Schako BSK-RPR Series, BSK-RPR-S, BSK-RPR-F Additional Operating Instructions

Page 1
Additional operating instructions according to
BSK-RPR
Fire Damper
GENERAL CONDITIONS ........................................... 1
DESCRIPTION .......................................................... 3
MODELS AND DIMENSIONS .................................... 4
EC Certificate of Conformity
0761 – CPD – 0245
Declaration of Performance
09-22-DoP-BSK-RPR-2013-07-01
SCHAKO | Ferdinand Schad KG Telephone +49 (0) 7463-980-0 Steigstraße 25-27 Fax +49 (0) 7463-980-200 D-78600 Kolbingen www.SCHAKO.de | info@SCHAKO.de
Page 2
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
GENERAL CONDITIONS
GENERAL CONDITIONS
GENERAL DESCRIPTION AND INSTRUCTIONS
These additional operating instructions must be observed prior to mounting and commissioning the device.
These additional operating instructions contain basic infor­mation regarding its use in areas subject to explosion haz­ards to be observed during assembly, operation and mainte­nance.
Prior to mounting and commissioning and during mainte­nance work, the present additional operating instructions must be read by the installer and the responsible skilled per­sonnel/system operator!
PERSONNEL QUALIFICATION AND TRAINING
The personnel for assembly, inspection and maintenance must have the relevant qualification for this work. The area of responsibility, competence and monitoring of the person­nel must be exactly regulated by the system operator. If the personnel does not have the required knowledge, it must be trained and instructed. Moreover, the system operator must ensure that the contents of the additional operating instruc­tions are completely understood and adhered to by the per­sonnel.
SAFETY-CONSCIOUS WORK
The safety instructions given in these additional operating instructions, the existing national and international regula­tions on explosion protection, accident prevention and the system operator's internal work, operating and safety regu­lations must be observed.
DESIGNATED USE
DELIVERY AND STORAGE
Upon receipt, the devices must be checked for completeness and transport damage. If the device was delivered incom­pletely or damaged, the forwarding company and the SCHAKO KG have to be informed immediately.
The fire dampers must not be exposed directly to weather, solar radiation and moisture ( see also "General infor­mation").
MOUNTING INFORMATION
Mounting, electrical connection work and commissioning must be carried out by skilled personnel only and in accord­ance with the recognised technical rules and the safety and accident prevention regulations.
MAINTENANCE
Only a device subjected to proper maintenance and kept in perfect condition can guarantee safe and reliable operation.
When defective parts are replaced with spare parts, only SCHAKO KG original spare parts may be used. The SCHAKO KG cannot be held liable for any damage caused by using spare parts that are not original and will not give any war­ranty.
HAZARD CAUSED BY NON-OBSERVANCE OF THE SAFETY INSTRUCTIONS
Non-observance of the safety instructions can result both in putting persons and the environment and operating units at risk. Likewise, non-observance of the safety instructions will re­sult in the loss of any claims for damages.
The devices have been designed for use in ventilation sys­tems in areas subject to explosion hazards according to the ATEX marking "Device group II, Zones 1, 2 and 21, 22.
These devices are not suitable for use in unreleased Ex zones.
The operating safety of the delivered devices is only guaran­teed when used in accordance with their designated use.
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 2
Page 3
DESCRIPTION
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
ON
DESCRIPTI
Fire dampers built into ventilation ducts (air-conditioning systems) are used for the automatic locking of fire lobbies. The fire damper BSK-RPR corresponds to DIN EN 15650, 13501-3 and EN 1366-2. The BSK-RPR has been tested ac­cording to EN 1366-2 in accordance with the Declaration of Performance No. 09-22-DoP-BSK-RPR-2013-07-01. It is in possession of the EC certificate of conformity 0761 - CPD -
0245. Its classification according to EN 13501-3 is EI 90 (ve, ho io) S. According to Directive 94/9/EC, EC Conformity Cer­tificate Number EPS 09 ATEX 2 153 X, its use is permitted in hazardous areas, not only with spring return actuator X10 (ExMax-5.10-BF), including safety temperature limiter (FireSafe /ExPro-TT), but also with mechanical trigger via fu­sible link (manual actuation with or without ATEX limit switch ES-Ex). The fire damper is marked as follows accord­ing to ATEX:
II 2 G IIC T6 II 2 D T80°C II 3 D T80°C
*)
when using the safety temperature limiter FireSafe.
The national standards and guidelines must be observed in connection with these additional operating instructions. For maintenance, servicing, retrofitting, etc., it may be nec­essary to provide on-site inspection openings in suspended ceilings, shaft walls, downstream ventilation ducts, etc. They must be built in in sufficient numbers and size and must not impair the functioning of the fire dampers.
*)
EPS 09 ATEX 2 153 X
The fire damper complies with the regulations of the ATEX directives and may be used in supply and return air installa­tions of ventilation systems in areas subject to explosion hazards.
The fire damper is certified for device group II, Zones 1, 2 and 21, 22. Zones 1 and 2 represent the application range containing gases/vapours, while Zones 21 and 22 represent the applica­tion range containing dusts.
Classification by zone must be established by the system op­erator or planner in compliance with current standards.
Note:
In explosion-protected zones, only devices that have an ATEX approval for this use may be used.
The fire dampers must be connected to the ventilation ducts of the ventilation system either on one or both sides. When connected on one side, finishing protective gratings made of non-flammable building materials (EN13501-1) must be pro­vided on the opposite side. The fire dampers can be con­nected to non-flammable or to flammable ventilation ducts.
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 3
Page 4
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
MODELS AND DIMENSIONS
Dimensions
BSK-RPR-S (plug-in connection)
Figure 1: Dimensions of the BSK-RPR-S
Figure 2: Dimensions of the BSK-RPR-S with drive X10
(ExMax-5.10-BF)
1 Housing 2 Damper blade 3 Hand lever 4 Locking profile 5 Trigger device 6 Fusible link 7 Mounting frame AR 8 Drive unit 9 Earthing connection 10 Drive X10 (ExMax-5.10-BF) 11 Safety temperature limiter
Rubber lip seal for BSK-RPR-S Model BSK-RPR-S is delivered as standard with rubber lip seal
Figure 3 : Rubber lip seal
Available sizes [mm]
Nominal
size 100 98 125 123 140 138 160 158 180 178 455 375 200 198 224 222 250 248 280 278 580 500 315 313 (standard) (standard) 355 353 400 398 450 448 500 498
øD
[mm]
BSK-RPR-S BSK-RPR-F
Table 1: Available sizes [mm]
L [mm]
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 4
Page 5
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
BSK-RPR-S with mounting frame AR
Figure 4: Dimensions of the BSK-RPR-S with
mounting frame AR
Figure 5: Dimensions of the BSK-RPR-S with mounting
frame AR with drive X10 (ExMax-5.10-BF)
BSK-RPR-F (flanged connection)
Figure 6: Dimensions of the BSK-RPR-F
Figure 7: Dimensions of the BSK-RPR-F with drive X10
(ExMax-5.10-BF)
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 5
Page 6
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
Weight table [kg]
BSK-RPR-S
Nominal
size
100 98 2.44 (6.73)¹⁾ 3.89 (8.18)¹⁾ 2.74 (7.03)¹⁾ 4.19 (8.48)¹ 125 123 2.83 (7.69)¹⁾ 4.28 (9.14)¹⁾ 3.21 (8.07)¹⁾ 4.66 (9.52)¹ 140 138 3.06 (8.27)¹⁾ 4.51 (9.72)¹⁾ 3.49 (8.70)¹⁾ 4.94 (10.15)¹ 160 158 3.35 (9.02)¹ 4.8 (10.47)¹⁾ 3.84 (9.51)¹⁾ 5.29 (10.96)¹ 180 178 3.65 (9.79)¹ 5.1 (11.24)¹ 4.2 (10.34)¹ 5.65 (11.79)¹ 200 198 3.97 (10.59)¹⁾ 5.42 (12.04)¹⁾ 4.59 (11.21)¹ 6.04 (12.66)¹ 224 222 4.37 (11.58)¹⁾ 5.82 (13.03)¹⁾ 5.07 (12.28)¹ 6.52 (13.73)¹ 250 248 4.8 (12.62)¹⁾ 6.25 (14.07)¹⁾ 5.58 (13.40)¹ 7.03 (14.85)¹ 280 278 6.31 (16.55)¹⁾ 7.79 (18.03)¹⁾ 7.17 (17.41)¹ 8.65 (18.89)¹ 315 313 7.14 (18.40)¹⁾ 8.62 (19.88)¹⁾ 8.13 (19.39)¹ 9.61 (20.87)¹ 355 353 8.08 (20.53)¹⁾ 9.56 (22.01)¹⁾ 9.19 (21.64)¹ 10.67 (23.12)¹ 400 398 9.09 (22.89)¹⁾ 10.57 (24.37)¹⁾ 10.34 (24.14)¹ 11.82 (25.62)¹ 450 448 10.5 (25.84)¹⁾ 11.98 (27.32)¹⁾ 11.91 (27.25)¹ 13.39 (28.73)¹ 500 498 11.85 (28.75)¹⁾ 13.33 (30.23)¹⁾ 13.42 (30.32)¹ 14.9 (31.80)¹
¹) approx. weight with additional mounting frame AR
BSK-RPR-F
Nominal
size
100 98 2.49 3.94 2.80 4.25 125 123 2.89 4.34 3.29 4.74 140 138 3.13 4.58 3.57 5.02 160 158 3.43 4.88 3.93 5.38 180 178 3.74 5.19 4.31 5.76 200 198 4.07 5.52 4.70 6.15 224 222 4.48 5.93 5.19 6.64 250 248 4.93 6.38 5.71 7.16 280 278 6.45 7.93 7.33 8.81 315 313 7.30 8.78 8.29 9.77 355 353 8.26 9.74 9.37 10.85 400 398 9.29 10.77 10.55 12.03 450 448 10.73 12.21 12.14 13.62
500 498 12.10 13.58 13.67 15.15
Table 2: Weight tables [kg]
øD
[mm]
øD
[mm]
Manual release
Manual release
L=455 L=580
10 Drive X10
L=375 L=500
10 Drive X10 (ExMax-5.10-BF)
(ExMax-5.10-BF)
Manual release
Manual release
10 Drive X10
10 Drive X10 (ExMax-5.10-BF)
(ExMax-5.10-BF)
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 6
Page 7
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
Electric spring return actuator X10 (ExMax-5.10-BF)
X10 (ExMax-5.10-BF)
Connection X10 (ExMax-5.10-BF)
Open/closed 1-wire spring return + Ex-i circuit SB 7.0
BSK
24…240 VAC/DC
Heating
Standard connection = spring return in ~ 10 sec.
Figure 8: Circuit diagram drive X10 (ExMax-5.10-BF)
Electric explosion-protected spring return actuators with safety temperature limiter (FireSafe/ ExPro-TT).
Trigger temperatures 72° optionally 95 °C (for hot-
air heating).
Operating position (damper "OPEN") and tension-
ing of the return spring by applying the supply voltage (universal power supply 24 - 240 VAC/DC)
Safety position (damper "CLOSED") through spring
force when supply voltage is interrupted or the temperature fuses (ambient temperature or inter­nal duct temperature) respond. A response of the thermal fuses will interrupt the sensor circuit per­manently and irrevocably.
End position signalling by integrated auxiliary
switches, switching at an angle of rotation of 5° and 85°.
On-site function control is possible by means of the
control key of of the safety temperature limiter
Attention! Safety function is only guaranteed if the drive has been connected to the supply voltage in accordance with regula­tions.
integrated, permanently set auxiliary switch, max. 24V/3A, 240V/0.5A switch­ing at an angle of rotation 5° and 85°.
The voltage on the auxiliary switch must
be identical to the supply voltage and
protected by an identical fuse.
! Attention!
For a 1-wire control, the heating is not ac­tive when the contact is in-
Ex-i circuit for passive, potential-free pushbuttons provided by the cus­tomer and thermally activated safety release device
Button
Technical data drive X10 (ExMax-5.10-BF)
Power supply 24…240 V AC/DC, ± 10% each,
Frequency 50...60 Hz ± 20%
Power consumption
Holding max. 20 W
Heating ca-
pacity
Current on making Running time Motor
Spring re­turn Auxiliary switch 2 integrated, permanently set, poten-
Switching voltage
Switch volt­age
Switching points Protection class I (earthed)
Protection type ac­cording to DIN 60529 Tested according to EMC Safety tested 2006/95/EC
Ambient temperature (operation)
Ambient humidity 95%, non-condensing
Table 3: Technical data drive X10
self adaptable
approx. 16 W
approx. 2.0 A at 24 V for approx. 1 sec.
30s
10s
tial-free auxiliary switches with change­over contact 24 V DC / 230 V AC
0.5 mA - 3 A
Angles of rotation: 5° / 85°
IP 66
2004/108/EC
-40 ... +40 °C
(ExMax-5.10-BF)
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 7
Page 8
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
Limit switch type ES-Ex
Limit switch for application in areas subject to explosion haz­ards
II 2G Ex d IIC T6/T5 Gb,
II 2D Ex tb IIIC T 80°C/ 95°C Db
IP65; 250V / 6A AC15; 230V / 0.25A DC13; -20°C Ta +65°C
Figure 9: Circuit diagram limit switch type ES-Ex
General information
During mounting or installation, there is a risk of injuries.
To avoid any possible injuries, personal protective equipment (PPE) must be worn.
Fire dampers must be installed such that external forces
do not impair their permanent functioning. During mounting it may be required to provide reinforcements for the housing or the like. The requirement of statically load-bearing lintels may have to be taken into considera­tion.
Improper transport/handling may result in dam-
age/functional impairment. In addition to that, the film of the transport packaging must be removed and the de­livery inspected for completeness.
In storage, fire dampers must be protected from dust,
dirt, moisture and the effects of temperature (e.g. direct sunlight, heat-emitting light source, etc.). They must not be exposed to direct effects of the weather and must not be stored below -40 °C (ES-Ex -20°C) or above 50 °C.
The fire damper must be protected from dirt and dam-
age. After installation is complete, any dirt must be re­moved immediately.
Enough space must be provided for installation, mortar
lining, etc.
Carry out a functional check of the fire damper before
and after mounting and ensure ready access.
Electrical installations or work on electrical components
may only be carried out by skilled electricians. The sup­ply voltage must be switched off when performing this work.
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 8
Page 9
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
Information regarding assembly and commissioning
Prior to being installed in the ventilation system, the fire damper must be checked for damage. Damaged fire damp­ers must not be installed.
The device may only be used in accordance with its desig­nated use in air ventilation systems for supply air and return air.
Use only approved fastening material for mounting.
No additional parts may be fastened to the fire damper.
The fire damper must be connected to the ventilation duct network on both sides in electrically conducting fashion.
In order to avoid the risk of static charges, the fire damper must be connected to the on-site equipotential bonding on the grounding connection provided for this purpose.
Make sure that the ventilaton systems are not subjected to any anomalous operating conditions, such as vibrations, pressure surges or high proportions of solids in the medium.
Information regarding maintenance and inspection
Proper maintenance increases operational safety and the service life of the device. This is why the devices should be subjected to regular inspection.
If inspection dates are prescribed by law, they must be com­plied with.
The operating personnel must be informed, prior to starting maintenance and inspection work.
The personal safety measures must be looked up in the safe­ty data sheet. Hazard caused by contact or inhaling hazard­ous substances must be excluded by taking appropriate safe­ty measures.
Prior to maintenance or inspection, all system components up- and downstream of the device must be switched off and secured against being switched on again.
The following inspection criteria must be observed:
Visual inspection of the device Check the fastening of the device Check the electrical connections Check the grounding connection for tight fit and good
contact.
Functional check For additional inspections, please refer to the technical
documentation or additional maintenance instructions.
Use and electrical connection of actuators in areas subject to explosion hazards
Only ATEX-approved electrical equipment according to ATEX Directive 94/9/EC for Zones 1, 2, 21, 22, such as actuators, terminal boxes and thermocouples as specified by SCHAKO KG may be used for devices from SCHAKO KG.
The connection lines must be installed for permanent use and in such a way that they are sufficiently protected from mechanical and thermal damage.
Devices with explosion-protected drives and terminal boxes have to be attached over the external potential connecting terminal to the potential equalisation provided by the cus­tomer with at least 4 mm² cooper solid-core.
The electrical connection lines of the actuators must be connected in a terminal box according to ATEX Di­rective 94/9/EC for Zones 1, 2, 21, 22 if the electrical connec­tion is made in the area subject to explosion hazards.
The dimensioning of the conductor cross-sections must be observed.
The actuators are maintenance-free with respect to their function, but the relevant maintenance regulations accord­ing to ATEX directives or factory regulations must be ob­served.
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 9
Page 10
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
Certificate of conformity
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 10
Page 11
Fire Damper Model BSK-RPR Additional operating instructions according to ATEX 94/9/EC
MODELS AND DIMENSIONS
Construction subject to change No return possible Version: 2015-08-17 | Document: Z09/46 | Page 11