1. About this document
1.1 Function
This operating instructions manual provides all the information you
need for the mounting, set-up and commissioning to ensure the safe
operation and disassembly of the safety-monitoring module. The
operating instructions must be available in a legible condition and a
complete version in the vicinity of the device.
1.2 Target group: authorised qualified personnel
All operations described in this operating instructions manual must
be carried out by trained specialist personnel, authorised by the plant
operator only.
Please make sure that you have read and understood these operating
instructions and that you know all applicable legislations regarding
occupational safety and accident prevention prior to installation and
putting the component into operation.
The machine builder must carefully select the harmonised standards
to be complied with as well as other technical specifications for the
selection, mounting and integration of the components.
1.3 Explanation of the symbols used
Information, hint, note:
This symbol is used for identifying useful additional information.
Caution: Failure to comply with this warning notice could
lead to failures or malfunctions.
Warning: Failure to comply with this warning notice could
lead to physical injury and/or damage to the machine.
The products described in these operating instructions are developed to
execute safety-related functions as part of an entire plant or machine. It
is the responsibility of the manufacturer of a machine or plant to ensure
the correct functionality of the entire machine or plant.
The safety-monitoring module must be exclusively used in accordance
with the versions listed below or for the applications authorised by the
manufacturer. Detailed information regarding the range of applications
can be found in the chapter "Product description".
1.5 General safety instructions
The user must observe the safety instructions in this operating
instructions manual, the country-specific installation standards as well
as all prevailing safety regulations and accident prevention rules.
Further technical information can be found in the Schmersal
catalogues or in the online catalogue on the Internet:
www.schmersal.net.
The information contained in this operating instructions manual is
provided without liability and is subject to technical modifications. There
are no residual risks, provided that the safety instructions as well as
the instructions regarding mounting, commissioning, operation and
maintenance are observed.
1.6 Warning about misuse
In case of inadequate or improper use or manipulations of
the safety-monitoring module, personal hazards or damage
to machinery or plant components cannot be excluded.
The relevant requirements of the standards ISO 14119 and
EN ISO 13850 must be observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages
resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary
repairs, conversions and modifications to the device are strictly
forbidden; the manufacturer shall accept no liability for damages
resulting from such invasive work, arbitrary repairs, conversions and/or
modifications to the device.
The safety relay module is to be operated in an area in which access by
personnel is restricted.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
(Signal contact 41/42, normally-closed contacts in series)
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The safety-monitoring modules for integration in safety circuits are
designed for fitting in control cabinets. They are used for the safe
evaluation of the signals of positive break position switches or safety
sensors for safety functions on sliding, hinged and removable safety
guards as well as emergency stop control devices, safety solenoid
switches and AOPD's.
The safety function is defined as deactivating outputs 13/14, 23/24,
33/34 when inputs S12 and/or S22 are opened. Taking account of a
PFH value assessment, the safety-relevant current paths meet the
following requirements (see also chapter 2.6 “Safety classification”):
• Control category 4 - PL e to ISO 13849-1
• SIL 3 to IEC 61508
• SILCL 3 to EN 62061
➀
Plug-in screw clamps: single wire (rigid)
or fine wire (flexible): 0.2 … 2.5 mm²;
fine wire with ferrule: 0.25 … 2.5 mm²
or fine wire (flexible): 0.2 … 1.5 mm²;
fine wire with ferrule: 0.25 … 1.5 mm²
➀
Plug-in screw clamps: single wire (rigid)
or fine wire (flexible): 0.2 … 2.5 mm²;
fine wire with ferrule: 0.25 … 2.5 mm²
or fine wire (flexible): 0.2 … 1.5 mm²;
fine wire with ferrule: 0.25 … 1.5 mm²
Only if the action described in these operating instructions is
carried out correctly will the safety function be safeguarded,
including compliance with the Machinery Directive.
To determine the Performance Level (PL) to ISO 13849-1 of the entire
safety function (e.g. sensor, logic, actuator), an assessment of all
relevant components is required.
The entire concept of the control system, in which the
safety component is integrated, must be validated to the
relevant standards.
2.4 Technical data
General data
Standards:EN 60204-1, IEC 60947-5-1; ISO 13849-1,
IEC 62061, IEC 61508
EMC rating: to EMC Directive
Air clearances and creepage distances:to IEC 60664-1
Mounting:standard rail in accordance with IEC 60715
Terminal designations:IEC 60947-1
2
EN
Operating instructions
10.000.000
0 1 2 3 4 5 6 7 8 9
Safety-monitoring module
SRB-E-301MC
Electrical characteristics:
Rated operating voltage Ue: 24 VDC –15% / +20%,
residual ripple max. 10%
24 VAC –15% / +10%
Frequency range:50 Hz/60 Hz
Power consumption:3.4 W, 8.5 VA
Fuse rating for the operating voltage:internal fuse,
tripping current > 1A
Insulation values in accordance with IEC 60664-1:
Rated insulation voltage Ui:
- Safety contacts:250 V
Rated impulse withstand voltage U
:
imp
- Safety contacts 13-14, 23-24, 33-34:4 kV
Overvoltage category: III
Degree of pollution: 2
Pull-in delay:< 120 ms
Drop-out delay in case of "emergency stop":< 10 ms
Drop-out delay on "supply failure":< 50 ms
Bridging in case of voltage drops: typ. 40 ms
Control current circuits/inputs:
Inputs S12, S22:24 VDC/10 mA
Inputs X2:24 VDC/10 mA
Cable length:1500 m with 1.5 mm²;
2500 m with 2.5 mm²
Conduction resistance: max. 40 Ω
Relay outputs:
Switching capacity of the safety contacts:13-14, 23-24, 33-34:
max. 250 VDC, 6 A ohmic,
min. 10 VDC / 10 mA
(Derating see 2.5)
Fuse rating of the safety contacts: external (Ik = 1000 A)
to IEC 60947-5-1
Safety fuse 10 A quick blow, 6 A slow blow
Utilisation category to IEC 60947-5-1:DC-13: 24 V / 4 A
AC-15: 230 V / 4 A
Switching capacity of the auxiliary contacts:41-42: 24 VDC / 1 A
Fuse rating for the auxiliary contact:safety fuse
1.5 A quick blow, 1 A slow blow
Electrical life:refer to 2.5
Mechanical life:10 million operations
Max. switching cycles / minute: 20
Inductive consumers:Provision should be made
for a suitable protection circuit.
Mechanical data:
Connection type:refer to 2.1
Cable section:refer to 2.1
Connecting cable:rigid or flexible
Tightening torque for the terminals:0.5 Nm
Material of enclosure:glass-fibre reinforced thermoplastic, ventilated
Weight:175 g
Ambient conditions:
Ambient temperature:–25°C … +60°C
(non condensing)
Storage and transport temperature:–40°C … +85°C
(non condensing)
Protection class:Enclosure: IP40,
Terminals: IP20,
Clearance: IP54
Resistance to shock:30 g / 11 ms
Resistance to vibrations
to IEC 60068-2-6:10 ... 55 Hz, amplitude 0.35 mm
Altitude:max. 2,000 m
2.5 Derating / electrical lifespan of safety contacts
No derating with individual installation of modules.
Derating on request if several modules are installed one after the
other without spacing and with maximum output load and ambient
temperatures.
Electrical life of the safety contacts
Operations
DC1 24V
1.000.000
AC1 230V
100.000
10.000
AC15 230V
DC13 24V
Contact load in amperes
2.6 Safety classification
2.6.1 Classification of relay output
Standards:ISO 13849-1, IEC 61508, IEC 62061
PL: e
Control Category: 4
DC: high
CCF:> 65 points
PFHD: ≤ 6.0 x 10-9 / h
PFD
: ≤ 4.0 x 10
avg
-4
SIL:suitable for SIL 3 applications
Service life:20 years
The PFH value of 6.0 × 10-9/h applies to the combinations of contact
load (current through enabling contacts) and number of switching
cycles (n
) mentioned in the table below. At 365 operating days per
op/y
year and a 24-hours operation, this results in the below-mentioned
switching cycle times (t
) for the relay contacts.
cycle
Diverging applications upon request.
Contact loadn
op/y
t
cycle
20 %880,0000.6 min
40 %330,0001.6 min
60 %110,0005.0 min
80 %44,00012.0 min
100 %17,60030.0 min
The data specified in this manual apply for operation of equipment with
rated operating voltage Ue ±0%.
EN
3
Operating instructions
Safety-monitoring module
SRB-E-301MC
3. Mounting
3.1 General mounting instructions
Mounting: snaps onto standard DIN rails to IEC 60715.
Hook bottom of enclosure in DIN rail and push down until it engages in
position.
3.2 Dimensions
All measurements in mm.
Device dimensions (H/W/D): 98 x 22.5 x 115 mm
4. Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out by
authorised personnel in a de-energised condition.
To avoid EMC disturbances, the physical ambient and
operational conditions at the place where the product is
installed, must meet the provisions laid down in the
paragraph "Electromagnetic Compatibility (EMC)" of
DIN EN 60204-1.
4.2 Coding of connecting terminals
5. Operating principle and settings
5.1 Description of the terminals and LED indications
PinFunctionLED Function
A1Operating voltage
+ 24 VDC
24 VAC
U
Operating voltage OK
B
U
Internal fuse OK
i
A2Operating voltage
0 V
24 VAC
QSCross-wire monitoring active
X1Output start circuit /
feedback circuit
X2Input start circuit /
feedback circuit
S11Output channel 1+24 VDC
S21Output channel 2+24 VDC without QS
All applications for 1 or 2-channel safe evaluation for protective
equipment as follows:
• Safety door monitoring to ISO 14119
• Position switches with positive break to IEC 60947-5-1
• Safety sensors to EN 60947-5-3
• Emergency stop command devices to ISO 13850 and IEC 60947-5-5
• Magnetic safety sensors to EN 60947-5-3
• Safety light curtain and photoelectric barriers according to IEC 61496
The connection of magnetic safety switches to the SRB-E-...
safety-monitoring module is only admitted when the
requirements of the standard IEC 60947-5-3 are observed.
As the technical data are regarded, the following minimum
requirements must be met:
•
Switching capacity: min. 240 mW
•
Switching voltage: min. 24 VDC
•
switching current: min. 10 mA
7.2 Application example
Dual-channel control, shown for a guard door monitor with
two position switches where one has a positive break contact;
with external reset button
J
• Relay outputs: Suitable for 2-channel control, for increase in capacity
or number of contacts by means of contactors or relays with positiveguided contacts
• H2 = Feedback circuit
Signalling outputs must not be used in safety circuits.
Wiring example
F1
H2
K
R
A
K
B
Option 20
41
A
B
42
0V / GND
e)f)
K1K2
X2A1S22S11A2S21X1S12
a)d)
K1
K2
K
A
231333 41
241434 42
K
B
K
K
N
Key
a) Safety inputs
d) Outputs
e) Processing
f) Power
For example, the following safety sensors meet the
requirements:
•
BNS 36-02Z(G), BNS 36-02/01Z(G)
•
BNS 260-02Z(G), BNS 260-02/01Z(G)
When sensors with LED are wired in the control circuit
(protective circuit), the following
rated operating voltage must be observed and respected:
• 24 VDC with a max. tolerance of –5%/+20%
Otherwise availability problems could occur, especially in
series-wired sensors, where a voltage drop in the control
circuit is triggered by LED's for instance.
6
EN
Operating instructions
Safety-monitoring module
SRB-E-301MC
7.3 Start configuration
7.3.1 External reset button
•
The external reset button is integrated in the feedback circuit in series.
• The manual start or the activation of the module occurs when the
button is pressed (not when it is released!).
X1
+24VDC
J
J
K
K
A
A
K
K
B
B
X2
X2
7.3.2 Feedback circuit / Automatic start
• The automatic start is programmed by connecting the feedback circuit
to the terminals X1-X2. If the feedback circuit is not required, establish
a bridge.
Not admitted without additional measure due to the risk of
gaining access by stepping behind!
Within the meaning of IEC/EN 60204-1 paragraph 9.2.5.4.2
the operating mode "automatic start" is only restrictedly admissible. In particular, any inadvertent restart of the machine
must be prevented by other suitable measures.
+24VDC
K
K
A
A
K
K
B
B
7.4 Sensor configuration
Single channel signal processing
S11 S21
+24VDC
S12 S22S12 S22
Rotary knob positionFunction
2, 6, 10, 14without cross-wire monitoring
Dual channel signal processing NC / NC
With cross-wire monitoring
(Category 4 – PL e to ISO 13849-1 possible)
S11 S21
S12 S22
Rotary knob positionFunction
1, 5, 9, 13with cross-wire monitoring
Without cross-wire monitoring
(Cat. 4 - PL e to ISO 13849-1 only possible with protective wiring)
S11 S21
S11 S21
S12 S22
S11 S21
+24VDC
+24V
+24V
X2X1X2
S12 S22
Rotary knob positionFunction
2, 6, 10, 14without cross-wire monitoring
S12 S22
S12 S22
S12
S22
EN
7
Operating instructions
Safety-monitoring module
SRB-E-301MC
8. Set-up and maintenance
8.1 Commissioning
The safety relay module features protection class IP54 for installation
in a switch cabinet.
The safety relay module is delivered ready for operation.
Application 1 is preset in the factory.
8.2 Functional testing
The safety function of the safety-monitoring module must be tested.
The following conditions must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3. Check the safety-monitoring module's enclosure for damage
4. Check the electrical function of the connected sensor technology and
their influence on the safety-monitoring module and the downstream
actuators
The safety relay module features self-test functions.
If a fault is detected, the system adopts a safe mode and leads,
if necessary, to undelayed deactivation of all safety outputs.
8.3 Behaviour in the case of faults
In the event of a fault the following procedure is recommended:
1. Identify faults according to chapter 6.1.
2. Rectify the fault if it is described in the table.
If fault could not be rectified, please contact the manufacturer.
8.4 Setting report
This report regarding the setting of the device must be completed
accordingly by the customer and enclosed in the technical
documentation of the machine.
The setting report must be available whenever a safety check is
performed.
8.5 Maintenance
A regular visual inspection and functional test, including the following
steps, is recommended:
1. Check the correct fixing of the safety-monitoring module
2. Check the cable for damages
3. Check electrical function
If a manual functional check is necessary to detect a
possible accumulation of faults, then this must take place
during the intervals noted as follows:
• at least every month for PL e with category 3 or
category 4 (according to ISO 13849-1) or SIL 3 with HFT
(hardware fault tolerance) = 1 (according to IEC 62061);
• at least every 12 months for PL d with category 3
(according to ISO 13849-1) or SIL 2 with HFT (hardware
fault tolerance) = 1 (according to IEC 62061).
Damaged or defective components must be replaced.
9. Disassembly and disposal
9.1 Disassembly
The safety-monitoring module must be disassembled in a de-energised
condition only.
9.2 Disposal
The safety-monitoring module must be disposed of in an appropriate
manner in accordance with the national prescriptions and legislations.
10. Appendix
10.1 Wiring/circuit information
Company:
The safety-monitoring module is used in the following machine:
Machine n°Machine typeModule n°
Configured application (mode):
Set on (date)Signature of the responsible person
Air clearances and creepage distances of the safety contacts:
S11 13 23 33
mode
U
U
K1
K2
QS
342414S12
1
B
i
SRB-E-301MC
A1X141S22
A2X242S21
The safety contacts comply with the requirements for basic insulation.
8
EN
Operating instructions
Safety-monitoring module
11. EU Declaration of conformity
EU Declaration of conformity
SRB-E-301MC
OriginalK.A. Schmersal GmbH & Co. KG
We hereby certify that the hereafter described components both in their basic design and construction conform
to the applicable European Directives.
Name of the component:SRB-E-301MC
Type:See ordering code
Description of the component:Relay-safety combination for emergency stop circuits,
Relevant Directives:Machinery Directive
Applied standards:DIN EN 60947-5-1:2010,
Notied body for the prototype test:DGUV Test Prüf- und Zertizierungsstelle Elektrotechnik