Schaller Automation VN115/87plus EX Operation Manual

Operation Manual
Part-No. 180081
VISATRON®
Oil Mist Detectors
VN115/87plus EX
IACS UR M67 type approved
Operation Manual VISATRON® VN115/87plus EX 06/2016
Page 2
About this Manual
This operation manual was designed to answer your questions concerning the handling, operation and maintenance of the Oil Mist Detector (OMD) VISATRON® VN115/87plus EX. It contains no details about repairs.
The operating instructions are applicable for:
VN115/87plus EX
Should you encounter any interruption or breakdown of your VISATRON® OMD device during operation, please contact your local representative (refer to chapter 10 ‘Service Partners’) or Schaller Automation, Industrielle Automationstechnik GmbH & Co. KG directly. The repair of OMD devices should be carried out by Schaller Automation directly. You can expect safe and reliable operation of your OMD only when the device is operated in accordance with this manual.
Please take note of the following:
Please read this manual thoroughly and acquaint yourself with the correct
installation, operation and maintenance of your VISATRON® VN115/87plus EX device.
Installations of the VISATRON® VN115/87plus EX devices have to be in
accordance to the IACS UR M10 if applicable.
Use the VISATRON® VN115/87plus EX devices only for the purpose described in
the operation manual.
Incorrect maintenance and handling errors may cause possible device failure or
an unsafe operating environment.
The VISATRON® VN115/87plus EX devices may only be used by authorised
staff.
This operation manual must be available at the place of installation at all times.
Terms and conditions of sale
The standard terms and conditions of sale of SCHALLER AUTOMATION shall apply to all VISATRON® and related products.
SCHALLER AUTOMATION Industrielle Automationstechnik GmbH & Co. KG warrants that under proper use, handling and maintenance OMD VISATRON® VN115/87plus EX is free from defects in material, design and/or workmanship. Claims of buyers/operators, in particular compensation for damage, which does not arise at OMD VISATRON® VN115/87plus EX itself or for natural wear and tear of consumable supplies, e.g. filters etc., are excluded. SCHALLER AUTOMATION Industrielle Automationstechnik GmbH & Co. KG is not responsible for defects, which arise as a result of:
a) natural wear and tear, improper commissioning, improper use/handling, use of
unsuitable power supply, welding processes on the engine as well as non­observance of commissioning, installation, operating and service instructions as given in this Operation Manual
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Page 3
b) components and design other than the OMD VISATRON® VN115/87plus EX c) alterations or modifications of the OMD VISATRON® VN115/87plus EX carried
out by the buyer/operator or third parties without written authorization of
SCHALLER AUTOMATION Industrielle Automationstechnik GmbH & Co. KG
d) incorrect combination of devices and/or components or operation of devices
and/or components which are not certified to be compatible or not permitted by the manufacturer - SCHALLER AUTOMATION Industrielle Automationstechnik
GmbH & Co. KG
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Used symbols
CAUTION! Do not ignore the text in this box. Personnel safety can be endangered or the device can be damaged.
WARNING! The marked text contains important information.
The marked text contains only a hint for faster processing.
EX-Symbol contains important interactions about Explosion proof. CAUTION! Personnel safety can be endangered!
CAUTION! Unplug the OMD during welding processes on the engine.
Reset of Oil Mist Alarms
CAUTION!
Use a monitoring device at a safe location (e.g. ECR) to check for the actual oil mist concentration that is requested by the IACS. In case of an Oil Mist Alarm, Schaller Automation strongly recommends to approach the engine only after indicated oil mist concentration (LED chain) has lowered to half of its bar indication (VISATRON®-device and Remote Indicator II).
Follow the instructions of engine builder, ship yard and ship owner!
In case of a High Oil Mist Alarm the Detector can be reset if the Oil Mist Concentration has lowered below the Alarm level.
Page 4
Safety instructions
The VN115/87plus EX devices are manufactured according to the high quality standards of SCHALLER AUTOMATION and must pass stringent factory tests. In order to keep the device in a smooth and problem free operation, the user has to take note of the safety hints and warnings. In the instruction manual they are marked with the following symbols.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Intended purpose
Operation in internal potentially explosive atmospheres corresponding classification II-/2G (group II, category 2G, operating resource for gas atmosphere). The requirements of EN60079-0:2012+A11:2013 and EN60079-28:2007 are met)
Labelling:
II (2G) [Ex op is IIB T4 Gb]
Permissible ambient temperature (during intended purpose):
Ta: +5°C ≤ Ta ≤ +70°C
Typical gasses of the ignition protection T4:
T4 maximum surface temperature <=135°C
Methane, acetone, ammonia, methanol, propane, toluol, acetic acid, city gas, hydrogen, ethanol, n-butane, ethylene, acetylene, automotive gas, diesel, heating oil, hydrogen sulphide, acetaldehyde, diethyl ether.
Do always connect the OMD’s exhaust tube back to the engine’s crankcase. The correct suction pressure in the
measuring head should be of 60mmWC!
In order to ensure the correct function of the OMD, the pressure inside the engine’s crankcase shall be limited to
+/-500mmWC!
If the pressure is higher (or lower), Schaller Automation has to be contacted!
Warning! The OMD has not to be cleaned with a steam cleaner, high-pressure cleaner or solvent!
Warning! Do not interchange components of VN115/87plus (non-EX) with VN115/87plusEX. Especially the detector’s baseplate shall be of type VN115/87plusEX.
Important: The device is not intended to be mounted in an EX area, it is designed to extract gases from a potentially explosive atmosphere (e.g. the crankcase of a gas engine).
Page 5
Advice for secure operation in potentially explosive atmospheres
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
VN115/87plus EX type label
VN115/87plus EX type label explanation
Page 6
Only expert staff is allowed to mount, connect and put into operation the devices. The staff must have knowledge of the ignition protection, instructions and prescriptions of the operating resources in EX-area.
Check, if the classification (see above “labelling” and labeling on the
device) is practical for this case of operation!
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Page 7
EC Declaration of Conformity
We, the manufacturer
SCHALLER AUTOMATION
Industrielle Automationstechnik GmbH & Co. KG
Industriering 14
D-66440 Blieskastel
Germany
Tel.: 06842 / 508-0
Fax: 06842 / 508-260
declare on our own responsibility, that the product:
Kind of equipment: Oil Mist Detector Type-designation: VISATRON® VN115/87plus EX Marking: 0637 || (2G) [EX op is llB T4 Gb]
to which this declaration relates exclusively used for the detection and signalizing of oil mist in diesel aggregates and complies with the following EU-directives
Machinery directive 2006/42/EC
EMC directive 2004/108/EC
ATEX Equipment Directive 2014/34/EU
is in compliance with following standards:
EN ISO 4414: 2010
EN 60529: 1991+ A1: 2000+ A3: 2013
EN 55022: 2010
EN 61000-part 6-1: 2007, EN 61000-part 6-2: 2005, EN 61000-part 6-3: 2007+
A1:2011, EN 61000-part 6-4: 2007+ A1:2011
EN ISO 12100: 2010
EN 60079-0: 2012+ A11:2013
EN 60079-28: 2007
CSPRI 16-1
CSPRI 16-2 IACS UR M10: Rev.4 2013 IACS UR M67: Rev.2 2015
A technical documentation is completely available. The operating manual according to the oil mist detectors is available in the original version.
D-66440 Blieskastel, 2016/06/15
Stephan Schaller
- Managing Director -
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Page 8
Table of Contents
1 Introduction and functional overview ............................. 10
2 Installation instructions .................................................. 14
2.1 Mechanical installation ............................................................. 14
2.1.1 Basics .................................................................................14
2.1.2 Pipe dimensions ...................................................................16
2.1.3 Installation of pipe siphons ....................................................17
2.1.4 Installation of the siphon block connection units .......................19
2.1.5 Suction funnels in the crankcase compartment ........................20
2.1.6 Compressed air connection ....................................................21
2.1.7 Air cleaner module ...............................................................21
2.2 Electrical installation ............................................................... 22
2.2.1 VISATRON® VN115/87plus EX device .....................................22
2.2.2 Connection of monitoring devices ...........................................25
2.2.3 Schematic electrical wiring diagram ........................................27
3 Commissioning ................................................................ 28
3.1 Adjusting or checking the suction pressure................................. 28
3.2 Filling of siphon blocks VN180 for VN115/87plus EX system with oil29
3.3 Filling of pipe siphons for VN115/87plus EX system with oil .......... 30
3.4 Adjusting the sensitivity of the OMD .......................................... 31
3.5 Commissioning check list ......................................................... 32
4 Operating instructions ..................................................... 33
4.1 Display .................................................................................. 33
4.2 Reset of Oil Mist Alarms ........................................................... 35
5 Troubleshooting .............................................................. 36
5.1 Clean fresh air bores ............................................................... 37
5.2 Clean infrared (IR-) filter ......................................................... 37
5.3 Exchange air filters in the measuring head ................................. 38
5.4 Exchange air filter cartridge in air cleaner module ....................... 38
5.5 Exchange measuring head ....................................................... 39
5.6 Exchange bellows and suspension-system .................................. 41
5.7 Measuring head fuses .............................................................. 43
5.8 Check for earth fault problem ................................................... 44
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Page 9
6 Maintenance procedures ................................................. 46
7 Functional test ................................................................ 47
7.1 On board test ......................................................................... 47
7.2 Factory test at engine builder with smoke generator on
VN115/87plus EX installations .................................................. 49
7.3 Additional pressure measurement on VN115/87plus EX installations50
7.4 Factory test at engine builder with fog machine on all installations 51
8 Optional Spare Parts and Accessories ............................. 53
8.1 Optional Service Box ............................................................... 55
8.2 VN-Smoke Test Box ................................................................ 57
9 Technical data ................................................................. 59
10 Service Partners .............................................................. 62
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Page 10
1 Introduction and functional overview
The newly developed VISATRON® VN87plus EX Oil Mist Detector (OMD) from SCHALLER AUTOMATION protects large diesel engines against oil mist explosion, caused by spontaneously occurring oil mist. It is part of a safety system that secures the life and health of the operating staff and prevents heavy damages to the engine.
SCHALLER AUTOMATION developed this device to meet the IACS UR M10. The VN115/87plus EX is compliant to ATEX 2014/34/EU.
It is not possible to directly monitor all potential sources of oil mist inside a large diesel engine. There are main bearings, large end bearings, pistons, liners, sliders, pumps, camshaft bearings, chains, gears or even tools left behind from installation – all of these parts could produce oil mist e.g. in case of lubrication problems. Therefore the philosophy of SCHALLER AUTOMATION is that only OMD-systems can securely prevent oil mist explosions by detecting the primary origin of danger: the oil mist itself.
The VISATRON® VN115/87plus EX OMD-System uses the approved wear-free suction system to continuously extract the atmosphere of the crankcase compartments and other engine locations. The system works actively and is not simply waiting for oil mist clouds. This ensures proper reaction times from the beginning of oil mist generation to an oil mist alarm.
To avoid false alarms, caused by splash oil, the suction system makes use of Schaller's special suction funnels working independent of the rotation sense of the engine. Additional draining components ensure correct working under all operating conditions. This includes the application in power plants as well as on vessels with their static or dynamic inclinations. False alarms initiated by condensing water vapour are prevented by an integrated heater inside the measuring head housing.
The OMD-System consists of following parts:
VISATRON® VN115/87plus EX oil mist detector Protection cover Suction system including pressure regulator Monitoring device (optional) Filter for air support / water and oil separator
The VN115/87plus EX (see Figure 1) is approved to work and use in potentially explosive atmospheres.
All devices have a measuring head (2) which includes the optical measuring track under the control cover (3) and a display to give the user all important information for normal operations conditions. The measuring head is mounted on a vibration protected base plate.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
VN115/87plus EX
Figure 1: VISATRON® VN115/87plus EX
Page 11
The negative pressure for the suction system is generated by an air jet pump (1) working with the Venturi principle. The electrical interface is integrated within a socket housing (5). The mating plug contains the Oil-Mist-Alarm button. The device can be connected directly to the engine safety system. The interface includes two Oil-Mist-Alarm outputs, a Pre-Alarm output and a Ready signal.
VN115/87plus EX The suction system is connected to the common "Connecting Box" (4). This type of oil mist detector is able to detect an oil mist development, without identifying the location of the oil mist source inside the engine.
In normal operation mode the VN115/87plus EX samples the atmosphere of the engine at all suction points in parallel through the suction system to the measuring head.
The VN115/87plus EX offers two alarm levels. The Main-Alarm level can be adjusted with a switch at the rear side of the measuring head. The Pre-Alarm will be activated at fix 70% of the Main-Alarm level.
To keep the optical track clean, the VN115/87plus EX use clean scavenging air in front of the filter glasses. This air is derived from the compressed air driving the air jet pump.
The device is integrated in a mounting unit. The scope of supply includes an air cleaner, an additional pressure regulator unit and a protection cover.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 2: VISATRON® VN115/87plus EX oil mist detector with protection cover
and pressure regulator unit
Figure 3:
Optional Siphon block VN180 optional Pipe siphon
Protection cover
Pressure regulator unit
Page 12
The suction system always requires a so called 'suction funnel' (see page 20, Figure
13) at each suction point. This prevents the system against incoming splash oil.
During normal operation mode of an engine the OMD sucks out a small concentration of oil mist which was generated by blow-by or mechanical spraying. This oil mist may fall out in the suction pipes and must be drained out the pipes. Ideally, drainage flow back ends inside the engine’s crankcase.
The best method on a VN115/87plus EX installation to drain the system is to use pipe siphons. Also recommended is the use of siphon blocks.
On 2-stroke engines the crankcase and the combustion chambers are separated by stuffing boxes, which let the crankcase be nearly free of blow-by. Therefore it's also possible to use the suction funnel as draining device. In this case it is necessary to mount the suction pipes with an inclination of greater than 6°.
It is not allowed to blow the air into the engine room!
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Caution! The exhaust from the air jet pump must be blown
back into the crankcase. It’s not allowed to blow the air into
the engine room! It could be dangerous for personnel safety, because of the air-fuel-mixture.
Figure 4: Optional Remote Indicator II
Page 13
Remote monitoring devices:
The OMD device can be connected to Schaller's monitoring devices Remote Indicator II to monitor the oil mist concentration and the status of the OMD device from a safe location as requested by IACS UR M10. The connection to the monitoring devices is realized by a RS485 two-wire bus.
Additionally Schaller realized an integration of the VISATRON® VN115/87plus EX into ship automation systems (e.g. Mega-Guard of Praxis Automation).
Thus, the VN115/87plus EX is a further contribution to safety at sea. Our goal is to avert damage to assets, personnel and the environment.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
CAUTION! Do not ignore the warnings. The safety of persons can be endangered
Page 14
2 Installation instructions
2.1 Mechanical installation
2.1.1 Basics
There are multiple potential sources of oil mist inside an engine. These are for example defective main bearings, connecting rod bearings as well as piston seizures, chains and covers of pumps. For each of these individual sources you could determine the "optimum" suction point. The result would be a vast number of holes to be distributed over the entire engine. To find out a safe and economic solution to monitor oil mist SCHALLER AUTOMATION recommends the OMDEA-test (Oil Mist Detection Efficiency Approval). In each case the following rules are recommended.
Following rules are recommended by SCHALLER AUTOMATION:
Use at least one suction point per compartment. Use always the long version of the suction funnels. This makes the
installation independent from the rotation sense of the engine.
At least one suction point per chain drive or gear drive is necessary. Avoid the splash oil disk of the crankshaft bearings. Select points in the upper area of the crankcase, as oil mist tends to rise
upwards!
The detection unit has to be placed above the suction points. Installation Rules: it is not allowed to make U-bends or kinks in the tubing
system.
o VN115 with pipe siphons: Mount one pipe siphon at each end of the
horizontal header pipes, place the pipes a little bit above the suction points and connect the pipes and the engine wall connections with flexible tubes.
o VN115 with siphon blocks: Use one siphon block at each compartment.
If possible mount the device on the engine side opposite to the crankcase
relief valves, to reduce danger to the crew during a damage situation.
If possible place the VISATRON® detection unit in the center of the engine to
avoid long pipe runs.
Select only suction points which allow the use of long suction funnels. In this
case the installation side is independent from the rotation sense of the engine. Installations without any suction funnels are not allowed.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Important: As an engine maker, you need a Declaration of Conformity from the OMD maker
compartment 1
additional suction points, e.g.:
chain/gear-case
thrust bearing
compartment 2 compartment 3 compartment 4 compartment 5 compartment 6
recommended: manoeuvre side
Example of an VISATRON VN115/87plus installation on a 6-cyl. engine with engine wall connections (oil draining through pipe siphons)
exhaust
suction point
engine wall connection
engine wall connection
pipe siphon
engine wall connection
engine wall connection
engine wall connection
engine wall connection
engine wall connection
pipe siphon
flexible hose
Figure 5: Recommendation for best VN115/87plus EX OMD installation
The exhaust gases of OMD need to be fed back to crankcase!
Page 15
If recommended by engine builder, determine an additional suction point at
the camshaft bed.
SCHALLER AUTOMATION recommends a final test procedure per engine type called OMDEA (Oil Mist Detection Efficiency Approval).
According to the IACS unified requirement M10 the installation drawings have to be approved from engine builder and SCHALLER AUTOMATION. The installations have to be executed in compliance with these drawings and the contents of this manual.
The following figures show typical installation arrangement on a 6 cylinder engine.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
siphon­block VN180
compartment 1
additional suction points, e.g.:
chain/gear-case
thrust bearing
siphon­block VN180
siphon­block VN180
siphon­block VN180
siphon­block VN180
siphon­block VN180
compartment 2 compartment 3 compartment 4 compartment 5 compartment 6
recommended: manoeuvre side
Example of an VISATRON VN115/87plus installation on a 6-cyl. engine with siphon blocks (oil draining through siphon blocks)
exhaust
suction point
optional
engine wall connection
Figure 6: Alternative installation of VN115/87plus EX OMD
The exhaust gases of OMD need to be fed back to crankcase!
Page 16
2.1.2 Pipe dimensions
For VN115 standard applications:
o Seamless steel pipes: 22 mm outer diameter, 2 mm wall thickness o Flexible hoses: inner diameter not less than 6 mm
The length of exhaust air pipe (outlet of the venturi injector) should be limited to max 4m. If a longer tube is required, please contact Schaller Automation. The inner diameter has to be ≥ 18 mm. U-bends and kinks are forbidden.
All installation solutions must have written agreements by SCHALLER AUTOMATION as required by IACS UR M10.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 7: Pipe siphon
Page 17
2.1.3 Installation of pipe siphons
Mount the engine wall connection into the G3/4" thread with 110 Nm torque Put the pipe siphon in the hole Fix the clamping nut Fill the pipe siphon with oil (see chapter 'commissioning') Fix the flexible tube on the top fitting
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 8: Pipe siphon at engine wall
Figure 9: Image of pipe siphon
Figure 10: Oil draining principle
Header pipe
Flexible hose from Flexible hose
to pipe siphon
Crank case atmosphere
Oil
Page 18
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
suction point
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 11: Connection unit
OKAY
Wrong alignment
Wrong angles
Wrong distance
Figure 12: Side view
1 2 3
Page 19
2.1.4 Installation of the siphon block connection units
Consider the following points:
Take note of the drilling template (made of paper, included with the
connection units)
Drill through Seal all threads with 'Loctite 572' Max. torque = 30 Nm
Avoid wrong alignment, wrong angles and incorrect distances (see Figure
12)
Insert the suction funnel from the crankcase side into the siphon block, align
it in a vertical position (see Figure 13) with the opening at the bottom and fix the small clamping nut.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
CAUTION! Make sure funnels do not interfere with rotating or moving parts of the engine.
Figure 13: Different types of suction funnels
Page 20
2.1.5 Suction funnels in the crankcase compartment
The suction funnels have to be fitted in such a way that flooding by splashing bearing oil or returning piston cooling oil is avoided (see Figure 13).
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 14: Pressure regulator unit
Figure 15: Air cleaner module
Air cleaner connection
Air outlet
Throttle block
Air filter
Fine pressure regulator
Air flow
Air inlet
Pressure regulator
Air cleaner module
Inside:
Filter Cartridge 273119
Page 21
2.1.6 Compressed air connection
The SAB pressure regulator (see Figure 14) is connected to the Air cleaner module.
2.1.7 Air cleaner module
Do always connect OMD to engine's control air system, pressure range 2 - 15bar. A dry and clean (ISO8573-1:2010 6-4-4) air with low humidity/oil contamination is of high importance. The Air cleaner module has an integrated float lever, when the filling level should be too high, it will release the fluid automatically.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 16: Socket housing
Fixing screws of terminal board
Cable entry
Cable entry
Page 22
2.2 Electrical installation
2.2.1 VISATRON® VN115/87plus EX device
The electrical terminal is inside the socket housing (see Figure 16) on the base plate of the VISATRON® device. The pin assignment is specified in Figure 19. The cable entry points are located on either side.
According to the pin assignment of Figure 19 connect the VISATRON® device to the 24 Volts power supply. The supply voltage can be potential free or not. The earth connection between the OMD and the engine is carried out by the fixings screw of the base plate or protection cover.
Additionally connect one alarm relay output to the safety system of the engine. As specified by the classification societies the 'Alarm' relay must be connected either to the shutdown or to the slow-down input.
During normal operation the alarm relay is switched off. In case of an oil mist alarm the relay is switched on. To monitor this output, a wire break resistor is installed
(between pin 7 and 8 and between 15 and 16 as shown in Figure 19).
To replace the wire break resistors the measuring head has to be dismounted. The
resistors (see Figure 18) are located on the rear side under the plastic cover (see Figure 17). The plastic cover can be removed via the screws. Do not forget to write
the resistor value on the plastic cover with a permanent marker.
Also placed on the rear side two jumpers are available to select the interface mode: RS485 bus or 4- 20mA output of the relative opacity at pin 11 and 13.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 17: Rear side of measuring head
Figure 18: Wire break resistors
Current values of wire break resistors
Fixing screws of plastic cover
Plastic cover
Wire break resistors
Security seal
Jumper to select the RS485 interface or the 4 -20 mA output
Page 23
Second 'Alarm' output and 'Ready' output must be connected to separate channels on vessel’s or power plant’s alarm monitoring system. The 'Ready' relay is switched on when OMD is in correct operation (see Figure 19).
The optional pre-alarm output can be used to initiate either a pre-warning signal or slow-down signal. The pre-alarm relay is switched on when the oil mist concentration has risen up to 70% of the Oil Mist alarm level. Please note that depending on the characteristics of an oil mist occurrence, the time between 'Pre­alarm' and 'Main Alarm' could be only a fraction of a second.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Description
Pin
Description
24 Volts DC +
1
9 'Pre-alarm' relay
24 Volts DC GND
2
10
'Pre-alarm' relay
'Ready' relay closed
3
11 RS485 B (opt. 4 - 20 mA -)
'Ready' relay open
4
12
Reserved, do not use
'Ready' relay common
5
13
RS485 A (opt. 4 - 20 mA +)
'Alarm' 1 relay closed
6
14 'Alarm' 2 relay closed
'Alarm' 1 relay open
7
15
'Alarm' 2 relay open
'Alarm' 1 relay common
8
16
'Alarm' 2 relay common
Power supply
18 – 31.2 Volts DC, max. 2 A
Nominal voltage
24 Volts DC
Relay Outputs
Max. 60 Volts DC, 1 A
Internal fuse
2 A semi time lag
Page 24
Shown is non-operated relay condition
Figure 19: Pin assignment
- We recommend connecting 'Alarm' 1 to the alarm system and 'Alarm' 2 to
the safety system.
- Alarms 1 and 2 are getting switched simultaneously by same relay.
- The relay outputs are potential-free.
- In case of a High Oil Mist Alarm, contacts 7 and 8 as well as 15 and 16
are closing
- In case detector goes into ‘READY’-Mode, contacts 4 and 5 are closing
- In case Pre-Alarm is activated, contacts 9 and 10 are opening. Pre-Alarm
will be switched as soon as 70% of High Oil Mist Alarm level is reached.
Table 1: Electrical specification
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 20: Cable entry and bus-terminator on the bottom side of the VISATRON®
device
WARNING! The shield must be connected directly at the cable grommet.
Page 25
2.2.2 Connection of monitoring devices
As required by IACS UR M10 the OMD device can be connected to Schaller's remote monitoring device Remote Indicator II to monitor the oil mist concentration and the OMD status from a safe location.
The connection to the monitoring device is accomplished via a RS485 two-wire bus. In case of a Remote Indicator II the connection is only a two point link. The bus system at the OMD device must be terminated by the resistor. It is integrated in the terminator (see Figure 21), which is supplied with the monitoring device.
The used communication cable must be twisted pair and shielded. We recommend LAPPKABEL UNITRONIC-FD CP (TP) plus UL-CSA, AWG20. The total bus length is limited to 400 m. The VISATRON® device cable entry (see Figure 20) at the VISATRON® device is designed for cable diameter between 7.5 and 10.0 mm.
The connection between the OMD device and the monitoring device for standard
applications is shown in the following wiring diagram (see Figure 21)
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 21: Wiring diagram to connect Remote Indicator II
Figure 22: Bus address switch at the rear side of the measuring head
13 11
2 1
Terminator
Monitoring device
Address switch
Page 26
The monitoring device is the bus master and the OMD devices are the slaves. It's necessary to adjust different bus addresses at each slave device. Normally the first OMD device gets the address '1' and so on. The switch is on the rear side of the measuring head (see Figure 22).
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Engine room
T
Ready and alarm signals
RS485 2-wire-bus
Remote Indicator II
Alarm monitoring system
Engine safety system
VN87plus EX
Engine control room
Optional 4 – 20 mA
Page 27
2.2.3 Schematic electrical wiring diagram
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
CAUTION! Unplug the OMD during welding processes on the engine.
Figure 23: Pressure regulator unit
WARNING! Adjust 60 mm WC negative pressure. After adjustment, remove U-tube pressure gauge and screw in the previously removed plug.
CAUTION! A pressure setting much higher than 60 mm WC negative pressure may cause a change in detecting sensitivity and can impact the functionality of the siphon blocks.
Setscrew
Counter-nut
No need to touch throttle-block for pressure setting. Pressure setting by setscrew on left side only!
Page 28
3 Commissioning
3.1 Adjusting or checking the suction pressure
The suction pressure must be set by adjusting the pressure regulator when the engine is at standstill. Make sure ventilation of the engine room is in operation.
Connect a U-tube manometer at inspection cover (see Figure 24).
(U-tube manometer is included in the service box, available as an option).
Switch on compressed air supply with inlet pressure in a range from 2 to 15
bar (before connecting the OMD the first time check the pressure).
If the negative suction pressure is already adjusted to 60 mm WC within a
tolerance of ±5 mm remove the U-tube manometer and finish the procedure.
Otherwise loosen counter-nut. Turn setscrew until the negative pressure is only 60 mm WC. Tighten counter-nut.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 24: U-tube manometer connected to OMD control cover
Figure 25: Siphon block VN180
Figure 26: Filling pump
Oil input
Fitting
Lock nut
Page 29
Remove U-tube manometer Screw in the removed plug
3.2 Filling of siphon blocks VN180 for VN115/87plus EX system with oil
Press the pump lever of the filling pump (see Figure 26) as many times until
first oil drops are coming out.
Unscrew the lower siphon block plug (see Figure 25). Insert filling pump nozzle (see Figure 27).
Screw in the fitting of the filling pump. Press the nozzle to stop position.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
CAUTION! Do not fill with more than 8 strokes. The excess oil may flow in the suction tubes. Additionally the excess oil can remove the required oil in the siphon by a physical suction effect through the draining channel.
Figure 27: Filling pump inserted and fixed in the siphon block
Figure 28: Pipe siphon
Fitting to flexible hose and oil input
Page 30
Tighten the lock nut. Fill the siphon with 8 strokes.
Remove the filling pump. Close the threaded hole with the plug (a small amount oil coming out does
not impact the functionality.
Clean the siphon block. Continue with the next block.
3.3 Filling of pipe siphons for VN115/87plus EX system with oil
Remove flexible hose Fill in 70ml lubrication oil Fix flexible hose again
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
CAUTION! Do not fill in more than 70ml; the excess oil can remove the required oil in the siphon by a physical suction effect through the draining channel.
Position
Relative VN115 alarm
level in opacity
3
1.5%
4
2.0%
5
3.0%
6
5.0%
Standard switch position 3 or 4 normally should be sufficient for all sorts of engines. However if necessary, choose the lower sensitivity level 5 or 6.
Figure 29: Sensitivity switch at rear side of measuring head
Sensitivity Switch
Page 31
3.4 Adjusting the sensitivity of the OMD
The detector determines the oil mist concentration by an optical measurement. The calculated values have the unit 'opacity'. 100% opacity means that no light is transmitted through the oil mist sample. This is equivalent to a complete white wall. The LEL (Lower Explosion Level) is equal to 47mg/l oil mist concentration in air at a temperature of 25 °C. IACS UR M67 rules do request that OMD’s do indicate an oil mist alarm latest at approx. 2.5mg/l. The lesser sensitivity level of all VN/87plus
OMD’s, level 6, still ensures an Oil Mist Alarm at oil mist concentrations inside the
engine of <2.5mg/l. This complies fully with the requirements given by the IACS UR M67.
Table 2: Sensitivity switch position and corresponding oil mist alarm level
The sensitivity of the VISATRON® oil mist detector can be adjusted by a switch on the rear side of the measuring head (see Figure 29).
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Mechanical check
Are all suction pipes installed as specified in the installation drawing?
□ yes / □ no Are all fittings fastened and tight?
□ yes / □ no
On installations with siphon blocks: Are all siphon blocks filled with oil and all un-used openings closed?
□ yes / □ no On installations with pipe siphon: Are all siphons filled with oil?
□ yes / □ no
On installations with oil separator: Is the separator filled with oil?
□ yes / □ no
Is the negative pressure at the measuring head adjusted to 60 mmWC?
yes / □ no Adjusted negative pressure
mmWC
Is the screw removed from the control cover
□ yes / □ no
Electrical check
Is the power supply connected to the terminal and is the voltage within the specified range?
yes / □ no Measured supply voltage
Volts
Is the monitoring device installed?
yes / □ no
Are the Alarm and Ready signals connected to the engine control and safety system?
yes / □ no Are the correct wire break resistors installed
□ yes / □ no
Value of wire break resistor
kOhm
Is the correct interface mode at pin 11 and 13 selected?
□ yes / □ no
Functional check
On vessels perform the on-board test with test plate. Test positive?
□ yes / □ no At engine factory perform smoke test. Test positive?
□ yes / □ no
As an alternative to the smoke test, measure the negative pressure at the end of the suction pipes. Values as specified?
□ yes / □ no
Page 32
3.5 Commissioning check list
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
VN115/87plus EX SN 5007009123
Oil Mist Alarm
Ready
Error Test
Opacity
14
1
VN115/87plus EX SN 5007009123
Oil Mist Alarm
Ready
Error Test
Opacity
14
1
Blinking
Operation Manual VISATRON® VN115/87plus EX 06/2016
Page 33
4 Operating instructions
4.1 Display
After power-on LED 1 is blinking for 30 seconds. The device will show the following display.
Figure 30: Normal display mode
In case of a high oil mist concentration the LED bar goes up and at 70 % opacity compared to the adjusted alarm level the 'Oil-Mist Alarm' LED switches on. At 100% opacity, compared to the alarm level, the 'Oil-Mist Alarm' LED starts blinking. If the opacity later goes down, the alarm condition will be stored.
Figure 31: Example of an oil mist alarm state
The opacity is shown in the right LED bar. If highest LED is switched on, the opacity has reached / exceeds the Oil Mist Alarm level.
Code
13 12 11 10 ..9 ..8 ..7 ..6 ..5 ..4 ..3 ..2
Code
13 12 11 10 ..9 ..8 ..7 ..6 ..5 ..4 ..3 ..2
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Blinking LED on display
VN115/87plus EX device failures
14
Negative pressure out of range
13
Optical sensor dirty
12
Voltage of internal battery too low
11
Ambient temperature too low (<0°C)
10
Ambient temperature too high (>70°C)
9
Electronics temperature too low (<0°C)
8
Electronics temperature too high (>75°C)
7
Reset button defective
6
Supply voltage too high
5
Sensitivity switch defective
4
Optical sensor defective
3
Pressure sensor defective
2
Electronic module defective
1
Blinking: Startup phase
Error
VN115/87plus EX SN 5007009123
Oil Mist Alarm
Ready
Test
Opacity
14 13 12 11 10 ..9 ..8 ..7 ..6 ..5 ..4 ..3 ..2 1
Blinking
LED off
Page 34
Figure 32: Device not ready, example of 'Negative pressure out of range'
If a device internal error or a system failure occurs the diagnostics system shows the failure condition by a blinking LED on the LED bar. The error codes are shown in
Table 3. A detected oil mist alarm is displayed at this time with the 'Test' LED. In
this case the alarm relay or shutdown relay is not switched on.
Code
Table 3: Error codes
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
CAUTION!
Use a monitoring device at a safe location (e.g. ECR) to check for the actual oil mist concentration that is requested by the IACS. In case of an Oil Mist Alarm, Schaller Automation strongly recommends to approach the engine only after indicated oil mist concentration (LED chain) has lowered to half of its bar indication (VISATRON®-device and Remote Indicator II).
Follow the instructions of engine builder, ship yard and ship owner!
In case of a High Oil Mist Alarm the Detector can be reset if the Oil Mist Concentration has lowered below the Alarm level.
Figure 33: Oil-Mist-Alarm RESET button
Page 35
4.2 Reset of Oil Mist Alarms
The alarm condition can be reset only by pressing the Oil-Mist-Alarm RESET button.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Error
Description
remedy
Chapter
14
Negative pressure out of range
1. Adjust suction pressure
2. Exchange air filters
3. Clean fresh air bores
4. Check suction system
5. Exchange bellows
6. Exchange filter cartridge
7. Exchange measuring head
3.1 page 28
5.3 page 38
5.1 page 37
5.6 page 41
5.4 page 38
5.5 page 39
13
Optical sensor dirty
1. Clean infrared filter
5.2 page 37
12
Voltage of internal battery too low
1. Exchange measuring head
5.5 page 39
11
Ambient temperature too low (<0°C)
1. Remove ambient cooling
components
10
Ambient temperature too high (>70°C)
1. Remove or turn away ambient
heating components
2. Install metal heat shields
against radiation
9
Electronics temperature too low (<0°C)
1. Remove ambient cooling
components
8
Electronics temperature too high (>75°C)
1. Remove or turn away ambient
heating components
2. Install metal heat shields
against radiation
7
Reset button defective
1. Eliminate blocking
2. Exchange Measuring head
5.5 page 39
6
Supply voltage too high
1. Measure supply voltage
2. Exchange measuring head
5.5 page 39
5
Sensitivity switch defective
1. Exchange measuring head
5.5 page 39
4
Optical sensor defective
1. Clean infrared filter
2. Exchange measuring head
5.2 page 37
5.5 page 39
3
Pressure sensor defective
1. Exchange measuring head
5.5 page 39
2
Electronic module defective
1. Exchange measuring head
5.5 page 39
All LED off
1. Measure supply voltage
2. Activate Self-repair of
Polyfuse
3. Replace measuring head fuse
4. Check for earth fault problem
5. Exchange measuring head
5.7 page 36
5.7 page 36
5.8 page 44
5.5 page 39
Page 36
5 Troubleshooting
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 34: Cleaning of fresh air bore in the left and the right chambers
CAUTION! Dirty IR-filter glass may cause a loss of sensitivity of the device. Clean filters acc. maintenance plan (page 46)
Figure 35: Cleaning of IR-Filter glass in the left and the right chamber
WARNING! Use only cleaning fluids for optical components as delivered in the service box.
To remove the control cover you have to unscrew it.
After finishing the cleaning, don’t forget to reinstall the
control cover again!
Do not open the Cover during engine operation (System not ready)! Explosive atmosphere may emit
from the engine causing an explosion hazard.
Fresh air bore of right chamber
Needle
IR­filter glass
Cleaning fluid
Cotton stick
Page 37
5.1 Clean fresh air bores
5.2 Clean infrared (IR-) filter
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 36: Exchange of the air filters
WARNING! Do not try to clean the filters, use always new ones.
Figure 37: The air filter cartridge can be found inside the air cleaner module
WARNING! Switch off the compressed air supply during the maintenance work. After the exchange re-check the negative suction pressure.
Circlip pliers for Seeger rings
Please wear protective glasses!
Fresh air filters
Filter cartridge part No: 273119
Page 38
5.3 Exchange air filters in the measuring head
5.4 Exchange air filter cartridge in air cleaner module
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 38: Step 1 is to open the scavenging air fitting
Figure 39: Step 2 is to unplug the connector
Measuring head main connector
Scavenging air fitting
Page 39
5.5 Exchange measuring head
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 40: Step 3 is to unscrew the measuring head
WARNING! Check the values of the wire break resistors or in case of doubt use the old ones.
Fixing screws
Page 40
To mount the new measuring head execute the 3 steps in reverse order.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 41: Step 2 is to press out the 4 rubber gaskets with a blunt tool and
finally to remove the carrier plate
Figure 42: Step 3 is to exchange the suspension-system if necessary
Rubber gasket
Upper spring/ insolation­system
Page 41
5.6 Exchange bellows and suspension-system
Step 1 is to dismount the measuring head.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 43: Step 4 is to exchange the 2 bellows if necessary. The bellow is
secured by a ring which is fixed by two screws.
Figure 44 Step 5 is to pull out the gaskets before the carrier plate is mounted
Figure 45 Step 6 is to check the electrical grounding
Upper bellow of the suction channel
Dismounted rubber sealing before start of assembly
Fixing screws
Electrical grounding has to be checked!
Page 42
To finish the assembly execute the first 2 steps in reverse order.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 46 Fuse on the rear side of the measuring head
WARNING! Unplug the main connector during the exchange of the fuse.
Fuse II
Page 43
5.7 Measuring head fuses
The device has two internal fuses. The first is located in the main connector of the measuring head. This is a ‘self-repairing’ fuse which protects the filter circuit in the connector.
To reset this fuse, unplug the main connector and wait 5 minutes before you plug it again.
If all LED’s remain off exchange the 2A semi lag fuse II at the rear side of the measuring head (see Figure 46).
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 47 isolation of earth fault problem
Measure contact of Pin No. 7 against ground. If short circuit: problem is outside the Oil Mist Detector, maybe in cabling system
Measure contact of Pin No. 8 against ground. If short circuit: problem is outside the Oil Mist Detector, maybe in cabling system
Measure resistance between Pin 7 & 8. Must be 33 kOhm or due to wire break resistor
Measure resistance between Pin 7 and plug earthing pin. If short circuit: measuring head has to be replaced
Measure resistance between Pin 8 and plug earthing pin. If short circuit: measuring head has to be replaced
Page 44
5.8 Check for earth fault problem
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
WARNING! Unplug the main connector during welding work around the engine or in engine room!
Page 45
In case all LED’s remain off despite fuses are ok, perform check as shown in Figure
47. Often it happens during welding work around the engine or in engine room that
electrical current of high energy passes through detector and its electrical wiring.
As a result, possible bursts and peaks may cause damage inside the measuring head. In that case, only a replacement of the measuring head helps.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
CAUTION! Maintenance work has to be done when engine is stopped.
Quarterly or after 2000 operating hours, whatever comes first
1 Check negative pressure in the measuring head: under 55 mmWC adjust pressure between 55 mmWC and 65 mmWC okay between 65 mmWC and 85 mmWC adjust pressure over 85 mmWC check pressure regulator unit
See chapter 3.1 page 28
2
Clean infrared filters in the measuring head
See chapter 5.2 page 37
3
Clean fresh air bores in the measuring head
See chapter 5.1 page 37
4
Check air cleaner module
See chapter 2.1.7 page 21
Half-yearly or after 4000 operating hours, whatever comes first
5
Perform quarterly maintenance procedure 1 - 4
6
Exchange air filters in the measuring head
See chapter 5.3 page 38
Yearly or after 8000 operating hours, whatever comes first
7
Perform half-yearly maintenance procedure 5 - 6
8
Exchange filter in air cleaner module
See chapter 5.4 page 38
9
Clean suction system with compressed air. ATTENTION, do not forget to refill siphons!
See chapter 3 page 29/30
10
Check the bellows and the suspension-system between measuring head and base plate, check the scavenging air outlet behind the control cover (see Figure 35) by feeling the air stream to control scavenging air system
11
Perform functional test with smoke-tubes
See chapter 7.1 page 47
Bi-yearly or after 16000 operating hours, whatever comes first
12 An inspection of the entire OMD installation onboard has to be executed by service staff being trained and authorized for this job by Schaller Automation
13
Perform functional test of entire OMD system with smoke
See chapter 7.2 Page 49
Additional every 5 years or 40000 operating hours, whatever comes first
14
Exchange suspension-system and bellows
See chapter 5.6 page 41
Page 46
6 Maintenance procedures
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Attention: Before starting the on board test, make sure, the OMD has been maintained according maintenance schedule (chapter 6). If used make sure, that all siphons have to be filled with oil (refer to chapter 2.1.3.)
Smoke Test-Box 151780
Smoke tubes Hand pump kit Working instruction
Attention: You will stop or slow down the engine Figure 48 Adapter assembly with smoke tube and pump
Step 1
Remove the lock screw.
Step 2
Mount the adapter for the smoke tube.
A
B
Page 47
7 Functional test
7.1 On board test
By using the VN Smoke Test-Box you can easily test the functionality of the VISATRON® oil mist detector and its connection to the safety system of the engine. The set can be ordered separately under Part.-No. 151780. It consists of the following parts:
Test procedure step by step:
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Step 3
Add the flexible hose.
Step 4
Mount the smoke tube and hand pump and then add them to the flexible hose.
Step 5
Use the hand pump to generate smoke (it may work even without the pump
Step 6
Wait for the 'Alarm'-LED. At this comes on, the engine has to stop or to enter the slowdown mode
Step 7
Dismount the test equipment and carefully reinstall the lock screw. Caution! Do not forget the gasket underneath the lock screw, otherwise you will risk a mixture of explosion zones!
Always use a new gasket for the lock screw after removing for testing!
Step 8
Wait for the 'Ready'-LED.
Step 9
Press the Oil-Mist-Alarm RESET button to acknowledge the alarm state and enter the normal monitoring mode.
If LED14 is blinking and the Oil-Mist-Alarm RESET button is pressed the OMD device enters a test mode. In this test mode the LED bar displays the measured opacity. After pressing the Oil-Mist-Alarm RESET button again the OMD device exits the test mode and LED14 is blinking again.
Attention: Always use a new gasket for the lock screw after removing it for testing! (Step 7)
Page 48
If applicable perform an additional pressure measurement to check the tightness of the suction system as described in chapter 7.3. Instead of an electronic gauge you can use the U-pipe manometer of the service box.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Attention: Before starting the on board test execute the procedures as specified in the maintenance schedule. The pipe system has to be clean and if used all siphons have to
be filled with oil refer to chapter 2.1.3.
Figure 49: SCHALLER AUTOMATION smoke generator, see 'Accessories'
Storage tank
Reservoir
Flexible hose
Page 49
7.2 Factory test at engine builder with smoke generator on
VN115/87plus EX installations
Due to vessels not normally having the equipment and SCHALLER AUTOMATION recommends this procedure only for the factory test by using the SCHALLER smoke generator (see Figure 49). If a smoke generator is available on a vessel, this test can be also performed. However, in this case observe the following warning.
A test of the entire OMD system (incl. tubing system) can be done only at standstill of the engine. The crankcase service covers must be opened first. Put a small
amount of smoke fluid (see Chapter 'Accessories') into the reservoir and switch on
the generator for a few seconds until the storage tank is completely filled with smoke. The last step is to hold the flexible hose directly into the suction funnels until an oil mist alarm is indicated.
If it's not possible to open the service covers a functional test can be performed without testing the suction funnels.
In this case the flexible hose has to be pressed over the opening under the lock screws of the siphon blocks as seen in Figure 50 or has to be pressed over the open header pipe end after removing the lock nut.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 50: Test inlet on the siphon blocks VN180
Attention: In case of siphon block VN180 installation you have to test all compartments and the additional suction points at running engine.
Figure 51: Manometer (not scope of
supply) connected to siphon block VN180
Figure 52: Manometer (not scope of
supply) connected to header pipe
Attention: You will only measure correct values with engine and lube oil pump at standstill.
19 mm nut
17 mm nut
Adapter
Lock screw
Page 50
7.3 Additional pressure measurement on VN115/87plus EX installations
Perform the functional and smoke test as shown in the previous chapters 'On board test' and ‘Factory test with smoke generator’.
Then carry out a pressure measurement at the end of the suction system. The engine including the oil pump must be at standstill.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Minimal suction pressure at the far left and right end of the suction tubing system
VN115/87plus EX >6.5 mmWC
Figure 53: optional Fog machine
Figure 54: optional Fog bag adapter
Page 51
On a VN115/87plus EX installation the tightness of the suction system can be determined by a pressure measurement at the outer siphon blocks or at the end of the header pipes.
This siphon block has an additional fitting for a manometer (see Figure 51). To
remove the 17 mm lock nut you have to counter the 19 mm nut with a jaw wrench.
The pressure measurement procedure can also performed at the end of the 22 mm diameter suction pipes which are delivered from SCHALLER AUTOMATION. These
pipes have also fittings for the manometer at the pipe end (see Figure 52).
Use only a digital manometer with a differential measuring method. On completion do not forget to lock all openings.
The minimal negative pressure values are defined in the table below. They are only valid if a negative pressure of 60 mm WC is adjusted at the measuring head.
7.4 Factory test at engine builder with fog machine on all installations
This test includes the indication of an oil mist alarm as well as the indication of the affected compartment. Instead of the above mentioned smoke generator you have to use the more powerful fog machine (see Figure 53) with a fog bag with adapter (see Figure 54).
This equipment guarantees a constant fog concentration during the test and due to high density no influence of the additionally sucked in crankcase atmosphere.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Attention: Let in fog at sampling points of all compartments including chain/gear drive.
Figure 55: Test fog inlet on the siphon blocks
Lock screws
Page 52
Due to the increasing request of the ship owners and classification societies to test the OMD-System at running engines SCHALLER AUTOMATION recommends now following procedure.
The first test must be performed at standstill to secure, that the engine is well protected by the OMD system. If it is not possible to open the service covers or if it is not possible to access the suction funnels, e.g. on large 2-stroke engines, a functional test can be performed alternatively using a special connection on the siphon block or respectively on the T-engine wall connection.
Fill the fog bag completely with fog and close the adapter with the yellow cap. The next step is to press the flexible hose of the fog bag adapter over the opened plug at the side of the siphon blocks as seen in Figure 55 or over the open tube end at T-engine wall connections. Do not remove the hose until an oil mist alarm is indicated and the search run to indicate the affected compartment is finished. The plugs can be countered by an 11 mm jaw wrench to open or close the lock screw.
The second test can be performed on request at running engine using the plugs of the siphon block or the T-engine-wall connection to induce the fog.
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Part-No. new
Part-No. old
Description
Quantity per OMD
150516
Service box series VN87plus EX
1
12601
Measuring head VN115/87plus EX; 33k (wire break resistor); RS485; sensitivity level 4
1
12602
Measuring head VN115/87plus EX; 24k; 4­20mA; sensitivity level 4
1
12603
Measuring head VN115/87plus EX; 3k; 4­20mA; sensitivity level 4
1
12604
Measuring head VN115/87plus EX; 10k; RS485; sensitivity level 4
1
12605
Measuring head VN115/87plus EX; 33k; 4­20mA; sensitivity level 4
1
12606
Measuring head VN115/87plus EX; 33k; RS485; sensitivity level 5
1
12607
Measuring head VN115/87plus EX; 10k; RS485; sensitivity level 6
1
12608
Measuring head VN115/87plus EX; 33k; RS485; sensitivity level 6
1
270975
Control cover measuring head VN115/87plus EX devices
1
355970
Gasket control cover VN87plus EX
1
150994
Base plate VN115/87plus EX compl.
1
270440
Mounting plate VN87plus EX compl.
1
365206
10002
Air filter for pressure regulator unit
1
365197
10042
Scavenging air filter (10 pcs.)
2
270090
10035
Bottle with cleaning fluid
1
190003
10135
Cleaning needle
1
452176
10036
Cotton buds to clean IR-filters (min. 10 pcs.)
1
200548
10046
U-pipe manometer
1
270502
Manometer adapter for siphon block VN180
1
270089
10040
Bottle with slacked water
1
270493
10053
Manometer adapter for control cover
1
310526
10087
Fuse cap
1
436551
10973
Semi lag fuses 3.15A (10 pcs.)
1
365193
10023
Bellow of suction Channel
2
365198
10041
Circlip for scavenging air filter (10 pcs.)
2
200175
11004
Main connector socket
1
273119
Air filter for oil/water separator
1
270416
Scavenging air hose assembly
1
270611
L-connection set
1
366663
Pressure regulation element VA M12x1,5
1
366664
Pressure regulation adapter
1
Page 53
8 Optional Spare Parts and Accessories
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
365280
Gasket G½" oil proof
1
Part-No. new
Part-No. old
Description
150516
Service box series VN87plus EX
151780
VN-Smoke Test-Box
180080
Manual DVD series VN87plus EX
151072
10001
Pressure regulator unit with input throttle
270888
10753
Protection cover
150938
11163
Oil separator for air outlet
150939
11164
Pipe siphon
150260
10013
Siphon block VN180
150166
10612
Siphon block VN180 with manometer fitting
270504
10089
Mounting plate VN180
270371
10062
Oil pump VN180
340375
10640
Blind plug VN180
150740
10353
Smoke generator, 230 Volts
151067
11089
Smoke generator, 110 Volts
451209
10097
Smoke fluid
151167
11049
Fog machine complete
450137
11052
Fog fluid
272059
Smoke tube (6 pcs.)
450421
Smoke hand pump
150998
11506
Monitoring device Remote Indicator II
230140
11503
Bus-cable 10m for monitoring devices
Depends on engine type
Suction funnel
Depends on engine type
Engine wall connection
Page 54
Table 4: Optional Spare parts
Table 5: Optional Accessories
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 56: Optional Service box 150516
Page 55
8.1 Optional Service Box
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Item
Description
Quantity
For spares
01
Service box VN87plus EX content list
1
180509
02
Scavenging air filters
6
365197 / 10042
03
Cleaning needle
1
190003 / 10135
04
Fuse 2A semi time lag
10
436551 / 10973
05
Screwdriver 3 mm
1
190143 / 10038
06
Hex key 5 mm L-shape
1
190138 / 10044
07
Flexible bellows of suction channels
2
365193 / 10023
08
Air filter for pressure regulator unit
1
365206 / 10002
09
Suspension elements bottom
2
355055
10
Suspension elements top
2
355054
11
Bottle with slacked water
1
270089 / 10040
12
Bottle with cleaning fluid
1
270090 / 10035
13
Service kit O-ring pressure regulator unit
1
270610
14
Manometer adapter for siphon block VN180
1
270502
15
U-pipe manometer
1
200548 / 10046
16
Manual series VN87plus EX in English
1
180080
17
Circlip pliers for Seeger rings
1
190146 / 10048
18
Screwdriver 4 mm
1
190046 / 10157
19
Hex key 4 mm with handle bar
1
190052
20
Philips screwdriver
1
190053
21
Double jaw wrench 14/17 mm
1
190050 / 10356
22
Hex key 6 mm L-shape
1
190206 / 10047
23
Hand pump
1
450421
24
Smoke tube
1
450420
25
Flexible hose D10
1
270705
26
Connection QS-10-6
1
366633
27
Flexible hose D6
1
366655
28
Connection QS-G¼-6
1
270704
29
Manometer adapter for control cover
1
270493 / 10053
30
Seeger circlip rings
4
365198 / 10041
31
Cotton sticks to clean IR-filters
5
452176 / 10036
32
Gasket for valve box
1
330721 / 10405
Page 56
Table 6: Contents of optional service box VN87plus EX 150516
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 57: VN-Smoke Test-Box 151780
Page 57
8.2 VN-Smoke Test Box
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Item
Description
Quantity
For Spares
01
Hand pump
1
450421
02
Smoke tube
1 (6 pcs.)
272059
03
Adapter flexible hose f. smoke tubes
1
270710
04
Connection QS-G¼-6
1
270704
05
Flexible hose D6
1
366655
Page 58
Table 7: Contents of VN-Smoke Test-Box 151780
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Mechanical data
Dimensions
See drawings (Figure 58)
Weight
VN115/87plus EX 8.4 kg
Display
LED-bar with 14 LED's 1 green Ready LED 1 red High Oil Mist Alarm LED 1 red Test LED
Suction pipes
VN115/87plus EX ø 22 x 2 x max. 9m
Pipe connections
VN115/87plus EX 2 x G3/4
Venturi injector connections
In NTP/BSP/G1/2A Out NTP/BSP/G3/4A
Pressure reducer connections
In NTP/BSP/G1/4A Out NTP/BSP/G1/4A
Electrical data
Power supply
18 Volts – 31.2 Volts DC, max. 2A
Nominal voltage
24 Volts DC
Relay Outputs
2 x 'High Oil Mist Alarm' 1 x 'Ready' 1 x 'Oil Mist Pre-Alarm' (max. 60 Volts DC, 1A)
Cable entry
2 x M25
Communication interface to monitoring device
2 wire RS485, galvanically isolated (opt. 4-20 mA, galvanically isolated)
Communication cable recommendation
LAPPKABEL UNITRONIC-FD CP (TP) plus UL-CSA, 2 x 2 x AWG20, max 400 m length, 7.5-10.0mm Ø
Air data
Air pressure
Pressure reducer inlet 2 – 15 bar Air jet pump inlet max. 500 mbar
Air consumption
Depends on the suction system (max. 2,5 m3/h)
Negative pressure in measuring head
- 60 mm WC or – 6 mbar
Air quality
ISO8573-1:2010 – “6-4-4”
Page 59
9 Technical data
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Environmental conditions
Operating temperature
+5 - +70 °C
Storage temperature
-25 – +80 °C
Max. vibrations
4 g (25-100Hz)
Relative humidity
up to 95%
Protection class
IP54
Approval of classes
Type approved for closed areas, designed for installation on combustion engines, environmental category D (GL), IACS UR M67 conform, list of type approvals see www.schaller.de
II (2G) [Ex op is IIB T4 Gb]
Figure 58: Mechanical dimensions of VN115/87plus EX: side view
Page 60
EC-Type examination for equipment and Components intended for use in potentially explosive atmosphere (directive 94/9/EC)
Table 8: Technical data
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Figure 59: Mechanical dimensions of VN115/87plus EX: top view
Figure 60: Drilling template of the OMD base plate
Page 61
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Operation Manual VISATRON® VN115/87plus EX 06/2016
Argentina
Latvia
Australia
Lithuania
Bahrain
Mauritania
Belgium
Mexico
Belize
Morocco
Bolivia
Netherlands
Brazil
Nicaragua
Canada
Norway
Cape Verde Islands
Oman
Chile
Panama
Colombia
Peru
Costa Rica
Philippines
Denmark
Poland
Ecuador
Portugal
El Salvador
Qatar
Estonia
Saudi Arabia
France
Senegal
Germany
Singapore
Greece
Spain
Guatemala
Sweden
Honduras
Taiwan
Iceland
Turkey
India
United Arabian Emirates
Iran
United Kingdom
Ireland
United States of America
Italy
Caribbean Islands
Japan
Korea
Kuwait
Page 62
10 Service Partners
Schaller Automation maintains a worldwide network of service partners in following countries:
For an up-to-date list of our representatives including address and contact details please visit our website:
www.schaller.de
or call our technical support center at the German headquarter:
Tel. +49 6842 508 0
SCHALLER AUTOMATION D-66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O Box 1280
Industrielle Automationstechnik GmbH & Co. KG Tel. +49(0)6842-508-0 / Fax -260 / eMail: info@schaller.de / www.schaller.de
Loading...