Schaffner Ecosine active sync User And Installation Manual

Page 1
User and Installation Manual
Ecosine active sync
Schaner Group | Nordstrasse 11 | 4542 Luterbach | Switzerland
T +41 32 681 66 26 | F +4132 681 66 30
|
www.schaner.com
www.myecosine.com
English version
Page 2
myecosine.com 1/165
Revision: 1.7 (October 2019) The most current edition of these instructions (PDF format) can be obtained from your contact of the
Schaffner organization or online at myecosine.com
Other technical documentation of our products is also available in the download area of our website www.schaffner.com
Document name: User and Installation Manual ecosine active sync Rev1.7.pdf
Valid for power module firmware version:
V03.02.03 or higher
(For firmware version, see parameter P010)
Meaning of firmware version number:
V XX.xx.xx – hardware release, downwards incompatible V xx.XX.xx – function version V xx.xx.XX – small compatible changes
Page 3
myecosine.com 2/165
Copyright ©2019 Schaffner International Ltd. All Rights Reserved. All rights of this User and Installation Manual (“Manual”) including but not limited to the contents, information, and figures are solely owned and reserved by Schaffner International Ltd. (“Schaffner”). The Manual can only be applied to the operation or the use of ecosine active sync harmonic filter. Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Schaffner. Given that Schaffner will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes. Schaffner will make all possible efforts to secure the accuracy and the integrity of this Manual. Schaffner disclaims any kinds or forms of warranty, guarantee, or undertaking, either expressly or implicitly, including but not limited to the completeness, faultlessness, accuracy, non-infringement, merchantability or fitness for a particular purpose of the Manual.
Page 4
myecosine.com 3/165
Content
1 Version History .................................................................................................... 7
2 Introduction .......................................................................................................... 8
Purpose ........................................................................................................................................ 8
Additional Resources ................................................................................................................. 8
Naming convention .................................................................................................................... 8
3 General Safety Notes and Installation Guidelines ............................................ 9
4 Environmental Conditions / Exclusion of warranty ........................................ 10
5 Ecosine Active Sync Product Line Overview .................................................. 13
Principle of operation ............................................................................................................... 13
Ecosine active sync system configuration ............................................................................ 14
5.2.1 Ecosine active sync power module FN3530 and FN3531 .................................................. 15
5.2.2 Ecosine active sync power module FN3540 and FN3541 .................................................. 16
5.2.3 Ecosine active sync Double Power Pack (DPP) FN3532 and FN3542 .............................. 17
5.2.4 Ecosine active sync cabinet version (cabinet + power modules) ........................................ 19
Ecosine active sync cabinet version type code information ............................................... 20
Technical specification ecosine active sync power module versions ................................ 24
Technical specification ecosine active sync cabinet versions ............................................ 25
Temperature derating of ecosine active sync power module .............................................. 27
Temperature derating of ecosine active sync cabinet version ............................................ 27
Sync Module SYNC300A .......................................................................................................... 28
5.8.1 Technical specification for Sync module SYNC300A .......................................................... 29
5.8.2 Mechanical dimensions of SYNC300A ................................................................................ 30
Ecosine active sync display module ...................................................................................... 31
5.9.1 RS485 communication ........................................................................................................ 32
5.9.2 AHF parameters and INI file ................................................................................................ 32
5.9.3 Event log and LOG file ........................................................................................................ 32
5.9.4 Load and save AHF parameter set ..................................................................................... 32
6 Mechanical Installation Guidelines .................................................................. 33
Pre-Installation Guidelines ...................................................................................................... 33
6.1.1 Receiving ecosine active sync ............................................................................................ 33
6.1.2 Transportation and unpacking of power modules ............................................................... 33
Page 5
myecosine.com 4/165
6.1.3 Lifting ................................................................................................................................... 33
6.1.4 Important note for installation .............................................................................................. 34
Mechanical installation of ecosine active sync power module ........................................... 34
6.2.1 Dimensions of an ecosine active sync power module ......................................................... 34
6.2.2 Ecosine active sync power module mounting options ......................................................... 37
Mechanical installation of ecosine active sync DPP ............................................................ 38
6.3.1 Dimensions of ecosine active sync DPP ............................................................................. 38
6.3.2 Mounting options of ecosine active sync DPP .................................................................... 38
Mechanical installation inside customer cabinet .................................................................. 40
6.4.1 Customer cabinet requirements .......................................................................................... 40
6.4.2 Cooling requirements of customer cabinet .......................................................................... 40
Mechanical data of ecosine active sync cabinet version ..................................................... 42
6.5.1 Dimensions of ecosine active sync cabinet version ............................................................ 42
6.5.2 Cooling requirements of ecosine active sync cabinet versions ........................................... 44
7 Electrical Installation Guidelines ...................................................................... 45
Protection (Fuses, Breakers) ................................................................................................... 45
Installation with power factor correction (PFC) systems ..................................................... 45
Power Module electrical installation ....................................................................................... 45
7.3.1 Connecting terminal locations ............................................................................................. 45
7.3.2 Connection of AC Mains ...................................................................................................... 52
Sync Module electrical installation ......................................................................................... 53
7.4.1 Connecting terminal location ............................................................................................... 53
7.4.2 Interconnection between Sync Module and Power Modules .............................................. 55
Ecosine active sync cabinet version electrical installation ................................................. 56
7.5.1 Connecting terminal locations ............................................................................................. 56
7.5.2 Connection of AC Mains ...................................................................................................... 58
Connection of current transformers ....................................................................................... 59
7.6.1 Connection of 3-phase 3-wire devices CT secondary output 5A ........................................ 60
7.6.2 Connection of 3-phase 3-wire devices CT secondary output 1A ........................................ 61
7.6.3 Connection of 3-phase 4-wire devices CT secondary output 5A ........................................ 62
7.6.4 Connection of 3-phase 4-wire devices CT secondary output 1A ........................................ 63
Current transformers specifications and cable selection .................................................... 64
Current transformer specification for UL conformity ........................................................... 67
Connection and verification of current measurements ........................................................ 68
7.9.1 CT connection for operation of single ecosine active sync power module ......................... 68
7.9.2 CT connection for operation of double power pack (DPP) ecosine active sync ................. 72
Page 6
myecosine.com 5/165
7.9.3 CT connection for operation of the sync module and multiple ecosine active sync power modules 76
7.9.4 CT connection for parallel operation of several ecosine active sync power modules without
sync module ....................................................................................................................................... 80
7.9.5 Grounding of the current transformers ................................................................................ 84
7.9.6 Checking current transformers rotating field ....................................................................... 85
7.9.7 Checking current transformers phase assignment .............................................................. 86
HS-Bus connection (master-slave configuration) ............................................................. 88
8 Comissioning and Programming ..................................................................... 91
Display module functions ........................................................................................................ 91
8.1.1 Boot window ........................................................................................................................ 92
8.1.2 Home window ...................................................................................................................... 92
8.1.3 Main menu ........................................................................................................................... 92
Ways of Software Commissioning .......................................................................................... 96
8.2.1 Commissioning via Ethernet ................................................................................................ 96
8.2.2 Commissioning via display module ..................................................................................... 96
Commissioning procedure ...................................................................................................... 96
8.3.1 Common steps for all configurations ................................................................................... 96
8.3.2 Single power module or asynchronous operation ............................................................... 97
8.3.3 Double Power Pack (DPP) operation .................................................................................. 99
8.3.4 Sync module operation (with SYNC300A installed) .......................................................... 100
Status message ...................................................................................................................... 103
Error message ......................................................................................................................... 105
9 Parameter List .................................................................................................. 106
Parameter list of power module ............................................................................................ 107
9.1.1 Power module parameter group P0XX, P1XX (read only) ................................................ 107
9.1.2 Power module parameter group P2XX and P3XX (Commissioning parameters) ............. 111
9.1.3 Power module parameter group P4XX (Compensation settings) ..................................... 115
9.1.4 Power module parameter group P6XX (Error message) .................................................. 119
Parameter list of sync module ............................................................................................... 121
9.2.1 Sync module parameter group P0XX, P1XX (read only) .................................................. 121
9.2.2 Sync module parameter group P2XX and P3XX (Commissioning parameters) ............... 125
9.2.3 Sync module parameter group P4XX ................................................................................ 133
9.2.4 Sync module parameter group P6XX and P7XX: Error message ..................................... 138
10 AHF Viewer Software .................................................................................... 141
Requirements and Setup .................................................................................................... 141
Connections......................................................................................................................... 142
Page 7
myecosine.com 6/165
10.2.1 Connection via RS485 ....................................................................................................... 142
10.2.2 Connection via Ethernet .................................................................................................... 144
11 AHF Firmware Update Tool .......................................................................... 145
Usage .................................................................................................................................... 145
11.1.1 Select serial port ................................................................................................................ 146
11.1.2 Communication configuration ............................................................................................ 147
11.1.3 Load firmware packet ........................................................................................................ 148
11.1.4 Upload Firmware ............................................................................................................... 149
12 Maintenance .................................................................................................. 151
13 Abbreviation .................................................................................................. 152
14 Index of Figures ............................................................................................ 153
15 Index of Tables .............................................................................................. 156
16 Appendix A: References .............................................................................. 157
17 Appendix B .................................................................................................... 158
Commissioning after longer storage ................................................................................ 158
Type Plate of ecosine active sync ..................................................................................... 159
18 Appendix C: Calculation example ............................................................... 160
Commutation notches ........................................................................................................ 160
18.1.1 Commutation notches calculation example 1 .................................................................... 161
18.1.2 Commutation notches calculation example 2 .................................................................... 162
18.1.3 Commutation notches calculation example 2 .................................................................... 163
Page 8
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 7/165

1 Version History

Revision
Date
Description
1.0
February 2018
Initial version
1.1
March 2018
Added index of figures, index of tables Optimized chapters order and content Updated LED indication table and parameters list
1.2
May 2018
Added Figure 7 dimension of drill pattern for wall mount Revised Group P4XX
1.3
June 2018
Added Appendix 17.2 Type Plate of ecosine active sync. Corrected control response time from 300 µs (AHF Gen I) to 100 µs. Corrected height of cabinet in chapter 5.5 to: 2328mm (including top Fan
and socket).
Replaced P203 (not used) by P559 in chapter 8.4.
1.4a
September 2018
Corrected description of X11 connector (valid for FW V03.01.02 or higher)
1.5
March 2019
Added Sync Module (SYNC300A)
- Technical specification
- Electrical connection
Updated Firmware of power module information to V03.01.07 or higher
1.6
July 2019
- Updated Label and technical specification of power modules with UL.
- Updated parameters table of power modules for V03.02.03.
- Updated commissioning procedure with sync module.
- Changed description of P320 settings in chapter 8.2 (with new Firmware V03.02.03 and higher, P320: Total current parallel = 120A for master and slave modules)
1.7
October 2019
Introduction of the new firmware Update Tool software replacing the bootloader in chapter 11
Additional information regarding the usage of the sync module Update of terminal X11 desciption in Table 15 Update of the parameters lists for power module Addition of the parameters lists for sync module Additional details in the commissioning procedure Additional appendix with calculation examples Several minor corrections across the whole document
Page 9
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 8/165

2 Introduction

2.1 Purpose

The ecosine active sync User and Installation Manual provides information for unpacking, installation and commissioning of the active harmonic filter and describe mechanical and electrical installation of the filter power module and cabinet version. It contains basic information about parameters and communication as well as troubleshooting information.
The instructions are intended for use by qualified personnel. Reading and following these instructions is mandatory. Particular attention needs to be given to the general safety notes and installation guidelines (cautions and warnings)! always keep these instructions available with the filter(s).
Installation of the ecosine active sync filter, inspections for proper operation, and certain troubleshooting measures may only be performed by qualified personnel. All other measures may be performed by people who have read these instructions.

2.2 Additional Resources

The Schaffner group does provide a number of additional resources available at schaffner.com to understand power quality in general and product in particular.
The ecosine active sync filter maintenance instruction provides information on maintenance and testing for field service technicians, as well as disassembly and assembly instructions for wear parts.

2.3 Naming convention

In this document the acronyme AHF, standing for Active Harmonic Filter, is often used in the text for easier reading. It refers to the ecosine active sync power module, Double Power Pack (DPP) or cabinet system.
Page 10
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 9/165

3 General Safety Notes and Installation Guidelines

Page 11
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 10/165

4 Environmental Conditions / Exclusion of warranty

This document classifies groups of environmental parameters and their severities to which ecosine active sync harmonic filters are subjected when mounted for stationary use at weather protected locations under use conditions, including periods of erection work, down time, maintenance and repair. The lifetime of electronic equipment is depending on the environmental conditions they are exposed to. Especially in harsh environments lifetime is reduced due to the corrosiveness of the atmospheric environment. Generally, corrosion in micro or power electronics depends on several factors such as the package type, materials involved, assembly processes, moisture, inorganic and organic contaminants, atmospheric pollutants, temperature, thermal stress and electrical bias. To increase the lifetime Schaffner provides all ecosine active sync filters with the ability to work within pollution degree 2 (PD2) and does use coated PCB’s according to IEC61721-3-3. Schaffner standard PCB construction complies with class 3C2. Please carefully read the provided information and check if your application fulfills the required specifications as Schaffner expressly points out that the manufacturer's warranty shall
lapse with immediate effect if ecosine active sync harmonic filters are transported, stored, installed or operated outside their published specifications.
Important
Ecosine active sync harmonic filters (AHF) listed below are IP20 or IP54 devices to be installed in an environment in compliance with the requirements named in this document.
All active harmonic filters (AHF) must be installed in a clean, dry location, e.g. in sufficiently ventilated or airconditioned electric cabinets or closed electric rooms. Contaminants such as oils, liquids, corrosive vapors, abrasive debris, dust and aggressive gases must be kept out of the filter enclosure.
WARNING: Conductive dust may cause damage to ecosine active sync harmonic filters. Ensure that installation site of ecosine active sync is free of conductive dust.
Products
FN3530/31 series, 3-wire filters, 380-480VAC, models 60A FN3540/41 series, 4-wire filters, 380-415 VAC, models 60A FN3532 series, 3-wire filters, 380-480VAC, models 120A FN3542 series, 4-wire filters, 380-415VAC, models 120A FN3545 series, 3/4-wire filters, models 60…300A SYNC300A, optional sync module for ecosine active sync
Overvoltage class (EN50178)
Ecosine active sync are designed according to EN 50178 overvoltage class III
Page 12
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 11/165
Storage environmental specifications
(IEC 60721-3-1, EN50178)
Climate conditions for storage class 1K3:
Temperature range: -25°C to +55°C
Relative humidity: < 95%, no condensation
Atmospheric pressure: 70KPa to 106KPa
Transportation environmental specifications
(IEC 60721-3-2, EN50178)
Climate conditions for transport class 2K3:
Temperature range: -25°C to +70°C
Relative humidity: < 95%, no condensation
Atmospheric pressure: 70KPa to 106KPa
Vibrations according to IEC 60068-2-6
Shocks according to IEC 60068-2-27
Operation environmental specifications
(IEC 60721-3-3, EN50178)
Climate conditions for operation class 3K3:
Temperature range:
| Power module: 0°C to +50°C | Cabinet: 0°C to +40°C
Relative humidity: < 95%, no condensation
Atmospheric pressure: 70KPa to 106KPa
Degree of pollution (IEC 61010, EN50178)
Pollution conditions for operation class PD2
Corrosive levels (IEC 60721-3-3)
Corrosive levels for storage, transport and operation Class 3C2
(3)
:
Applies to locations with normal levels of contaminants, experienced in urban areas with industrial activities
Levels:
Environmental parameter
Units
(1)
Class 3C2
(2)
Mean value
Max value
Sea salt Salt mist
Sulphur dioxide
ppm
cm3/m3
0.3
0.11
1.0
0.37
Hydrogen sulphide
ppm
cm3/m3
0.1
0.071
0.5
0.36
Chlorine
ppm
cm3/m3
0.1
0.034
0.3
0.1
Hydrogen chloride
ppm
cm3/m3
0.1
0.066
0.5
0.33
Hydrogen fluoride
ppm
cm3/m3
0.01
0.012
0.03
0.036
Ammonia
ppm
cm3/m3
1.0
1.4
3.0
4.2
Ozone
ppm
cm3/m3
0.05
0.025
0.1
0.05
Nitrogen oxides
ppm
cm3/m3
0.5
0.26
1.0
0.52
(1)
The values given in cm3/m3 have been calculated from the values given in mg/m3 and refer to a temperature of 20 °C and a pressure of 101,3 kPa. The table uses rounded values.
(2)
Mean values are expected long-term values. Maximum values are limit or peak values, occurring over a period of time of not more than 30 min per day.
Page 13
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 12/165
(3)
IEC 60721-3-3 is only applied to the coated PCB covered areas and not the entire device. The unprotected areas, such as connections, terminations and exposed magnetics, may not survive these exposure levels over time.
Page 14
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 13/165

5 Ecosine Active Sync Product Line Overview

5.1 Principle of operation

Ecosine active sync filters are used for harmonic current mitigation, reactive current compensation (both inductive and capacitive) and phase unbalance correction and optimization. The filter units can be integrated into systems and applications as a centrally installed filter unit to mitigate all application related harmonics or can be combined with frequency converters and motor drives to turn standard converters and motor drives into low harmonic solutions.
Ecosine active sync filters are connected in parallel to the load and do steadily monitor all 3-phase line currents (simplified schematic in Figure 1). Harmonic currents and reactive power components are reliably detected and processed in an ultra fast digital control structure. By generating and actively imposing currents in the opposite phase shift, unwanted harmonic and reactive currents are reliably mitigated. By using the latest generation of 3-level IGBT technology ultra fast (real time) feeding is possible with lower losses compared to older generation active harmonic filters. Build-in LCL-filter technology ensures that neither the switching frequency (16 kHz) nor DC components are imposed into the mains. Operation is possible independend of the source, thus the use of the filter in generator or transformer supply applications is feasible. Connected loads can be of various nature, e.g. individual non-linear loads or groups of non-linear loads.
Figure 1 Principle of operation of the ecosine active sync harmonic filter
Page 15
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 14/165

5.2 Ecosine active sync system configuration

With the below listed power module variants, optional kits and cabinet variants it is possible to build tailored ecosine active sync filters and systems. Schaffner offers power modules, optional kits and cabinets independently or ready to use filter systems integrated in cabinets.
In the following the designations of ecosine active sync systems and options are introduced.
Table 1 Ecosine active sync power modules versions and options
Designation
Description
FN3530
Power Module 380-480 VAC 3-wire
FN3531
Power Module 380-480 VAC 3-wire with CT Module
FN3540
Power Module 380-415 VAC 4-wire
FN3541
Power Module 380-415 VAC 4-wire with CT Module
FN3532
DPP Double Power Pack 120A 380-480 VAC 3-wire
FN3542
DPP Double Power Pack 120A 380-415 VAC 4-wire
CTM
Current Transformer Module
LCD
Display module
Patch Cable Set
Patch cable set sync module
KITIP21
Ecosine active sync IP21 cover KIT
SYNC300A
Sync module for ecosine active sync
Page 16
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 15/165

5.2.1 Ecosine active sync power module FN3530 and FN3531

FN3530 and FN3531 ecosine active sync power modules are 3-phase 3-wire power modules with 60A of mitigation current. FN3530 and FN3531 are applied to 3-phase network without neutral line. FN3530 power modules do not have the CT module included whereas FN3531 power modules come with the CT module included.
FN3530/31
Number of phases (system input)
3-phase 3-wire
Mains frequency
50/60 Hz ± 3 Hz
Mains voltage
380VAC ± 15% to 480VAC± 10%
Inverter topology
3-level NPC topology, IGBT
Switching frequency
16 kHz
Response time
<100 µs
Harmonic mitigation performance
Up to the 50th harmonic
Total harmonic current distortion THDi
< 5%
Power factor correction
cosφ = -0.7 … 1 … 0.7 (inductive and capacitive
compensation)
Mitigation current
60Arms
Dimensions of a single unit
440 mm × 420 mm × 222mm (w × d × h)
Page 17
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 16/165

5.2.2 Ecosine active sync power module FN3540 and FN3541

FN3540 and FN3541 ecosine active sync power modules are 3-phase 4-wire power modules with 60A of mitigation current. FN3540 and FN3541 are applied to 3-phase network with neutral line. FN3540 power modules do not have the CT module included whereas FN3541 power modules come with the CT module included.
FN3540/41
Number of phases (system input)
3-phase 4-wire
Mains frequency
50/60 Hz ± 3 Hz
Mains voltage
380VAC ± 15% to 415VAC± 10%
Inverter topology
3-level NPC topology, IGBT
Switching frequency
16 kHz
Response time
<100 µs
Harmonic mitigation performance
Up to the 50th harmonic
Total harmonic current distortion THDi
< 5%
Power factor correction
cosφ = -0.7 … 1 … 0.7 (inductive and capacitive
compensation)
Rated phase mitigation current
60Arms
Rated neutral conductor mitigation current
180Apk
Dimensions of a single unit
440 mm × 420 mm × 222mm (w × d × h)
Page 18
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 17/165

5.2.3 Ecosine active sync Double Power Pack (DPP) FN3532 and FN3542

FN3532 and FN3542 are so called Double Power Packs consisting of two ecosine active sync power modules. FN3532 is applied to 3-phase 3-wire networks without neutral wire. FN3542 is applied to 3­phase 4-wire network with neutral wire. Both DPP packages will always include two power modules (3­wire or 4-wire) and will work in master-slave architecture. That’s why only one CT module and only one display module is needed and will be included in the package. Communication between the modules is realized via a high-speed bus.
FN3532
Number of phases (system input)
3-phase 3-wire
Mains frequency
50/60 Hz ± 3 Hz
Mains voltage
380VAC ± 15% to 480VAC± 10%
Inverter topology
3-level NPC topology, IGBT
Switching frequency
2x16kHz interleaved (32kHz effective)
Response time
<100 µs
Harmonic mitigation performance
Up to the 50th harmonic
Total harmonic current distortion THDi
< 5%
Power factor correction
cosφ = -0.7 … 1 … 0.7 (inductive and capacitive
compensation)
Rated phase mitigation current
60Arms
Dimensions of a single unit
440 mm × 420 mm × 222mm (w × d × h)
Page 19
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 18/165
FN3542
Number of phases (system input)
3-phase 4-wire
Mains frequency
50/60 Hz ± 3 Hz
Mains voltage
380VAC ± 15% to 415VAC± 10%
Inverter topology
3-level NPC topology, IGBT
Switching frequency
2x16kHz interleaved (32kHz effective)
Response time
100 µs
Harmonic mitigation performance
Up to the 50th harmonic
Total harmonic current distortion THDi
< 5%
Power factor correction
cosφ = -0.7 … 1 … 0.7 (inductive and capacitive
compensation)
Mitigation current
120A
Rated neutral conductor mitigation current
180Apk
Dimensions of a single unit
440 mm × 420 mm × 222mm (w × d × h)
Page 20
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 19/165

5.2.4 Ecosine active sync cabinet version (cabinet + power modules)

The ecosine active sync power modules can be integrated into a cabinet and delivered as a system. The cabinet version can include up to 5 modules depending on the configuration and options defined in the typecode (see chapter 5.3). The cabinet version is designated as FN3545 + the typecode as shown later in Table 2. The main features are summarized below:
FN3545-_ _ _ _ _ _ _ _ _ _
Number of phases (system input)
3-phase 3-wire or 3-phase 4-wire
Mains frequency
50/60 Hz ± 3 Hz
Mains voltage 3-wire
380VAC ± 15% to 480VAC± 10%
Mains voltage 4-wire
380VAC ± 15% to 415VAC± 10%
Inverter topology
3-level NPC topology, IGBT
Switching frequency
number of modules x 16kHz interleaved (up to 5x16kHz effective)
Response time
<100 µs
Harmonic mitigation performance
Up to the 50th harmonic
Total harmonic current distortion THDi
< 5%
Power factor correction
cosφ = -0.7 … 1 … 0.7 (inductive and capacitive
compensation)
Mitigation current
60A, 120A, 180A, 240A, 300A
Dimensions
600 mm × 600 mm × 2265mm (w × d × h)
Page 21
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 20/165

5.3 Ecosine active sync cabinet version type code information

Schaffner ecosine active sync series offers a modular solution which enables users to build tailored systems with respect to application and installation needs. Ecosine active sync power modules and options are listed in Table 1, while cabinet versions are listed in Table 2 and Table 3.
The Typecode is defined as a combination of FN3545 (indicating a cabinet version) plus an extension containing information about configuration and options.
Figure 2 Typecode description of ecosine active sync cabinet version
Page 22
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 21/165
Table 2 Ecosine active sync cabinet versions without sync module
Designation
Voltage
Sync
Module
Mitigation
Current
3-wire /
4-wire
setup
Power
Module
Display Module
Protection
(Main
Switch)
FN3545-X0603WXXP
380-480 VAC
No
60A
3-wire
1 x FN3531
No
Yes
FN3545-X0603WLXP
380-480 VAC
No
60A
3-wire
1 x FN3531
Yes
Yes
FN3545-X0604WXXP
380-415 VAC
No
60A
4-wire
1 x FN3541
No
Yes
FN3545-X0604WLXP
380-415 VAC
No
60A
4-wire
1 x FN3541
Yes
Yes
FN3545-X1203WXXP
380-480 VAC
No
120A
3-wire
2x FN3531
No
Yes
FN3545-X1203WLXP
380-480 VAC
No
120A
3-wire
2x FN3531
Yes
Yes
FN3545-X1204WXXP
380-415 VAC
No
120A
4-wire
2x FN3541
No
Yes
FN3545-X1204WLXP
380-415 VAC
No
120A
4-wire
2x FN3541
Yes
Yes
FN3545-X1803WXXP
380-480 VAC
No
180A
3-wire
3x FN3531
No
Yes
FN3545-X1803WLXP
380-480 VAC
No
180A
3-wire
3x FN3531
Yes
Yes
FN3545-X1804WXXP
380-415 VAC
No
180A
4-wire
3x FN3541
No
Yes
FN3545-X1804WLXP
380-415 VAC
No
180A
4-wire
3x FN3541
Yes
Yes
FN3545-X2403WXXP
380-480 VAC
No
240A
3-wire
4x FN3531
No
Yes
FN3545-X2403WLXP
380-480 VAC
No
240A
3-wire
4x FN3531
Yes
Yes
FN3545-X2404WXXP
380-415 VAC
No
240A
4-wire
4x FN3541
No
Yes
FN3545-X2404WLXP
380-415 VAC
No
240A
4-wire
4x FN3541
Yes
Yes
FN3545-X3003WXXP
380-480 VAC
No
300A
3-wire
5x FN3531
No
Yes
FN3545-X3003WLXP
380-480 VAC
No
300A
3-wire
5x FN3531
Yes
Yes
FN3545-X3004WXXP
380-415 VAC
No
300A
4-wire
5x FN3541
No
Yes
FN3545-X3004WLXP
380-415 VAC
No
300A
4-wire
5x FN3541
Yes
Yes
Page 23
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 22/165
Table 3 Ecosine active sync cabinet versions with sync module
Designation
Voltage
Sync
Module
Mitigation
Current
3-wire /
4-wire
setup
Power
Module
Display Module
Protection
(Main
Switch)
FN3545-S0603WXXP
380-480 VAC
Yes
60A
3-wire
1 x FN3530
No
Yes
FN3545-S0603WLXP
380-480 VAC
Yes
60A
3-wire
1 x FN3530
Yes
Yes
FN3545-S0604WXXP
380-415 VAC
Yes
60A
4-wire
1 x FN3540
No
Yes
FN3545-S0604WLXP
380-415 VAC
Yes
60A
4-wire
1 x FN3540
Yes
Yes
FN3545-S1203WXXP
380-480 VAC
Yes
120A
3-wire
2x FN3530
No
Yes
FN3545-S1203WLXP
380-480 VAC
Yes
120A
3-wire
2x FN3530
Yes
Yes
FN3545-S1204WXXP
380-415 VAC
Yes
120A
4-wire
2x FN3540
No
Yes
FN3545-S1204WLXP
380-415 VAC
Yes
120A
4-wire
2x FN3540
Yes
Yes
FN3545-S1803WXXP
380-480 VAC
Yes
180A
3-wire
3x FN3530
No
Yes
FN3545-S1803WLXP
380-480 VAC
Yes
180A
3-wire
3x FN3530
Yes
Yes
FN3545-S1804WXXP
380-415 VAC
Yes
180A
4-wire
3x FN3540
No
Yes
FN3545-S1804WLXP
380-415 VAC
Yes
180A
4-wire
3x FN3540
Yes
Yes
FN3545-S2403WXXP
380-480 VAC
Yes
240A
3-wire
4x FN3530
No
Yes
FN3545-S2403WLXP
380-480 VAC
Yes
240A
3-wire
4x FN3530
Yes
Yes
FN3545-S2404WXXP
380-415 VAC
Yes
240A
4-wire
4x FN3540
No
Yes
FN3545-S2404WLXP
380-415 VAC
Yes
240A
4-wire
4x FN3540
Yes
Yes
FN3545-S3003WXXP
380-480 VAC
Yes
300A
3-wire
5x FN3530
No
Yes
FN3545-S3003WLXP
380-480 VAC
Yes
300A
3-wire
5x FN3530
Yes
Yes
FN3545-S3004WXXP
380-415 VAC
Yes
300A
4-wire
5x FN3540
No
Yes
FN3545-S3004WLXP
380-415 VAC
Yes
300A
4-wire
5x FN3540
Yes
Yes
Page 24
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 23/165
Table 4 Ecosine active sync cabinet only versions and cabinet accessoiries
Designation
Description
Cabinet 380-480V IP54 3W
IP54 Cabinet 600x600x2328 3-wire (w/o modules) 480V
Cabinet 380-415V IP54 4W
IP54 Cabinet 600x600x2328 4-wire (w/o modules) 415V
Plinth panel 100
Cabinet plinth panel 100mm
Plinth panel 200
Cabinet plinth panel 200mm
Page 25
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 24/165

5.4 Technical specification ecosine active sync power module versions

Number of phases (system input)
3-phase 3-wire or 3-phase 4-wire
Mains frequency
50/60Hz ± 3 Hz
Mains voltage
3-wire: 380VAC ± 15% - 480VAC± 10% 4-wire: 380VAC ± 15% - 415VAC± 10%
Inverter topology
3-level NPC topology, IGBT
Switching frequency
16 kHz
Response time
<100 µs
Harmonic mitigation performance
Up to the 50th harmonic
Total harmonic current distortion THDi
< 5%
Power factor correction
cos φ = -0.7 … 1 … 0.7 (inductive and capacitive compensation)
Dimensions of a single unit
440 mm × 420 mm × 222mm (w × d × h)
Rated phase mitigation current
60Arms
Rated neutral conductor mitigation current
180Apk
Overload capability (Amp for 10 ms)
150A
Current transformer placement
Mains side or load side
Current transformer ratio
50…50000:5A or 50…50000:1A
Mounting
Wall-mounting (book or flat mounting)
Weight of a single unit
44 kg
Cooling type
Air cooling
Communication interface
Ethernet TCP/IP, Modbus RTU RS485
Digital I/O
2 DIO + 2 DO
Ambient temperature of power modules
0 …50°C full performance, up to 55°C with derating of 3% per Kelvini
Power Losses
<1100W under full mitigation performance (< 2.6%) <970W in typical operation (< 2.3%)
Protection class
IP 20 / IP 21
Noise level
< 56 to 63 dB A (depending on load situation)
Self-protection
Yes
Overheat protection
Yes
i
See chapter 5.6
Page 26
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 25/165
Overvoltage and undervoltage protection
Yes
Recommended fuse protection
100A, type gL or gG
Earthing system
TT, TN-C, TN-S, TN-C-S, IT, corner grounded delta
Altitude
<1000m without derating; Up to 4000m with derating 1% / 100m
Ambient conditions
Pollution degree 2 Relative humidity < 95% non-condensing, 3K3 Temperature: Storage 55°C, 1K3, 1K4, Transportation -25°C to 75°C,
2K3
Approval
CE, RoHS, cUL
Design standards
IEC 61000-4-2, 4-4, 4-5, 4-6 EN 61000-3-11, 3-12 EN 61000-6-2 EN 55011 EN 62477-1 EN 61800-3

5.5 Technical specification ecosine active sync cabinet versions

Number of phases (system input)
3-phase 3-wire or 3-phase 4-wire
Mains frequency
50/60Hz ± 3 Hz
Mains voltage
3-wire: 380VAC ± 15% - 480VAC± 10% 4-wire: 380VAC ± 15% - 415VAC± 10%
Inverter topology
3-level NPC topology, IGBT
Switching frequency
16 kHz
Response time
<100 µs
Harmonic mitigation performance
Up to the 50th harmonic
Total harmonic current distortion THDi
< 5%
Power factor correction
cosφ = -0.7 … 1 … 0.7 (inductive and capacitive compensation)
Dimensions cabinet
600 mm × 600 mm × 2328mm (w × d × h)
Number of Modules
0 i 1 2 3 4 5 Rated phase mitigation current
0 A
60A
120A
180A
240A
300A
Rated neutral conductor mitigation current
0 A
180A
360A
540A
720A
900A
Overload capability (for 10 ms)
0 A
150A
300A
450A
600A
750A
Weight
180kg
224kg
268kg
312kg
356kg
400kg
Power Losses full mitigation performance
200W
< 1300W
<2400W
<3500W
<4600W
<5700W
Power Losses typical operation
200W
< 1170W
<2100W
<3100W
<4000W
<5000W
Current transformer placement
Mains side or load side
Current transformer ratio
50…50000:5A or 50…50000:1A
Mounting
Floor mounting
i
Parameters of cabinet only configuration
Page 27
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 26/165
Cooling type
Air cooling
Communication interface
Ethernet TCP/IP, Modbus RTU RS485
Digital I/O
2 DIO + 2 DO
Ambient temperature
0 …40°C full performance, up to 50°C with derating of 3% per Kelvini
Protection class
IP 54
Noise level
< 75 dB A (depending on load situation)
Self-protection
Yes
Overheat protection
Yes
Overvoltage and undervoltage protection
Yes
Earthing system
TT, TN-C, TN-S, TN-C-S, IT, corner grounded delta
Altitude
<1000m without derating; Up to 4000m with derating 1% / 100m
Ambient conditions
Pollution degree 2 Relative humidity < 95% non-condensing, 3K3 Temperature: Storage 55°C, 1K3, 1K4, Transportation -25°C to 75°C,
2K3
Approval
CE, RoHS, UL (pending)
Design standards
IEC 61000-4-2, 4-4, 4-5, 4-6 EN 61000-3-11, 3-12 EN 61000-6-2 EN 55011 EN 62477-1 EN 61800-3
i
See chapter 5.7
Page 28
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 27/165

5.6 Temperature derating of ecosine active sync power module

The rated current of ecosine active sync power module is 60A when the ambient temperature is between 0°C and 50°C. Derated operation is necessary if the ambient temperature is above 50°C, the rated current reduced 3% per kelvin, and the maximum ambient temperature for derated operation is 55°C. The derating curve of ecosine active sync power module is shown below in Figure 3.
Figure 3 Temperature derating curve of ecosine active sync power module

5.7 Temperature derating of ecosine active sync cabinet version

The rated current of ecosine active sync cabinet version is n*60A (with n = number of installed power modules in operation) when the ambient temperature is between 0°C and 40°C. Derated operation is necessary if the ambient temperature is above 40°C, the rated current reduced 3% per kelvin, and the maximum ambient temperature for derated operation is 50°C. The derating curve of ecosine active sync power module is shown below in Figure 4.
Figure 4 Temperature derating curve of ecosine active sync cabinet versions referred to the rating of one module
Page 29
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 28/165

5.8 Sync Module SYNC300A

The Sync Module SYNC300A is a master communication module with following features and advantages:
| Intelligent load and energy management | Redundancy management | Flexible installation with current transformers on mains or load side; one simple CT connection
point for all modules
| Recommended for more than two power modules in parallel operation | Simple and modular installation (wall-mount or rack-mount) | Available as part of the ecosine active sync cabinet FN 3545 or as an option for later upgrade
in wall-mounting or custom cabinet configurations
| Easy filter scalability and extension of mitigation current beyond 300 A;
one sync module can connect and coordinate up to 5 power modules (5x60A) in parallel; interconnection of up to 4 sync modules for a total compensation current up to 1200A
Page 30
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 29/165

5.8.1 Technical specification for Sync module SYNC300A

Input voltage
22,0 … 27,0 VDC
Nominal current
< 1 A
Dimensions
440 mm × 200 mm × 87 mm (w × d × h)
Weight
3.0 kg
Protection class
IP20 (option IP21)
Digital I/O
3 DI, 2 DO, 4 DI/O (programmable) 2 relays NO/NC - 2 relays NO with common COM (250 VAC/3A)
24VDC GND
Ambient conditions
Pollution degree 2 Relative humidity < 95% non-condensing, 3K3 Temperature: Storage 55°C, 1K3, 1K4, Transportation -25°C to 75°C, 2K3
Approval
CE, RoHS
The sync module does not contain live parts and has no risk of shock and fire. Due to the low-voltage level of nominal 24 Volts and design as load (in point of limited current consumption), the sync module does not require UL approval.
It is applicable for use in industrial control equipment (i.e. for listed components of category NMTR or NITW).
Page 31
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 30/165

5.8.2 Mechanical dimensions of SYNC300A

Table 5 Sync module dimensions
[mm]
[in]
A
440 17.32
B
200 7.88
C
87 3.43
Page 32
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 31/165

5.9 Ecosine active sync display module

Ecosine active sync harmonic filters can be commissioned via the display module. It furthermore can be used to change and monitor all filter parameters and measured values of the three-phase network. One display module fit for all power modules and can be used in any of the system setups, whether it is single power module, Double Power Pack or cabinet version.
Function
Display module and keypad
Mounting types
The display module is used to monitor the measured values of the three-phase network and to change the filter parameters. More details can be found in chapter 8.
For DPP configuration, one display module is used and mounted on the master power module as shown in section 5.2.3.
For cabinet version, the display module is mounted on the front door of the cabinet as shown on the cover picture.
Page 33
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 32/165

5.9.1 RS485 communication

The display module is connected to the AHF through a RS485 bus and the communication protocol used is Modbus. In addition, the display module acts like a master and the AHF acts like a slave.
The display module can address only one slave device connected on a RS485 multi-slave bus and the target slave device is defined by the Modbus address.
During the normal working conditions, the display module polls almost continuously the AHF slave device to get the required information. In case the communication is missing, an exclamation mark is shown on the top-right corner of the window in order to make the user aware of the situation.

5.9.2 AHF parameters and INI file

The display module can access all parameters of the AHF and, for the purpose of supporting them dynamically, the display module is also able to manage the INI file. Exactly like for AHF-viewer, the INI file is the format used to get all the data regarding parameters and folder structure from the AHF.
Since the downloading and parsing of the INI file is a time-consuming operation, the display module saves it on the serial flash memory in order to avoid this operation at every start up.
At the beginning, the display module compares the software version of the current AHF with the software version of the saved INI file. In case of match, the display module loads the INI file from the serial flash memory and, after a couple of seconds, is already able to launch the application. In case of mismatch, the display module must download the INI file from the AHF, do the parsing and overwrite the old one in the serial flash memory.
This process could take more than one minute and depends strictly on the baudrate of the RS485 communication and on the number of parameters.

5.9.3 Event log and LOG file

With the display module it is possible to see the latest record of the event log, just like AHF-viewer does. The number of visible events is not fixed, it depends on how long the description strings associated to every event are, but it can be considered between 250 to 350 events.

5.9.4 Load and save AHF parameter set

The display module is able to save up to 10 different parameters sets on the serial flash memory. Every set is made up by all the “read/write” parameters of the AHF, the “read only” parameters are not taken into consideration. In addition, the display module is also able to load a complete parameter set to the AHF.
In order to guarantee the compatibility between parameter sets and AHF devices, the software version of the AHF and the software version the parameter set to be loaded must be the same.
Page 34
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 33/165

6 Mechanical Installation Guidelines

6.1 Pre-Installation Guidelines

6.1.1 Receiving ecosine active sync

Every single ecosine active sync power module is packed in a wooden box, additionally there are two sets of handlebars (wall-mount and rack-mount), a screw-set as well as the User and Installation manual.
The pre-attached handlebars are necessary for lifting the ecosine active sync base modules from the pallet using a crane or other appropriate lifting equipments. The handlebars might be removed from the power modules after lifting depending on the way of installation of the modules.
Every ecosine active sync cabinet version is packed in a wooden box. Please carefully inspect the shipping container and the product prior to the installation. In case of visual
damage, don’t install the filter and file a claim with the freight carrier involved.

6.1.2 Transportation and unpacking of power modules

Please note that transportation of ecosine active sync power modules must always be realized with the original packaging. Any other than that might lead to damages and will void warranty.
After receiving of ecosine active sync power modules please follow carefully the upacking instructions. Please refer to the document “Unpacking Instruction ecosine active sync filters (module or cabinet)”, which is attached to the transportation package.

6.1.3 Lifting

Figure 5 Instruction for lifting power module
Page 35
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 34/165

6.1.4 Important note for installation

All other installation positions than the ones described in the following chapters of this manual are prohibited and might result in improper air-cooling capabilities or unsafe operation.
Additionally, in case of wall mounted modules, the customer or installer is fully responsible to ensure proper mounting on a suitable wall using appropriate and compatible fixation material.
Schaffner is not responsible for any damage on the ecosine active sync device or any other device due to improper usage. Failing to respect the requirement will void the guarantee.

6.2 Mechanical installation of ecosine active sync power module

6.2.1 Dimensions of an ecosine active sync power module

Figure 6 mechanical drawing of ecosine active sync power module (see dimensions in Table 6 and Table 7 below)
Page 36
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 35/165
Figure 7 Dimensions [mm] drill-pattern for wall-mount (book and flat mounting)
Page 37
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 36/165
Dimensions of ecosine active sync power module and minimum required clearance are shown in the following tables.
Table 6 Ecosine active sync power module dimensions
[mm]
[in]
A
440 17.32
B
420 16.54
C
219.5i
8.64
D
463.5
18.25
E
56 2.20
F
112 4.41
G
23.5
0.93
H
60
2.36
J
3
0.12
K
80
3.15
Table 7 Ecosine active sync power module (internal dimensions)
[mm]
[in]
a
90 3.54
b
12 0.47
c
11.5 0.45
d
20 0.79
e
95 3.74
f
105 4.13
g
65 2.56
h
82.5 3.25
j
49 1.93
Table 8 Ecosine active sync power module clearance distances
Side
Minimum required
clearance [mm]
[in]
Front (air intel)
200 7.85
Back (air outlet)
200 7.85
Lateral 50 1.97
i
Module height: ~ 5 rack units
Page 38
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 37/165

6.2.2 Ecosine active sync power module mounting options

Ecosine active sync power module is designed for wall-mounting installation, there are flat mounting and book mounting options. The mounting rackets are mounted on the power module differently for flat mounting and book mounting, the details are presented in the following.
6.2.2.1 Flat mounting
For flat mounting, please mount the four mounting rackets as shown in Figure 8.
Figure 8 Instruction of power module flat mounting
6.2.2.2 Book mounting
For book mounting please mount the four mounting brackets as shown in Figure 9
Figure 9 Instruction of power module book mounting
Page 39
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 38/165
Important: In order to ensure sufficient air flow, make
sure a clearance of minimum 200mm, above and below the filter to walls or other components, is available.

6.3 Mechanical installation of ecosine active sync DPP

6.3.1 Dimensions of ecosine active sync DPP

A double power pack DPP filter is composed of two single ecosine active sync power module. The dimensions as in 6.2.1 apply.

6.3.2 Mounting options of ecosine active sync DPP

For Double Power Pack mounting, please install the modules next to each other horizontally, and keep the clearance distance above and below the filter as mentioned above. This principle also applies when more than two power modules are installed on the wall.
(a) Book mounting (b) Flat mounting
Figure 10 Double Power Pack installation variants It is not recommended to install power modules vertically close to each other, as shown in Figure 11;
because the warm exhaust air of the lower module heats up the upper module and therefore the air cooling for the upper module may not be sufficient.
Page 40
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 39/165
Figure 11 Wrong ways to install DPP
Page 41
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 40/165

6.4 Mechanical installation inside customer cabinet

6.4.1 Customer cabinet requirements

Ecosine active sync power module up to five modules in total can also be installed in a cabinet provided by customer. To ensure the normal operation of ecosine active sync modules the cabinet must fulfill the cooling requirements mentioned below in chapters 6.4.2 and 6.5.2; the power modules must be connected according to the power module electrical installation as described later in chapter 7.
Table 9 Technical data for one ecosine active sync power module
Parameter
Value
Comments
Recommended fuse protection
100A
e.g. gL or gG
Cross-section of power cables (cable from distribution to power module)
| 3 Phase and PE: 1 x 25mm2 | Neutral: 2 x 25 mm2
System input (number of phases)
50/60Hz ± 3Hz 3-wire or 4-wire
Input voltage
| For 3-wire module: 380VAC ±
15% … 480VAC ± 10%
| For 4-wire module: 380VAC ±
15% … 415VAC ± 10%
Rated current
Phase: 60 A Neutral: 180A
CT cable cross section
2.5 mm2
If input is 1A signal, the cross section can be reduced to 1.5 mm2.

6.4.2 Cooling requirements of customer cabinet

If recommended components are used, it is important to seal the air channel as good as possible. The following points should be double checked to ensure the normal operation conditions for ecosine active sync modules.
1. The minimum required cross-section and length for air channel must be fulfilled.
2. Air channels between modules and air outlet must be sealed (metal sheets must be overlapped;
foam or gaskets should be used).
3. There is no air flow shortage. Attention should be paid at the holes on the cabinet frame.
Page 42
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 41/165
Parameter
Value
Comments
Power losses per module
Typical 1200 W Max. 1450 W
At maximum load current of 60 Arms
Air flow per module
270 m3/h
Depending on the position and pressure it can deviate
Max. air flow per cabinet
Max. 1400 m3/h
Including the cooling for fuse section
Area – air inlet per module
Min. 450 cm2
Placement in front of fans on each power module
Max. length of air guide channel behind power module
Max. 1200 mm
Min. space in air guide channel behind modules
Min. 70 mm
Top view of a cabinet.
Area – air guide channel in the roof
Min. 900 cm2
Front view of a cabinet
Max. length of air guide channel in the roof
Max. 800 mm
Distance air inlet filter to the front of power module
Min. 45 mm
Placement in front of fans on each power module (not interfered by cable connections)
Note: the aboved conditions are valid only when the channel is completely sealed. A small opening can cause shortages in air flow. In consequence, the module temperature increase is unbalanced among modules and the module operation can change to derating mode.
Page 43
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 42/165

6.5 Mechanical data of ecosine active sync cabinet version

6.5.1 Dimensions of ecosine active sync cabinet version

Figure 12 mechanical drawing of ecosine active sync cabinet (see Table 10 below)
Page 44
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 43/165
The ecosine active sync cabinet has protection degree IP54. The default color of the cabinet is RAL
7035. The cabinet dimensions are as shown in Table 10. Table 10 Ecosine active sync cabinet dimensions
Table 11 Ecosine active sync cabinet clearance distance
Side
Minimum required
clearance [mm]
[in]
Front (air inlet)
900 mm (to open the
door)
35.43
Back -
-
Lateral -
-
There are no clearance requirements for back and lateral installation of ecosine active sync cabinet version.
[mm]
[in]
A
2057 81
B
100 3.94
C
171.2
6.74
D
458.3
18.04
E
606.7
23.9
F
608 23.9
G
642.5
25.3
H
653.7
25.7
Page 45
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 44/165

6.5.2 Cooling requirements of ecosine active sync cabinet versions

Cooling air inlet is in the front door and outlet is in the top front of the cabinet cover.
Table 12 Air cooling requirement for ecosine active sync cabinet version
Parameter
Values
Side view into cabinet with
direction of air flow
Protection category
IP54
Default color
RAL 7035
Required air flow per module
270 m3/h
Maximum air flow per cabinet
1400 m3/h
Air flow through fuse section
100 m3/h
Area - air inlet per module
Min. 450 cm2
Area - air duct channel behind power modules
Min. 370 cm2
Max. length of air duct channel behind power modules
Max. 1200 mm
Min. space in air duct channel behind modules
Min. 70mm
Area - air duct channel in the roof
Min. 900cm2
Max. length of air duct channel in the roof
Max. 800mm
Distance between air inlet filter and front of power module
Min. 45mm
Page 46
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 45/165

7 Electrical Installation Guidelines

7.1 Protection (Fuses, Breakers)

Ecosine active sync filters must always be protected on the mains side of the filter with suitable fuses or circuit breakers. Depending on the operation mode, alternation of the load and the harmonic spectrum of ecosine active sync output current, fuses will be stressed differently. Recommended fuse protection type can be found in the technical specification in section 5.4.
Each power module must have own fuse protection of 100A e.g. type gL or gG.

7.2 Installation with power factor correction (PFC) systems

In case of installation of the ecosine active sync in combination with a PFC system, the following requirement are mandatory.
| The use of pure capacitive PFC system is not allowed, a reactor must be installed | The PFC system must be de-tuned to avoid overloading the capacitors
Table 13: Example of typical detuning order for 50Hz and 60Hz networks
Tuning order
Relative impedance [%]
Tuning frequency [Hz] @50Hz
Tuning frequency [Hz] @60Hz
2.7
14
135
162
3.8 7 190
228

7.3 Power Module electrical installation

7.3.1 Connecting terminal locations

| X1: Mains power input
Page 47
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 46/165
| X2: Current transformer input | S1: Switch on/off | LEDs: Indication LEDs | X11: Customer IOs: Digital Inputs and outputs | X12: HS-Bus Port | X13: Service port RS485 | X14: Ethernet / Modbus TCP | X15: ModBus Daisy Chain RS485 | X16: Display Module Port | X-PE: Protective Earth Connection
Terminal X1 - Mains Power Input
The three phase conducter and neutral line connection. Details of connecting ecosine active sync to the mains see section 7.5.2.
Page 48
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 47/165
Terminal X2 – Current transformer input (CT Module)
Switch S1 – Switch on/off
To switch on or switch off ecosine active sync module, when the parameter P202 is set to
“Switch S1”.
LEDs – Indication LEDs
To show the status of ecosine active sync module, the color of each LED is relevant. The indications of the LEDs are listed in
Table 14.
Page 49
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 48/165
Table 14 Indication of LED
Color
LED# / name
Meaning
LED1 Error
Blinking = Error ON = Fatal Error / Restart blocked
LED2 Ready/Operation
Blinking = ready to operate ON= operating
LED3 Alarm/Warning
ON= warning (HSB link not o.k.)
LED4 Status/Notice
Blinking 0.5sec = overload condition Blinking 1sec = Standby
Terminal 11 - Customer IOs: Digital Inputs and Outputs
Page 50
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 49/165
Table 15 Terminal 11 - customer Digital IOs (see chapter 9.1.2 for more detail)
Pin­No.
Signal
Description
1
GND (potential-free)
Ground 0V (Reference for digital outputs)
2
IN1 / OUT4
Digital input/output (24V, 20mA)
| Set P262 as “Input” for using X11.2 as digital input or “Output”
for using X11.2 as digital output.
| Set P261 to select the polarity of the Input/Output X11.2, “low
active” or “high active”.
| Select the function of X11.2 from the list of functions in P260
3
IN2 / OUT3
Digital input/output (24V, 20mA)
| Set P265 as “Input” for using X11.3 as digital input or “Output”
for using X11.3 as digital output.
| Set P264 to select the polarity of the Input/Output X11.3, “low
active” or “high active”.
| Select the function of X11.3 from the list of functions in P263
4
OUT1
Relay output (230V, 3A)
| Select the function of X11.4 relay output from the list in P266
| Set P267 to select the polarity of the relay X11.4, “normal
open” or “normal closed”.
5
OUT2
Relay output (230V, 3A)
| Select the function of X11.5 relay output from the list in P268
| Set P269 to select the polarity of the relay X11.5, “normal
open” or “normal closed”.
6
COM
Relay input (common) for both relay outputs
Page 51
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 50/165
Figure 13: Logic schematic of the digital input/output
Page 52
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 51/165
Out4
+24V
In1
+24V
Gnd
+24V
X11.2
X11.2
P262=1
P262=0
Figure 14: Functional connection of digital input/output
Terminal X12 - HS-Bus Port
HSB is used to realize data exchange and synchronization of interconnected sync module and power modules, more details refer to section
7.10.
Terminal X13 – Service port RS485
This port is mainly used for firmware updates. For further information refer to ecosine active sync service manual, available on www.schaffner.com.
Terminal X14 – Ethernet / Modbus TCP
HSB is used to realize data exchange and synchronization of interconnected sync module and power modules, for more details refer to section 7.10. Alternatively, this interface could be used to connect AHF with a device on LAN network, i.e. a PC with the AHF Viewer operating program.
Terminal X15 – ModBus Daisy Chain RS485
For DPP version and sync module, only one display module is used to display the information of multiple modules by connecting the X15 terminal of the power modules and sync module.
Terminal X16 – Display Port
Display port provides a Modbus connection including 24V powering the display module.
Warning: 24V power supply must be switched off before connecting other than original Schaffner display module (P255=OFF). There is
Page 53
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 52/165
a risk that external interface adapters will be damaged.
Terminal X-PE – Protective Earth Connection
Ecosine active sync power module must be grounded by connecting the protective earth at terminal X-PE.

7.3.2 Connection of AC Mains

The device must be grounded (connect the protective earth at terminal X-PE of the power module). The AC mains connection cross sections and the tightening torque are presented inTable 16:
Table 16 Connection cross sections and tightening torque mains connection
Device
Min. value cable cross section
Max. value cable cross section
Connecting bolt and tightening torque
Ecosine active sync single 60A Power Module
1 x 25 mm2 per phase and PE
2 x 25 mm2 (N)
1 x 25 mm2 per phase and PE
2 x 25 mm2 (N)
Terminal L1, L2, L3, N
| 4.2 Nm (0.47 lbf in)
PE bolt:
| M8 | 9.5 Nm (1.07 lbf in)
Always use the correct cable cross sections in consideration of cable type and type of cable mounting. To ensure UL conformity, use UL listed cable (90°C, AWG4 or larger) and suitable UL listed wire-lugs.
DANGER
Ensure correct grounding
Insufficient grounding of ecosine active sync filter may cause malfunction of the device and its destruction.
Each power module must have its own fuse protection of 100A e.g., type gL or gG (see section 7.1).
Page 54
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 53/165

7.4 Sync Module electrical installation

7.4.1 Connecting terminal location

| X101: Customer IOs: Digital Inputs and outputs | X102: Customer interface: relays 250 VAC | X103, X104, X105: HS-Bus to additional sync module (up to 3) | X106: Fans feedback signals | X107: power supply of sync module, 24 VDC | X110: Current transformer input | S1: Switch on/off | LEDs: Indication LEDs | X111: Customer IOs: Digital Inputs and outputs | X112: HS-Bus #1 Port to power module | X113: Service port RS485 – interface to Ethernet Port | X114: HS-Bus #2 to power module | X115: ModBus Daisy Chain RS485 | X116: LCD Display Port | X-PE: Protective Earth Connection
Page 55
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 54/165
Terminal X110 – Current transformer input (CT Module)
When Sync module is installed, the CT connections are only done to the CT Module of SYNC300A.
No need to wire through the power modules.
With SYNC300A, the connection of the current transformers is done at one single point to the X110 CTM-interface of the sync module.
The sync module transmits the current measurements over the HSB to the installed power modules.
Switch S1 – Switch on/off
To switch on or switch off the sync module, when the parameter P202 is set to “Switch
S1”.
LEDs – Indication LEDs
To show the status of ecosine active sync power module and/or sync module, the color of each LED is relevant. The indications of the LEDs are listed in
Table 14.
Page 56
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 55/165

7.4.2 Interconnection between Sync Module and Power Modules

The connection between the Sync Module (designated as SM) and the power modules (designated as PM) is done via HSB-link on terminal X112 and X114 of the sync module and terminal X12 and X14 of the power modules using with RJ45 cables.
The sync module connection needs to be done exact in the way seen on Figure 15, otherwise the sync module is not able to read the power modules correctly. In Schaffner’s ecosine active sync cabinet, the power modules 1 to 5 are installed from bottom to top.
Figure 15 HSB connection between sync module and power modules
Page 57
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 56/165

7.5 Ecosine active sync cabinet version electrical installation

7.5.1 Connecting terminal locations

See detailed drawing of the lower part of the cabinet in the following pages.
Page 58
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 57/165
Terminal
Description
XC1
Terminal for connection of mains input cable
XC2
Terminal for connection of current transformers
XC-N
Terminal for connection of neutral conductors
XC-PE
Terminal for connection of protective earth conductors
Terminal XC1 – connection of mains 3-phase input cables L1, L2 and L3 (phase A, phase B and phase C)
Page 59
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 58/165
Terminal XC2 – connections of external Current Transformers (CT)
Note: The cabinet is assembled per default for 5A
CT secondary output. For CTs with 1A secondary output, the
terminations must be re-wired during electrical installation (same as indicated in Figure 21).

7.5.2 Connection of AC Mains

The device must be grounded (connect the protective earth at terminal XC-PE at the bottom left of the cabinet). The AC mains connection cross sections and the tightening torque are presented in Table 17:
Table 17 Connection cross sections and tightening torque mains connection
Device
Min. value cable cross section
Max. value cable cross section
Connecting bolt and tightening torque
Ecosine active sync max. 300A cabinet version
1 x 185 mm2 per phase and PE 2 x 240 mm2 (N)
2 x 120 mm2 or 1 x 240 mm2 per phase and PE 2x 240 mm2 (N)
| M10 | 19Nm (168.0 lbf in)
Always use the correct cable cross sections in consideration of cable type and type of cable mounting. To ensure UL conformity, use UL listed cable (90°C, AWG4 or larger) and suitable UL listed wire-lugs.
DANGER
Ensure correct grounding
Insufficient grounding of ecosine active sync filter may cause malfunction of the device and its destruction.
Each power module has its own fuse protection of 100A e.g., type gL or gG (see section 7.1) installed. Customer must ensure that protection fuses according to local regulations are installed for the mains input cables.
Page 60
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 59/165

7.6 Connection of current transformers

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
De-energize the active harmonic filter before carrying out this procedure. Failure to follow these instructions will result in death or serious injury.
CAUTION RISK OF INCORRECT MOUNTING
Respect and check the phase order and polarity of the current sensors. Failure to follow these instructions can result in injury or equipment
damage.
Dangerous Voltage Risk of death due to short circuits and electric shock if the current transformers are connected incorrectly
BEFORE installing current transformers on the primary conductor short circuit CTs on secondary side with separable short-circuit jumpers (not in the scope of delivery)
Keep the current transformers short circuited until
the ecosine active sync devices are connected with these
separable connecting terminals
the correct wiring of the secondary circuit has been confirmed
(5A or 1A)
BEFORE disconnecting current transformers from ecosine active sync devices always short-circuit them with separable short-circuit plugs.
Page 61
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 60/165

7.6.1 Connection of 3-phase 3-wire devices CT secondary output 5A

Figure 16 Connection of 3-phase 3-wire device CT secondary output 5A
Page 62
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 61/165

7.6.2 Connection of 3-phase 3-wire devices CT secondary output 1A

Figure 17 Connection of 3-phase 3-wire device CT secondary output 1A
Page 63
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 62/165

7.6.3 Connection of 3-phase 4-wire devices CT secondary output 5A

Figure 18 Connection of 3-phase 4-wire devices CT secondary output 5A
Page 64
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 63/165

7.6.4 Connection of 3-phase 4-wire devices CT secondary output 1A

Figure 19 Connection of 3-phase 4-wire devices CT secondary output 1A
Page 65
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 64/165

7.7 Current transformers specifications and cable selection

For correct ecosine active sync operation, three external current transformers (CT) must be connected. This applies regardless of whether ecosine active sync is used as 3 phase 3-wire or 3 phase 4-wire filter,
Please observe the following instructions when installing external current transformers:
For operation of one ecosine active sync power module FN3531 or FN3541, the CTs can be
installed on the mains or load side of the filter.
For Double Power Pack FN3532 and FN3542, current transformers can be installed either on
the mains or load side.
For use of more than two power modules in parallel, the use of the sync module SYNC300A
offers the optimal and more flexible solution. In this configuration, the CTs can be installed either on the mains or load side. Moreover, the PWM switching patterns of all power modules are synchronized leading to lowest switching harmonic content.
For use with more than two power modules in parallel without the sync module, the CTs must
be installed on the load side only. For installations with main side CTs special summation CTs are needed (for more information please refer to the document “Knowledge base information No. 002”).
Separate transformer circuits are mandatory for proper operation of ecosine active sync.
Dedicated current transformers must be used. Current transformer secondary circuits must not be looped through additional loads (i.e., the CT cable should not be routed through the CT loop itself or other burden that could influence the signal).
A current transformer terminal-block with separable short-circuit plugs must be installed
between the external current transformers and the connecting terminal of CT module interface of the ecosine active sync device (CTM terminal strip X2 for power module, X110 for sync module). This is necessary to be able to short-circuit the current transformers before disconnecting the CTM terminal strip on the ecosine active sync device during any kind of service work.
The power dissipation of the current transformer wiring must be considered when selecting the
current transformer power. See Table 18 and Table 19.
Grounding of CT secondary cicuit should be avoided. The wires of the secondary side of the current transformers must be separated from the power
cables of the ecosine active sync. The usage of twisted pair cables is recommended in case of high risk of perturbation but not mandatory in most cases.
Page 66
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 65/165
Characteristic
Value
Rated secondary current
1 A or 5 A
Primary current
For current signals with high crest factor, the primary current must be selected according to the peak value of the current signal.
Nominal CT current > I
peak
/ √2
Accuracy class
1.0 (or better) The total accuracy calculated from CT primary current and CT class
should not exceed 10% of the AHF nominal current. example 1: CT 1000:5A (class 1.0), AHF 120A
accuracy 10A (1% of 1000A) ≤ 12A (10% of 120A) ok example 2: CT 2000:5A (class 1.0), AHF 60A accuracy 20A (1% of 2000A) ≥ 6A (10% of 60A) not ok example 3: CT 2000:5A (class 0.5), AHF 120A
accuracy 10A (0.5% of 2000 A) ≤ 12 A (10% of 120 A) ok
Output power1
At least 1.5 VA (1 ecosine active sync) At least 3.0 VA (2 ecosine active sync in parallel operation) At least 4.5 VA (3 ecosine active sync in parallel operation) At least 6.0 VA (4 ecosine active sync in parallel operation) At least 7.5 VA (5 ecosine active sync in parallel operation)
1
The output power is defined for CT with 5A secondary output. For CTs with 1A secondary output, the CT output
power should be lower (i.e. around 0.25 VA pro power module).
Page 67
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 66/165
Table 18 Power consumption of the CT lines valid for copper wires and CT with secondary output 5A
Cross section
AWG
Distance between current transformer and ecosine active sync vs. CT 5A secondary burden in VA (Twin Wire)
(Consider forward and return lines!)
1 m
2 m
4 m
6m
8 m
10m
1.0 mm2
18 - - - - - -
1.5 mm2
16
0.58
1.15
2.31
3.46
4.62
5.77
2.5 mm2
14
0.36
0.71
1.43
2.14
2.86
3.57
4.0 mm2
12
0.22
0.45
0.89
1.34
1.79
2.24
6.0 mm2
10
0.15
0.30
0.60
0.89
1.19
1.49
10.0 mm2
8
0.09
0.18
0.36
0.54
0.71
0.89
Example: With 4 meters between current transformer and ecosine active sync, the line length in the CT circuit is 8 meters. If 2.5mm² cables are used, the CT output power need to be at least 2.86VA.
Table 19 Power consumption of the CT lines valid for copper wires and CT with secondary output 1A
Cross section
AWG
Distance between current transformer and ecosine active sync vs. CT 1A secondary burden in VA (Twin Wire)
(Consider forward and return lines!)
10 m
20 m
40 m
60m
80 m
100m
1.0 mm2
18
0.35
0.71
1.43
2.14
2.85
3.57
1.5 mm2
16
0.23
0.46
0.92
1.39
1.85
2.31
2.5 mm2
14
0.14
0.29
0.57
0.86
1.14
1.43
4.0 mm2
12
0.09
0.18
0.36
0.54
0.71
0.89
6.0 mm2
10
0.06
0.12
0.24
0.36
0.48
0.60
10.0 mm2
8
0.04
0.07
0.14
0.21
0.29
0.36
Example: With 20 meters between current transformer and ecosine active sync, the line length in the transformer circuit is 40 meters. If 1.5mm² cables are used, the CT output power need to be at least
1.85VA.
Page 68
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 67/165

7.8 Current transformer specification for UL conformity

To ensure UL conformity, UL-compliant external current transformers must be used. Table 20 Example of a current transformer with UL conformity
Manufacturer
Current transformer type
Flex Core
FCL series
Page 69
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 68/165

7.9 Connection and verification of current measurements

7.9.1 CT connection for operation of single ecosine active sync power module

To ensure that currents are correctly detected, observe the specified direction of the current flow from the transformers and the correct phase assignment. The CT wiring for operation of single power module is shown below in Figure 20 for secondary output 5A, resp. Figure 21 for secondary output 1A.
Figure 20 CT (5A) wiring for single power module
Page 70
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 69/165
Figure 21 CT (1A) wiring for single power module
Page 71
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 70/165
Figure 22 CT installation on load side for operation of one power module
Page 72
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 71/165
Figure 23 CT installation on mains side for operation of one power module
Page 73
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 72/165

7.9.2 CT connection for operation of double power pack (DPP) ecosine active sync

Configuration with double power pack (DPP) need to have the CTs connected to one power module only. For DDP, the current transformer can be installed on the mains or the load side like for operation with one single power module.
To ensure that currents are correctly detected, observe the specified direction of the current flow from the transformers and the correct phase assignment. The CT wiring for operation of single power module is shown below in Figure 20 for secondary output 5A, resp. Figure 21 for secondary output 1A.
Figure 24 CT (5A) wiring for DPP, CTs connected to one module only
Page 74
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 73/165
Figure 25 CT (1A) wiring for DPP, CTs connected to one module only
Page 75
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 74/165
Figure 26 CT installation on load side for operation of DPP
Page 76
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 75/165
Figure 27 CT installation on mains side for operation of DPP
Page 77
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 76/165

7.9.3 CT connection for operation of the sync module and multiple ecosine active sync power modules

Configuration using the sync module need only to have the CT connect to the sync module. To ensure that currents are correctly detected, observe the specified direction of the current flow from
the transformers and the correct phase assignment. The CT wiring for operation of single power module is shown below in Figure 20 for secondary output 5A, resp. Figure 21 for secondary output 1A.
Figure 28 CT (5A) wiring for the sync module
Page 78
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 77/165
Figure 29 CT (1A) wiring for the sync module
Page 79
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 78/165
Figure 30 CT installation on load side for operation of the sync module and multiple power modules
Page 80
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 79/165
Figure 31 CT installation on mains side for operation of the sync module and multiple power modules
Page 81
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 80/165

7.9.4 CT connection for parallel operation of several ecosine active sync power modules without sync module

The available compensation current can be increased through parallel operation of several ecosine active sync devices. In doing so, the current signal from the external current transformers is looped through all the ecosine active sync devices in accordance with the following schematic.
For more than 2 ecosine active sync power module in parallel connection, the current transformers must be installed on load side. For installation on mains side, the usage of the sync module is mandatory.
Figure 32 CT (5A) wiring for parallel operation up to five power modules, no sync module
Page 82
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 81/165
Figure 33 CT (1A) wiring for parallel operation up to five ecosine active sync power modules
Page 83
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 82/165
Figure 34 CT installation on load side for parallel operation of several (>2) ecosine active sync modules FN3531 or FN3541 without sync module
Page 84
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 83/165
Note
A maximum of five ecosine active sync devices may be operated on one current transformer set due to the maximum power output of the external current transformers. Usage of the sync module or additional current transformers must be installed if more than five devices are to be operated in parallel.
For parallel operation of more than one ecosine active sync without sync module (except for DPP), the current transformers must be installed on load side of the filter. Operation using the sync module allow to have the current transformers either on load or mains side.
P320 must be set to the sum of the entire rated compensation currents connected in parallel (See section 9.1.2).
Note
For additional CT installations, as well as additional information regarding sizing and connection of CTs two knowledge base articles are available:
Knowledge base information No. 002 – Current transformer special applications Knowledge base information No. 011 – Current transformer installation
Page 85
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 84/165

7.9.5 Grounding of the current transformers

According to DIN VDE 0100 one-side grounding of the current transformers is compulsory only starting from 3 kV rated voltage, it helps to prevent risk for the operating personnel in case of an insulation fault. For voltages below 3 kV, grounding of the current transformers is not required, unless it is necessary for a correct measurement. If it is necessary to ground the current transformers, then grounding should be performed in the following way:
Note
Grounding must be performed only once for each current transformer circuit!
Figure 35 Grounding of the current transformers (optional)
Page 86
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 85/165

7.9.6 Checking current transformers rotating field

Start a single measurement using the AHF Viewer and display the following parameters:
I Voltage values
| Instantaneous voltage value in phase 1 (P113) | Instantaneous voltage value in phase 2 (P114) | Instantaneous voltage value in phase 3 (P115)
I Current values depending on the installation of the current transformers
Current transformers on the load side:
| Load current phase 1 (P133) | Load current phase 2 (P134) | Load current phase 3 (P135)
Current transformers on the mains side:
| Mains current phase 1 (P123) | Mains current phase 2 (P124) | Mains current phase 3 (P125)
If the current transformers are connected correctly, then the rotating field of the voltage and current is identical. If the rotating field is revolving in the opposite direction, two current transformers are reversed in the phases.
Correct
Wrong
Figure 36 Checking rotating field of current and voltage
Page 87
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 86/165

7.9.7 Checking current transformers phase assignment

If the rotating field is correct, the same measured values can be used to check the phase location of current and voltage.
Example 1:
Phase location of current and voltage match.
Correct
Figure 37 Phase of current and voltage is correct
Example 2:
Phase location of current and voltage is shifted through 180°. Here both connections (S1 and S2) of the current transformer are interchanged or the current transformer is installed incorrectly. It becomes evident in 2 different ways. On the one hand, it becomes apparent, as shown in Figure 38, in form of the opposite current with respect to the voltage curve of the same phase. Just as it is apparent in Figure 39 when displaying all 3 currents, on the basis of incomplete current pattern which does not have a negative current curve for each positive current curve.
Wrong
Figure 38 Phase of current and voltage is shifted through 180°
Page 88
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 87/165
Wrong
Figure 39 Current transformer 1 phase-is shifted through 180°.
Example 3:
Current transformers of individual phases are interchanged, it becomes apparent already during the rotating field check. The comparison of current and voltage shows that the phase shifting of current and voltage exceeds 90°. See Figure 40.
Wrong
Figure 40 Current transformers of phase 1 and 3 are interchanged
Page 89
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 88/165

7.10 HS-Bus connection (master-slave configuration)

Double Power Pack is realized by connecting two ecosine active sync power module in parallel via HS­Bus. HS-Bus enables the communication between the modules and the workload is distributed equally between the two modules.
HSB communication link implements a MASTER-SLAVE point to point protocol. The MASTER device measures the external current (mains side or load side) needed by the current controllers and generates the base PWM modulation and control loop frequency used by MASTER and SLAVE devices.
HS-Bus configuration steps
Step 1: Master-slave device assignment
Figure 41 Master slave device assignment
Step 2: Connect the modules in parallel to the grid
Step 3: Connect the modules via Terminal X12
Build HSB between the master and slave module by connecting Terminal X12 of both modules with a twisted pair Ethernet CAT5 cable with RJ45 connectors not longer than 10m.
CT can be installed on the mains or the load side of the filters, see Figure 27 and Figure 26.
Page 90
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 89/165
Figure 42 Location of Terminal X12 on ecosine active sync module
Software step up: Software settings must be independently configured, this means that two different AHF viewer
sessions will be needed to set both MASTER and SLAVE devices up.
Step 4: Check firmware version
To read the firmware version of the ecosine active sync filter module, connect the target device with AHF viewer; under Device Parameters | 0 device specifications, the parameter with ID10 shows the present firmware version.
Figure 43 Ecosine active sync device Firmware version in AHF viewer.
Page 91
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 90/165
Step 5: Master-Slave configuration
In AHF Viewer ecosine active sync, under Device Parameters | 2..5 commissioning | base settings double click on parameter with ID205 (Operation Mode).
Figure 44 Ecosine active sync DPP operation Master/Slave configuration.
Operation mode, parameter P205
Value
Description
Asynchronous
Single or asynchronous operation mode.
Synchronous Master
HSB Master configuration. With this configuration, the AHF device must have a CT module connected.
In this mode (DDP), each power module will compensate 50% of the grid distortion.
Synchronous Slave
HSB Slave configuration. This power module will act as SLAVE and does not need a CT module. The
load current values, PWM modulation and base control frequency will follow the MASTER device.
In DPP configuration, the power module will compensate 50% of the grid distortion.
With sync module as MASTER, each power module is set automatically by the sync module to compensate 1/n (where n is the total number of installed power module in operation) of the total compensation current.
Page 92
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 91/165

8 Comissioning and Programming

Ecosine active sync harmonic filters can be commissioned via the display module and its keypad.

8.1 Display module functions

Figure 45 Display module and keypad The keys have the following functions:
Key
Function
| Go down one menu level
| Back to the higher menu level, exit menu | Scroll inside information screen
| Go up one line | Change information screen
| Go down one line | Change information screen
OK
| Change parameters | Save value
| Go down one menu level
ESC
| Discard selection or new value | Back to home window
Page 93
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 92/165

8.1.1 Boot window

The boot window automatically appears at every start up for some seconds and simply represents the “Schaffner” logo.

8.1.2 Home window

The home window shows some basic information of the AHF. Here are the descriptions of the fields:
| product code: it’s a string defining the device type | AHF state: it represents the current status of the AHF, and it corresponds to the parameter
P020
| grid voltage: is the rms value of the line voltage U12, it corresponds to the parameter P110 | load current: this is the line current and it corresponds to the parameter P120 | device load %: this is the percentage value of the output current of the AHF, it corresponds to
the parameter P104

8.1.3 Main menu

The main menu is where the user can select the available functionalities, it is made up by the following five entries:
| AHF parameters | Event log | Save parameter set | Load parameter set | Settings
Page 94
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 93/165
8.1.3.1 Ecosine active sync (AHF) parameters
In the following section as in the whole document AHF designates the ecosine active sync filter. Table 21 AHF parameter menu on the display module
Level 1
Level 2
Level 3
AHF Parameters
0 Device Specifications
1 Measurements
2…5 Commissioning
6 Alarms
0 Device specifications
002 Rated current
003 Overload current
1 Measurements
100 Mains frequency
102 Cos phi
2 ... 5 Commissioning
2 Basic settings
3 Current transformer s
4 Compensation settings
5 Experts settings
2 Basic settings
200 Language
202 Switch on mode
3 Current transformer
settings
300 CT placement
310 CT primary value
4 Compensation settings
400 Reactive power
401 Cosphi lower limit
6 Alarms
600 Phase L3 IGBT4
615 Overcurrent L1
Page 95
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 94/165
8.1.3.2 Event log
When entering the event log, the display module downloads from the AHF the last record of events. By pushing the up and down arrow it is possible to scroll the event log and move through the event list.
For each event the following information is recorded:
| State | Date | Time | Description | Operating hours
8.1.3.3 Save parameter set
By entering this menu, the user has access to the 10 spots available for saving a parameter set. If a spot is already used, the relative SW version of the parameter set is shown aside of the set number. If a spot is empty, nothing is shown aside the set number.
By pressing right arrow button or ok button, the user can start a saving procedure on the selected spot.
8.1.3.4 Load parameter set
By entering this menu, the user can check all the available parameter sets that have been previously saved. Like before, next to the set number lies the SW version of the parameter set.
By pressing right arrow button or ok button, the user can start a loading procedure of the selected set to the AHF. The SW version of the AHF and the SW version of the parameter set must match, otherwise the load procedure does not start, and an info message is shown to the user.
Page 96
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 95/165
8.1.3.5 Settings
This sub-menu “Settings” contains all the features related to the display module itself; it has the following items:
| Modbus | Password | Screen saver | Information | FW update | Reload INI file | Restart
item
Description
Modbus
Here the user can configure the Modbus features (address, baudrate and frame type) of the display module itself. The Modbus configuration of the AHF has to be done separately through the proper parameters, not in this sub-menu.
Beware that the Modbus configuration of the display module and AHF must match, otherwise the communication between the two devices doesn’t work.
Password
Access to change the expert parameters password. The password is only needed for accessing expert parameters and can be used only by Schaffner service team or selected partners. First enter the old password then enter the new one twice. After pressing OK, the display module confirms if the operation was successful or not.
Screen saver
Access to set the timeout of the screen saver. Press the right arrow or OK button to modify the numerical value of the timeout before showing the screen saver.
Information
Information about the firmware. Page 1 is the firmware of the sync module or power module currently selected. Page 2 (press down arrow to access) display the display module firmware information.
FW update
Access to update the firmware of the display module. Note: Updating the firmware of the sync or power module cannot be
done from the display. Please refer to chapter 11 for more information.
Reload INI file
Access to force the loading of the INI file if necessary.
Restart
Select to restart the display module.
Page 97
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 96/165

8.2 Ways of Software Commissioning

8.2.1 Commissioning via Ethernet

Comissioning via Ethernet interface or RS485 can be used by connecting a PC with the AHF Viewer operating program (see section 10.2.2).

8.2.2 Commissioning via display module

Commisioning ecosine active sync via display module please refer to section 8.1 and Table 21.

8.3 Commissioning procedure

Note for Commissioning with AHF-Viewer (PC commissioning tool) It is always recommended to use the newest version of AHF-Viewer. The software can be
downloaded at www.schaffner.com in Downloads/Software.

8.3.1 Common steps for all configurations

1. Check the ambient conditions
| Ambient temperature < 40°C (cabinet) or 50°C (power module), with higher temperature values
of up to max. 55°C, the device switches to derating mode.
| Altitude < 1000 m, for higher altitudes the output power needs to be derated by setting the output
current limit in parameter P510.
𝑃510 = 100 −
(
𝐴𝑙𝑡𝑖𝑡𝑢𝑑𝑒 − 1000𝑚
)
100
| Check the ventilation of the room or control cabinet to find out whether sufficient cooling air is
available.
| Make sure that the ambient conditions from section 4 (environmental condition) are complied
with and no conductive dust can enter the ecosine active sync.
| The line voltage must be within 480V ±10% rms, corresponding to a maximum peak voltage of
746Vpk
| The commutation notches, if present, must be acceptable based on calculation according to
IEEE 519 (see appendix 18.1 for detail and examples).
2. Make sure that the electrical connection has been done correctly. The following prerequisites must be met.
| External fuse protection is installed, see section 7.1. | Make sure that the grounding has been performed correctly, check the conductor cross-section. | Mains phases L1, L2 and L3 are connected correctly (see section 7.5.2). | Check the conductor cross-section of the external conductors | Check the conductor cross-section of the neutral conductor (for 4-wire devices) | Check the tightening torque of the conductors
3. Check the current transformers
| External current transformers for all three mains phases are correctly connected, installation
site, current flow direction and phase assignment are ok (see section 7.6).
Page 98
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 97/165
| Check if the power of the current transformers is suitable for the application, see section 7.7. | Check, if the current transformers are connected correctly to the current transformers input
terminals of the device (5A or 1A input). NOTICE! Incorrect connection of the current transformers can result in damage to the CT module!
4. Check the installation clearances and conditions (power module and cabinet)
| Minimum installation clearance for wall mounting see section 6.1.4. | Minimum installation clearance for Schaffner cabinet version see section 6.5. | Minimum installation clearance for customized cabinets.
5. Before the first switching-on
| Check, if formation of the DC-link capacitor is necessary in case manufacturing date is over one
year. (see section 17.1)
| Disconnect the short circuit jumpers of the external current transformers | Switch ecosine active sync control off: Terminal X11.2 = open (neither 0V nor +24V shall be
connected to X11.2)
6. Switch on the mains voltage and wait until green LED2 is blinking (see Table 14) and the ecosine active sync is showing state OFF.
| Set all Modbus addresses of the interconnected modules to different values | We recommend using the same address for Service (P230) and Display Modbus (P250) | We recommend using the number according to the module number | Make sure all RS-485 connections between the ecosine active sync power modules and sync
modules (if installed) are correctly connected
| Now a normal operation and parametrization is possible
In the following paragraphs the commissioning procedure differs depending on the configuration of your active harmonic filter.
Application parameters P300, P310 and P312 must be set in each power module (single and Double Power Pack) with the correct application values independently of filter’s configuration. If the sync module is installed in the AHF system, the parameters shall be set only into the sync module.

8.3.2 Single power module or asynchronous operation

1. Check whether the DC-link has been charged correctly and the mains voltage and frequency have been determined correctly. (Note: A short-term charging current is flowing in the DC-link.)
|
P100 = 50 Hz (60 Hz) mains frequency
|
P110, P111, P112 = 342… 528 V mains voltages
|
P109: Check the rotating field to be the same at all power modules
2. Set the factory settings
Page 99
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 98/165
|
P210 = load default values
|
P220 = set date and time
3. Set ecosine active sync parameters for the application accordingly (for exact meaning of the parameters refer to section 9):
|
P300: Positioning of the external current transformers (mains side, load side)
|
P310: Primary current value of the external current transformers
|
P312: Secondary current value of the external current transformers P300, P310 and P312 must be set in each power module with the correct application values independently of filter configuration.
Following parameters must be set as shown below:
|
P205: Parallel Operation Mode = Asynchronous
|
P320: Sum of the rated compensating currents of the overall ecosine active sync power modules connected to one current transformer set (maximum 5 devices).
If more than 5 devices are operated at the same time, the power of the current transformers must be increased, or additional current transformers must be installed.
4. Check whether the displayed values are plausible. For motor load, the values must be positive and approximately the same:
| P102 = cosφ has a plausible value | Check active power value per phase:
o P105 = + … kW? – power L1 o P106 = + … kW? – power L2 o P107 = + … kW? – power L3
| P105 ≈ P106 ≈ P107? Are all values positive? | Check the phase voltages and currents by measuring them using the AHF Viewer oscilloscope
function to determine whether they are in phase (see sections 7.9.6 and 7.9.7).
| Otherwise, the current transformers wiring and parameter settings must be checked, except for
generator load.
5. Check whether the compensation has been deactivated (these parameters are set OFF by default when loading default factory settings in point 2. above):
| P403: Reactive power control = OFF | P405: Load balancing = OFF | P410: Harmonic current compensation = OFF
6. Switch on ecosine active sync control:
|
P202 = Terminal strip
o
Terminal X11.2 = 0 V or open => OFF-command
o
Terminal X11.2 = +24 V => ON-command (e.g. from external PLC)
|
P202 = Switch S1, use the control switch S1 on the front plate of the device
|
P202 = Direct ON (filter is always on)
7. Activate the required type of compensation:
| P400: Reactive power compensation degree = 0 ... 100% | P401: min. cos phi = -0.7 … +0.7 | P402: max. cos phi = -0.7 … +0.7 | P403: Reactive power control | P405: Load balancing
Page 100
Schaffner Group User and Installation Manual Ecosine active sync
September 2019
myecosine.com 99/165
| P407: Priority at full load | P410: Harmonic current compensation
8. Set degrees of compensation P421 and Pxyz (xyz = 421+(3*n), with n = 1, 2, …,23)
9. If necessary, adjust the standby limit (P406)
10. Check if the compensation result on the mains side is correct by using a suitable measuring instrument

8.3.3 Double Power Pack (DPP) operation

1. Check in both power modules whether the DC-link has been charged correctly and the mains voltage and frequency have been determined correctly. (Note: A short-term charging current is flowing in the DC-link.)
|
P100 = 50 Hz (60 Hz) mains frequency
|
P110, P111, P112 = 342… 528 V mains voltages
|
P109: Check the rotating field to be the same at both power modules
|
P010 "FPGA Firmware Version" needs to be the same at all power modules
|
P026 "Mains connection" needs to be the same at all power modules
|
P230 "Service - MB address" needs to be different at all power modules and the sync module
|
P250 "Display - MB adress" needs to be different at all power moules and the sync module
2. Set the factory settings at both power modules
|
P210 = load default values
|
P220 = set date and time
3. Set ecosine active sync parameters at both power modules for the application accordingly (for exact meaning of the parameters refer to section 9):
|
P300: Positioning of the external current transformers (mains side, load side)
|
P310: Primary current value of the external current transformers
|
P312: Secondary current value of the external current transformers P300, P310 and P312 must be set in each power module with the correct application values independently of filter configuration.
Following parameters must be set as shown below: a. Master power module (FN3531/FN3541 with CT module):
|
P205: Parallel Operation Mode = Synchronous Master
|
P320: Total current parallel = 120A
b. Slave power module (FN3530/FN3540):
|
P205: Parallel Operation Mode = Synchronous Slave
|
P320: Total current parallel = 120A
4. Check whether the displayed values are plausible. For motor load, the values must be positive and approximately the same.
| P102 = cosφ has a plausible value | Check active power value per phase:
Loading...