this publication.
Last Sunday in
October at 3 h
Last Sunday in
October at 2 h
Last Sunday in
October at 4 h
Last Sunday in
October at 3 h
h
10 x 36 W (4.7 µF), 6 x 58 W (7 µF),
2 x 100 W (18 µF)
Great Britain Portugal
Finland - Greece
-Turkey
USA - Canada
week and time
(between 1 h and 4 h)
"MAN" holidays
Move to the holiday mode " " :
Press "Menu", access the "MAN" mode via
b
the "+" key
The " " mode temporarily cancels On periods by
b
conguring the dates and times of start and end of
absence.
6
ON - OFF override " "
Activate temporary ON or OFF (up to the next
b
switching operation) by pressing for less than 2 sec.
simultaneously the 2 keys " ":
the output contact changes status
v
The IC2000P+ indicates by "MAN ON " or
b
"MAN OFF " the new status of the output contact
Return to automatic mode by pressing less than
b
2 sec. these 2 keys
Move to permanent ON or OFF by pressing more
b
than 2 sec. simultaneously the 2 keys " ":
each time you press for more than 2 sec., the output
v
contact changes status
The IC2000P+ indicates by "PERM ON " or
b
"PERM OFF " the new status of the output contact
Return to automatic mode by pressing less than
b
8
2 sec. these 2 keys.
The IC2000P+ also allows override external control
of lighting by NO contact, cabled to terminal 6
(external override takes priority over the product
ON-OFF override function).
Technical data
Consumption: max 3 VA
b
Back-lighting: activate by pressing a key, switch-off
b
after 5 min
Lux threshold: 2 to 2100 lx:
b
range 1: 2 to 50 lx
v
range 2: 60 to 300 lx
v
range 3: 350 to 2100 lx
v
Time delay: separate setting between 20 sec. and
b
140 sec. (80 sec. by default)
Contact: potential free
b
Time base: quartz
b
Operating accuracy: y ±1 sec. / day at 20°C
b
Number of switching operations: 42
b
Min switching: 1 minute
b
Switching accuracy: 1 second
b
Operating reserve: lithium battery; 5-6 years
b
Ambient temperature: -20°C...+50°C
b
Insulation class: II as per EN 60730-1 in installed
b
10
status
Degree of protection: IP20 as per EN 60529
b
RS type 1B as per EN 60730-1
Connection terminals:
b
max capacity: 6 mm
v
Pozidriv 1 or at 0.8 x 4 mm
v
Overall dimensions: 5 modules of 9 mm
b
Weight: 180 g
b
Cell
Photoresistance, 2-wire cable, 100 m max do not
b
install parallel to mains cables
IP54, IK05
b
Operating temperature: -40°C...+70°C
b
External input
Voltage: 230 Va +10 % -15 %
b
Frequency: 50/60 Hz
b
Input current: max 2.5 mA
b
Consumption: max 0.4 mW
b
Cable length: max 100 m.
b
2