SCHAFFNHER FN 3258 Technical data

Ultra-compact EMC/RFI filter for three-phase systems and motor drives
available for the whole range
n Exceptional attenuation performance
from 150kHz to 30MHz
50m cable length
n Most compact and slim filter design
in its class
3-phase filters
FN 3258
Approvalsn New: solid safety connector blocks
Technical specifications
Maximum continuous operating voltage: 3x 480/277VAC (FN 3258) 3x 520/300VAC (FN 3258H) Operating frequency: dc to 60Hz Rated currents: 7 to 180A @ 50°C High potential test voltage: P –> E 2650VDC for 2 sec P –> P 2100VDC for 2 sec Protection category: IP20 Overload capability: 4x rated current at switch on,
1.5x rated current for 1 minute, once per hour Temperature range (operation and storage): -25°C to +100°C (25/100/21) Flammability corresponding to: UL 94V-2 or better Design corresponding to: UL 1283, CSA 22.2 No. 8 1986, EN 60939 MTBF @ 50°C/400V (Mil-HB-217F): 300,000 hours
Features and benefits
n The extremely compact and slim filter
design allows a trouble-free installation
even where the available mounting space
is minimal.
n With new additional filter types providing
safety terminal blocks, the most preferred
connection style can be chosen fast and
easy. This helps to stay in line with the
electrical connection concept of a given
n Filter operation on the mains input side
of consumers increases their reliability and
conducted immunity significant.
n Chokes with exceptional saturation resist-
ance and excellent thermal behavior are a
vital part of FN 3258 design. Thus, all filters
retain the expected filter performance
even in very noisy applications and under
full load conditions.
application.
n FN 3258 filters ensure compliance with
Class A limits according to EN 55011 up to
50m cable length and beyond. Further
they can contribute significantly to meet
conducted emission limits according to
Class B.
Typical electrical schematic
L1
L2
L3
Cx R1
PE
Line
L
Cx
Cy
R2
L1‘
L2‘
L3‘
PE
Load
Typical applications
n Three-phase variable speed motor drives,
servo drives, inverters and converters
n Applications comprising energy conversion
devices like machines or process auto-
mation equipment
n HVAC equipment, elevators, power
supplies, UPS and further three-phase
applications
> Components > FN 3258
Filter selection table
Filter* Rated current Typical drive Leakage current*** Power loss Input/Output Weight @ 50°C (40°C) power rating** @ 400VAC/50Hz @ 25°C/50Hz connections
[A] [kW] [mA] [W] [kg]
FN 3258-7-.. 7 (7.7) 4 33.0 3.8 -45 -44 0.5 FN 3258-16-.. 16 (17.5) 7.5 33.0 6.1 -45 -44 0.8 FN 3258-30-.. 30 (32.9) 15 33.0 11.8 -47 -33 1.2 FN 3258-42-.. 42 (46.0) 22 33.0 15.7 -47 -33 1.4 FN 3258-55-.. 55 (60.2) 30 33.0 25.9 -52 -34 2.0 FN 3258-75-.. 75 (82.2) 37 33.0 32.2 -52 -34 2.7 FN 3258-100-35 100 (109.5) 55 33.0 34.5 -35 4.3 FN 3258-130-35 130 (142.4) 75 33.0 43.1 -35 4.5 FN 3258-180-40 180 (197.1) 90 33.0 58.3 -40 6.0
FN 3258H-7-.. 7 (7.7) 4 33.0 3.8 -45 -44 0.5 FN 3258H-16-.. 16 (17.5) 7.5 33.0 6.1 -45 -44 0.8 FN 3258H-30-.. 30 (32.9) 18.5 33.0 11.8 -47 -33 1.2 FN 3258H-42-.. 42 (46.0) 22 33.0 15.7 -47 -33 1.4 FN 3258H-55-.. 55 (60.2) 37 33.0 25.9 -52 -34 2.0 FN 3258H-75-.. 75 (82.2) 45 33.0 32.2 -52 -34 2.7 FN 3258H-100-35 100 (109.5) 55 33.0 34.5 -35 4.3 FN 3258H-130-35 130 (142.4) 75 33.0 43.1 -35 4.5 FN 3258H-180-40 180 (197.1) 110 33.0 58.3 -40 6.0
* To compile a complete part number, please replace the -.. with the required I/O connection style.
** Calculated at rated current, 440VAC (FN 3258)/480VAC (FN 3258H) and cos phi = 0.8. The exact value depends upon the efficiency of the drive, the motor and the entire application.
*** Maximum leakage under normal operating conditions. Note: if two phases are interrupted, worst case leakage could reach 5.4 times higher levels.
Typical filter attenuation
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym