schmersal TQ 700 S Operating Instructions Manual

Operating instructions Pull-wire switches
Operating instructions. . . . . . . . . . . . .pages 1 to 4
EN
Original
TQ 700 S
1. About this document
1.1 Function
This operating instructions manual provides all the information required for the mounting, set-up and commissioning to ensure the safe operation and disassembly of the safety switchgear. The operating instructions must be available in a legible condition and a complete version in the vicinity of the device.
1.2 Target group: authorised qualified personnel
All operations described in this operating instructions manual must be carried out by trained specialist personnel, authorised by the plant operator only.
Please make sure that you have read and understood these operating instructions and that you know all applicable legislations regarding occupational safety and accident prevention prior to installation and putting the component into operation.
The machine builder must carefully select the harmonised standards to be complied with as well as other technical specifications for the selection, mounting and integration of the components.
1.3 Explanation of the symbols used
Content
1 About this document
1.1 Function ..............................................1
1.2 Target group: authorised qualied personnel ..................1
1.3 Explanation of the symbols used ...........................1
1.4 Appropriate use ........................................1
1.5 General safety instructions ...............................1
1.6 Warning about misuse ...................................1
1.7 Exclusion of liability .....................................2
2 Product description
2.1 Ordering code .........................................2
2.2 Special versions........................................2
2.3 Destination and use .....................................2
2.4 Technical data .........................................2
3 Mounting
3.1 General mounting instructions .............................2
3.2 Assembly layout........................................2
3.3 Dimensions ...........................................3
Information, hint, note:
This symbol is used for identifying useful additional information.
Caution: Failure to comply with this warning notice could lead to failures or malfunctions. Warning: Failure to comply with this warning notice could lead to physical injury and/or damage to the machine.
1.4 Appropriate use
The product must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer. Detailed information regarding the range of applications can be found in the chapter "Product description".
1.5 General safety instructions
The user must observe the safety instructions in this operating instructions manual, the country-specific installation standards as well as all prevailing safety regulations and accident prevention rules.
Further technical information can be found in the Schmersal catalogues or in the online catalogue on the Internet: www.schmersal.net.
The information contained in this operating instructions manual is provided without liability and is subject to technical modifications.
There are no residual risks, provided that the safety instructions as well as the instructions regarding mounting, commissioning, operation and maintenance are observed.
1.6 Warning about misuse
4 Electrical connection
4.1 General information for electrical connection..................3
4.2 Contact variants........................................3
4.3 Switch travel diagrams...................................3
5 Set-up and maintenance
5.1 Functional testing.......................................3
5.2 Maintenance ..........................................3
6 Disassembly and disposal
6.1 Disassembly...........................................3
6.2 Disposal ..............................................3
7 EU Declaration of conformity
01.2017 / 574454-EN / F
EN
In case of inadequate or improper use or manipulations of the component, personal hazards or damage to machinery or plant components cannot be excluded.
1
Operating instructions Pull-wire switches
TQ 700 S
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual. The manufacturer shall accept no liability for damages resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary repairs, conversions and modifications to the device are strictly forbidden; the manufacturer shall accept no liability for damages resulting from such invasive work, arbitrary repairs, conversions and/or modifications to the device.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
kTQ 700-➀S-➁­No. Option Description
11 1 NO/1 NC contacts
20 2 NO contacts 02 2 NC contacts
40N Traction force 40 N
ST Connector plug M12 (A-coding)
2.2 Special versions
For special versions, which are not listed in the order code below 2.1, these specifications apply accordingly, provided that they correspond to the standard version.
Traction force 88 N
cable entry M20
2.4 Technical data
Standards: IEC 60947-5-1 Enclosure: thermoplastic Cover: thermoplastic Protection class: IP67 to IEC 60529 Protection rating: II, Degree of pollution: 3 Contact material: Silver Switching system: slow action with double break,
NC contact with positive break
Connection: screw terminal, connector plug M12 Cable section: 2.5 mm² (incl. conductor ferrules) Cable entry: 1 x M20 x 1.5 Rated impulse withstand voltage U
- screw terminal: 6 kV
- connector plug M12: 0.8 kV Rated insulation voltage Ui:
- screw terminal: 500 V
- connector plug M12: 50 V Thermal test current I Rated operating current/voltage Ie/Ue: 4 A / 230 VAC,
Utilisation category: AC-15, DC-13 Required short-circuit current: 1000 A Max. fuse rating: 6 A gG D-fuse (IEC 60269-1) Ambient temperature: –25 °C … +70 °C Relative humidity: 30 … 95%,
Mechanical life: >1 million operations Traction force F: 88 N (± 15 %)
- version TQ 700-..S-40N: 40 N (± 15%)
: 10 A
the
:
imp
4 A / 24 VDC
no condensation,
no icing
X
A
2.3 Destination and use
Pull-wire switches are used to give signals to start machines and to open or close electrically-driven doors and gates. If the pull-wire is pulled, the switching function of the pull-wire switch is activated.
AWG 14, Solid/Stranded. Max. torque: 7 in. lb. Use copper conductors only.
3. Mounting
3.1 General mounting instructions
The installation may only be carried out by authorised personnel. The pull-wire switch is fitted by means of four screws (distance of the drill holes 30 mm or 60 mm).
3.2 Assembly layout
The pull-wire switch must be fitted vertically. (Pull wire with ball available as accessory.)
Traction force F
2
EN
Operating instructions
14
13
12
11
21
14
13
24
23
13
14
11
12
13
14
0
4
3
3,7
5
0
3
3,7
5
11-12
21-22
0
4
5
0
3
2
5
0
2
5
11-12
21-22
0
3
5
Pull-wire switches
TQ 700 S
3.3 Dimensions
All measurements in mm.
TQ 700 S
60
M20x1,5
160
17
30,5
40,5
42,2
2
p/M5
30
40,5
4. Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out by authorised personnel in a de-energised condition.
1. Cover screws must be loosened
2. Dust shield cap remove
3. Cable glands M20 x 1.5 with an appropriate degree of protection must be used
4. When wiring, please ensure that no cables are located within the range of the lever system
5. The inside of the switch must be imperatively cleaned (e.g. removal of cable residues), considering that foreign bodies can affect the switching behaviour
6. The cover screws must be tightened uniformly (tightening torque 0.5 Nm)
4.3 Switch travel diagrams
TQ 700-11S TQ 700-02S
13-14
21-22
TQ 700-20S
13-14
23-24
TQ 700-11S-40N TQ 700-02S-40N
13-14
21-22
TQ 700-20S-40N
13-14
23-24
5. Set-up and maintenance
5.1 Functional testing
The function of the component must be tested. The following conditions must be previously checked and met:
1. Correct fixing of the pull-wire switch
2. Check the integrity of the cable entry and connections
3. Check the switch enclosure for damage
4. Check the functionality of the switch by actuating the wire
5.2 Maintenance
A regular visual inspection and functional test, including the following steps, is recommended:
1. Check the functionality of the switch by actuating the wire
2. Check the cable entries and the wire connections
3. Remove particles of dust and soiling
Do not open the device when live.
Damaged or defective components must be replaced.
Accessories cable gland:
Ordering code: 103006013 Authorised cable diameter: 6 - 12 mm Tightening torque: 4.5 Nm
4.2 Contact variants
The symbols are shown for the switch in non-actuated condition.
TQ 700-11S TQ 700-02S TQ 700-20S
21
Connector
TQ 700-11S-...-ST TQ 700-02S-...-ST TQ 700-20S-...-ST
21
Key
A
22
22
1234
Positive break NC contact
21
1234
22
22
23
24
1234
6. Disassembly and disposal
6.1 Disassembly
The switch must be disassembled in a de-energised condition only.
6.2 Disposal
The switch must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations.
EN
3
Operating instructions Pull-wire switches
7. EU Declaration of conformity

EU Declaration of conformity

TQ 700 S
Original ACE Schmersal
We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives.
Name of the component: TQ 700 S
Type: See ordering code
Description of the component: Pull-wire switches
Relevant Directives: Low Voltage Directive
Eletroeletrônica Industrial Ltda. Av. Brasil, nº 815 Jardim Esplanada CEP: 18550-000 Boituva – SP Brazil Internet: www.schmersal.com.br
RoHS-Directive
2014/35/EU 2011/65/EU
Applied standards: DIN EN 60947-5-1:2010
Person authorised for the compilation of the technical documentation:
Place and date of issue: Boituva, 11. Januar 2017
TQ700S-F-EN
K.A. Schmersal GmbH & Co. KG
Möddinghofe 30, D - 42279 Wuppertal Postfach 24 02 63, D - 42232 Wuppertal
Phone +49 - (0)2 02 - 64 74 - 0 Telefax: +49 - (0)2 02 - 64 74 - 1 00 E-Mail: info@schmersal.com Internet: http://www.schmersal.com
Oliver Wacker Möddinghofe 30 42279 Wuppertal
Authorised signature
Marco Antonio De Dato
Head of Engineering and Design
Production site:
ACE Schmersal
Eletroeletrônica Industrial Ltda. Av. Brasil, nº 815 Jardim Esplanada – CEP: 18550-000, Boituva – SP Brazil Phone +55 - (0)15 - 32 63 - 9866 Fax +55 - (0)15 - 32 63 - 9890 E-Mail: vendas@schmersal.com.br Internet: http://www.schmersal.com.br
4