schmersal AZM201 Operating Instructions Manual

Operating instructions Solenoid interlock
Operating Instructions . . . . . . . . . . .pages 1 to 12
EN
Original
AZM201
7 Set-up and maintenance
7.1 Functional testing .....................................8
7.2 Maintenance .........................................8
8 Disassembly and disposal
8.1 Disassembly .........................................8
8.2 Disposal.............................................8
9 Appendix
9.1 Wiring examples ......................................9
9.2 -Wiring conguration and accessories ....................10
10 EU Declaration of conformity
1. About this document
1.1 Function
This operating instructions manual provides all the information you need for the mounting, set-up and commissioning to ensure the safe operation and disassembly of the safety switchgear. The operating instructions must be available in a legible condition and a complete version in the vicinity of the device.
x.000 / 08.2018 / v.A. - 103013247-EN / E / 2018-08-10 / AE-Nr. 9673
Content

1 About this document

1.1 Function.............................................1
1.2 Target group: authorised qualied personnel ................1
1.3 Explanation of the symbols used..........................1
1.4 Appropriate use.......................................1
1.5 General safety instructions ..............................1
1.6 Warning about misuse..................................2
1.7 Exclusion of liability ....................................2
2 Product description
2.1 Ordering code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.2 Special versions ......................................2
2.3 Comprehensive quality insurance to 2006/42/EC .............2
2.4 Purpose.............................................2
2.5 Technical data ........................................3
2.6 Safety classication....................................3
3 Mounting
3.1 General mounting instructions............................4
3.2 Manual release .......................................4
3.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3.4 Retrot kit for Manual release/Emergency exit . . . . . . . . . . . . . . .4
4 Electrical connection
4.1 General information for electrical connection ................5
5 Operating principles and coding
5.1 Magnet control........................................5
5.2 Mode of operation of the safety outputs ....................5
5.3 Actuator teaching / actuator detection......................5
6 Diagnostic functions
6.1 Diagnostic-LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
6.2 Solenoid interlock with conventional diagnostic output .........6
6.3 Solenoid interlock with serial diagnostic function SD ..........8
1.2 Target group: authorised qualified personnel
All operations described in this operating instructions manual must be carried out by trained specialist personnel, authorised by the plant operator only.
Please make sure that you have read and understood these operating instructions and that you know all applicable legislations regarding occupational safety and accident prevention prior to installation and putting the component into operation.
The machine builder must carefully select the harmonised standards to be complied with as well as other technical specifications for the selection, mounting and integration of the components.
1.3 Explanation of the symbols used
Information, hint, note:
This symbol is used for identifying useful additional information.
Caution: Failure to comply with this warning notice could lead to failures or malfunctions. Warning: Failure to comply with this warning notice could lead to physical injury and/or damage to the machine.
1.4 Appropriate use
The products described in these operating instructions are developed to execute safety-related functions as part of an entire plant or machine. It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant.
The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer. Detailed information regarding the range of applications can be found in the chapter "Product description".
1.5 General safety instructions
The user must observe the safety instructions in this operating instructions manual, the country specific installation standards as well as all prevailing safety regulations and accident prevention rules.
Further technical information can be found in the Schmersal catalogues or in the online catalogue on the Internet: www.schmersal.net.
EN
1
Operating instructions Solenoid interlock
AZM201
The information contained in this operating instructions manual is provided without liability and is subject to technical modifications.
There are no residual risks, provided that the safety instructions as well as the instructions regarding mounting, commissioning, operation and maintenance are observed.
1.6 Warning about misuse
In case of improper use or manipulation of the safety switchgear, personal hazards or damages to machinery or plant components cannot be excluded. The relevant requirements of the standard ISO 14119 must be observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual. The manufacturer shall accept no liability for damages resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary repairs, conversions and modifications to the device are strictly forbidden; the manufacturer shall accept no liability for damages resulting from such invasive work, arbitrary repairs, conversions and/or modifications to the device.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
AZM201➀-➁-➂-T-➃­No. Option Description
2.3 Comprehensive quality insurance to 2006/42/EC
Schmersal is a certified company to appendix X of the Machinery Directive. As a result, Schmersal is entitled to autonomously conduct the conformity assessment procedure for the products listed in Appendix IV of the MD without involving a notified body. The prototype test certificates are available upon request or can be downloaded from the Internet at www.schmersal.com.
2.4 Purpose
The non-contact, electronic safety switchgear is designed for application in safety circuits and is used for monitoring the position and locking of movable safety guards.
The safety switchgears are classified according to ISO 14119 as type 4 interlocking devices. Designs with individual coding are classified as highly coded.
The different variants can be used as safety switch with interlocking function either as solenoid interlock.
If the risk analysis indicates the use of a monitored interlock then a variant with the monitored interlock is to be used, labelled with the symbol. The actuator monitoring variant (B) is a safety switch with an interlock function for process protection.
The safety function consists of safely switching off the safety outputs when the safety guard is opened and maintaining the safe switched off condition of the safety outputs for as long as the safety guard is open.
Interlocks with power to lock principle may only be used in special cases after a thorough evaluation of the accident risk, since the safety guard can be opened immediately on failure of the power supply or upon activation of the main switch.
Z Solenoid interlock monitored
B Actuator monitored
I1 Individual coding I2 Individual coding, re-teaching enabled SK Screw connection
CC Cage clamps ST2 Connector plug M12, 8-pole 1P2PW 1 p-type diagnostic output and
SD2P serial diagnostic output and
A Power to lock
Actuator suitable for
AZ/AZM201-B1-… Sliding safety guards AZ/AZM201-B30-… Hinged safety guards AZ/AZM201-B40-… hinged-doors with overlapping folds
Only if the information described in this operating instructions manual are realised correctly, the safety function and therefore the compliance with the Machinery Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1, these specifications apply accordingly, provided that they correspond to the standard version.
Standard coding
2 safety outputs, p-type (combined diagnostic signal: guard system closed and interlock engaged)
2 p-type safety outputs Power to unlock
Series-wiring
Series-wiring can be set up. The risk time is not altered by wiring in series. The number of components is only limited by the external cable protection according to the technical data and the line loss. Series­wiring of up to 31 AZM201…-SD components with serial diagnostics is possible. In devices with the serial diagnostics function (ordering suffix -SD), the serial diagnostics connections are wired in series and connected to a SD Gateway for evaluation purposes. Wiring examples for series-wiring, refer to appendix.
The user must evaluate and design the safety chain in accordance with the relevant standards and the required safety level. If multiple safety switchgears are involved in the same safety function, the PFH values of the individual components must be added.
The entire concept of the control system, in which the safety component is integrated, must be validated to the relevant standards.
2
EN
Operating instructions Solenoid interlock
AZM201
2.5 Technical data
Standards: IEC 60947-5-1, IEC 60947-5-3, ISO 14119,
ISO 13849-1, IEC 61508, IEC 62061
Enclosure: glass-fibre reinforced thermoplastic, self-extinguishing Working principle: RFID Frequency band: 125 kHz Transmitter output: max. -6 dBm Coding level according to ISO 14119:
- I1-version: high
- I2-version: high
- Standard coding version: low Reaction time:
- Actuator: ≤ 100 ms
- Inputs: ≤ 0.5 ms Duration of risk: < 200 ms Time to readiness: < 4,000 ms Series-wiring: Unlimited number of components,
please observe external cable protection,
max. 31 components in case of serial diagnostics
Cable length: max. 200 m
(cable length and cable section alter the voltage
drop depending on the output current)
Mechanical data
Termination: Screw terminals or cage clamps,
Connector plug M12
Cable section: min. 0.25 mm², max. 1.5 mm²
(including conductor ferrules)
Cable entry: M20 Tightening torque for the cover screws: 0.7 ... 1 Nm (Torx T10) Latching force: 30 N Holding force F
: 2,600 N (1,300 N when used with the
max
AZ/AZM201-B30 actuator, for indoor use)
Holding force FZh: 2,000 N (1,000 N when used with the
AZ/AZM201-B30 actuator, for indoor use)
Actuating speed: ≤ 0.2 m/s Mechanical life: ≥ 1,000,000 operations
Ambient conditions
Ambient temperature: −25 °C ... +60 °C Storage and transport temperature: −25 °C ... +85 °C Relative humidity: max. 93 %,
non condensing, non icing
Protection class: IP66, IP67 to IEC 60529 Protection class: III Resistance to shock: 30 g / 11 ms Resistance to vibration: 10 ... 150 Hz, amplitude 0.35 mm Insulation values to IEC 60664-1:
- Rated insulation voltage Ui: 32 VDC
- Rated impulse withstand voltage U
: 0.8 kV
imp
- Over-voltage category: III
- Degree of pollution: 3
Switching frequency: 1 Hz
Electrical data
Operating voltage UB: 24 VDC −15% / +10%
(stabilised PELV power supply)
Power consumption device: ≤ 0.05 A Operating current device with magnet switched on:
- Averaged: < 0.2 A
- Peak current: < 0.7 A / 100 ms Required rated short-circuit current: 100 A External device fuse rating:
- Screw terminals or cage clamps: ≤ 4 A when used
in accordance with UL 508;
- Connector plug M12 or M23: ≤ 2 A
Electrical data - Safety inputs
Safety inputs: X1 and X2 Switching thresholds: −3 V ... 5 V (Low)
15 V ... 30 V (High)
Power consumption per input: typically 2 mA / 24 V Accepted test pulse duration on input signal: ≤ 1.0 ms
- With test pulse interval of: ≥ 100 ms Classification: ZVEI CB24I
Countersink: C1 Source: C1 C2 C3
Electrical data - Safety outputs
Safety outputs: Y1 and Y2 Switching elements: OSSD, p-type, short-circuit proof Utilisation category: DC-13: Ue/Ie: 24 VDC / 0.25 A Rated operating current Ie: each max. 0.25 A Leakage current Ir: ≤ 0.5 mA Voltage drop Ud: ≤ 4 V Cross-wire monitoring by device: Ye s Test pulse duration: < 0.5 ms Test pulse interval: 1,000 ms Classification: ZVEI CB24I
Source: C2 Countersink: C1 C2
Electrical data - Diagnostic output
Diagnostic output: OUT Switching element: p-type, short-circuit proof Utilisation category: DC-13: Ue/Ie: 24 VDC / 0.05 A Rated operating current le: max. depending 0.05 A Voltage drop Ud: ≤ 4 V
Serial diagnostic SD
Operating current: 0.15 A Wiring capacitance: max. 50 nF
Electrical data - Magnet control
Solenoid input: IN Switching thresholds: −3 V ... 5 V (Low)
15 V ... 30 V (High)
Power consumption: typical 10 mA / 24 V,
dynamic 20 mA
Magnet switch-on time ED: 100 % Accepted test pulse duration on input signal: ≤ 5.0 ms
- With test pulse interval of: ≥ 40 ms Classification: ZVEI CB24I
Countersink: C0 Source: C1 C2 C3
LED status display
green LED: Supply voltage yellow LED: Device condition red LED: Fault
Use isolated power supply only. For use in NFPA 79 Applications only. Adapters providing field wiring means are available from the manufacturer. Refer to manufacturers information.
2.6 Safety classification
- of the interlocking function
Standards: ISO 13849-1, IEC 61508, IEC 62061 PL: e Control Category: 4 PFH value: 1.9 x 10-9 / h PFD: 1.6 x 10
-4
SIL: suitable for SIL 3 applications Service life: 20 years
- of the guard locking function
Standards: ISO 13849-1, IEC 61508, IEC 62061 PL: d Control Category: 2 PFH: 1.0 x 10-8 / h PFD: 8.9 x 10
-4
SIL: suitable for SIL 2 applications Service life: 20 years
The safety consideration of the guard locking function only applies for standard devices with monitored solenoid interlock AZM201Z-…-1P2PW-… (see Ordering code). A safety assessment of the guard locking function for devices with serial diagnostics "SD2P" is not allowed due to the non-safe locking/unlocking signal from the SD Gateway
EN
3
Operating instructions
M23
24,4
50
ST3
71
16
Solenoid interlock
AZM201
The actuation of the interlock must be compared with the external OSSD enabler. If a shut-down now occurs due to an unintentional unlocking this is detected by an external diagnostic.
If for a certain application the quiescent current version of a solenoid interlock cannot be used, then for this exception an interlock with power to lock can be used if additional safety measure need to be realised that have an equivalent safety level.
The safety analysis of the guard locking function refers to the component solenoid interlock AZM as part of the complete system. On the customer side further measures such as safe actuation and safe cable installation to prevent faults are to be implemented. In the event of a fault resulting in the unlocking of the guard locking, this is detected by the solenoid interlock and the safety gates Y1/Y2 switch off. When such a fault occurs the protection equipment may open immediately, just once, before the safe condition of the machine is reached. The system reaction of category 2 allows that a fault can occur between tests causing the loss of the safety function which is detected by the test.
3. Mounting
3.2 Manual release
For the machine set-up, the solenoid interlock can be unlocked in a de­energised condition. After opening of the plastic flap "A" (refer to image "Dimensions"), the triangular key must be turned clockwise to bring the blocking bolt in unlocking condition. The normal locking function is only restored after the triangular key has been returned to its original position. Caution: do not turn beyond the latching point! After being put into operation, the manual release must be secured by closing the plastic flap "A" and affixing the seal, which is included in delivery.
Component ready for operation
3.3 Dimensions
All measurements in mm.
3,3
A
5
7,5
32,5
6,5
Component not ready for operation
50
±
20 1
38
3.1 General mounting instructions
Please observe the relevant requirements of the standards ISO 12100, ISO 14119 and ISO 14120.
For fitting the solenoid interlock, two mounting holes for M6 screws with washers (washers included in delivery) are provided. The solenoid interlock must not be used as an end stop. Any mounting position. The mounting position however must be chosen so that the ingress of dirt and soiling in the used opening is avoided. The unused actuator opening must be sealed by means of the dust-proof flap (included in delivery).
Minimum distance between two solenoid interlocks
as well as other systems with same frequency (125 kHz): 100 mm.
Mounting of the solenoid interlock and the actuator
Refer to the mounting instructions manual for the corresponding actuator.
The actuator must be permanently fitted to the safety guards and protected against displacement by suitable measures (tamperproof screws, gluing, drilling of the screw heads).
GN RD YE
155,5
220
15,5
B
Key
A: Manual release B: Cable entry
3.4 Retrofit kit for Manual release/Emergency exit
The retrofit kit is used for subsequent functional expansion of the solenoid interlock.
Emergency release RF-AZM200-N 103003543 Emergency exit RF-AZM200-T 103004966
M20x1,5
40
Designation Ordering code
M12
4
EN
Operating instructions
40 5
Solenoid interlock
AZM201
4. Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out by authorised personnel in a de-energised condition.
The power supply for the solenoid interlock must provide protection against permanent overvoltage. To that effect, stabilised PELV supply units must be used. The safety outputs can be directly integrated in the safety circuit of the control system. For applications up to PL e / control category 4 in accordance with ISO 13849-1, the safety outputs of the solenoid interlock(s) must be connected to a safety­monitoring module of the same control category (refer to wiring examples). Inductive loads (e.g. contactors, relays, etc.) are to be provided with suitable interference suppression circuitry.
Requirements for the connected safety-monitoring module:
• Dual-channel safety input, suitable for 2 p-type semi-conductor outputs
Configuration of the safety controller
If the safety switchgear is connected to electronic safety­monitoring modules, we recommend that you set a discrepancy time of 100 ms. The safety inputs of the safety­monitoring module must be able to blank a test impulse of approx. 1 ms. The safety-monitoring module does not need to have a cross-wire short monitoring function, if necessary, the cross-wire short monitoring function must be disabled.
Information for the selection of suitable safety-monitoring modules can be found in the Schmersal catalogues or in the online catalogue on the Internet: www.schmersal.net.
If the safety component is wired to relays or to non-safety relevant control components, a new risk analysis must be carried out.
Cable
The cable entry is realised by a metric M20 gland. This gland must be measured by the user so that it is suitable for the cable used. A cable gland with strain relief and suitable IP protection class must be used.
The maximum cable length is 200 m (for ST2 M12 connectors approx. 20 m depending on the cable section used for an operating current of 0.5 A). The maximum cable section is 1.5 mm², incl. conductuor ferrules. Prior to the connection, the cable must be stripped by
40+5 mm and insulated by 5 mm. The fitted 24V, X1, X2 bridge is
included in the delivery of …-1P2PW and …-SD2P.
5. Operating principles and coding
5.1 Magnet control
In the power to unlock version of the AZM201, the solenoid interlock is unlocked when the IN signal (= 24V) is set. In the power to lock version of the AZM201, the solenoid interlock is locked when the IN signal (= 24 V) is set.
5.2 Mode of operation of the safety outputs
In the standard AZM201 variant, the unlocking of the solenoid interlock causes the safety outputs to be disabled. The unlocked safety guard can be relocked as long as the actuator is inserted in the AZM201 solenoid interlock; in that case, the safety outputs are re-enabled.
The safety guard must not be opened.
In the B-variant AZM201B, the opening of the safety guard causes the safety outputs to be disabled.
5.3 Actuator teaching / actuator detection
Solenoid interlocks with standard coding are ready to use upon delivery.
Individually coded solenoid interlocks and actuators will require the following "teach-in" procedure:
1. Switch the solenoid interlock's voltage supply off and back on.
2. Introduce the actuator in the detection range. The teach-in procedure is signalled at the solenoid interlock, green LED off, red LED on, yellow LED flashes (1 Hz).
3. After 10 seconds, brief yellow cyclic flashes (5 Hz) request the
switch-off of the operating voltage of the solenoid interlock. (If the voltage is not switched off within 5 minutes, the solenoid interlock cancels the "teach-in" procedure and signals a false actuator by 5 red flashes).
4. After the operating voltage is switched back on, the actuator must
be detected once more in order to activate the taught actuator code. In this way, the activated code is definitively saved!
For ordering suffix -I1, the executed allocation of safety interlock and actuator is irreversible.
For ordering suffix -I2, the "teach-in" procedure for a new actuator can be repeated an unlimited number of times. When a new actuator is taught, the code, which was applicable until that moment, becomes invalid. Subsequent to that, an enabling inhibit will be active for ten minutes, thus providing for an increased protection against tampering. The green LED will flash until the expiration of the time of the enabling inhibit and the detection of the new actuator. In case of power failure during the lapse of time, the 10-minutes tampering protection time will restart.
Accessories for the series-wiring
For convenient wiring and series-wiring of SD components, the SD junction boxes PFB-SD-4M12-SD (variant for the field) and PDM-SD-4CC-SD (variant for control cabinet on carrier rail) are available along with additional comprehensive accessories. Detailed information is available on the Internet, www.schmersal.net.
EN
5
Operating instructions Solenoid interlock
AZM201
6. Diagnostic functions
6.1 Diagnostic-LEDs
The solenoid interlock signals the operational state as well as errors through three coloured LED’s installed on the front side of the device.
green (Power) Supply voltage on yellow (Status) Operating condition red (Fault) Error (see table: Error messages /
flash codes red diagnostic LED)
6.2 Solenoid interlock with conventional diagnostic output
The short-circuit proof diagnostic output can be used for central visualisation or control functions, e.g. in a PLC.
The diagnostic output is not a safety-related output.
Error
Errors, which no longer guarantee the function of the solenoid interlock (internal error)s cause the safety outputs to be disabled within the risk time. Any error that does not immediately affect the safe functionality of the solenoid interlock will lead to a delayed shut-down (refer to table 2).
After fault rectification (fault at output Y1 or Y2, temperature fault), the fault is acknowledged by opening and relocking the relevant guard door. The safety outputs enable and allow a restart. An interlocking chain must be permanently "locked" to enable the reactivation.
Automatic, electronic locking takes place if more than one fault is detected at the safety outputs or a cross circuit is detected between Y1 and Y2. This means that normal fault acknowledgement is no longer possible. To reset this type of interlocking, the solenoid interlock must be isolated from the power supply after elimination of the error causes.
Error warning
A fault has occurred, which causes the safety outputs to be disabled after 30 minutes. The safety outputs initially remain enabled. This enables the shutdown of the process in a controlled manner. An error warning is deleted when the cause of error is eliminated.
Behaviour of the diagnostic output (Version ...-1P2PW)
(Example: power to unlock version)
Input signal magnet control
IN
Normal sequence, door was locked
OUT
Door could not be locked or fault
OUT
Key
Safety guard open Safety guard closed
Unlock safety guard Safety guard locked
Locking time: 150 ... 250 ms,
typically 200 ms 250 ms, typically 200 ms
Safety guard not locked or fault
Evaluation of the diagnostic output (Version ...-1P2PW)
SPS
A1.0
E1.0
AZM 200
AZM201
IN
OUT
Power to unlock: IN = 0 = locking
A1.0
E1.0
A1.0
E1.0
Power to lock: IN = 1 = locking
A1.0
E1.0
A1.0
E1.0
M1.0
&
&
M2.0
&
M1.0
M2.0
&
Door can be locked
Door is locked
Door can be locked
Door is locked
6
EN
Operating instructions Solenoid interlock
Table 1: Diagnostic information for the safety switchgear
The safety switch signals the switching condition as well as malfunctions via three coloured LEDs installed on the device.
AZM201
System condition Solenoid control
IN
Power to
unlock
Power to
lock
green red yellow AZM201Z AZM201B -1P2PW
LED Safety outputs
Y1, Y2
Diagnostic
output OUT
Safety guard open 24 V (0 V) 0 V (24 V) On Off Off 0 V 0 V 0 V Door closed, actuator not inserted 24 V 0 V On Off Off 0 V 0 V 0 V
Door closed, actuator inserted,
24 V 0 V On Off Flashes 0 V 24 V 24 V
not locked
Door closed, actuator inserted,
0 V 24 V On Off Flashes 0 V 24 V 0 V
interlocking blocked
Guard closed,
0 V 24 V On Off On 24 V 24 V 24 V
actuator inserted and locked
Error warning
1)
solenoid interlock locked 0 V 24 V On Flashes
Error 0 V (24 V) 24 V (0 V) On Flashes
2)
On 24 V
2)
Off 0 V 0 V 0 V
1)
24 V
1)
0 V
Additionally for variant I1/I2:
Teach-in procedure actuator started Off On Flashes 0 V 0 V 0 V Only I2: teach-in procedure actuator
Flashes Off Off 0 V 0 V 0 V
(release block)
1) after 30 min: disabling due to fault
2) refer to flash code
Table 2: Error messages / flash codes red diagnostic LED
Flash codes (red)
Designation Autonomous
switch-off after
Error cause
1 flash pulse Error (warning) at output Y1 30 min Fault in output test or voltage at output Y1,
although the output is disabled.
2 flash pulses Error (warning) at output Y2 30 min Fault in output test or voltage at output Y2,
although the output is disabled. 3 flash pulses Error (warning) cross-wire short 30 min Cross-wire short between the output cables or fault at both outputs 4 flash pulses Error (warning) temperature too
high
30 min The temperature measurement reveals an internal temperature
that is too high 5 flash pulses Actuator fault 0 min incorrect or defective actuator 6 flash pulses Error actuator combination 0 min An invalid combination of actuators was detected
(blocking bolt detection or tamper attempt). Continuous red Internal fault /
overvoltage or undervoltage fault
0 min Device defective /
supply voltage not within specifications
EN
7
Operating instructions Solenoid interlock
AZM201
6.3 Solenoid interlock with serial diagnostic function SD
Solenoid interlocks with serial diagnostic cable have a serial input and output cable instead of the conventional diagnostic output. If solenoid interlocks are wired in series, the diagnostic data is transmitted through the series-wiring of the inputs and outputs.
Max. 31 solenoid interlocks can be wired in series. For the evaluation of the serial diagnostics line either the PROFIBUS-Gateway SD-I-DP-V0-2 or the Universal-Gateway SD-I-U-... are used. This serial diagnostic interface is integrated as a slave in an existing field bus system. In this way, the diagnostic signals can be evaluated by means of a PLC.
The response data and the diagnostic data are automatically and permanently written in an input byte of the PLC for each solenoid interlock in the series-wired chain. The request data for each solenoid interlock is transmitted to the component through an output byte of the PLC. In case of a communication error between the field bus gateway and the solenoid interlock, the switching condition of the solenoid interlock is maintained.
Error
A fault has occurred, which causes the safety outputs to be disabled. The fault is reset, when the cause is eliminated and bit 7 of the request byte changes from 1 to 0 or the safety guard is opened. Faults at the safety outputs are only deleted upon the next release, as the fault rectification cannot be detected sooner.
Automatic, electronic locking takes place if more than one fault is detected at the safety outputs or a cross circuit is detected between Y1 and Y2. This means that normal fault acknowledgement is no longer possible. To reset this type of interlocking, the solenoid interlock must be isolated from the power supply after elimination of the error causes.
Error warning
A fault has occurred, which causes the safety outputs to be disabled after 30 minutes. The safety outputs initially remain enabled. This enables the shutdown of the process in a controlled manner. An error warning is deleted when the cause of error is eliminated.
Diagnostic error (warning)
If an error (warning) is signalled in the response byte, detailed fault information can be read out.
Accessories for the series-wiring
To provide for a comfortable wiring and series-wiring of SD components, the connectors and the SD-2V-F-SK SD junction boxes (variant for the field in closed enclosure) and SD-2V-S-SK (variant for DIN rail mounting in the control cabinet) are available.
On wiring SD devices, please pay attention to the voltage drop on the cables and the current carrying capacity of the individual components.
Table 3: I/O data and diagnostic data
Bit n° Request byte Response byte Diagnostic error warning Diagnostic error
Bit 0: Magnet in, irrespective of
power to lock or power to
unlock principle Bit 1: --- Actuator detected Error output Y2 Error output Y2 Bit 2: --- Actuator detected and locked Cross-wire short Cross-wire short Bit 3: --- --- Temperature too high Temperature too high Bit 4: --- Input condition X1 and X2 --- incorrect or defective
Bit 5: --- Guard door detected Internal device error Internal device error Bit 6: --- Error warning
Bit 7: Error reset Error (enabling path switched off) Operating voltage too low ---
1)
after 30 min -> fault
The described condition is reached, when Bit = 1
7. Set-up and maintenance
7.1 Functional testing
The safety function of the safety components must be tested. The following conditions must be previously checked and met:
1. Fitting of the solenoid interlock and the actuator
2. Check the integrity of the cable entry and connections
3. Check the switch enclosure for damage
7.2 Maintenance
We recommend a regular visual inspection and functional test, including the following steps:
1. Check for tight installation of the actuator and the switch
2. Remove particles of dust and soiling
3. Check cable entry and connections
Safety output activated Error output Y1 Error output Y1
actuator
1)
Communication error between the field bus Gateway and the safety switchgear
---
8. Disassembly and disposal
8.1 Disassembly
The safety switchgear must be disassembled in a de-energised condition only.
8.2 Disposal
The safety switchgear must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations.
Adequate measures must be taken to ensure protection against tampering either to prevent tampering of the safety guard, for instance by means of replacement actuators.
Damaged or defective components must be replaced.
8
EN
Operating instructions
GND
GND
Solenoid interlock
9. Appendix
9.1 Wiring examples
The application examples shown are suggestions. They however do not release the user from carefully checking whether the switchgear and its
set-up are suitable for the individual application.
Wiring example 1: Series-wiring of the AZM201 with conventional diagnostic output
In the series-wiring, the 24V-X1-X2 bridge must be removed from all components up to the last component.
The voltage is supplied at both safety inputs of the terminal safety component of the chain (considered from the safety-monitoring module).
The safety outputs of the first safety component are wired to the safety-monitoring module.
AZM201
X1
OUT
SPS/PLC
12356 8
X2
24V
GND
7
4
IN
Y1
Y2
SPS/PLC
Y1 Y2
OUT
SPS/PLC
X1 X2
X1
X2
7
12356 8
4
Y1
Y2
24V
GND
IN
SPS/PLC
Y1 Y2
Safety outputs → evaluation
24 VDC
Wiring example 2: Series-wiring of the AZM201 with serial diagnostic function
The safety outputs of the first safety component are wired to the safety-monitoring module.
The serial Diagnostic Gateway is connected to the serial diagnostic input of the first safety component.
1235468
X1
X2
24V
GND
SD OUT
7
Y1
Y2
SD IN
1235468
X1
X2
24V
GND
SD OUT
7
Y1
Y2
SD IN
24 VDC
SD IN
Y1 Y2
n-participants max. 31 components in series
SD OUT
X1 X2
SD IN
Y1 Y2
EN
Field bus
Safety outputs → evaluation
9
Operating instructions
5
8
3
7
Solenoid interlock
9.2 -Wiring configuration and accessories
AZM201
Function safety switchgear Pin
configuration
with conventional
diagnostic output
24 V U
X1 Safety input 1 2 2 BN WH
GND GND 3 5 GN BU
Y1 Safety output 1 4 7 YE BK
OUT Diagnostic output SD output 5 9 GY GY
X2 Safety input 2 6 3 PK PK Y2 Safety output 2 7 8 BU VT
IN Solenoid control SD input 8 4 RD OR
without function 6
View of the terminal block for ordering suffix -SK or -CC View of the version with removable terminal blocks
Y1 Y2
IN
OUTGND
24V 24V X1 X2
AZM 200.-.-1P2P.
AZM201.-.-.-1P2PW-.
Connector plug ST2 M12, 8-pole
4
6
e
with serial diagnostic
function
24V 24V X1 X2
AZM201.-.-.-SD2P-.
AZM 200.-.-SD2P.
of the
connector
1 1 WH BN
IN
OUTGND
Y1 Y2
Configuration of
the removible
terminal blocks
1
AZM 200.-.-1P2P.-.
AZM201.-.-.-1P2PW-.
5
6
Colour code of
the Schmersal connector
to DIN 47100
2
4
3
9
78
Possible colour codes for more
commercially available connectors
based on IEC 60947-5-2
2
1
Accessories: Pre-wired cables
Connecting cables with coupling (female) IP67, M12, 8-pole - 8 x 0.25 mm²
Cable length Part number
2.5 m
5.0 m
10.0 m
Further versions in other lengths and with angled cable exit are available upon request.
103011415 103007358 103007359
10
EN
Operating instructions
Solenoid interlock
10. EU Declaration of conformity

EU Declaration of conformity

AZM201
Original K.A. Schmersal GmbH & Co. KG
We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives.
Name of the component: AZM201
Type: See ordering code
Description of the component: Interlocking device with electromagnetic
Relevant Directives: Machinery Directive
Applied standards: EN 60947-5-1:2004 + AC:2005 + A1:2009,
Notied body for the prototype test: TÜV Rheinland Industrie Service GmbH
Möddinghofe 30 42279 Wuppertal Germany Internet: www.schmersal.com
interlock for safety functions
RED-Directive RoHS-Directive
EN 60947-5-3:2013, ISO 14119:2013, EN 300 330 V2.1.1:2017, EN ISO 13849-1:2015, EN 61508 parts 1-7:2010,
EN 62061:2005 + AC:2010 + A1:2013 + A2:2015
Alboinstr. 56, 12103 Berlin
ID n°: 0035
2006/42/EG 2014/53/EU 2011/65/EU
EC-prototype test certicate: 01/205/5608.00/17
Person authorised for the compilation of the technical documentation:
Place and date of issue: Wuppertal, July 3, 2018
AZM201-E-EN
Oliver Wacker Möddinghofe 30 42279 Wuppertal
Authorised signature
Philip Schmersal
Managing Director
The currently valid declaration of conformity can be downloaded from the internet at www.schmersal.net.
EN
11
K. A. Schmersal GmbH & Co. KG
Möddinghofe 30, D - 42279 Wuppertal Postfach 24 02 63, D - 42232 Wuppertal
Phone: +49 - (0)2 02 - 64 74 - 0 Telefax: +49 - (0)2 02 - 64 74 - 1 00 E-Mail: info@schmersal.com Internet: http://www.schmersal.com
Loading...