schmersal SRB-E-301MC Operating Instructions Manual

Operating instructions Safety-monitoring module
Operating instructions. . . . . . . . . . . .pages 1 to 10
EN
Original
SRB-E-301MC
7 Wiring examples
7.1 Possible applications ....................................6
7.2 Application example.....................................6
7.3 Start conguration ......................................7
7.4 Sensor conguration ....................................7
8 Set-up and maintenance
8.1 Commissioning ........................................8
8.2 Functional testing.......................................8
8.3 Behaviour in the case of faults.............................8
8.4 Setting report ..........................................8
8.5 Maintenance ..........................................8
9 Disassembly and disposal
9.1 Disassembly...........................................8
9.2 Disposal ..............................................8
10 Appendix
10.1 Wiring/circuit information ................................8
11 EU Declaration of conformity
Content
1 About this document
1.1 Function ..............................................1
1.2 Target group: authorised qualied personnel..................1
1.3 Explanation of the symbols used ...........................1
1.4 Appropriate use ........................................2
1.5 General safety instructions ...............................2
1.6 Warning about misuse ...................................2
1.7 Exclusion of liability .....................................2
2 Product description
2.1 Ordering code .........................................2
2.2 Special versions........................................2
2.3 Destination and use .....................................2
2.4 Technical data .........................................2
2.5 Derating / electrical lifespan of safety contacts ................3
2.6 Safety classication ....................................3
3 Mounting
3.1 General mounting instructions .............................4
3.2 Dimensions ...........................................4
4 Electrical connection
4.1 General information for electrical connection..................4
4.2 Coding of connecting terminals ............................4
5 Operating principle and settings
5.1 Description of the terminals and LED indications ..............4
5.2 Adjustable applications ..................................5
5.3 Changing setting or application ............................5
6 Diagnostic
6.1 LED indicators / malfunctions .............................6
1. About this document
1.1 Function
This operating instructions manual provides all the information you need for the mounting, set-up and commissioning to ensure the safe operation and disassembly of the safety-monitoring module. The operating instructions must be available in a legible condition and a complete version in the vicinity of the device.
1.2 Target group: authorised qualified personnel
All operations described in this operating instructions manual must be carried out by trained specialist personnel, authorised by the plant operator only.
Please make sure that you have read and understood these operating instructions and that you know all applicable legislations regarding occupational safety and accident prevention prior to installation and putting the component into operation.
The machine builder must carefully select the harmonised standards to be complied with as well as other technical specifications for the selection, mounting and integration of the components.
1.3 Explanation of the symbols used
Information, hint, note:
This symbol is used for identifying useful additional information.
Caution: Failure to comply with this warning notice could lead to failures or malfunctions. Warning: Failure to comply with this warning notice could lead to physical injury and/or damage to the machine.
x.000 / 07.2018 / v.A. - 103014373-EN / B / 2018-07-17 / AE-Nr. 9647
EN
1
Operating instructions Safety-monitoring module
SRB-E-301MC
1.4 Appropriate use
The products described in these operating instructions are developed to execute safety-related functions as part of an entire plant or machine. It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant.
The safety-monitoring module must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer. Detailed information regarding the range of applications can be found in the chapter "Product description".
1.5 General safety instructions
The user must observe the safety instructions in this operating instructions manual, the country-specific installation standards as well as all prevailing safety regulations and accident prevention rules.
Further technical information can be found in the Schmersal catalogues or in the online catalogue on the Internet: www.schmersal.net.
The information contained in this operating instructions manual is provided without liability and is subject to technical modifications. There are no residual risks, provided that the safety instructions as well as the instructions regarding mounting, commissioning, operation and maintenance are observed.
1.6 Warning about misuse
In case of inadequate or improper use or manipulations of the safety-monitoring module, personal hazards or damage to machinery or plant components cannot be excluded. The relevant requirements of the standards ISO 14119 and EN ISO 13850 must be observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual. The manufacturer shall accept no liability for damages resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary repairs, conversions and modifications to the device are strictly forbidden; the manufacturer shall accept no liability for damages resulting from such invasive work, arbitrary repairs, conversions and/or modifications to the device.
The safety relay module is to be operated in an area in which access by personnel is restricted.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
SRB-E-301MC­No. Option Description
CC Plug-in cage clamps: single wire (rigid)
(Signal contact 41/42, normally-closed contacts parallel)
SRB-E-301MC20­No. Option Description
CC Plug-in cage clamps: single wire (rigid)
(Signal contact 41/42, normally-closed contacts in series)
2.2 Special versions
For special versions, which are not listed in the order code below 2.1, these specifications apply accordingly, provided that they correspond to the standard version.
2.3 Destination and use
The safety-monitoring modules for integration in safety circuits are designed for fitting in control cabinets. They are used for the safe evaluation of the signals of positive break position switches or safety sensors for safety functions on sliding, hinged and removable safety guards as well as emergency stop control devices, safety solenoid switches and AOPD's.
The safety function is defined as deactivating outputs 13/14, 23/24, 33/34 when inputs S12 and/or S22 are opened. Taking account of a PFH value assessment, the safety-relevant current paths meet the following requirements (see also chapter 2.6 “Safety classification”):
• Control category 4 - PL e to ISO 13849-1
• SIL 3 to IEC 61508
• SILCL 3 to EN 62061
Plug-in screw clamps: single wire (rigid) or fine wire (flexible): 0.2 … 2.5 mm²; fine wire with ferrule: 0.25 … 2.5 mm²
or fine wire (flexible): 0.2 … 1.5 mm²; fine wire with ferrule: 0.25 … 1.5 mm²
Plug-in screw clamps: single wire (rigid) or fine wire (flexible): 0.2 … 2.5 mm²; fine wire with ferrule: 0.25 … 2.5 mm²
or fine wire (flexible): 0.2 … 1.5 mm²; fine wire with ferrule: 0.25 … 1.5 mm²
Only if the action described in these operating instructions is carried out correctly will the safety function be safeguarded, including compliance with the Machinery Directive.
To determine the Performance Level (PL) to ISO 13849-1 of the entire safety function (e.g. sensor, logic, actuator), an assessment of all relevant components is required.
The entire concept of the control system, in which the safety component is integrated, must be validated to the relevant standards.
2.4 Technical data General data
Standards: EN 60204-1, IEC 60947-5-1; ISO 13849-1,
IEC 62061, IEC 61508
EMC rating: to EMC Directive Air clearances and creepage distances: to IEC 60664-1 Mounting: standard rail in accordance with IEC 60715 Terminal designations: IEC 60947-1
2
EN
Operating instructions
10.000.000
0 1 2 3 4 5 6 7 8 9
Safety-monitoring module
SRB-E-301MC
Electrical characteristics:
Rated operating voltage Ue: 24 VDC –15% / +20%,
residual ripple max. 10%
24 VAC –15% / +10%
Frequency range: 50 Hz/60 Hz Power consumption: 3.4 W, 8.5 VA Fuse rating for the operating voltage: internal fuse,
tripping current > 1A
Insulation values in accordance with IEC 60664-1: Rated insulation voltage Ui:
- Safety contacts: 250 V Rated impulse withstand voltage U
:
imp
- Safety contacts 13-14, 23-24, 33-34: 4 kV Overvoltage category: III Degree of pollution: 2 Pull-in delay: < 120 ms Drop-out delay in case of "emergency stop": < 10 ms Drop-out delay on "supply failure": < 50 ms Bridging in case of voltage drops: typ. 40 ms
Control current circuits/inputs:
Inputs S12, S22: 24 VDC/10 mA Inputs X2: 24 VDC/10 mA Cable length: 1500 m with 1.5 mm²;
2500 m with 2.5 mm²
Conduction resistance: max. 40 Ω
Relay outputs:
Switching capacity of the safety contacts: 13-14, 23-24, 33-34:
max. 250 VDC, 6 A ohmic,
min. 10 VDC / 10 mA
(Derating see 2.5)
Fuse rating of the safety contacts: external (Ik = 1000 A)
to IEC 60947-5-1
Safety fuse 10 A quick blow, 6 A slow blow
Utilisation category to IEC 60947-5-1: DC-13: 24 V / 4 A
AC-15: 230 V / 4 A
Switching capacity of the auxiliary contacts: 41-42: 24 VDC / 1 A Fuse rating for the auxiliary contact: safety fuse
1.5 A quick blow, 1 A slow blow
Electrical life: refer to 2.5 Mechanical life: 10 million operations
Safety contact values: resistance max. 100 mΩ, AgNi,
self-cleaning, positive action
Max. switching cycles / minute: 20 Inductive consumers: Provision should be made
for a suitable protection circuit.
Mechanical data:
Connection type: refer to 2.1 Cable section: refer to 2.1 Connecting cable: rigid or flexible Tightening torque for the terminals: 0.5 Nm Material of enclosure: glass-fibre reinforced thermoplastic, ventilated Weight: 175 g
Ambient conditions:
Ambient temperature: –25°C … +60°C
(non condensing)
Storage and transport temperature: –40°C … +85°C
(non condensing)
Protection class: Enclosure: IP40,
Terminals: IP20,
Clearance: IP54
Resistance to shock: 30 g / 11 ms Resistance to vibrations to IEC 60068-2-6: 10 ... 55 Hz, amplitude 0.35 mm Altitude: max. 2,000 m
2.5 Derating / electrical lifespan of safety contacts
No derating with individual installation of modules.
Derating on request if several modules are installed one after the other without spacing and with maximum output load and ambient temperatures.
Electrical life of the safety contacts
Operations
DC1 24V
1.000.000
AC1 230V
100.000
10.000
AC15 230V
DC13 24V
Contact load in amperes
2.6 Safety classification
2.6.1 Classification of relay output
Standards: ISO 13849-1, IEC 61508, IEC 62061 PL: e Control Category: 4 DC: high CCF: > 65 points PFHD: ≤ 6.0 x 10-9 / h PFD
: ≤ 4.0 x 10
avg
-4
SIL: suitable for SIL 3 applications Service life: 20 years
The PFH value of 6.0 × 10-9/h applies to the combinations of contact load (current through enabling contacts) and number of switching cycles (n
) mentioned in the table below. At 365 operating days per
op/y
year and a 24-hours operation, this results in the below-mentioned switching cycle times (t
) for the relay contacts.
cycle
Diverging applications upon request.
Contact load n
op/y
t
cycle
20 % 880,000 0.6 min 40 % 330,000 1.6 min 60 % 110,000 5.0 min 80 % 44,000 12.0 min
100 % 17,600 30.0 min
The data specified in this manual apply for operation of equipment with rated operating voltage Ue ±0%.
EN
3
Operating instructions Safety-monitoring module
SRB-E-301MC
3. Mounting
3.1 General mounting instructions
Mounting: snaps onto standard DIN rails to IEC 60715.
Hook bottom of enclosure in DIN rail and push down until it engages in position.
3.2 Dimensions
All measurements in mm. Device dimensions (H/W/D): 98 x 22.5 x 115 mm
4. Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out by authorised personnel in a de-energised condition.
To avoid EMC disturbances, the physical ambient and operational conditions at the place where the product is installed, must meet the provisions laid down in the paragraph "Electromagnetic Compatibility (EMC)" of DIN EN 60204-1.
4.2 Coding of connecting terminals
5. Operating principle and settings
5.1 Description of the terminals and LED indications
Pin Function LED Function
A1 Operating voltage
+ 24 VDC 24 VAC
U
Operating voltage OK
B
U
Internal fuse OK
i
A2 Operating voltage
0 V 24 VAC
QS Cross-wire monitoring active
X1 Output start circuit /
feedback circuit
X2 Input start circuit /
feedback circuit
S11 Output channel 1 +24 VDC S21 Output channel 2 +24 VDC without QS
0 V with QS
S12 Input channel 1 K1 Status K1 S22 Input channel 2 K2 Status K2 41/42 Signalling contact (NC) 13/14,
Safety outputs
23/24, 33/34
S11 13 23 33
mode
1
U
B
U
i
K1 K2
QS
342414S12
SRB-E-301MC
A1X141S22 A2X242S21
4
EN
Operating instructions Safety-monitoring module
5.2 Adjustable applications
SRB-E-301MC
Adjustment of application using rotary “mode” switch
• Open front transparent cover (see fig.).
• Opening is carried out by lifting side with lock.
• Select desired application using rotary mode switch by turning up or down (see 5.3).
• After performing setting, close front cover again.
• Front cover can be secured with a lead seal to protect it from being opened unintentionally
Only touch the components after electrical discharge!
Rotary knob
position
1, 5, 9, 13 Yes Yes NC / NC
2, 6, 10, 14 Yes No NC / NC
5.3 Changing setting or application
Description / procedure Rotary (mode) switch System response LED indications
Factory setting Position 1 Ready for application 1 - - ­Switch operating voltage on Position 1 Ready for application 1 Lights up Lights up Lights up
Change SRB-E application
Switch off operating voltage Select desired application (2) - - ­Switch operating voltage on Ready for application 2 Lights up Lights up
Reset button /
feedback circuit
Cross-wire
monitoring active
Input / Sensor
configuration
U
U
B
QS
i
EN
5
Operating instructions
+24VDC
L1
Safety-monitoring module
SRB-E-301MC
6. Diagnostic
6.1 LED indicators / malfunctions
LED Function Display type
Ready for operation Continuously lit
U
B
No operating voltage at A1 and A2 Not lit Operationally ready and internal fuse OK Continuously lit No operating voltage at A1 and A2
U
i
Internal fuse triggered
Not lit
Relay channel 1 active Continuously lit Input S12 open, relay K1 deactivated
K1
Not litManual start signal, feedback circuit missing Invalid rotary switch setting Relay channel 2 active Continuously lit Input S22 open, relay K2 deactivated
K2
Not litManual start signal, feedback circuit missing Invalid rotary switch setting
7. Wiring examples
7.1 Possible applications
All applications for 1 or 2-channel safe evaluation for protective equipment as follows:
• Safety door monitoring to ISO 14119
• Position switches with positive break to IEC 60947-5-1
• Safety sensors to EN 60947-5-3
• Emergency stop command devices to ISO 13850 and IEC 60947-5-5
• Magnetic safety sensors to EN 60947-5-3
• Safety light curtain and photoelectric barriers according to IEC 61496
The connection of magnetic safety switches to the SRB-E-... safety-monitoring module is only admitted when the requirements of the standard IEC 60947-5-3 are observed.
As the technical data are regarded, the following minimum requirements must be met:
Switching capacity: min. 240 mW
Switching voltage: min. 24 VDC
switching current: min. 10 mA
7.2 Application example
Dual-channel control, shown for a guard door monitor with two position switches where one has a positive break contact; with external reset button
J
• Relay outputs: Suitable for 2-channel control, for increase in capacity or number of contacts by means of contactors or relays with positive­guided contacts
• H2 = Feedback circuit
Signalling outputs must not be used in safety circuits.
Wiring example
F1
H2
K
R
A
K
B
Option 20
41
A
B
42
0V / GND
e)f)
K1 K2
X2A1 S22S11A2S21X1S12
a)d)
K1
K2
K
A
2313 33 41
2414 34 42
K
B
K
K
N
Key
a) Safety inputs d) Outputs e) Processing f) Power
For example, the following safety sensors meet the requirements:
BNS 36-02Z(G), BNS 36-02/01Z(G)
BNS 260-02Z(G), BNS 260-02/01Z(G)
When sensors with LED are wired in the control circuit (protective circuit), the following rated operating voltage must be observed and respected:
• 24 VDC with a max. tolerance of –5%/+20%
Otherwise availability problems could occur, especially in series-wired sensors, where a voltage drop in the control circuit is triggered by LED's for instance.
6
EN
Operating instructions Safety-monitoring module
SRB-E-301MC
7.3 Start configuration
7.3.1 External reset button
The external reset button is integrated in the feedback circuit in series.
• The manual start or the activation of the module occurs when the button is pressed (not when it is released!).
X1
+24 VDC
J
J
K
K
A
A
K
K
B
B
X2
X2
7.3.2 Feedback circuit / Automatic start
• The automatic start is programmed by connecting the feedback circuit to the terminals X1-X2. If the feedback circuit is not required, establish a bridge.
Not admitted without additional measure due to the risk of gaining access by stepping behind!
Within the meaning of IEC/EN 60204-1 paragraph 9.2.5.4.2 the operating mode "automatic start" is only restrictedly ad­missible. In particular, any inadvertent restart of the machine must be prevented by other suitable measures.
+24 VDC
K
K
A
A
K
K
B
B
7.4 Sensor configuration
Single channel signal processing
S11 S21
+24 VDC
S12 S22 S12 S22
Rotary knob position Function
2, 6, 10, 14 without cross-wire monitoring
Dual channel signal processing NC / NC
With cross-wire monitoring
(Category 4 – PL e to ISO 13849-1 possible)
S11 S21
S12 S22
Rotary knob position Function
1, 5, 9, 13 with cross-wire monitoring
Without cross-wire monitoring
(Cat. 4 - PL e to ISO 13849-1 only possible with protective wiring)
S11 S21
S11 S21
S12 S22
S11 S21
+24 VDC
+24V
+24V
X2X1X2
S12 S22
Rotary knob position Function
2, 6, 10, 14 without cross-wire monitoring
S12 S22
S12 S22
S12
S22
EN
7
Operating instructions Safety-monitoring module
SRB-E-301MC
8. Set-up and maintenance
8.1 Commissioning
The safety relay module features protection class IP54 for installation in a switch cabinet.
The safety relay module is delivered ready for operation.
Application 1 is preset in the factory.
8.2 Functional testing
The safety function of the safety-monitoring module must be tested. The following conditions must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3. Check the safety-monitoring module's enclosure for damage
4. Check the electrical function of the connected sensor technology and their influence on the safety-monitoring module and the downstream actuators
The safety relay module features self-test functions. If a fault is detected, the system adopts a safe mode and leads, if necessary, to undelayed deactivation of all safety outputs.
8.3 Behaviour in the case of faults
In the event of a fault the following procedure is recommended:
1. Identify faults according to chapter 6.1.
2. Rectify the fault if it is described in the table.
If fault could not be rectified, please contact the manufacturer.
8.4 Setting report
This report regarding the setting of the device must be completed accordingly by the customer and enclosed in the technical documentation of the machine.
The setting report must be available whenever a safety check is performed.
8.5 Maintenance
A regular visual inspection and functional test, including the following steps, is recommended:
1. Check the correct fixing of the safety-monitoring module
2. Check the cable for damages
3. Check electrical function
If a manual functional check is necessary to detect a possible accumulation of faults, then this must take place during the intervals noted as follows:
• at least every month for PL e with category 3 or category 4 (according to ISO 13849-1) or SIL 3 with HFT (hardware fault tolerance) = 1 (according to IEC 62061);
• at least every 12 months for PL d with category 3 (according to ISO 13849-1) or SIL 2 with HFT (hardware fault tolerance) = 1 (according to IEC 62061).
Damaged or defective components must be replaced.
9. Disassembly and disposal
9.1 Disassembly
The safety-monitoring module must be disassembled in a de-energised condition only.
9.2 Disposal
The safety-monitoring module must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations.
10. Appendix
10.1 Wiring/circuit information
Company:
The safety-monitoring module is used in the following machine:
Machine n° Machine type Module n°
Configured application (mode):
Set on (date) Signature of the responsible person
Air clearances and creepage distances of the safety contacts:
S11 13 23 33
mode
U U
K1 K2
QS
342414S12
1
B
i
SRB-E-301MC
A1X141S22 A2X242S21
The safety contacts comply with the requirements for basic insulation.
8
EN
Operating instructions Safety-monitoring module
11. EU Declaration of conformity

EU Declaration of conformity

SRB-E-301MC
Original K.A. Schmersal GmbH & Co. KG
We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives.
Name of the component: SRB-E-301MC
Type: See ordering code
Description of the component: Relay-safety combination for emergency stop circuits,
Relevant Directives: Machinery Directive
Applied standards: DIN EN 60947-5-1:2010,
Notied body for the prototype test: DGUV Test Prüf- und Zertizierungsstelle Elektrotechnik
Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com
guard door monitoring, solenoid safety switches and AOPDs
EMC-Directive RoHS-Directive
DIN EN ISO 13849-1:2016, DIN EN ISO 13849-2:2013
Fachbereich Energie Textil Elektro Medienerzeugnisse der Deutschen Gesetzlichen Unfallversicherung e.V. (DGUV)
Gustav-Heinemann-Ufer 130, 50968 Köln, Deutschland ID n°: 0340
2006/42/EC 2014/30/EU 2011/65/EU
EC-prototype test certicate: ET 18044
Person authorised for the compilation of the technical documentation:
Place and date of issue: Wuppertal, July 12, 2018
SRB-E-301MC-B-EN
Oliver Wacker Möddinghofe 30 42279 Wuppertal
Authorised signature
Philip Schmersal
Managing Director
The currently valid declaration of conformity can be downloaded from the internet at www.schmersal.net.
EN
9
K. A. Schmersal GmbH & Co. KG
Möddinghofe 30, D - 42279 Wuppertal Postfach 24 02 63, D - 42232 Wuppertal
Phone: +49 - (0)2 02 - 64 74 - 0 Telefax: +49 - (0)2 02 - 64 74 - 1 00 E-Mail: info@schmersal.com Internet: http://www.schmersal.com
Loading...