schmersal CSS 34F0, CSS 34F1 Operating Instructions Manual

Operating instructions Safety sensor
Operating instructions. . . . . . . . . . . .pages 1 to 12
EN
Translation of the original operating instructions
CSS 34F0 CSS 34F1
7 Disassembly and disposal
7.1 Disassembly...........................................8
7.2 Disposal ..............................................8
8 Appendix
8.1 Wiring examples .......................................8
8.2 Connection example ...................................11
9 Declaration of conformity
9.1 EC Declaration of conformity .............................12
1. About this document
1.1 Function
This operating instructions manual provides all the information you need for the mounting, set-up and commissioning to ensure the safe operation and disassembly of the safety switchgear. he operating instructions must be available in a legible condition and a complete version in the vicinity of the device.
1.2 Target group: authorised qualified personnel
All operations described in this operating instructions manual must be carried out by trained specialist personnel, authorised by the plant operator only.
Content
1 About this document
1.1 Function ..............................................1
1.2 Target group: authorised qualied personnel..................1
1.3 Explanation of the symbols used ...........................1
1.4 Appropriate use ........................................1
1.5 General safety instructions ...............................1
1.6 Warning about misuse ...................................2
1.7 Exclusion of liability .....................................2
2 Product description
2.1 Ordering code .........................................2
2.2 Special versions........................................2
2.3 Comprehensive quality insurance to 2006/42/EC ..............2
2.4 Destination and use .....................................2
2.5 Technical data .........................................3
2.6 Safety classication .....................................3
3 Mounting
3.1 General mounting instructions .............................3
3.2 Dimensions ...........................................4
3.3 Actuating positions of the safety sensor with regard to the actuator 4
3.4 Switching distance ......................................4
3.5 Adjustment............................................5
4 Electrical connection
4.1 General information for electrical connection..................5
4.2 Series-wiring ..........................................5
5 Set-up and maintenance
5.1 Functional testing.......................................6
5.2 Maintenance ..........................................6
Please make sure that you have read and understood these operating instructions and that you know all applicable legislations regarding occupational safety and accident prevention prior to installation and putting the component into operation.
The machine builder must carefully select the harmonised standards to be complied with as well as other technical specifications for the selec­tion, mounting and integration of the components.
1.3 Explanation of the symbols used
Information, hint, note:
This symbol is used for identifying useful additional information.
Caution: Failure to comply with this warning notice could lead to failures or malfunctions. Warning: Failure to comply with this warning notice could lead to physical injury and/or damage to the machine.
1.4 Appropriate use
The products described in these operating instructions are developed to execute safety-related functions as part of an entire plant or machine. It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machinery or plant.
The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufac­turer. Detailed information regarding the range of applications can be found in the chapter "Product description".
1.5 General safety instructions
The user must observe the safety instructions in this operating instruc­tions manual, the country-specific installation standards as well as all prevailing safety regulations and accident prevention rules.
Further technical information can be found in the Schmersal catalogues or in the online catalogue on the Internet: www.schmersal.net.
The information contained in this operating instructions manual is pro­vided without liability and is subject to technical modifications.
x.000 / 07.2015 / v.A. - 101191603-EN / D / 2015-07-06 / AE-Nr. 4883
6 Diagnostic functions
6.1 Operating principle of the diagnostic LED's ...................6
6.2 Operating principle of the electronic diagnostic output ..........6
6.3 Safety-sensors with serial diagnostic function .................7
EN
1
Operating instructions Safety sensor
CSS 34F0 CSS 34F1
There are no residual risks, provided that the safety instructions as well as the instructions regarding mounting, commissioning, operation and maintenance are observed.
1.6 Warning about misuse
In case of improper use or manipulation of the safety switch­gear, personal hazards or damages to machinery or plant components cannot be excluded when safety switchgear is used. The relevant requirements of the standard ISO 14119 must be observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual. The manufacturer shall accept no liability for damages result­ing from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary re­pairs, conversions and modifications to the device are strictly forbidden; the manufacturer shall accept no liability for damages resulting from such invasive work, arbitrary repairs, conversions and/or modifications to the device.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
CSS-➀-34-➁-➂-➃-M-ST No. Option Description
12 14
F0 F1
2.2 Special versions
For special versions, which are not listed in the order code below 2.1, these specifications apply accordingly, provided that they correspond to the standard version.
2.3 Comprehensive quality insurance to 2006/42/EC
Schmersal is a certified company to appendix X of the Machinery Di­rective. As a result, Schmersal is entitled to autonomously conduct the conformity assessment procedure for the products listed in Appendix IV of the MD without involving a notified body. The EC prototype test certificates are available upon request or can be downloaded from the Internet at www.schmersal.com.
S lateral active surface V frontal active surface D With diagnostic output SD with serial diagnostic function
Only if the information described in this operating instructions manual are realised correctly, the safety function and therefo­re the compliance with the Machinery Directive is maintained.
Switching distance Sn (mm)
Actuation from top Actuation from side Relay feedback without edge monitoring with edge monitoring
2.4 Destination and use
This non-contact, electronic safety sensor is designed for application in safety circuits and is used for monitoring the position of movable safety guards. In this application, the safety sensor monitors the closed position of hinged, sliding or removable safety guards by means of the coded electronic CST 34 or CST 180 actuators (refer to table "Actuators and switching distances").
The sensor additionally executes functions of a safety-monitoring module. At both safety outputs, two auxiliary contactors can be connected, whose safety-related function is checked by the sensor by means of a feedback circuit. The feedback circuit includes the series-wiring of the NC contacts of the auxiliary contactors1) or re­lays1). For the F0 version, a so-called "enabling switch" (without safety function) can be integrated in this feedback circuit. For the F1 version, a so-called "reset button" is required, which is monitored for a trailing edge. This function corresponds to the "manual reset function" to ISO 13849-1.
1)
with positive-guided contacts to IEC 60947-5-1 or
EN 50205
The safety switchgears are classified according to ISO 14119 as type 4 switching devices.
Mode of operation of the safety outputs
The safety outputs can be integrated into the safety circuit of the control system. The opening of a safety guard, i.e. the actuator is removed out of the active zone of the sensor, will immediately disable the safety out­puts of the sensor (refer to table “Actuators and switching distances”).
Any error that does not immediately affect the functionality of the safety sensor (e.g. the ambient temperature being too high, interference potential at a safety output, cross-wire short) will lead to a delayed shut-down. The safety outputs are disabled after 30 minutes if the error is not rectified. The signal combination, diagnostic output disabled and safety channels still enabled, can be used to stop the production pro­cess in a controlled manner. After fault rectification, the error message is reset by opening and re-closing the corresponding safety guard. The safety outputs enable and allow a restart. For devices with serial diagnostic, a bit can be set/deleted in the call telegram to reset the fault. If more than one fault is detected, the device must be isolated from the voltage supply after the fault rectification is reset.
Safety-sensors with serial diagnostic function
The safety sensor indicates the operating condition and faults by means of three-colour LED's located in the lateral surfaces of the sensor. A diagnostic output additionally indicates the operating condition. These signals can be used in a downstream control. The diagnostic output of the CSS 34 safety sensor alternatively can be used as conventional output or as “serial output“ with input and output channel. The serial connections of the individual sensors are wired in series together with other devices and connected to a fieldbus Gateway.
Series-wiring
Max. 31 sensors can be wired in series. In this way, a 200 m long sen­sor chain can be set up. The self-monitoring safety sensors of the CSS 34F0 or CSS 34F1 series can replace the safety-monitoring module. Therefore, they can only be used as first sensor of a series-wired sen­sor chain (refer to operating instructions CSS 34F0 / CSS 34F1).
1)
or relays1)
2
EN
Operating instructions Safety sensor
CSS 34F0 CSS 34F1
The user must evaluate and design the safety chain in accord­ance with the relevant standards and the required safety level. If multiple safety sensors are involved in the same safety function, the PFH values of the individual components must be added.
The entire concept of the control system, in which the safety component is integrated, must be validated to the relevant standards.
2.5 Technical data
Standards: IEC 60947-5-3; ISO 13849-1;
IEC 61508 , IEC 62061
Enclosure: glass-fibre reinforced thermoplastic Operating principle: inductive Coding levels according to ISO 14119: low Actuator and switch distances (according to IEC 60947-5-3): see table "Actuator / Switch distances“ Series wiring: max. 31 device, CSS 34F. as first
sensor and evaluation replacement
Cable length: max. 200 m Hysteresis: max: 1.5 mm Repeat accuracy R: < 0.5 mm Switching frequency f: 3 Hz Connector: M12, 8-pin in casing Temperature resistance of the cable:
- at rest: −30 °C … +105 °C
- in motion: −10 °C … +105 °C
Ambient conditions:
Ambient temperature Tu:
- Output current ≤ 0.1 A / Output –25 °C to 70 °C
- Output current ≤ 0.25 A / Output –25 °C to +65 °C
Storage and transport temperature: –25 °C … +85 ºC Resistance to vibration: 10 … 55 Hz, amplitude 1 mm Resistance to shock: 30 g / 11 ms
Protection class: IP65, IP67 to IEC 60529
Electrical data:
Rated operating voltage Ue: 24 VDC -15% / +10%
(stabilised PELV)
Rated operating current Ie: 0.6 A Required rated short-circuit current: 100 A Fuse (line protection): note the wire
diameter of continuing wire:
- for wire variants :up to 45 °C ambient temperature: 4.0 A
up to 60 °C ambient temperature: 3.15 A
up to 65 °C ambient temperature: 2.5 A up to 70 °C ambient temperature: 2.0 A
- for plug version :2.0 A Rated insulation voltage Ui: 32 VDC Rated impulse withstand voltage U No-load current Io: 0.1 A Response time: < 30 ms Duration of risk: < 60 ms Protection class: II Overvoltage category: III Degree of pollution: 3 EMC rating: according to IEC 60947-5-3 Electromagnetic interference: according to IEC 60947-5-3
Safety outputs Y1/Y2: normally open function, 2 channel,
Voltage drop: < 1 V Rated operating voltage Ue1: min. Ue - 1 V Leakage current Ir: < 0.5 mA Rated operating current Ie1: max. 0.25 A, dependent
Minimum operating current Im: 0.5 mA Utilisation category: DC-12, DC-13 Rated operating voltage/current Ue1/Ie1: 24 VDC / 0.25 A
: 800 V
imp
p-type, short-circuit proof
on ambient temperature
Diagnostic output: short-circuit proof, p-type
Voltage drop: < 5 V Rated operating voltage Ue2: min. (Ue – 5 V) Operating current Ie2: max. 0,05 A Utilisation category: DC-12, DC-13 Rated operating voltage/current Ue2/Ie2: 24 VDC / 0.05 A Wiring capacitance for serial diagnostics: max. 50 nF
2.6 Safety classification
Standards: ISO 13849-1, IEC 61508, IEC 62061 PL: e Control Category: 4 PFH value: 3.6 x 10-9 / h
SIL: suitable for SIL 3 applications
Service life: 20 years
3. Mounting
3.1 General mounting instructions
During fitting, the requirements of ISO 14119 must be ob­served.
The component can be mounted in any position. The active surface of the safety sensor and the actuator has to be opposite. The sensor enclosure must not be used as an end stop. The active surface of the safety sensor is either the lateral surface marked with the type plate or the front, rounded surface. The safety sensor must only be used within
the assured switching distances ≤ sao and ≥ sar.
The safety sensor and the CST 34-.-1 or CST 34-S-2 actuators are supplied with integrated mounting plate. With the slotted holes of the mounting plates, possible tolerances can be horizontally and vertically compensated. The components are fitted with M4 screws.
The safety sensors and the actuators can be clipped onto the mounting plate with different actuating directions. Both components are fixed by means of a locking cap.
Safety sensor and actuator must be permanently fitted to the safety guards and protected against displacement by suitable measures (tamperproof screws, gluing, drilling of the screw heads).
The mounting plates must be pinned after their fixation. The mounting brackets also must be secured by means of the supplied locking pin to protect them against tampering. The CST-S-3 and CST 180 actuators must be protected by tam­per-proof screws or a tamper-proof fitting.
At an ambient temperature of over 55°C, the safety sensor
must be fitted so that it is protected against unintentional contact with persons.
In order to prevent confusion with the CSS 34 without relay feedback, a functional test (refer to page 5) must be executed after the electrical wiring.
To avoid any interference inherent to this kind of system and any reduc­tion of the switching distances, please observe the following guidelines:
Minimum distance between two sensors: 100 mm
EN
3
Operating instructions
8
27
Safety sensor
CSS 34F0 CSS 34F1
3.2 Dimensions
All measurements in mm.
Safety sensor size
35
97,2
108,2
Dimensions Actuator
97,2
3.3 Actuating positions of the safety sensor with regard to the actuator
Lateral actuation Actuation from front
27
CST 34-S-1
CSS ..-34-S
CST 34-S-3
CSS ..-34-V CST 34-S-3
M 12x1
2735
101,7
CSS ..-34-S
CST 34-S-2
CSS ..-34-V CST 34-S-2
CSS ..-34-S
CST 180-1/-2
CSS ..-34-V CST 180-1/-2
CSS ..-34-S
CST 34-V-1CSS ..-34-V
Alternative suitable actuators with different design: refer to www.schmersal.net.
Integrated mounting plate
101,7
42,5
¤5
4,5
R2,1
R4,6
50
Holes to be pinned Hole for the pin
3.4 Switching distance
Actuators and switching distances (to EN 60947-5-3)
Actuator Sensor CSS ..-34-S
(Actuation from side)
35
CST 34-V-1 s
CST 34-S-1 CST 34-S-3
CST 34-S-2 (increased misalignment) CST 180-1 CST 180-2
n
s
ao
s
ar
s
n
s
ao
s
ar
s
n
s
ao
s
ar
s
n
s
ao
s
ar
10 mm
8 mm 13 mm 14 mm 12 mm 17 mm 14 mm 12 mm 17 mm 10 mm
8 mm 13 mm
CSS ..-34-V (Actuation from front)
12 mm 10 mm 15 mm 15 mm 13 mm 18 mm 10 mm
8 mm 16 mm 12 mm 10 mm 16 mm
Key
S
Rated operating distance
n
Sao Assured switching distance Sar Assured switch-off distance
4
EN
Operating instructions
Z
Safety sensor
CSS 34F0 CSS 34F1
Maximum misalignment from side
Y
X
Actuation from side
The long side allows for a maximum height misalignment (x) of sensor and actuator of 36 mm (e.g. mounting tolerance or due to guard door sagging). Increased misalignment, max. 53 mm, possible when the CST 34-S-2 actuator is used. The axial misalignment (y) is max. ± 10 mm.
Maximum misalignment from front
Requirements for the connected safety switchgear
Dual-channel safety input, suitable for p-type safety sensors with NO function. The safety sensors cyclically switch off the output to test them.
The switch-off times of max. 500 μs must be tolerated by the switching
device. An extension with short-circuit recognition for the evaluation is not required. Note on the total length of a safety sensor chain, refer to paragraph "Series-wiring". The maximum load current of 250 mA per safety channel must be observed. Contactors with higher load currents must be controlled by intermediate control relays.
Information for the selection of suitable safety-monitoring modules can be found in the Schmersal catalogues or in the online catalogue on the Internet: www.schmersal.net.
If the safety sensor is connected to electronic safety-monito­ring modules, we recommend that you set a discrepancy time of 100 ms. The safety inputs of the safety-monitoring module must be able blanking a test impulse of approx. 1 ms. The safety-monitoring module does not need to have a cross-wire short monitoring function, if necessary, the cross-wire short monitoring function must be disabled.
Wiring capacitance for serial diagnostics
The connecting cable of the safety sensor must have a maximum length of 200 m; its wiring capacitance must not exceed 50 nF. De­pending on the strand structure, normal unshielded 200 m long control cables LIYY 0.25 mm² to 1.5 mm² have a wiring capacitance of approx.
20 … 48n F
Actuation from front
The front face allows for an axial misalignment (z) of max. ± 8 mm.
3.5 Adjustment
The distance between the sensor and the actuator must be set to < sao. If variations in the clearance between the sensor and the actuator must be detected (e.g. sagging of a safety guard), this distance must be reduced by 4 mm. The yellow LED’s and the diagnostic output indicate the different ranges.
4. Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out by autho­rised personnel in a de-energised condition.
The power supply for the safety sensors must provide protection against permanent overvoltage. Under fault conditions, the voltage must not exceed 60 V. The use of PELV supply units is recommended.
If a safety chain including multiple sensors is set up, only the first device of this chain may be a CSS 34F. type sensor. All other devices of the chain must be of the default CSS 34 type. The CSS 34F. performs the check of the connected contactors or relays and the optional button for the entire chain.
The self-monitoring safety sensors of the CSS 34F0 or CSS 34F1 series can replace the safety-monitoring module. Therefore, they can only be used as first sensor of a series-wired sensor chain (refer to operating instructions CSS 34F0 / CSS 34F1).
The safety outputs can be integrated into the safety circuit of the control system. For applications of PL e / control category 4 to EN ISO 13849­1, the safety outputs of the safety sensor or of the sensor chain must be wired to a safety monitoring-module of the same control category.
4.2 Series-wiring
Max. 31 sensors can be wired in series. The self-monitoring safety sen­sors of the CSS 34F0 or CSS 34F1 series can replace the safety-mon­itoring module. Therefore, they can only be used as first sensor of a series-wired sensor chain. A 200 m long sensor chain can be set up. Please note that voltage losses could occur (due to cable length, cable section, voltage drop/ sensor)! For longer cable lengths, the section of the connecting cables must be taken as large as possible.
Wiring examples for series-wiring, refer to appendix
Protection is not required when pilot wires are laid. The cables however must be separated from the supply and energy cables. The max. fuse rate for a sensor chain depends on the section of the connecting cable of the sensor.
When wiring SD devices, please observe the voltage drop on the cables and the current carrying capacity of the individual components.
EN
5
Operating instructions Safety sensor
CSS 34F0 CSS 34F1
5. Set-up and maintenance
5.1 Functional testing
The safety function of the safety components must be tested. The following conditions must be previously checked and met:
1. Fitting of the sensor and the actuator
2. Fitting and integrity of the power cable
3. The system is free of dirt and soiling (in particular metal chips)
Functional test after assembly and connection of the CSS 34F.
All safety guards must be closed prior to the start of the functional test. The feedback circuit must be opened, the button must not be actuated2).
No. Action to test the
operation
1 Switch on the opera-
ting voltage
2 Close the feedback
circuit: actuate the connected button
3 Only version F1: reset
button actuation
2)
If no button is used, the feedback circuit must be opened by loosening the cable. To
that effect, the voltage must be switched off.
3)
If no button is used, the feedback circuit must be closed by is reconnecting the cable.
To that effect, the voltage must be switched off.
5.2 Maintenance
In the case of correct installation and adequate use, the safety sensor features maintenance-free functionality. A regular visual inspection and functional test, including the following steps, is recommended:
• Check the fitting of the sensor and the actuator
• Remove possible metal chips
• Check the cable for damage.
Measures must be taken to protect against manipulation or against the bypassing of safety device, for example, using an extra actuator.
Damaged or defective components must be replaced.
Reaction CSS 34 F0 version
The yellow LED flashes at 5 Hz and the relays are disabled. The yellow LED is on + both con-
3)
nected relays are enabled No change com­pared to 2
Reaction CSS 34 F1 version
The yellow LED flashes at 5 Hz and the relays are disabled. No change com­pared to 1
The yellow LED is on + both con­nected relays are enabled
6. Diagnostic functions
6.1 Operating principle of the diagnostic LED's
The safety sensor indicates the operating condition and faults by means of three-colour LED's located in the lateral surfaces of the sensor.
The green LED indicates that the safety sensor is ready for operation. The supply voltage is on. The yellow LED's signal the detection of an actuator. If the actuator is operating near the limit of the hysteresis range of the safety sensor, the LED is flashing.
The flashing can be used to prematurely detect variations in the clear­ance between the sensor and the actuator (e.g. sagging of a safety guard). The sensor must be adjusted before the distance to the actuator increases and before the safety outputs are disabled, thus stopping the machine. The yellow LED flashing at 5 Hz signals that the sensor is actuated but that the feedback circuit however is still open. If a fault is detected, the red LED's will flash.
Flash codes red diagnostic LED
LED indication (red) Error cause
1 flash pulse 2 flash pulses 3 flash pulses 4 flash pulses 5 flash pulses Continuous red
6.2 Operating principle of the electronic diagnostic output
The short-circuit proof diagnostic output OUT can be used for cen­tral visualisation or control functions, e.g. in a PLC. It indicates the switching condition as shown in the table. The diagnostic output can also be used to detect clearance variations between the sensor and the actuator in the same way as the yellow LED. An active fault causes the diagnostic output to be disabled. The safety outputs are disabled after max. 30 minutes if the fault is not rectified. The signal combination, diagnostic output disabled and safety channels still enabled, can be used to stop the production process in a controlled manner. The inverse signal combination, diagnostic output enabled and safety outputs dis­abled, can be used to enable the internal safety-monitoring module by means of a reset/enabling signal.
Error output Y1
Error output Y2
Cross-wire Y1/Y2
ambient temperature too high
Wrong or defective actuator
Internal error
Table 1: Examples of the diagnostic function of the safety-sensor with conventional diagnostic output
Sensor function LED
I. Supply voltage On Off Off 0 V 0 V Voltage on,
II. Actuated On Off On 24 V 24 V The yellow LED always signals the presence of an
III. Actuated, actuator in limit
area
IV. Actuated and feedback
circuit open
V. Actuated in limit area and
feedback circuit open
VI. Error warning, sensor
actuated
VII. Error On Flashes On 0 V 0 V Refer to table with flash codes
6
Green Red Yellow
On Off Flashes
(1Hz)
On Off Flashes
(5Hz)
On Off flashes
alternating
(1Hz / 5Hz)
On Flashes On 0 V 24 V After 30 minutes if the error is not rectified
Diagnos-
tic output
24 V
pulsed
24 V 0 V The sensor waits for a signal at the feedback circuit:
24 V
pulsed
EN
Safety
outputs
24 V The sensor must be adjusted before the distance to the
0 V LED indication combines the sensor functions III. and IV.
Note
no evaluation of the voltage quality
actuator within range
actuator increases and before the safety outputs are disabled, thus stopping the machine
F0: Closing of the feedback circuit F1: Trailing edge at feedback circuit
Operating instructions Safety sensor
CSS 34F0 CSS 34F1
6.3 Safety-sensors with serial diagnostic function
Safety sensors with serial diagnostic cable have a serial input and out­put cable instead of the conventional diagnostic output. If CSS sensors are daisy-chained, the diagnostic data are transmitted through the series-wiring of the inputs and outputs.
Max. 30 CSS 34 sensors can be wired in series with one CSS 34 F0/ F1. For the evaluation of the serial diagnostics line either the PROFI­BUS-Gateway SD-I-DP-V0-2 or the Universal-Gateway SD-I-U-... are used. The PROFIBUS-Gate way is integrated as slave in an available PROFIBUS DP system.
Accessories SD interface
For ease of wiring and series-wiring of SD devices, consi­derable accessories are available. Detailed information is available on the Internet, www.schmersal.net.
In this way the diagnostic signals can be evaluated with a PLC. The fol­lowing operational information is automatically and permanently written in an input byte of the PLC for each CSS 34 sensor of the series-wired chain: Bit 0: safety outputs enabled Bit 1: safety sensor actuated, actuator identified Bit 3: feedback circuit open or button not actuated Bit 4: both safety inputs live Bit 5: safety sensor actuated in hysteresis area Bit 6: error warning, switch-off delay activated Bit 7: error, safety outputs switched off
In the event of a communication error between the field bus Gateway and the safety sensor, the switching condition of the safety output of the safety sensor is maintained.
Detailed information regarding the use of serial diagnostics can be found in the operating instructions manuals of the FIELDBUS Gateway as well as in the Online Catalogue on the Internet, check out: www. schmersal.net.
Wiring capacitance for serial diagnostics
The connecting cable of the safety sensor must have a maximum length of 200 m; its wiring capacitance must not exceed 50 nF. Depending on the strand structure, normal unshielded 200 m long LIYY cables with a section of 0,5 mm² to 1,5 mm² have a wiring capacitance of approx. 20 ­48 nF.
When wiring SD devices, please observe the voltage drop on the cables and the current carrying capacity of the individual components.
Fault
A fault has occurred, which causes the safety outputs to be disabled. The fault is reset, when the cause is eliminated and bit 7 of the request byte changes from 1 to 0 or the safety guard is opened. Faults at the safety outputs are only deleted upon the next release, as the fault recti­fication cannot be detected sooner.
Error warning
A fault has occurred, which causes the safety outputs to be disabled af­ter 30 minutes. The safety outputs initially remain enabled. This enables the shutdown of the process in a controlled manner. An error warning is deleted when the cause of error is eliminated.
Table 2: Function of the visual diagnostic LED`s, the serial status signals and the safety outputs by means of an example
System condition LED Safety outputs serial diagnostic byte bit no.
green red yellow Y1, Y2 7 6 5 4 3 2 1 0
Supply voltage on, not actuated On Off Off 0 V 0 0 0 0 0 0 0 0 Actuated, feedback circuit open / not actuated Actuated, safety outputs enabled Actuated in limit area On Off Flashes
Actuated, warning On On/flashes On 24 V 0 1 0 1 0 0 1 1 Actuated, fault On On/flashes On 0 V 1 1 0 1 0 1 1 0
The shown bit order of the diagnostic byte is an example. A different combination of the operational conditions will lead to a change of the bit order.
Table 3: I/O data and diagnostic data
Communication directions: Request byte: from the PLC to the local safety sensor
Response byte: from the local safety sensor to the PLC Warning/error byte: from the local safety sensor to the PLC
Bit n° Request byte Response byte Diagnostic
Bit 0: Error reset Safety output activated Error output Y1 Error output Y1 Bit 1: --- Actuator detected Error output Y2 Error output Y2 Bit 2: --- --- Cross-wire short Cross-wire short Bit 3: --- Start function missing / feedback circuit open Temperature too high Temperature too high Bit 4: --- Input condition X1 and X2 --- Actuator fault, coding error Bit 5: --- Actuated in limit area Internal device error Internal device error Bit 6: --- Error warning Communication error between the field
Bit 7: Error reset Error (enabling path switched off) Operating voltage too low ---
On Off Flashes
(5Hz)
On Off On 24 V 0 0 0 1 0 0 1 1
(1Hz)
error warning
bus Gateway and the safety switch
0 V 0 0 0 1 1 0 1 0
24 V 0 0 1 1 0 0 1 1
Diagnostic error
---
The described condition is reached, when Bit = 1
EN
7
Operating instructions Safety sensor
CSS 34F0 CSS 34F1
7. Disassembly and disposal
7.1 Disassembly
The safety switchgear must be disassembled in a de-energised condi­tion only.
7.2 Disposal
The safety switchgear must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations.
8. Appendix
8.1 Wiring examples
The application examples shown are suggestions. They however do not release the user from carefully checking whether the switchgear and its set-up are suitable for the individual application.
The components in the load circuit must be dimensioned so that a "short-circuit" does not cause a welding of the "NO contacts" of K1 and K2.
8
EN
Operating instructions Safety sensor
Wiring example 1 Wiring example 1: Series-wiring of the safety sensor CSS 34F0 with diagnostic output
The CSS 34 F0 safety sensor directly controls auxiliary contactors1) or relays1). The monitoring of the external contactors or relays is enabled by the feedback circuit, which is built by the NC contacts of K1, K2. As no further button is used, the auxiliary contactors1) or relays1) are immediately enabled when the safety guard is closed.
The feedback circuit can be extended by an enabling button. The sensor is switched on, as soon as the button is pushed. The set-up is shown on the following wiring example of the CSS 34F1. The internal safety-monitoring module of variant F0 is not equipped with an edge detection for the button. If required, a "manual reset" to ISO 13849-1 must be realised by other components of a local control system.
In this example, the CSS 34 F0 safety sensor is connected as individual device. To that effect, the safety inputs are connected to 24 VDC.
CSS 34F0 CSS 34F1
24 V
0V
CST 34-S-1
CSS 14-34F0-S-D-M-L
Field
Control cabinet
BN BU
BK RD
WH
GY
VT
K2
K1
Feedback circuit
K1
0V
Wiring, refer to table 4
Wiring example 2 Wiring example for a series-wiring of the CSS 34 and CSS 34F1 safety sensors with conventional diagnostic outputs
The safety sensor directly controls auxiliary contactors 1) or relays 1). The internal safety monitoring module of the CSS 34F1 variant monitors in addition to the feedback contacts a trailing edge of the reset button. The sensor switches on when the button is released. It can be used for manual reset on safety guards, which can be stepped over. The protected area must be designed so that a single reset button suffices.
K1
K2
K2
Load
24 V
0V
reset button
J
Field
CST 34-S-1
CSS 14-34-S-D-M-L
BN BU
BK RD
WH
GY
VT
n-participants
BN BU
WH
VT
CST 34-S-1
CSS 14-34F1-S-D-M-L
Feedback circuit
BK RD
GY
Control cabinet
Wiring, refer to table 4
0V
max. 31 components in series
EN
0V
K2
K1
Load
K1
K2
K1
K2
9
Operating instructions Safety sensor
Wiring example 3 Wiring example for a series-wiring of the CSS 34 and CSS 34F1 safety sensors with serial diagnostic outputs
The CSS 34 F1 safety sensor directly controls auxiliary contactors 1) or relays 1). The internal safety monitoring module of the CSS 34F1 variant mon­itors in addition to the feedback contacts a trailing edge of the reset button. The sensor switches on when the button is released. It can be used for manual reset on safety guards, which can be stepped over. The protected area must be designed so that a single reset button suffices. The Fieldbus Gateway is connected to the serial diagnostic input of the first sensor.
CSS 34F0 CSS 34F1
24 V
0V
reset button
CST 34-S-1
CSS 14-34-S-SD-M-L
CST 34-S-1
CSS 14-34F1-S-D-M-L
J
K1
Feedback circuit
K2
K1
K2
K1
Load
K2
Field
Control cabinet max. 31 components in series
Wiring, refer to table 4
Wiring example 4 Wiring example of the CSS 34F0 safety sensor with conventional diagnostic output wired with auxiliary relays for controlling auxiliary contactors 1) with actuating currents > 250 mA
Additional auxiliary relays are used, when the power of the safety outputs of the safety sensor is insufficient to directly control the auxiliary contactors
1)
. The NO contacts of the load-switching auxiliary contactors 1) are monitored.
Optional executions of the feedback circuit with one button, refer to previous wiring examples.
BN BU
BK RD
WH
PK
VT GY GY
n-participants
BN BU
BK RD
WH
PK
VT
SD-i-DP
Field bus
24 V
0V
Field
Control cabinet
Wiring, refer to table 4
10
CST 34-S-1
CSS 14-34F0-S-D-M-L
BN BU
BK RD
WH
GY
VT
L1 L1 L2 L3
Load on/off
0V
Relay
K2
K1
positive-guided auxiliary contactors
EN
Load
Operating instructions
5
3
5
7
Safety sensor
8.2 Connection example
Schedule 4: Wiring of the safety sensor with cable or integrated connector
CSS 34F0 CSS 34F1
Function safety switchgear
with conventional diagnostic output
A1 U X1 Safety input 1 2 WH WH BN A2 GND 3 BU BU GN Y1 Safety output 1 4 BK BK YE
OUT Diagnostic output SD output 5 GY GY GY
X2 Safety input 2 6 VT PK PK Y2 Safety output 2 7 RD VT BU
IN without function SD input 8 PK OR / shielded RD
4
6
7
2
1
8
Connecting cables with coupling (female) IP67, M12, 8-pole - 8 x 0.23 mm²
Cable length 2.5 m 101209963 Cable length 5 m 101209964 Cable length 10 m 101209960
with serial diagnostic
function
e
6
4
3
2
1
8
Pin configuration of
the integrated connector
1 BN BN WH
Colour code of the
Schmersal connector or
the integrated cable
possible colour codes of
other conventional connectors
to
IEC 60947-5-2: 2008
to DIN 47100
IP69K, M12, 8-pole - 8 x 0.21 mm²
Cable length 5 m 101210560 Cable length 5 m, angled 101210561
EN
11
Operating instructions Safety sensor
9. Declaration of conformity
9.1 EC Declaration of conformity

EC Declaration of conformity

CSS 34F0 CSS 34F1
Translation of the original Declaration of Conformity
We hereby certify that the hereafter described safety components both in its basic design and construc­tion conform to the applicable European Directives.
Name of the safety component: CSS 34F0
Type: Refer to ordering code
Description of the safety component: Non-contact safety sensor
Relevant EC-Directives: 2006/42/EC EC-Machinery Directive
Person authorised for the compilation of the technical documentation:
Notied body, which approved the full
quality assurance system, referred to in Appendix X, 2006/42/EC:
K.A. Schmersal GmbH & Co. KG Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com
CSS 34F1
2004/108/EC EMC-Directive
Oliver Wacker Möddinghofe 30 42279 Wuppertal
TÜV Rheinland Industrie Service GmbH Alboinstr. 56 12103 Berlin
ID n°: 0035
Place and date of issue: Wuppertal, March 10, 2015
CSS34F-C-EN
The currently valid declaration of conformity can be down­loaded from the internet at www.schmersal.net.
K.A. Schmersal GmbH & Co. KG
Möddinghofe 30, D - 42279 Wuppertal Postfach 24 02 63, D - 42232 Wuppertal
Phone: +49 - (0)2 02 - 64 74 - 0 Telefax: +49 - (0)2 02 - 64 74 - 1 00 E-Mail: info@schmersal.com Internet: http://www.schmersal.com
Authorised signature
Philip Schmersal
Managing Director
12
EN
Loading...