Schaffner ECOsine Maintenance Manual

Page 1
April 2015
ECOsine® active Harmonic Filters
Maintenance Manual for FN3420-200-690-3
Page 2
2 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
© All rights reserved, even and especially in cases of proprietary rights applications. We also retain sole power of disposal, including all rights relating to copying, transmission and dissemination.
Revision: 01 (March 2016)
The most current edition of these instructions (PDF format) can be obtained from your contact of the Schaffner service organization.
Other technical documentation of our products is also available in the download area of our website www.schaffner.com
Document name: Maintenance Manual for FN3420-200-690-3
Version history
Revision
Date
Description
01
April 2016
Initial version
Page 3
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 3
Table of Contents
1 General Safety Instructions 5
1.1 Intended use 6
1.2 Personnel qualification 7
1.3 Environmental conditions / Exclusion of warranty 8
2 Introduction 10
2.1 Principle of operation 11
2.2 About these instructions 12
2.3 Type plate 13
2.4 Type code 14
3 Welcome 15
3.1 About this manual 16
3.2 Who should read this guide 17
3.3 Personnel qualification 18
3.4 Get help 19
3.5 Get training 20
3.6 Contact us 21
4 AHF 200-690-3 22
4.1 Maintenance Schedule 23
4.2 Wear parts 24
4.2.1 Wear parts - AHF 200-690-3 (No UL) 24
4.2.2 Wear parts - AHF 200-690-3 (UL) 25
4.3 Replacement Instruction 26
4.3.1 Check operation of main fan and DC-Bus fan and clean fan guards 26
4.3.2 Check of coolant level 32
4.3.3 Check coolant pump for any signs of coolant-leakage 34
4.3.4 Replace inverter fan (DC bus fan) 36
4.3.5 Replace pre-charge fuses F1 & F2 40
4.3.6 Replace 230V auxiliary power supply 43
4.3.7 Replace 24V power supply fuses F45 & F46 46
4.3.8 Replace cooling system power supply fuses F47 & F48 48
4.3.9 Replace cooling system control unit fuses F1-F3 51
4.3.10 Replace air-conditioning fuses F11 53
4.3.11 Change cooling liquid 56
4.3.12 Replace main fan 59
Page 4
4 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Index of Tables
Table 1: Use of symbols, terms, and designations 12 Table 2: Type code 14 Table 3: Maintenance schedule 200-690-3 23 Table 4: Wear parts 200-690-3 24 Table 5: Wear parts 200-690-3 (UL) 25
Index of Figures
Fig. 1: Principle of operation of the ECOsine® active filter 11
Page 5
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 5
1 General Safety Instructions
Page 6
6 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
1.1 Intended use
The ECOsine® active harmonic filter is used for active compensation of reactive power and harmonic content and for load balancing. Please ensure that no compensation systems, which are not detuned, are connected to the same grid. Otherwise interactions between ECOsine® active and these compensation systems may occur.
DANGER
Dangerous voltage
Risk of death due to short circuits and electric shock if the active filter is opened improperly. The discharge time of the intermediate circuit after disconnecting from the mains can be more than 5 minutes.
All interventions involving opening the device cover or removing or installing the connection cable may only be performed by qualified personnel.
WARNING
High-frequency interferences
In a residential environment, high-frequency interferences could occur, which necessitate interference suppression.
Note
Please note that there are additional manuals for some product variants. For the latest versions of these manuals go to www.schaffner.com It particularly applies to types FN3420-100/120-400-3-GL, please observe the special EMC-Filter Manual for these types (ECOsine EMC Filters for Applications with GL)
Page 7
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 7
1.2 Personnel qualification
Installation of the ECOsine® active filter, inspections for proper operation, and certain troubleshooting measures may only be performed by qualified personnel. All other measures may be performed by people who have read these instructions.
Page 8
8 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
1.3 Environmental conditions / Exclusion of warranty
This document classifies groups of environmental parameters and their severities to which ECOsine® active harmonic filters are subjected when mounted for stationary use at weather protected locations under use conditions, including periods of erection work, down time, maintenance and repair. The lifetime of electronic equipment is depending on the environmental conditions they are exposed to. Especially in harsh environments lifetime is reduced due to the corrosiveness of the atmospheric environment. Generally corrosion in micro or power electronics depends on several variants such as the package type, materials involved, assembly processes, moisture, inorganic and organic contaminants, atmospheric pollutants, temperature, thermal stress and electrical bias. To increase the lifetime Schaffner provides all ECOsine® active filters with the ability to work within pollution degree 2 (PD2) and does use coated PCB’s according to IEC61721-3-3. Schaffner standard PCB construction complies with class 3C2. Please carefully read the provided information and check if your application fulfills the required specifications as Schaffner expressly points
out that the manufacturer's warranty shall lapse with immediate effect if ECOsine® active harmonic filters are transported, stored, installed or operated outside their published specifications.
Important
ECOsine® active harmonic filters (AHF) listed below are IP20 or IP54 devices to be installed in an environment in compliance with the requirements named in this document.
All AHF must be installed in a clean, dry location, e.g. in sufficiently ventilated or air conditioned electric cabinets or closed electric rooms. Contaminants such as oils, liquids, corrosive vapors, abrasive debris, dust and aggressive gases must be kept out of the filter enclosure.
WARNING: Conductive dust may cause damage to ECOsine® active harmonic filters. Ensure that installation site of ECOsine® active is free of conductive dust.
Products
FN3420 series, 3-wire filters, models 30…300A FN3430 series, 4-wire filters, models 30…300A
Overvoltage class (EN50178)
ECOsine® active are designed according to EN 50178 overvoltage class III
Page 9
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 9
Storage environmental specifications
(IEC 60721-3-1, EN50178)
Climate conditions for storage class 1K3:
Temperature range: -25°C to +55°C Relative humidity: < 95%, no condensation Atmospheric pressure: 70KPa to 106KPa
Transportation environmental specifications
(IEC 60721-3-2, EN50178)
Climate conditions for transport class 2K3:
Temperature range: -25°C to +70°C Relative humidity: < 95%, no condensation Atmospheric pressure: 70KPa to 106KPa
Operation environmental specifications
(IEC 60721-3-3, EN50178)
Climate conditions for operation class 3K3:
Temperature range: 0°C to +40°C Relative humidity: < 95%, no condensation Atmospheric pressure: 70KPa to 106KPa
Degree of pollution (IEC 61010, EN50178)
Pollution conditions for operation class PD2
Corrosive levels (IEC 60721-3-3)
Corrosive levels for storage, transport and operation Class 3C2
(3)
:
Applies to locations with normal levels of contaminants,
experienced in urban areas with industrial activities
Levels:
Environmental parameter
Units
(1)
Class 3C2
(2)
Mean value
Max value
Sea salt Salt mist
Sulphur dioxide
ppm
cm3/m3
0.3
0.11
1.0
0.37
Hydrogen sulphide
ppm
cm3/m3
0.1
0.071
0.5
0.36
Chlorine
ppm
cm3/m3
0.1
0.034
0.3
0.1
Hydrogen chloride
ppm
cm3/m3
0.1
0.066
0.5
0.33
Hydrogen fluoride
ppm
cm3/m3
0.01
0.012
0.03
0.036
Ammonia
ppm
cm3/m3
1.0
1.4
3.0
4.2
Ozone
ppm
cm3/m3
0.05
0.025
0.1
0.05
Nitrogen oxides
ppm
cm3/m3
0.5
0.26
1.0
0.52
(1)
The values given in cm3/m3 have been calculated from the values given in mg/m3 and refer to a temperature of 20 °C and a pressure of 101,3 kPa. The table uses rounded values.
(2)
Mean values are expected long-term values. Maximum values are limit or peak values, occurring over a period of time of not more than 30 min per day.
(3)
IEC 60721-3-3 is only applied to the coated PCB covered areas and not the entire device. The unprotected areas, such as connections, terminations and exposed magnetics, may not survive these exposure levels over time.
Page 10
10 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
2 Introduction
Page 11
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 11
2.1 Principle of operation
The ac mains current, which is drawn by a non-linear load, is measured by ECOsine® active either directly or indirectly via external current transformers. The harmonic content and reactive power components are detected and processed in a digital control structure. The active filter continually generates a compensating current that offsets the harmonic content and reactive current in the load, so the ac mains only has to provide the minimum fundamental in phase current.
Compensating current
Mains supply
Load
Neutral
Fig. 1: Principle of operation of the ECOsine® active filter
The active filter instantly adapts to all changes in the load and the systems harmonic content spectrum, in order to be able to optimally respond at any time.
Page 12
12 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
2.2 About these instructions
The following symbols, terms and designations are used in these operating and installation instructions:
Description
NOTICE
Notice
Follow these instructions to avoid damages to the unit.
CAUTION
Caution
Follow these instructions to avoid damages to the unit or injuries of personnel.
WARNING
Warning
Follow these instructions to avoid situations which may cause severe or deadly injuries.
DANGER
Danger
Follow these instructions to avoid situations which may cause severe or deadly injuries.
DANGER
Dangerous voltage
Follow these instructions to avoid situations which cause severe or deadly injuries due to dangerous electrical voltage.
NOTE
Note text
Note
Please observe these notes..
1.
2.
Operation steps
Complete the operation described (multiple steps are numbered, arrow indicates a single step).
Table 1: Use of symbols, terms, and designations
Page 13
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 13
Serial number
WO 1234567 + S/N 00001
Date of manufacture (year (yy) + calendar week (ww))
WO number
Part number
2.3 Type plate
Type code
Page 14
14 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
2.4 Type code
The type designations of all ECOsine® active have the following structure: FN34TT-AAA-VVV-W-CC
Variable
Description
TT
Type: 20 – 3-wire device 30 – 4-wire device
AAA
Rated current
VVV
Rated voltage
W
Number of compensated conductors
CC
Certificates and variants (optional)
Table 2: Type code
Page 15
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 15
3 Welcome
Page 16
16 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
3.1 About this manual
This manual is meant to provide comprehensive information on maintenance requirements of ECOsine® active harmonic filters. The issues discussed in this guide cover the basic maintenance schedule, necessary wear parts as well as practical aspects of working with ECOsine® active harmonic filters. The guide will familiarize you with the required hardware checks and settings to conduct various maintenance tasks.
Page 17
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 17
3.2 Who should read this guide
The primary audience for this book is anyone interested in or responsible for maintenance of ECOsine® active harmonic filters. To fully understand the guide, you should have a good knowledge of electronic and electrical systems and at least some basic power quality habits. Attending Schaffner International training courses is considered helpful.
Page 18
18 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
3.3 Personnel qualification
Any maintenance actions on ECOsine® active harmonic filter has to be performed only by skilled electricians who additionally must be familiar with the instructions in the Installation
and Operation Manual as well as this Maintenance and Wear Parts Manual.
CAUTION
Caution
Maintenance tasks should only be performed by trained and skilled personnel to avoid damages to the unit or injuries of personnel.
WARNING
Warning
Changing of wear parts may cause malfunction of device and can cause injuries of personnel if not properly performed.
Page 19
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 19
3.4 Get help
Schaffner believes in the value of service and partnering. We do offer help with a lot of topics. In order to provide the most successful help Schaffner does operate a service organization and worldwide service centers. We do also closely collaborate with a growing network of qualified and authorized service partners to maintain our high service quality on a global approach.
Page 20
20 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
3.5 Get training
Do you need training? Schaffner can offer a training course comprised of lecture and hands-on workshops designed to introduce you to the fundamental concepts of power quality, ECOsine® harmonic filters and filter maintenance. We also offer customized training courses designed to meet your specific needs. Please contact your local Schaffner sales organization or Schaffner representative to discuss how we can help you achieve success in your power quality efforts.
Page 21
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 21
3.6 Contact us
Schaffner – More than just filters. Schaffner is in the unique position of being able to support the user with problem analyses, engineering advice, testing and measurement support, custom products, and a worldwide customer service organization. Our goal is to ensure that you obtain the level of support you actually need. Toward this objective, we invite you to contact your local Schaffner representative at any time that we may be of service to you. You can find out more about us and your local contact on our corporate website or you may contact us via email:
Corporate URL: www.schaffner.com Corporate E-mail: info@schaffner.com
Page 22
22 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
4 AHF 200-690-3
Page 23
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 23
4.1 Maintenance Schedule
Year after start
operation
Maintenance job
1 2 3 4 5 6 7 8 9
10
11
12
Check operation of main fan, DC-bus fan and clean fan guards
          
Check of coolant level
          
Check coolant pump for any signs of coolant-leakage
          
Replace inverter fan (DC bus fan)
 Replace pre-charge fuses F1 & F2
 Replace 230V auxiliary power supply fuses F3 & F4
 Replace 24V power supply fuses F45 & F46
 Replace cooling system power supply fuses. F47 & F48
Replace cooling system control unit fuses F1-F3
Replace air-conditioning fuses F11
 Change cooling liquid
  Replace main fan
Table 3: Maintenance schedule 200-690-3
Page 24
24 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
4.2 Wear parts
4.2.1 Wear parts - AHF 200-690-3 (Not UL)
Required amount / filter
Description
Part #
Classification
1x
DC-bus fan assembly (Set incl. 2 fans)
814878
Wear part
1x
DC-bus pre-charge fuse (Set incl. 2 fuses) 10A 690VAC / 14x51mm (Position F1 & F2)
814437
Wear part
1x
230V auxiliary power supply fuse (Set incl. 2 fuses) 10A 690V / 14x51mm (Position F3 & F4)
814437
Wear part
1x
24V power supply fuse (Set incl. 2 fuses) 1,25A 500V / 6,3x32mm (Position F45 & F46)
814442
Wear part
1x
Cooling system power supply fuses (Set incl. 2 fuses) 10A 500V / 6,3x32mm (Position F47 & F48)
814440
Wear part
1x
Cooling system control unit & air-conditioning fuses (Set incl. 3 fuses) 4A 500V / 6,3x32mm (Position F1, F2 & F11)
811403
Wear part
1x
Cooling system control unit fuses (Set incl. 1 fuses) 2A 250V / 5x20mm (Position F3)
811405
Wear part
1x
Cooling liquid Antifrogen N 10kg / 8,8l (Mix for use 70% water and 30% Antifrogen N)
814453
Wear Part
1x
Main fan (Set incl. 1 fan) 812275
Wear part
Table 4: Wear parts 200-690-3 (not UL)
Page 25
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 25
4.2.2 Wear parts - AHF 200-690-3 (UL)
Required amount / filter
Description
Part #
Classification
1x
DC-bus fan assembly (Set incl. 2 fans)
814878
Wear part
1x
DC-bus pre-charge fuse (Set incl. 2 fuses) 10A 600VAC / 10x38mm (Position F1 & F2)
814438
Wear part
1x
230V auxiliary power supply fuse (Set incl. 2 fuses) 8A 600V / 10x38mm (Position F3 & F4)
814441
Wear part
1x
24V power supply fuse (Set incl. 2 fuses) 1,25A 500V / 6,3x32mm (Position F45 & F46)
814442
Wear part
1x
Cooling system power supply fuses (Set incl. 2 fuses) 10A 500V / 6,3x32mm (Position F47 & F48)
814440
Wear part
1x
Cooling system control unit & air-conditioning fuses (Set incl. 3 fuses) 4A 500V / 6,3x32mm (Position F1, F2 & F11)
811403
Wear part
1x
Cooling system control unit fuses (Set incl. 1 fuses) 2A 250V / 5x20mm (Position F3)
811405
Wear part
1x
Cooling liquid Antifrogen N 10kg / 8,8l (Mix for use 70% water and 30% Antifrogen N)
814453
Wear Part
1x
Main fan (Set incl. 1 fan) 812275
Wear part
Table 5: Wear parts 200-690-3 (UL)
Page 26
26 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
4.3 Replacement Instruction
Attention! Before starting to work on the device, ensure that it is switched of, disconnected from the grid and capacitors are discharged
4.3.1 Check operation of main fan and DC-Bus fan and clean fan guards
1. Tools List
TOOLS LIST
1. Glove
2. Brush
3. Mask
4. Cleaning paper
5. Alcohol
6. Water Tips:
Prefer to have vacuum cleaner
2. Work Instruction – Dismantling process
Check with parameter group P1XX Measured values / No.182 Enclosure fan 3, Check the speed (rpm) of fan 3. In case rpm stays on “0, then replace it according to the instruction <<Replace DC­LINK fan>>
Tips: for main fan only do physically check if you feel some moving air
Page 27
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 27
Check with parameter group P1XX Measured values / No. 183 Enclosure fan 4, Check the speed (rpm) of fan 3. In case rpm stays on “0, then replace it according to the instruction <<Replace DC­LINK fan>>
Tips: for main fan only do physically check if you feel some moving air
Switch off the device on Main Switch, disconnect from the grid and ensure that thecapacitors are discharged before starting to work on the device.
Unlock the cabinet by key
Page 28
28 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Make sure that the control box is closed during the whole cleaning process
Locating the position of main fan
Remove the marked lifting bolts
Page 29
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 29
Remove the top cover and use vacuum cleaner / compressor to clean main fan and surrounding area.
Remove the marked screws and take out the protection panel.
Remove the marked screws and take out the protection panel
Page 30
30 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Use the brush to clean the two inverter fans
3. Work instruction – Reassembly process
Close the top cover
Tighten the marked lifting bolts
Page 31
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 31
Mount the protection panel and tighten all marked screws with 5 Nm.
Mount the second protection panel and tighten marked screws with 5Nm
Close and lock the door
Page 32
32 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
4.3.2 Check of coolant level
1. Tools List
Tool list
1. Funnel with extended tube
2. Spare Parts
Spare Parts
1x 814453 AHF Coolant mixed SP (10l)
3. Work instruction
Unlock the cabinet by key
Page 33
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 33
Check the position of level indicator
Max level
Min level
Only fill in the coolant in case level indicator
under “Min level “
Remove the cap of water tank and insert funnel into water tank
Fill in coolant into water tank till the level of indicator reaching the position max level
Page 34
34 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Remove the funnel and close the cap of water tank. Close and lock the door
4.3.3 Check coolant pump for any signs of coolant­leakage
1. Tools List
Tool list
1. Visual inspection only
2. Work instruction
Unlock the cabinet by key
Page 35
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 35
Locating the position of pump
Visual checking left side area of pump & tubes
Attention!
Contact Schaffner Service Center in case any leakage points are detected
Visual checking right side area of pump & tubes
Attention!
Contact Schaffner Service Center in case any leakage points are detected
Page 36
36 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
If no any leakage are found, close and lock the door
4.3.4 Replace inverter fan (DC bus fan)
1. Tools List
TOOLS LIST
1. M6 Hex socket wrench
2. Philips screwdriver
3. Pliers
4. Cabinet key
2. Spare Parts
Spare Parts
1x 814878 AHF FAN SAN ACE 120 690 SP
Page 37
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 37
3. Work instruction - Dismantling process
Unlock the cabinet by key
Remove the marked screws and take out the protection panel.
Remove the marked screws and take out the protection panel
Page 38
38 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Disconnect the fan cables of the two fan modules.
Bend the clip on fan plate straight.
Pull out the fans away from cover
Page 39
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 39
4. Work instruction – Reassembly process
Insert the fans into the fan cover and reconnect the fan cables
Bend the clip on fan plate back to block fix the fan
Mount the protection panel and tighten all marked screws with 5 Nm.
Page 40
40 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Mount the second protection panel and tighten marked screws with 5Nm
Close and lock the door
4.3.5 Replace pre-charge fuses F1 & F2
1. Tools List
Tool list
1. Cabinet Key
Page 41
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 41
2. Spare Parts
Spare Parts
1x 814437 (For no UL-Version) AHF FUSE 10AMP 690VAC 14X51MM 690 SP 1x 814438 (For UL-Version) AHF FUSE 10AMP 600VAC 14X38MM 690 SP
3. Work instruction - Dismantling process
Unlock the cabinet by key
Locating the position of pre-charging fuses F1 F2
Page 42
42 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Open the fuse holder F1 and F2 and take out the fuses
4. Work instruction – Reassembly process
Insert the two new fuses into teh fuse holder
Close the covers and take care that the covers are closed complete
Page 43
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 43
Close and lock the door
4.3.6 Replace 230V auxiliary power supply
1. Tools List
Tool list
1. Cabinet Key
2. Spare Parts
Spare Parts
1x 814437 AHF FUSE 10AMP 600VAC 14X38MM 690 SP 1x 814441 AHF FUSE 8AMP 600VAC 14X38MM 690 SP
Page 44
44 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
3. Work instruction - Dismantling process
Unlock the cabinet by key
Locating the position of pre-charging fuses F3 F4
Open the fuse holder F3 and F4 and take out the fuses
Page 45
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 45
4. Work instruction – Reassembly process
Insert the two new fuses into the fuse holder
Close the covers and take care that the covers are closed complete
Close and lock the door
Page 46
46 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
4.3.7 Replace 24V power supply fuses F45 & F46
1. Tools List
Tool list
1. Cabinet Key
2. Spare Parts
Spare Parts
1x 814442 AHF FUSE 1.25AMP 500VAC 6.3X32 690 SP
3. Work instruction - Dismantling process
Unlock the cabinet by key
Page 47
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 47
Locating the position of GCS module PCB
Take out the fuse of position F45 F46
4. Work instruction – Reassembly process
Insert the two new fuses into the fuse clip
Page 48
48 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Close and lock the door
4.3.8 Replace cooling system power supply fuses F47 & F48
1. Tools List
Tool list
1. Cabinet Key
2. Spare Parts
Spare Parts
1x 814440 AHF FUSE 10AMP 500VAC 6.3X32MM 690 SP
Page 49
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 49
3. Work instruction - Dismantling process
Unlock the cabinet by key
Locating the position of GCS module PCB
Take out the fuse of position F47 F48
Page 50
50 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
4. Work instruction – Reassembly process
Insert the two new fuses into the fuse clip
Close and lock the door
Page 51
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 51
4.3.9 Replace cooling system control unit fuses F1­F3
1. Tools List
Tool list
1. Cabinet Key
2. Spare Parts
Spare Parts F1 & F2
1x 811403 AHF FUSE 4A 500VAC 63X32 300A SP
Spare Parts F3
1x 811405 AHF FUSE 2A 250VAC 5X20 690 SP
F1 F2
F3
3. Work instruction - Dismantling process
Unlock the cabinet by key
Page 52
52 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Open the cover of liquid cooling control box with Key
Remark: The position of liquid cooling control box can vary, depends on version.
Lift up the fuse holder, open the cover and take out the fuses. Repeat the same procedure for F2 and F3
4. Work instruction – Reassembly process
Insert the new fuse into the fuse holder. Repeat the same procedure for F2 and F3
Attention!
Use the right part for the right position (F3 has another type of fuse)
Page 53
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 53
Close the cover of liquid cooling control box with Key
Close and lock the door
4.3.10 Replace air-conditioning fuses F11
1. Tools List
TOOLS LIST
- Slotted screwdriver
- Rittal cabinet key
Page 54
54 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
2. Spare Parts
Spare Parts
1x 811403 AHF FUSE 4A 500VAC 63X32 300A SP
3. Work instruction - Dismantling process
Unlock the cabinet by key
Remove the fuse holder cover F11
Page 55
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 55
Take out fuse from fuse holder
4. Work instruction – Reassembly process
Insert the fuse into the fuse holder
Insert the fuse into the position F11
Page 56
56 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Close and lock the door
4.3.11 Change cooling liquid
1. Tools List
Tool list
1. Funnel with extended tube
2. Spare Parts
Spare Parts
1x 814453 AHF Coolant mixed SP (10l)
Page 57
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 57
3. Work instruction – Dismantling process
Unlock the cabinet by key
Open the coiled silicon tube and guide this into a vessel.
Open the shut-off cock and drain the whole content of water tank into the vessel.
Page 58
58 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
4. Work instruction – Reassembly process
Close the shut-off cock. Remove the cap of water tank and insert
funnel into water tank
Fill in coolant into water tank till the level of indicator reaching the position max level
Page 59
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 59
Remove the funnel and close the cap of water tank. Close and lock the door
4.3.12 Replace main fan
1. Tools List
Tool list
1. Cabinet Key
2. M13 socket wrench with extension
3. Slotted screw driver
2. Spare Parts
Spare Parts
1x 812275 AHF FAN FOR WARTER COOLING 300A SP
Page 60
60 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
3. Work instruction - Dismantling process
Locating the position of main fan
Remove the marked lifting bolts
Remove the top cover
Page 61
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 61
Remove the marked screws with socket wrench
Loosen the two cable glands
Unlock the cabinet by key
Page 62
62 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Open the cover of liquid cooling control box with Key
Remark: The position of liquid cooling control box can vary, depends on version.
Loosen the conection of the two fan cables with slotted screw driver
Remark: Take a picture to remember the correct wiring of both cables
Pull out the two fan cables throught cable glands
Page 63
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 63
Take out the main fan from top cover
4. Work instruction – Reassembly process
Insert the new main fan
Insert the two fan cables into the cable glands and fix it
Page 64
64 ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3
Tighten the marked screws with 13.6Nm Close the top cover
Tighten the marked lifting bolts
Page 65
ECOsine® active Harmonic Filters – Maintenance Manual for FN3420-200-690-3 65
Rewiring all removed fan cables
Close the cover of liquid cooling control box with Key
Close and lock the door
Page 66
Headquarters, Global Service Center
Schaffner Group
Nordstrasse 11 4542 Luterbach Switzerland T +41 32 681 66 26 F +41 32 681 66 30 info@schaffner.com www.schaffner.com
www. schaffner-trenco.com
Service Centers
Asia - China
Schaffner EMC Ltd. Shanghai
T20-3, No 565 Chuangye Road Pudong New Area Shanghai 201201
Europe - Switzerland
Schaffner International Ltd.
Nordstrasse 11 4542 Luterbach
United States - Edison
Schaffner EMC Inc.
52 Mayfield Avenue
Edison New Jersey 08837
To find your local partner within Schaffner‘s global network, please go to www.schaffner.com
®
2014 Schaffner Group
The content of this document has been carefully checked and understood. However, neither Schaffner nor its subsidiaries assume any liability whatsoever for any errors or inaccuracies of this document and the consequences thereof. Published specifications are subject to change without notice. Product suitability for any area of application must ultimately be determined by the customer. In all cases, products must never be operated outside their published specifications. Schaffner does not guarantee the availability of all published products. This disclaimer shall be governed by substantive Swiss law and resulting disputes shall be settled by the courts at the place of business of Schaffner Holding AG. Latest publications and a complete disclaimer can be downloaded from the Schaffner website. All
Loading...