INERIS 15ATEX0017X 2022
IECEx INE 15.0033X
Ex eb IIC T5 Gb
Ex tb IIIC T80°C Db
0051
II 2GD
0051
ITALIANO
INDICE
1. Istruzioni di Installazione, Funzionamento e Manutenzione per l’uso sicuro 4
2. Dati tecnici 5
3. Codice identificativo 6
4. Caratteristiche tecniche 6
5. Installazione 7
6. Assistenza, manutenzione e riparazione 8
A MinøGL MinTYPEIP66
140,5
73
2P+-
16A
32A
63A
125A
3P+-
3P+N+-
2P+-
3P+-
3P+N+-
3P+-
3P+N+-
3P+-
3P+N+-
A
L
ØG
116
123
140,5
142,6
142,6
150
166,5
166,5
214,5
214,5
81
88
92
92
101
112
112
128
128
147,5
180,5
217,5
217,5
IT
(mm)
165
174
174
274
274
Disegno tecnico della spina.
Un esempio dell’etichetta usata per la spina certificata è qui riprodotta.
Esempio di etichettatura ATEX / IECEx
Via Costa Erta, 15 - 24020 Parre (BG) Italy
219.1633
2P+T 16A
6h 200-250V 50/60Hz
MP39684ZP90905-73
WARNING
Tcable 80°C when the
maximum Ta is +60°C
OPTIMA-EX[GD]
Ex tb IIIC T80°C Db X IP66
1 Ex e IIC T5 Gb X 2022
Ta mb. -50°C to +60°C
1 Ex e IIC T6 Gb X
Ta mb. -50°C to +50°C
0051
II 2GD
Esempio di etichettatura EAC Ex
BHИМАНИЕ
Teмnepaтypa кaбeля 80°C,
Via Costa Erta, 15 - 24020 Parre (BG) Italy
219.1633.RU
2P+T 16A
6h 200-250V
LEGGERE A FONDO IL PRESENTE DOCUMENTO PRIMA DI ESEGUIRE L’INSTALLAZIONE
1. ISTRUZIONI DI INSTALLAZIONE, FUNZIONAMENTO E MANUTENZIONE PER L’USO SICURO
1.1 NORME DI SICUREZZA.
I dispositivi OPTIMA-EX[GD] sono progettati come apparecchiature di Gruppo II, Categoria 2 e sono adatti all’utilizzo in installazioni
fisse in aree a rischio di esplosione designate come Zona 1/21 e Zona 2/22. Conservare le presenti istruzioni in un luogo sicuro
per consultazione futura. Utilizzare i dispositivi OPTIMA-EX[GD] solamente per lo scopo previsto, solo se gli stessi appaiono integri
e puliti e solo se viene garantita la resistenza del materiale all’ambiente circostante.
Non sono consentite modifiche ai dispositivi OPTIMA-EX[GD] non espressamente menzionate nel presente manuale di istruzioni.
Durante l’installazione dei dispositivi OPTIMA-EX[GD] prendere debitamente in considerazione le distanze di isolamento in aria e
superficiali riportate al punto 5.3 (tabella).
I dispositivi OPTIMA-EX[GD] sono disponibili in termoindurente con la seguente corrente nominale: 16A, 32A, 63A, 125A.
Utilizzare le spine della serie OPTIMA-EX[GD] solo con le prese della serie SCAME ADVANCE-GRP[GD], Ex db eb IIC/Ex tb IIIC, con
certificazione separata. La presa ADVANCE-GRP[GD] dispone di una manovra che aziona un meccanismo di interblocco meccanico
evitando di separare i contatti della spina dalla presa quando i contatti sono chiusi. La spina della serie OPTIMA-EX[GD] potrà
essere estratta solamente se la manovra è in posizione 0 (zero).
когда максимум
Ta составляет +60°C
HAHИO ЦCBЭ
№ TC RU C-IT.AA87.B.00XXX
1.2 CONFORMITÀ ALLE NORMATIVE
La presa OPTIMA-EX[GD] è progettata per la Zona 1/21 e Zona 2/22 ai sensi di:
• EN IEC 60079-0:2018,
• EN IEC 60079-7:2015+A1:2018
• EN 60079-31:2014
• EN 60309-1:1999 +A1:2007, +A2:2012
• EN 60309-2:1999 +A1:2007, +A2:2012
• IEC 60079-0:2017,
• IEC 60079-7:2017,
• IEC 60079-31:2013
• IEC 60309-1:1999, +A1:2005, +A2:2012
• IEC 60309-2:1999, +A1:2005, +A2:2012
• ГОСТ 31610.0-2014, (IEC 60079-0:2011)
• ГОСТ Р МЭК 60079-7-2012
• ГОСТ IEC 60079-31-2010
Sono prodotte e collaudate ai sensi della direttiva ATEX 2014/34/UE, schema IECEx, certificazione EAC Ex.
MP39684ZP90905-74
OPTIMA-EX[GD]
2. DATI TECNICI
2.1 TIPO DI PROTEZIONE
ATEX / IECEx :
Ex eb IIC T
Ex tb IIIC T80°C Db IP66
Tamb.
EAC Ex :
1Ex eb IIC T
(1)
Gb
(2)
- Tcable:
(1)
(3)
Gb X
Ex tb IIIC T80°C Db X
IP66
(2)
Tamb.
- Tcable:
(1)
Classe di temperatura per gas vedi tabella 1.
(2)
Intervallo temperatura ambiente vedi tabella 1, se diverso da -20 ° C a + 40 ° C.
(3)
Tcavo: 80°C per tipo 219.16… se la temperatura ambiente massima è +60°C;
(3)
Tcavo: 85°C per tipo 219.32… se la temperatura ambiente massima è +60°C;
Tcavo: 90°C per tipo 219.63… se la temperatura ambiente massima è +60°C;
Tcavo: 85°C per tipo 219.125…
2.2 CERTIFICATI
Certificato Atex: INERIS 15ATEX0017 X
Certificato IECEx: IECEx INE 15.0033 X
Certificato EAC Ex: НАНИО ЦСВЭ № TC RU C-IT.AA87.B.00870
2.3 INTERVALLO TEMPERATURA AMBIENTE
OPTIMA-EX[GD]
Tipo spina
219.16…
Intervallo temperatura
ambiente (Ta)
Temperatura classe
-50°C a +50°CT6
-50°C a +60°CT5
-50°C a +60°CT4
-50°C a +50°CT4
219.32…
-50°C a +40°CT5
-40°C a +60°CT4
-40°C a +50°CT4
-40°C a +40°CT5
-35°C a +60°CT3
219.63…
-35°C a +50°CT3
-35°C a +40°CT4
219.125…-35°C a +40°CT4
tabella 1
IT
Temperatura massima
superficiale
T80°C
La temperatura ambiente della presa serie OPTIMA-EX[GD] utilizzata potrebbe limitare l’intervallo di
temperatura ambiente.
2.4 ETICHETTA DI AVVERTIMENTO
ATTENZIONE:
non aprire in presenza di atmosfera esplosiva
(*) ATTENZIONE:
L’ingresso del cavo può raggiungere alte temperature. Utilizzare solo cavi idonei.
5. INSTALLAZIONE
L’installazione dovrà essere eseguita a regola d’arte da personale qualificato (ad esempio IEC EN 60079-14),
e in conformità alle normative nazionali sulla sicurezza e prevenzione degli incidenti e al presente manuale.
5.1 ISTRUZIONI DI SICUREZZA
Utilizzare la spina solamente per lo scopo previsto. L’uso scorretto, non consentito o non conforme alle presenti istruzioni invaliderà
la garanzia. Non sono consentite modifiche che pregiudichino il livello di protezione dalle esplosioni della spina. Montare e azionare
il sezionatore solamente nel caso che lo stesso sia pulito e integro.
5.2 ACCESSORI
• Cappuccio di protezione contatti spina
Utilizzare solo accessori originali SCAME approvati.
5.3 DISTANZA DI ISOLAMENTO IN ARIA E SUPERFICIALE
Tutto il cablaggio deve essere eseguito a regola d’arte e in conformità alle normative di installazione in zone pericolose come IEC
EN 60079-14.
Utilizzare utensili idonei e la coppia di chiusura corretta (vedi documentazione del produttore) per il serraggio dei morsetti (cacciavite
o chiave).
Le distanze di isolamento in aria e superficiali delle parti devono essere conformi alla norma EN IEC 60079-7:2015+A1:2018 /
ГОСТ Р МЭК 60079-7-2012 (tabella 1). I parametri elettrici non devono superare il massimo consentito.
Note: Le distanze di isolamento in aria e superficiali delle parti conduttive o altre parti sotto tensione sono:
Ta 40°CTa 50°CTa 60°C
Corrente massima
IT
Distanza minima di dispersioneSpazio libero minimo
250 V
400 V
500 V
630 V
Note: Le tensioni sono tensioni nominali; la tensione di esercizio può superare del 10% il livello di tensione dato.
I dispositivi OPTIMA-EX[GD] sono sottoposti ad una prova di routine di forza dielettrica di 1000 rms V + 2U o
1500 V rms, a seconda di quale è maggiore, per un periodo di 60 s, come previsto dalla clausola 6.1 della
norma EN IEC 60079-7:2015+A1:2018/ ГОСТ Р МЭК 60079-7-2012. In alternativa, la prova viene effettuata a 1,2 volte
la tensione di prova, ma mantenuta per almeno 100 ms.
MP39684ZP90905-77
5 mm
8 mm
10 mm
12 mm
250 V
400 V
500 V
630 V
5 mm
6 mm
8 mm
10 mm
OPTIMA-EX[GD]
6. ASSISTENZA, MANUTENZIONE E RIPARAZIONE
L’installazione, l’ispezione e la manutenzione della presente apparecchiatura devono essere eseguite a regola
d’arte da personale qualificato (ad esempio IEC/EN 60079-14 e IEC/EN 60079-17). La riparazione della
presente apparecchiatura dovrà essere eseguita a regola d’arte da personale qualificato ai sensi delle prassi
applicabili. Durante la manutenzione, è particolarmente importante controllare i componenti dai quali dipende il tipo
di protezione.
6.1 MANUTENZIONE ORDINARIA
La manutenzione ordinaria è necessaria per garantire l’efficienza della cassetta e per mantenere il livello di protezione richiesto.
1) Controllare che la guarnizione della ghiera sia in posizione e non danneggiato ogni volta che il corpo spina è aperto.
2) Controllare che le viti di fissaggio siano in posizione e serrate a fondo ogni volta che la spina è inserita nella presa
3) Verificare annualmente che le viti/bulloni di montaggio siano ben serrati
4) Controllare eventuali danni al corpo spina annualmente
5) Nelle aree con presenza di polveri combustibili pulire periodicamente la superficie superiore dell’assemblato, limitando la
profondità dello strato a meno di 5 mm.
Condizioni di stoccaggio
Temperatura di stoccaggio: da -50°C a +70°C per 16A/32A.
Temperatura di Stoccaggio : da -35°C a +70°C per 63A/125A.
Umidità relativa : ≤95%RH.
La durata stimata del prodotto è di 25 anni se le condizioni di manutenzione e conservazione sono rispettate e tutte le prescrizioni
specificate sono applicate in queste istruzioni.
6.2 RESISTENZA AGLI AGENTI CHIMICI
Occorre prendere in considerazione l’ambiente in cui le cassette saranno utilizzate per determinare l’idoneità dei materiali di
resistere a eventuali agenti corrosivi che potrebbero essere presenti.
6.3 SMALTIMENTO
Lo smaltimento e il riciclaggio del prodotto devono essere effettuati secondo le normative nazionali per lo smaltimento e il
riciclaggio dei rifiuti.
MP39684ZP90905-78
OPTIMA-EX[GD]
DICHIARAZIONE DI CONFORMITÀ UE
Noi : SCAME PARRE S.p.A.Via Costa Erta, 15 – 24020 Parre (BG) ITALY
(Il codice prodotto specifico e il numero di serie sono indicati in targa e sull’imballo)
ai quali la presente dichiarazione si riferisce sono conformi a :
Direttiva ATEX 2014/34/UE
Direttiva LVD 2014/35/UE
Schema di certificazione IECEx
La conformità è stata verificata sulla base delle seguenti norme :
EN IEC 60079-0:2018 IEC 60079-0:2017
EN IEC 60079-7:2015+A1:2018 IEC 60079-7:2017
EN 60079-31:2014 IEC 60079-31:2013
EN 60309-1:1999+A1:2007+A2:2012 IEC 60309-1:1999+A1:2005+A2:2012
EN 60309-2:1999+A1:2007+A2:2012 IEC 60309-2:1999+A1:2005+A2:2012
EN 60309-4:2007+A1:2012 IEC 60309-4:2006+A1:2012
IT
Marcatura Direttiva ATEX : Modo di protezione ATEX/IECEx (*):
Ex eb IIC T6... T3 Gb
0051 II 2GD
Ex tb IIIC T80°C Db IP66
Tamb.: -50°C ≤ Ta ≤ +60°C
(*) I dati specifici relativi a: classe di temperatura, massima temperatura superficiale e temperatura
ambiente sono indicati in targa.
I modelli appartenenti a questa famiglia di prodotti sono oggetto dei certificati INERIS 15ATEX0017X (in
conformità all’Allegato III della Direttiva ATEX), IECEx INE 15.0033X (in conformità allo schema IECEx) e
alla notifica del sistema di qualità IMQ 08 ATEX 013 Q (in conformità all’Allegato VII della Direttiva ATEX).
Organismo notificatore per il certificato di esame del tipo ATEX UE: INERIS, numero 0080
Indirizzo: Parc Technologique Alata BP 2 F-60550 Verneuil-en-Halatte
Parre, 04-02-2022 SCAME PARRE S.p.A.
Direttore ricerca e sviluppo
Ing. Giampietro Camilli
VIA COSTA ERTA, 15 - 24020 PARRE (BG) ITALY - TEL. +39 035 705000 - FAX +39 035 703122 -
INERIS 15ATEX0017X 2022
IECEx INE 15.0033X
Ex eb IIC T5 Gb
Ex tb IIIC T80°C Db
0051
II 2GD
0051
ENGLISH
CONTENTS
1. Installation, Operation and Maintenance Instructions for safe use 11
2. Technical data 12
3. Identification Code 13
4. Technical Features 13
5. Installation 14
6. Servicing and maintenance and repairing 15
A MinøGL MinTYPEIP66
140,5
73
2P+-
16A
32A
63A
125A
3P+-
3P+N+-
2P+-
3P+-
3P+N+-
3P+-
3P+N+-
3P+-
3P+N+-
A
L
ØG
116
123
140,5
142,6
142,6
150
166,5
166,5
214,5
214,5
81
88
92
92
101
112
112
128
128
147,5
180,5
217,5
217,5
(mm)
165
174
174
274
274
Technical drawing of the plug
An example of the label used for the certified plug is shown below:
Example of marking label ATEX / IECEx
Via Costa Erta, 15 - 24020 Parre (BG) Italy
219.1633
2P+T 16A
6h 200-250V 50/60Hz
MP39684ZP90905-710
WARNING
Tcable 80°C when the
maximum Ta is +60°C
OPTIMA-EX[GD]
Ex tb IIIC T80°C Db X IP66
1 Ex e IIC T5 Gb X 2022
Ta mb. -50°C to +60°C
1 Ex e IIC T6 Gb X
Ta mb. -50°C to +50°C
0051
II 2GD
Example of marking label EAC Ex
BHИМАНИЕ
Teмnepaтypa кaбeля 80°C,
Via Costa Erta, 15 - 24020 Parre (BG) Italy
219.1633.RU
2P+T 16A
6h 200-250V
THIS DOCUMENT SHOULD BE READ CAREFULLY BEFORE INSTALLATION
1. INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR SAFE USE.
1.1 SAFETY RULES.
OPTIMA-EX[GD] are designed as Group II Category 2 equipment and is suitable for use for fixed installation in areas with
explosion hazard designated Zone 1/21 and Zone 2/22. These operating instructions must be kept in safe place for later
consultation. Use OPTIMA-EX[GD] only for their intended duty in the undamaged and clean condition, and only where the
resistance of the material to the surroundings is assured. No modifications are allowed to the OPTIMA-EX[GD] that are not
expressly mentioned in this instruction manual. When installing the OPTIMA-EX[GD] the clearance and creepage distance shall
be duly considered as topic 5.3 (table).
The OPTIMA-EX[GD] are available in materials GRP with the following rated current 16A, 32A, 63A, 125A.
The plug series OPTIMA-EX[GD] have to be used only with SCAME socket series ADVANCE-GRP[GD], Ex db eb IIC / Ex tb IIIC ,
with separated certification. The ADVANCE-GRP[GD] socket switch-handle move a mechanical interlock mechanism that avoid
to separate the plug contacts from the plug outlet when the contacts are energized. The plug series OPTIMA-EX[GD] can be to
pull-out only when the handle is in position 0 (zero).
1.2 CONFORMITY TO STANDARDS
The socket OPTIMA-EX[GD] are designed for Zone 1/21 and Zone 2/22 according to :
• EN IEC 60079-0:2018,
• EN IEC 60079-7:2015+A1:2018
• EN 60079-31:2014
• EN 60309-1:1999+A1:2007+A2:2012
• EN 60309-2:1999+A1:2007+A2:2012
• IEC 60079-0:2017,
• IEC 60079-7:2017,
• IEC 60079-31:2013
• IEC 60309-1:1999+A1:2005+A2:2012
• IEC 60309-2:1999+A1:2005+A2:2012
• ГОСТ 31610.0-2014, (IEC 60079-0:2011)
• ГОСТ Р МЭК 60079-7-2012
• ГОСТ IEC 60079-31-2010
They are manufactured and tested in accordance with ATEX directive 2014/34/EU, IECEx scheme, EAC Ex certification.
когда максимум
Ta составляет +60°C
HAHИO ЦCBЭ
№ TC RU C-IT.AA87.B.00XXX
EN
MP39684ZP90905-711
OPTIMA-EX[GD]
2. TECHNICAL DATA
2.1 TYPE OF PROTECTION
ATEX / IECEx :
Ex eb IIC T
Ex tb IIIC T80°C Db
IP66
Tamb.
(1
) Gb
(2)
- Tcable:
(3)
EAC Ex :
1Ex eb IIC T
(1)
Gb X
Ex tb IIIC T80°C Db X
IP66
(2)
Tamb.
- Tcable:
(1)
Temperature Class for Gas according to the table 1
(2)
Ambient temperature range according to the table 1, when different from –20°C to +40°C.
(3)
Tcable: 80°C for type 219.16… when maximum ambient temperature is +60°C;
(3)
Tcable: 85°C for type 219.32… when maximum ambient temperature is +60°C;
Tcable: 90°C for type 219.63… when maximum ambient temperature is +60°C;
Tcable: 85°C for type 219.125…
2.4 CERTIFICATES
Atex Certificate: INERIS 15ATEX0017 X
IECEx Certificate: IECEx INE 15.0033 X
EAC Ex Certificate НАНИО ЦСВЭ № TC RU C-IT.AA87.B.00870
2.5 AMBIENT TEMPERATURE RANGE
OPTIMA-EX[GD]
Plug Type
219.16…
Ambient Temperature
Range (Ta)
CLASS Temperature
-50°C to +50°CT6
-50°C to +60°CT5
-50°C to +60°CT4
-50°C to +50°CT4
219.32…
-50°C to +40°CT5
-40°C to +60°CT4
-40°C to +50°CT4
-40°C to +40°CT5
-35°C to +60°CT3
219.63…
-35°C to +50°CT3
-35°C to +40°CT4
219.125…-35°C to +40°CT4
table 1
Max. Surface
Temperature
T80°C
The ambient temperature range can be limited by the ambient temperature of socket series OPTIMA-EX[GD]
used.
2.4 WARNING LABEL
do not open when an explosive atmosphere is present
(*) WARNING:
The cable entry can be reach high temperature – Suitable cable shall be used.
5. INSTALLATION
Installation shall be carried out by suitably-trained personnel in accordance with the applicable code of
practice (e.g. IEC EN 60079-14) and the provisions of the national safety and accident prevention regulations
and this instruction manual.
5.1 SAFETY INSTRUCTIONS
Use the plug only for its intended purpose. Incorrect or impermissible use or noncompliance with these instructions invalidates
our warranty provision. No changes to the plug impairing its explosion protection are permitted. Fit and operate the switch only if
it is clean and undamaged.
5.2 ACCESSORIES
• Protection cup
Only approved and genuine SCAME accessories must be used.
5.3 CREEPAGE AND CLEARANCE DISTANCES
All wiring must be carried out in accordance with the code of practice and installation standards in hazardous areas like IEC EN
60079-14.
Use the correct size of tool and torque (see manufacturer documents) for tightening the terminal clamps (screwdriver or spanner).
Creepage and clearance distances shall comply with EN IEC 60079-7:2015+A1:2018 / ГОСТ Р МЭК 60079-7-2012 (table 1),
electrical parameters shall not exceed the maximum allowed.
Note: Minimum creepage and clearance distances that shall be maintained to conductive parts or other live parts are:
Ta 40°CTa 50°CTa 60°C
Maximun Current
Minimum creepageMinimum clearance
250 V
400 V
500 V
630 V
Note: Voltages are nominal voltages – the working voltage may exceed by 10% the voltage level given.
OPTIMA-EX[GD]shall be subject to a routine dielectric streght test of 1000 V + 2U rms or 1500 V rms, whichever
is the greater applied for a period of 60 s as required by clause 6.1 of EN IEC 60079-7:2015+A1:2018 / ГОСТ Р
МЭК 60079-7-2012. Alternatively, a test shall be carried out at 1.2 times the test voltage, but maintained for at least
100 ms.
MP39684ZP90905-714
5 mm
8 mm
10 mm
12 mm
250 V
400 V
500 V
630 V
5 mm
6 mm
8 mm
10 mm
OPTIMA-EX[GD]
6. SERVICING AND MAINTENANCE AND REPAIRING.
Installation, inspection and maintenance of this equipment shall be carried out by suitably trained personnel
in accordance with the applicable code of practice (e.g. IEC/EN 60079-14, IEC/EN 60079-17). Repair of this
equipment shall be carried out by suitably trained personnel in accordance with the applicable code of practice.
During servicing, it is particularly important to check those components upon which the type of protection depends.
6.1 ROUTINE MAINTENANCE
Routine maintenance is required in order to guarantee the efficiency of the enclosure and to maintain the required level of
protection.
1) Check that the sealing ring is in place and not damaged…each time the enclosure is opened
2) Check that all the fixing screws are in place and secured…each time the enclosure is closed
3) Check that the mounting screws are tight and free of corrosion…annually
4) Check the body for damage…annually
5) In zones with presence of combustible dusts it is necessary to periodically clean the upper surface of the box, limiting the depth
of the layer to less than 5 mm.
Storage conditions
Storage Temperature : from -50°C to +70°C for 16A/32A
Storage Temperature : from -35°C to +70°C for 63A/125A
Relative Humidity : ≤95%RH
The estimated product lifetime is 25 years if maintenance and storage condition are respected and all prescriptions specified
applied in this instructions .
6.2 RESISTANCE TO CHEMICAL AGENT
Consideration should be given to the environment in which these enclosures are to be used to determine the suitability of these
materials to withstand any corrosive agents that may be present.
6.3 DISPOSAL
Disposal and recycling of the product shall be done according to national regulations for waste disposal and recycling.
EN
MP39684ZP90905-715
OPTIMA-EX[GD]
DECLARATION OF CONFORMITY EU
The company : SCAME PARRE S.p.A.Via Costa Erta, 15 – 24020 Parre (BG) ITALY
Hereby declares that the following products:
Plug type OPTIMA-EX[GD] Code 219.16… , 219.32… , 219.63… or 219.125…
(The specific product code and the serial number are indicated on the packing label)
Compliance was verified on the basis of the following standards:
EN IEC 60079-0:2018 IEC 60079-0:2017
EN IEC 60079-7:2015+A1:2018 IEC 60079-7:2017
EN 60079-31:2014 IEC 60079-31:2013
EN 60309-1:1999+A1:2007+A2:2012 IEC 60309-1:1999+A1:2005+A2:2012
EN 60309-2:1999+A1:2007+A2:2012 IEC 60309-2:1999+A1:2005+A2:2012
EN 60309-4:2007+A1:2012 IEC 60309-4:2006+A1:2012
Ex tb IIIC T80°C Db IP66
Tamb.: -50°C ≤ Ta ≤ +60°C
(*) The specific data pertaining to: temperature class, maximum surface temperature and ambient
temperature are indicated on the plate.
The models belonging to this product family are covered by the INERIS 15ATEX0017X certificates (in
compliance with Annex III of the ATEX Directive), IECEx INE 15.0033X (in compliance with the IECEx scheme)
and the quality system notification IMQ 08 ATEX 013 Q (in compliance with Annex VII of the ATEX Directive).
Notified Body for ATEX EU Type Examination certificate: INERIS, number 0080
Address: Parc Technologique Alata BP 2 F-60550 Verneuil-en-Halatte
Parre, 04-02-2022 SCAME PARRE S.p.A.
R&D Director
Giampietro Camilli, Engineer
VIA COSTA ERTA, 15 - 24020 PARRE (BG) ITALY - TEL. +39 035 705000 - FAX +39 035 703122 -
INERIS 15ATEX0017X 2022
IECEx INE 15.0033X
Ex eb IIC T5 Gb
Ex tb IIIC T80°C Db
0051
II 2GD
0051
FRANÇAIS
SOMMAIRE
1. Instructions de montage, d’utilisation et de maintenance pour un usage sur 18
2. Donnees techniques 19
3. Code d’identification 20
4. Caractéristiques techniques 20
5. Montage 21
6. Entretien et reparation 22
A MinøGL MinTYPEIP66
140,5
73
2P+-
16A
32A
63A
125A
3P+-
3P+N+-
2P+-
3P+-
3P+N+-
3P+-
3P+N+-
3P+-
3P+N+-
A
L
ØG
116
123
140,5
142,6
142,6
150
166,5
166,5
214,5
214,5
81
88
92
92
101
112
112
128
128
147,5
180,5
217,5
217,5
Schéma technique de la fiche.
Un exemple d’étiquette utilisée pour la fiche certifiée est reproduit ci-dessous.
Exemple d’étiquette de marquage ATEX / IECEx
FR
(mm)
165
174
174
274
274
MP39684ZP90905-717
Via Costa Erta, 15 - 24020 Parre (BG) Italy
219.1633
2P+T 16A
6h 200-250V 50/60Hz
WARNING
Tcable 80°C when the
maximum Ta is +60°C
OPTIMA-EX[GD]
Ex tb IIIC T80°C Db X IP66
1 Ex e IIC T5 Gb X 2022
Ta mb. -50°C to +60°C
1 Ex e IIC T6 Gb X
Ta mb. -50°C to +50°C
0051
II 2GD
Exemple d’étiquette de marquage EAC Ex
BHИМАНИЕ
Teмnepaтypa кaбeля 80°C,
Via Costa Erta, 15 - 24020 Parre (BG) Italy
219.1633.RU
2P+T 16A
6h 200-250V
VEUILLEZ LIRE AVEC ATTENTION CE DOCUMENT AVANT DE PROCÉDER AU MONTAGE
1. INSTRUCTIONS DE MONTAGE, D’UTILISATION ET DE MAINTENANCE POUR UN USAGE SÛR
1.1 NORMES DE SECURITE
OPTIMA-EX[GD] est un équipement classé dans le Groupe II et Catégorie 2 pouvant être utilisé sur une installation fixe dans des
zones présentant un risque d’explosion classées comme Zone 1/21 et Zone 2/22.
Ces instructions d’utilisation doivent être rangées en lieu sûr afin de pouvoir être consultées par la suite.
N’utilisez OPTIMA-EX[GD] que de la façon prévue, uniquement s’il est propre et en bon état et si la résistance de l’appareil
aux conditions environnantes est garantie. Il est interdit de modifier OPTIMA-EX[GD] à moins d’une indication expresse de
ce manuel d’instruction. Montez OPTIMA-EX[GD] en tenant compte des distances de dégagement et d’isolement indiquées
comme élément 5.3 (tableau).
OPTIMA-EX[GD] existe aussi en matériaux thermoset avec les courants nominaux suivants 16A, 32A, 63A, 125A.
Les fiches de la série OPTIMA-EX[GD] ne peuvent être utilisées qu’avec les prises de la série ADVANCE-GRP[GD], Ex db eb IIC /
Ex tb IIIC, avec certification séparée.
La poignée de la prise ADVANCE-GRP[GD] actionne un mécanisme d’interverrouillage afin d’éviter de séparer les contacts de la
fiche de la prise de courant lorsque les contacts sont mis sous tension. Les fiches de la série OPTIMA-EX[GD] ne peuvent être
extraites que lorsque la poignée est en position 0 (zéro).
когда максимум
Ta составляет +60°C
HAHИO ЦCBЭ
№ TC RU C-IT.AA87.B.00XXX
1.2 CONFORMITÉ AUX NORMES
La prise OPTIMA-EX[GD] est conçue pour la Zone 1/21 et la Zone 2/22 conformément à :
• EN IEC 60079-0:2018,
• EN IEC 60079-7:2015+A1:2018
• EN 60079-31:2014
• EN 60309-1:1999+A1:2007+A2:2012
• EN 60309-2:1999+A1:2007+A2:2012
• IEC 60079-0:2017,
• IEC 60079-7:2017,
• IEC 60079-31:2013
• IEC 60309-1:1999+A1:2005+A2:2012
• IEC 60309-2:1999+A1:2005+A2:2012
• ГОСТ 31610.0-2014, (IEC 60079-0:2011)
• ГОСТ Р МЭК 60079-7-2012
• ГОСТ IEC 60079-31-2010
Elles sont produites et essayées conformément à la Directive ATEX 2014/34/UE, schème IECEx, certification EAC Ex.
MP39684ZP90905-718
OPTIMA-EX[GD]
2. DONNÉES TECHNIQUES
2.1 TYPE DE PROTECTION
ATEX / IECEx :
Ex eb IIC T
Ex tb IIIC T80°C Db
IP66
Tamb.
(1)
Gb
(2)
- Tcable:
(3)
EAC Ex :
1Ex eb IIC T
(1)
Gb X
Ex tb IIIC T80°C Db X
IP66
(2)
Tamb.
- Tcable:
(1)
Classe de température des gaz conformément au tableau 1.
(2)
Plage de la température ambiante conformément au tableau 1 si elle n’est pas comprise entre -20°Cet +40°C.
(3)
Tcable: 80°C pour le type 219.16… si la temperature ambiante maximum est +60°C;
(3)
Tcable: 85°C pour le type 219.32… si la temperature ambiante maximum est +60°C;
Tcable: 90°C pour le type 219.63… si la temperature ambiante maximum est +60°C;
Tcable: 85°C pour le type 219.125…
2.2 CERTIFICATS
Certificat Atex: INERIS 15ATEX0017 X
Certificat IECEx: IECEx INE 15.0033 X
Certificat EAC Ex: НАНИО ЦСВЭ № TC RU C-IT.AA87.B.00870
2.3 PLAGE DE LA TEMPÉRATURE AMBIANTE
OPTIMA-EX[GD]
Type de fiche
219.16…
Plage température
ambiante (Ta)
CLASSE température
-50°C à +50°CT6
-50°C à +60°CT5
Température superficielle
maximum
-50°C à +60°CT4
-50°C à +50°CT4
219.32…
-50°C à +40°CT5
-40°C à +60°CT4
-40°C à +50°CT4
T80°C
-40°C à +40°CT5
-35°C à +60°CT3
219.63…
-35°C à +50°CT3
-35°C à +40°CT4
219.125…-35°C à +40°CT4
tableau 1
La plage de la température ambiante peut être limitée par la température ambiante de la prise de la série
OPTIMA-EX[GD] utilisée.
2.4 ETIQUETTE D’AVERTISSEMENT
AVERTISSEMENT:
n’ouvrez pas si l’atmosphère est explosive
FR
MP39684ZP90905-719
OPTIMA-EX[GD]
3. CODE D’IDENTIFICATION
Types des numéros de pièce disponibles du OPTIMA-EX[GD].
(*) AVERTISSEMENT:
L’entrée de câble peut atteindre une température élevée – Utilisez un câble adéquat.
5. MONTAGE
Le montage ne doit être confié qu’à du personnel dûment formé conformément au code de pratique applicable
(IEC-EN 60079-14) et aux prescriptions des règlements nationaux en vigueur sur la sécurité et la prévention
des accidents et de manuel d’instruction.
5.1 INSTRUCTIONS DE SÉCURITÉ
N’utilisez la fiche que pour l’usage prévu. Toute utilisation incorrecte ou non autorisée ou non conforme à ces instructions annule
la garantie. Il est interdit de modifier la protection contre l’explosion de la fiche. Ne fixez et n’utilisez l’interrupteur que s’il est
propre et en parfait état.
5.2 ACCESSOIRES
• Coquille de protection
N’utilisez que des accessoires d’origine homologués SCAME.
5.3 DISTANCES DE DÉGAGEMENT ET D’ISOLATION
Tout le câblage doit être réalisé conformément au code de pratique et aux normes de montage dans les zones dangereuses tels que
IEC EN 60079-14. Utilisez un outil ayant la bonne dimension et le couple correct (cf. la documentation du fabricant) pour serrer les
bornes (tournevis ou clé). Les distances de dégagement et d’isolation doivent être conformes à EN IEC 60079-7:2015+A1:2018 /
ГОСТ Р МЭК 60079-7-2012 (tableau 1) les paramètres électriques ne doivent pas dépasser la valeur maximum admise.
Remarque: Les distances minimum de dégagement et d’isolation à maintenir sur les parties conductrices et les autres parties
sous tension sont :
Isolation minimumDégagement minimum
250 V
400 V
500 V
630 V
Remarque: Les tensions sont des tensions nominales à la tension de travail peut dépasser de 10% le niveau de tension indiqué.
5 mm
8 mm
10 mm
12 mm
250 V
400 V
500 V
630 V
5 mm
6 mm
8 mm
10 mm
FR
OPTIMA-EX[GD]doit subir un essai de résistance diélectrique régulier à 1000 V + 2U rms ou 1500 V rms, selon
le courant le plus élevé appliqué pendant 60 s conformément à la clause 6.1 de EN IEC 60079-7:2015+A1:2018
/ ГОСТ Р МЭК 60079-7-2012. Un essai peut aussi être accompli à 1,2 fois la tension d’essai, mais elle doit alors être
maintenue pendant 100 ms.
MP39684ZP90905-721
OPTIMA-EX[GD]
6. ENTRETIEN ET RÉPARATION
Le montage, l’inspection et l’entretien de cet appareil ne doivent être confiés qu’à du personnel dûment formé
conformément au code de pratique applicable (par ex. IEC/EN 60079-14, IEC/EN 60079-17). Cet appareil ne
doit être réparé que par du personnel dûment formé conformément au code de pratique. Pendant l’entretien, il est
essentiel de vérifier les composants dont la protection dépend.
6.1 ENTRETIEN ORDINAIRE
L’entretien ordinaire est nécessaire pour garantir le bon fonctionnement du boîtier et pour maintenir le niveau de protection prescrit.
1) Vérifiez si la bague d’étanchéité est en place et pas endommagée…chaque fois que le boîtier est ouvert
2) Vérifiez si toutes les vis de fixation sont en place et bien fixées…chaque fois que le boîtier est ouvert
3) Vérifiez si les vis de montage sont serrées et dépourvues de corrosion…tous les ans
4) Vérifiez si le corps n’est pas endommagé…tous les ans
5) Dans les endroits où de trouvent des poussières de combustible vous devez nettoyer régulièrement la surface supérieure du
boîtier, en limitant l’épaisseur de la couche à 5 mm.
Conditions de stockage
Température de stockage: de -50°C à +70°C pour 16A/32A
Température de stockage: de -35°C à +70°C pour 63A/125A
Humidité relative: ≤95%RH
La durée de vie du produit est d’environ 25 ans si les conditions d’entretien et de stockage sont respectées et si toutes les
prescriptions citées dans ces instructions sont respectées.
6.2 RÉSISTANCE AUX AGENTS CHIMIQUES
Considérez l’environnement dans lequel ces boîtiers doivent être utilisés pour établir si les matériaux sont en mesure de supporter
les agents corrosifs susceptibles de s’y trouver.
6.3 ELIMINATION
Le produit doit être éliminé et recyclé conformément aux règlements nationaux en vigueur sur l’élimination et le recyclage des
déchets.
MP39684ZP90905-722
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.