S&C 2000, 2040 Installation Manual

Page 1
S&C Series 2000 Circuit-Switchers
Outdoor Transmission (68 kV and 230 kV)
Model 2040 — With Horizontal Interrupters and Without Disconnect
Installation
Table of Contents
Section Page Section Page
Introduction
Qualified Persons ..............................2
Read this Instruction Sheet ......................2
Retain this Instruction Sheet .....................2
Proper Application .............................2
Usual Operating Conditions ......................2
Special Warranty Provisions .....................3
Warranty ....................................3
Safety Information
Understanding Safety-Alert Messages .............4
Following Safety Instructions ....................4
Replacement Instructions and Labels ..............4
Location of Safety and Instruction Labels and Tags ...5
Safety Precautions ............................7
Inspection ....................................8
Packing ......................................8
Storage ......................................9
Installation
Before Starting ...............................11
Installing the Mounting Pedestals
and High-Speed Base .......................12
Installing the Switch Operator ...................14
Installing the Pole-Units ........................15
Connecting the Pole-Units
to the High-Speed Power Train ................17
Connecting the Operator
to the High-Speed Power Train ................18
Connecting Conductors ........................19
Removing the Interrupter Containers ..............19
Setting up the Operator and Checkout ............20
Operation
Understanding Trip-Free Operation ...............26
Electrical Operation ...........................26
Manual Operation .............................27
Understanding the Gas-Pressure
Indicator and Safety Relief Device .............28
Understanding the Optical Remote
Gas-Density Monitor ........................28
Inspection Recommendations ...................28
April 23, 2018
© S&C Electric Company 2002-2018, all rights reserved
Instruction Sheet 716-502
Page 2
Introduction
Qualified Persons
Read this Instruction Sheet
Retain this Instruction Sheet
Proper Application
WARNING
The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of substation and overhead electric power transmission and distribution equipment along with the associated hazards. A qualified person is someone who is trained and competent in:
• The skills and techniques necessary to distinguish exposed live parts from nonlive parts of electrical equipment
• The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed
• The proper use of the special precautionary techniques, per sonal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment
These instructions are intended ON LY for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment.
NOTICE
Thoroughly and carefully read this instruction sheet and all materials included in the product's S&C Instruction Handbook before installing or operating your S&C Series 2000 Circuit-Switcher, Model 2040. Familiarize yourself with Safety Information and Safety Precautions on pages 4 through 7.
This instruction sheet is a permanent part of your S&C Series 2000 Circuit-Switcher, Model2040. These instructions should be stored in the Series 2000 Switch Operator using the instruction manual holder. The latest version is available online in PDF format at sandc.com/en/support /product-literature.
WARNING
The equipment in this publication must be selected for a specific application. The application must be within the ratings furnished for the equipment. The ratings for this Circuit-Switcher are listed on the nameplate on the front of the switch operator. Additional application information can be found in Specification Bulletin 716-31.
Usual Operating Conditions
2 S&C Instruction Sheet 716- 502
Series 2000 Circuit-Switchers will perform as intended at temperatures within the range of –40°C (-40°F) to +40°C (104°F) (–35°C (-31°F) to +40°C (104°F) for 161-kV and 230-kV models), at altitudes of up to 5000 feet (1524m), and at wind loadings of up to 90 miles per hour (145kmph). Fur ther, Series 2000 Circuit-Switchers, when installed with the recommended S&C anchor bolts and with exible-conductor connections at all six terminal pads, are capable of withstanding seismic loading of 0.2g ground acceleration in any direction as well as per forming as intended during such loading and afterward. For applications at temperatures not within the specied range, at higher altitudes, at higher wind loadings, or where higher seismic withstand capabilities are required, refer to the nearest S&C Sales Ofce.
Page 3
Introduction
Special Warranty Provisions
Warranty Qualifications
The standard warranty contained in the seller’s standard conditions of sale, as set forth in Price Sheet 150, applies to S&C Series 2000 Circuit-Switchers and associated options, except that the rst paragraph of said warranty is replaced by the following:
(1) G ene r a l : The seller warrants to the purchaser for a period of five years from the date of shipment that the equipment delivered will be of the kind and quality specified in the contract description and will be free of defects of workmanship and material. Should any failure to conform to this warranty appear under proper and normal use within five years after the date of ship ment the seller agrees, upon prompt notification thereof and confirma­tion that the equipment has been stored, installed, operated, inspected, and main tained in accordance with recommendations of the seller and standard industr y practice, to correct the nonconformity either by repairing any damaged or defective parts of the equipment or (at seller’s option) by shipment of necessary replacement parts.
Replacement parts provided by the seller under the warranty for the original equipment will be covered by the original-equipment warranty for its duration. Replacement parts purchased separately will be cov ered by the warranty contained in the seller’s standard conditions of sale, as set forth in Price Sheet 150.
Warranty of Series 2000 Circuit-Switchers is contingent upon both of the following:
• Installation and adjustment of Series 2000 Circuit-Switchers in accordance with S&C’s
applicable instruction sheets
• Conformance with the inspection recommendations defined in S&C Instruction Sheet
716-590
S&C Instruction Sheet 716-502 3
Page 4
Safety InformationSafety Information
Understanding Safety-Alert Messages
Following Safety Instructions
Several types of sa fety-alert messages may appear th roughout this ins truction sheet as well as on labels and tags attached to the S&C Series 2000 Circuit-Switcher, Model 2040. Familiarize yourself with these types of messages and the importance of these signal words:
DANGER
“DANGER” identifies the most serious and immediate hazards that will likely result in serious personal injury or death if instructions, including recommended precautions, are not followed.
WARNING
“WARNING” identifies hazards or unsafe practices that can result in serious personal injury or death if instructions, including recommended precautions, are not followed.
CAUTION
“CAUTION” identifies hazards or unsafe practices that can result in minor personal injury if instructions, including recommended precautions, are not followed.
NOTICE
“NOTICE” identifies important procedures or requirements that can result in product or property damage if instructions are not followed.
If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor. Their tele­phone numbers are listed on S&C’s website sandc.com, or call the S&C Global Monitoring and Suppor t Center at 1-888-762-1100.
Replacement Instructions and Labels
NOTICE
Thoroughly and carefully read this instruction sheet before installing or operat ing your S&C Series 2000 Circuit­Switcher, Model 2040.
If you need additional copies of this instruction sheet, contact your nearest S&C Sales Ofce, S&C Authorized Distributor, S&C Head quarters, or S&C Electric Canada Ltd.
It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distrib utor, S&C Headquarters, or S&C Electric Canada Ltd.
4 S&C Instruction Sheet 716- 502
Page 5
Location of Safety and Instruction Labels and Tags
A
Safety Information
H
P
N
G
F
B
C
M
J
K
L
E
D
Q
S&C Instruction Sheet 716-502 5
Page 6
Safety Information
Reorder Information for Safety Labels
Location Safety Alert Message Description Number
A
B
C
D
E
F
G
H
K
WARNING
WARNING
CAUTION
CAUTION
CAUTION
Instruction
CAUTION
Instruction
J
CAUTION
Instruction
Do not remove steel outer wrapper...
Do not remove steel over wrapper until installation is complete...
This shield must be removed during installation...
161 kV
Lifting instructions…
230 kV
Connect the insulated operating rod…
Connecting-Pin Installation… G-5952
Transition box contains a stop bracket and spacer…
Instructions for attaching operator connecting link…
48 Vdc G-5948-1
Control Voltage
Instructions for Fuse Slugs
125 Vdc G-5948-2
115 V 60 Hz G-5948-3
G-5993
G-5699
G-6043
G-5995
G-5994
G-5950
G-5807
G-5792
G-5939
L
M
N
P
Q
This is a tag that is to be removed and discarded after the switch is installed and adjusted.
This label contains important instructions and should be promptly replaced if illegible or missing.
This label is affixed to the shipping package and will be removed and discarded after the switch is installed and adjusted.
CAUTION
CAUTION
CAUTION
Instruction
CAUTION
Do not apply control voltage to this device or insert…
Do not apply control voltage to this device or manually...
Do not attempt to close the circuit-switcher using manual trip lever
Instructions — Operation, Gas-Pressure Indicator
Connect the interphase drive lever to the operator uni-ball coupling with the attached pin.
G-5959
G-5945
G-6222
G-5672
G-5949
6 S&C Instruction Sheet 716- 502
Page 7
Safety Precautions
Safety Precautions
DANGER
Series 2000 Circuit-Switchers operate at high voltage. Failure to observe the precautions below will result in serious personal injury or death.
Some of these precautions may differ from company operating procedures and rules. Where a discrepancy exists, users should follow their company’s operating procedures and rules.
QUALIFIED PERSONS. Access to substation switching equipment must be restricted only to qualified persons. See “Qualified Persons” on page2.
SAFETY PROCEDURES. Always follow safe operating procedures and rules.
PERSONAL PROTECTIVE EQUIPMENT. Always use suitable protective equipment such as rubber gloves, rubber mats, hard hats, safety glasses, fall protection, and flash clothing in accordance with safe operating procedures and rules.
SAFETY LABELS AND TAGS. Do not remove or obscure any of the “DANGER,” “WARNING,” “CAUTION,” or “NOTICE” labels and tags. Remove tags ONLY if instructed to do so.
ENERGIZED COMPONENTS. Always consider all parts live until de-energized, tested, and grounded.
CIRCUIT-SWITCHER POSITION. Always confirm the circuit-switcher Open/Close position by visually observing the position of the switch position indicator located on the high-speed base. Switches may be energized from either side.
MAINTAINING PROPER CLEARANCE. Always maintain proper clearance from energized components.
OP E R AT ION. Circuit making and breaking is involved in the normal operation of this interrupter switch. To operate, follow the operating procedure as outlined in this instruction sheet starting on page 26.
S&C Instruction Sheet 716-502 7
Page 8
Shipping and Handling
Inspection
Packing
Examine the shipment for damage as soon after receipt as possible, preferably before removal from the carrier’s conveyance. Check the bill of lading to make sure all shipping skids, crates, and containers listed are present.
If there is visible loss and/or damage:
1. Notify the delivering carrier immediately.
2. Ask for a carrier inspection.
3. Note condition of shipment on all copies of the delivery receipt.
4. File a claim with the carrier.
If concealed damage is discovered:
1. Notify the delivering carrier within 15 days of receipt of shipment.
2. Ask for a carrier inspection.
3. File a claim with the carrier.
Notify S&C Electric Company in all instances of loss and damage.
An S&C catalog drawing will be found in a water-resistant envelope attached to the wrapper around one of the insulating support columns. Study this drawing carefully and check the bill of materials to verify all parts are at hand. The Model 2040 Series 2000 Circuit-Switcher shipment should include the following items, as shown in Figures 1 and 2 on pages 10 and 11.
CAUTION
DO NOT mix components from different installations.
The Series 2000 Circuit-Switcher is completely factory-assembled and thoroughly tested. To speed installation and maintain the proper adjustment of the circuit-switcher
and switch operator that was made in the factory, components belonging to a specific circuit-switcher installation must not be intermixed with components belonging to a different installation. Each Series 2000 Circuit-Switcher is serially numbered. This serial number appears on the circuit-switcher high-speed base, pole units, mounting pedestals, and the operator.
Mixing parts from different circuit-switchers will result in significant damage to the switch operator and mis-operation of the circuit-switcher.
S&C mainta ins a historical record—by serial number—of every circuit-switcher produced. This record lists information pertinent to each installation, such as application, date of shipment, and any service performed by S&C factory ser vice specialists. This record is an invaluable reference for future maintenance, modifications, or replacements.
8 S&C Instruction Sheet 716- 502
Page 9
Shipping and Handling
The shipment contains:
• Three pole-units each consisting of an interrupter, an insulating support column, a support insulator, and a base – all factory-assembled and adjusted
• A single high-speed base, enclosing the high-speed power train which drives the inter­rupters
• The appropriate number of mounting pedestals complete with support arms and channels:
— Single-pedestal: 69 kV (with 48-inch (1219-mm)phase spacing)
— Two-pedestals: 69 kV (with 84-inch (2134-mm) phase spacing); 115 kV and 138 kV and
can be specied on 161 kV
— Three-pedestals: Can be specied on 161 kV, and standard on 230 kV.
• A Series 2000 Circuit-Switcher switch operator
• A container of operating-mecha nism components a nd hardware —all individually identied
• Any optional features or accessories specied, such as a grounding switch
DANGER
DO NOT disassemble or modify the interrupters. The interrupters are pressurized at 75PSIG. Serious personal injury can result.
Storage
CAUTION
Connect control power to the switch operator when storing it outdoors. The switch operator is equipped with a space heater that must be energized during storage to prevent condensation and corrosion within the operator enclosure. Alternatively, store the operator in a climate controlled area.
If the Series 2000 Circuit-Switcher must be stored before installation, keep it in a clean, dry, corrosion-free area to protect it from damage. Make sure each skid rests rmly on the ground and is reasonably level. Shoring under the skids may be necessary if the ground is uneven. If storing outdoors or in a non-climate-controlled area, connect control power to the space heater inside the Series 2000 Switch Operator per the wiring diagram. Inspect the circuit­switcher regularly when storing for prolonged periods.
NOTICE
Please complete and mail the circuit-switcher registration card (enclosed in a vinyl envelope located inside the operator) after the circuit-switcher has been installed. The information requested on this card is vital to ensure prompt notification in the event field modifications are needed.
S&C Instruction Sheet 716-502 9
Page 10
Support brace
Operator support plate
Pressure-relief
device and low-
gas-pressure
Installation
Insulating support column
Single-gap SF6 puffer-type Interrupter
Transition Box
Pressure-relief device and low­gas-pressure indicator (not visble)
Support brace
Switch- position indicator
Figure 1. Model 2040 Series 2000 Circuit-Switcher rated 138 kV.
Pole-unit base
High-speed interrupter power train enclosed in
steel-sheathed box-type high-speed base
Operator support plate
10 S&C Instruction Sheet 716-502
Page 11
Before Starting
CAUTION
Do not remove the containers from the interrupters or the plastic bubble-wrap from the insulating support columns until the installation is complete.
NOTICE
Bolted and Pinned Connections: A typical bolted connection requires a flat washer underneath the cap screw and one under the nut. When self-locking hex nuts are specified, it is essential that the threads of the associated cap screw are lubricated with a general­purpose grease to facilitate tightening. All pins and cotter pins used in field assembly should also be lubricated to facilitate insertion.
STEP 1. Cut the ste el straps t hat bind the mount ing pedest als
to the high-speed base. Cut the straps binding the container of operating mechanism components and hardware and the straps binding the pole-units. Remove any wood bracing between the terminal pads. See Figure 2.
For circuit-switchers rated 161 kV and 230 kV:
Remove and discard the lifting angles attached to the pole-unit bases.
Installation
Pole-unit
CAUTION
The foundations and anchor bolts for S&C Mounting Pedestals must be designed to meet the loading limits specified in S&C Data Bulletin 716-61. Failure to meet
these loading limits can result in equipment damage.
Support arms
Miscellaneous hardware
High-speed base
Figure 2. Typical shipment of Model 2040 Series 2000 Circuit-Switcher. Operator is shipped on a separate skid.
Mounting pedestal
S&C Instruction Sheet 716-502 11
Page 12
Two nuts and
two flat washers
provide leveling
means
Grounding pad
Installation
Installing the Mounting Pedestals and High­Speed Base
STEP 2. Install each pedestal as follows:
(a) Install the lower set of anchor bolt nuts and  at
washers onto the pre-installed anchor bolts. Level all anchor bolts the same height, leaving space below and above for leveling. See Figure 3.
(b) Install the temporary eyebolts into the holes
provided a t the top of the mount ing pedes tal. At tach lifting slings to the eyebolts. See Figure 4.
(c) Lift the pedestal over the anchor bolts. Before
lowering , make sur e the grou nding pa d is posit ioned properly for the installation. See Figure 4. Refer to the accompanying catalog drawing for details.
(d) Lower the pedestal onto the anchor bolt nuts and
 at washer s. Loosely secu re a  at w asher and nut to each anchor bolt above the pedestal base. See Figure 3. Remove the lifting slings and eyebolts.
(e) Adjust the lower set of anchor-bolt nuts to plumb
and level the pedestal. The upper set of anchor bolt nuts should remain loosely attached. See Figure 3.
STEP 3. Atta ch the support a rms to the mou nting pedes tals,
as shown on the catalog drawing, using the -11 × 1-¼ -inch hex-head galvanized steel cap screws and  at washers furnished. See Figure 1 on page 10. Lubricate the nut s to facilit ate tighten ing. Securely tighten the cap screws. Also install the covers on top of the mounting pedestals, as shown on the catalog drawing, using the ½ -13 × 2-inch hex-head galvanized steel cap screws,  at washers, and self­locking hex nuts furnished. Lubricate the cap screws to facilitate tightening. Securely tighten the cap screws.
STEP 4. Attach four suitable lifting slings to the high-speed
base. S ee Figu re 5 on page 13. Unbolt the hig h-speed base from the shipping skid and lift the base on top of the support arms, as shown on the catalog drawing. Verify the switch-position indicator on the base is visible on the desired side. This is also the side on which the operator door will open.
Two nuts and
Pedestal
Anchor bolts
Concrete pad
Figure 3. Pedestal anchor-bolt mounting detail.
Eye bolts
two flat washers
provide leveling means
12 S&C Instruction Sheet 716-502
Grounding pad
Figure 4. Lift the pedestal into position.
Page 13
CAUTION
Eye bolts
The operator directly drives the interrupters open and closed through a simple high-speed power train leading from the top of the operator, through a horizontal interphase linkage enclosed in a steel-sheathed box-type base, and to the reciprocating-action insulated operating rods that pass through the center of the insulating support columns. Permanently lubricated bearings are used throughout the power train. The high-speed base has been fully pre-assembled and adjusted at the factory.
DO NOT disassemble the high-speed base or high­speed power train. Damage to the high-speed base and
personal injury may result.
STEP 5. Loosely bolt the high-speed base to the support
arms using the ½ -13 × 2-inch hex-head galvanized steel cap screws,  at washers, and self-locking hex nuts furnished. Lubricate the bolts to facilitate tightening. Use a level to verify the high-speed base is horizontal, both lengthwise and sideways. Ad just the lower set of anchor-bolt nuts at the pedestals to achieve level. Refer to the catalog drawing for details. See Figure 3 on page 12 for anchor-bolt nut detail.
STEP 6. Attach the support brace to the support arms, using
the ½ -13 × 2-inch hex-head galvanized steel cap screws,  at washers, and self-locking hex-nuts furnished. See Figure 1 on page 10 and the catalog drawing. Lubricate the hardware to facilitate tightening.
STEP 7. Check the lower set of anchor-bolt nuts at each
mounting pedestal to verify all nuts are in contact with t he bottom of the pede stal. Se e Figure 3 on p age
12. Hand-tighten the lower anchor-bolt nuts as necessary. Then, securely tighten the upper set of anchor-bolt nuts at each mounting pedestal.
Installation
Protective cover at pole-unit mounting position. See Step 12.
Eye bolts
Figure 5. Hoist the high-speed base using a crane.
S&C Instruction Sheet 716-502 13
Page 14
Installation
Installing the Switch Operator
STEP 8. Loosen the ½ -13 × 1-¼ -inch galvanized steel cap
screws,  at washers, and nuts attaching the bottom plates to the underside of the high-speed base. Remove the plates and place them and their hardware aside on a clean surface. See Figure 6.
Remove the ¾ -inch stainless steel pin and cotter pin from the inter phase drive lever enclosed in the high-speed base. See Figure 7. Retain the pin and cotter pin for re-use in Step 14 on page 18.
CAUTION
Do not attempt to set the operator upright by slinging to the skid. The skid is not
designed to carry the weight of the switch operator. Damage to the operator and minor personal injury may result.
STEP 9. Wrap a lifting sling around the stored-energy
housing of the operator, as shown in Figure 8 (left).
Now carefully raise the operator to the upright position so that it rests on its base skid, as shown in Figure 8 (right).
Bottom plate
Figure 6. Remove bottom plates from high-speed base.
Pin and cotter pin
CAUTION
DO NOT remove the lifting sling around the stored-energy housing after raising the operator. The operator is top-heavy and must be adequately supported until it is attached to the high-speed base. Damage to the operator may result.
Remove the skid and bracing that runs the length of the operator, the stored-energy housing, and the operator support tube. See Figure 8. Also remove the protective cover and packing on top of the operator support tube as well as the packing on the operator enclosure louvers. See Figure 8, and Figure 9 on page 15.
STEP 10. Lift and install the operator as follows:
CAUTION
Be careful not to damage the uni-ball coupling on the operator connecting link during hoisting and attachment of the operator. The uni­ball coupling cannot be replaced in the field. Damage will necessitate returning the operator for replacement.
Figure 7. Remove the ¾-inch stainless-steel pin and cotter pin from the interphase drive lever inside the high-speed base.
Packing
Stored-energy housing
(a) Reposition the lifting sling around the front of the
stored-energy housing and wrap another lifting sling around the back of the stored-energy housing, as shown in Figure 9 on page 15. Make sure the operator door faces the same way as the switch­position indicator on the high-speed base.
14 S&C Instruction Sheet 716-502
Figure 8. (Left and Right) Typical shipment of Series 2000 Opera­tor. Wrap lifting slings around stored-energy housing to raise the operator to the upright position.
Page 15
(b) Carefully hoist the operator into place. Be careful
½
13
Operator
tube
Stored-energy
coupling
coupling
Operator
support
Operator
coupling
not to damage the uni-ball coupling on the operator connecting link during hoisting and installation of the operator to the high-speed base.
(c) Attach the operator support tube mounting plate to
the underside of the high-speed base using four ½ -13 × 1-¼ hex-head galvanized-steel cap screws,  at washers, and self-locking hex nuts. Lubricate the bolts to facilitate tightening. Tighten all four screws securely.
STEP 11.
Attach the operator-support angle to the mounting pedestal using the -11 × 1¼-inch hex-head galvanized steel cap screws, four  at washers, and two self-locking hex nuts. Refer to the catalog drawing for exact placement.
Attach the operator-support plate to the angle on the side of the operator enclosure and to the operator support angle on the mounting ped­estal using the four ½ -13
× 1-¼ -inch hex-head
galvanized-steel cap screws, flat washers, and self­locking hex nuts furnished. Lubricate the bolts to facilitate tightening. Securely tighten the screws. See Figure 1 on page 10 and Figure 9.
On circuit-switchers with two or three mount­ing pedestals, insert the hole-plugs furnished into all unused holes in the pedestal.
Holes for ½ 132 ¾-inch hex-head galvanized steel cap screws, flat washers, and self-locking nuts
Operator support tube
Installation
Uni-ball coupling
Operator support tube mounting plate
Stored-energy housing
Operator support angles
Uni-ball coupling
Installing the Pole-Units
NOTICE
The pole-units are numbered “Pole 1,” “Pole 2,” and “Pole 3.” Make sure to install the pole-units in the order marked on the catalog drawing. Please note that the pole numbers do not have to correspond with your system’s phase designations.
NOTICE
Do not disassemble the insulating support columns. The insulating support columns are filled with lubricated dielectric filler which prevents contamination from affecting the dielectric integrity of the column or the insulated operating rod. An aerator is used at the upper end of each support column to eliminate water from being pumped in due to pressure differentials caused by temperature cycling. Disassembling the insulating
support column will cause the lubricated filler to evacuate.
CAUTION
Lift the pole-unit by the pole-unit base only. Do not
attempt to lift the pole-unit by the interrupter or other live parts. Lifting the pole-unit by any other means can cause damage to the pole-unit or personal injury.
Figure 9. Hoist operator into position below the high-speed base using a lifting crane.
S&C Instruction Sheet 716-502 15
Page 16
(shipping bracket removed in photo)
channel base
Installation
STEP 12. Lift and install the pole-units as follows:
(a) Install four eyebolts on each pole-unit base.
See Figure 10.
(b) Attach four suitable lifting slings to the eyebolts on
the pole-unit to be mounted at the center of the high­speed base—marked “Pole 2”— as shown in Figure 10.
(c) Make certain the rigging does not stress the pole-
unit. Unbolt the base from the skid. Raise the pole­unit a few feet, then remove the two ½-13 × 1¾ -inch hex-head galvanized steel cap screws,  at washers, and hex nuts that attach the shipping bracket to the bottom of the pole-unit base. The shipping bracket protects the insulated operating rod. Discard the shipping bracket and associated hardware. See Figure 10.
Figure 10. Hoisting the pole-unit.
16 S&C Instruction Sheet 716-502
Eyebolts (not furnished)
Insulated operating rod (shipping bracket removed in photo)
Pole-unit channel base
Page 17
CAUTION
Operating rod link
Spacer
½
The insulated operating rod is under pressure. Removal of the shipping bracket may result in the operating rod quickly moving down approximately
-inch (9.5 mm). Keep hands clear of the operating rod when removing the shipping bracket.
(d) Remove the ½ –inch silicon-bronze pin and cotter
pin from the insulated operating rod. Retain these pins for re-use in Step 13(d).
(e) Remove the prote ctive cover on the h igh-spe ed base
at the pole-unit mounting position. See Figure 5 on page 13. Ra ise the pole-u nit to its mount ing position at the cent er of the high- speed base , as shown on the catalog drawing. Carefully guide the pole-unit to avoid damaging the insulated operating rod.
(f) Attach the pole-unit base to the high-speed base,
usin g the ½ -13 × 1-¾ -inch hex-head ga lvani zed-ste el cap screws,  at washers, and self-locking hex nuts furnished. Lubricate the cap screws to facilitate tightening. Securely tighten all cap screws.
(g) Attach the pole-unit base to the support brace,
usin g the ½ -13 × 1-¾ -i nch hex-head galva nized- steel cap screws,  at washers, and self-locking hex nuts furnished. Lubricate the cap screws to facilitate tightening. Securely tighten all cap screws.
(h) Install shims as necessary between the pole-unit
base and the support brace to compensate for any irregularities between the mating surfaces.
Repeat for the pole-units—marked “Pole 1” and “Pole 3.”
Connecting the Pole-Units to the High-Speed Power Train
STEP 13. Prepare the insulated operating rod of each pole-
unit for attachment to the inter phase drive in the high-speed base as follows:
(a) Remove the six 5/16 -18 × ¾ -inch hex-head stainless
steel cap screws used to attach the access cover to the side of the t ransit ion box. See F igure 11. Remove the cover and place it and the hardware on a clean surface.
(b) Check that the transition lever is in the open
position. The lever should be turned fully counterclockwise. See Figures 11 and 12. If the lever is not in the Open position, carefully turn the transition lever to the Open position.
If the transition lever cannot be freely rotated to its fully counterclockwise position, misa lignment of the interphase drive is occurring in the high-speed base. Swing the insulated operating rod end links up, away from the interphase drive linkage lever, and tr y rotating the transition lever to its fully counterclockwise position.
5/16 —18 ¾ hex-head stainless-steel cap screws for access cover (removed)
Transition lever
Transition Box
Operating rod link
Transition lever in shipping position
Figure 11. Transition lever in shipping position
Stop bracket (marked with a black/
yellow striped label)
stainless-steel connecting pin
Connecting pin retainer
5/16 18 x 2 ¼ hex-head stainless-steel screw
Transition lever in shipping position
Figure 12. Transition lever in open position
Interphase drive linkage lever
Insulated operating rod end links
½ -inch silicon­bronze pin and cotter pin
Installation
Spacer (marked with a black/yellow striped label)
Figure 13. Attach insulated operating rod to interphase drive.
S&C Instruction Sheet 716-502 17
Page 18
Installation
¾ -inch stainless steel pin and cotter pin
CAUTION
Keep fingers clear of the transition lever’s travel.
The transition lever is under pressure and could quickly rotate counterclockwise. Injury to the fingers could result.
(c) Remove the -inch stainless steel connecting pin
used to attach the transition lever to the operating rod link. See Figure 12 on page 17. The pin is locked in place by a retainer. Lift and turn the retainer to remove the pin. Keep the pin for re-use in Step 13(e)
(d) Attach the insulated operating rod end links to the
interphase drive linkage lever in the high-speed base using the ½-inch silicon-bronze pin and cotter pin retained from Step 12(d). See Figure 13 on page
17. The insulated operating rod may be moved up or down, as required, to make the connection.
(e) Replace the -inch stainless-steel connecting pin
retained from Step 13(c). See Figure 12. It will be necessary to loosen the 5/16 -18 × 2-¼ -inch hex-head stainless-steel screw, holding the spacer in place, and withdraw it approximately -inch, so the connecting pin can be inserted. Do not remove the screw at this time.
(f) After the connecti ng pin has been i nserted, lock it in
place with its retainer.
(g) Remove and discard the 5/16 -18 x 2-¼ -inch hex-head
stainless-steel screw, spacer and stop bracket (marked with a black/yellow str iped label) shown in Figure 12 on page 17.
Connecting the Operator to the High-Speed Power Train
STEP 14. Attach the uni-ball coupling on the operator
connecting link to the interphase drive lever in the high-speed base using the ¾ -inch stainless steel pin and cotter pin retained from Step 8. See Figure 14. An ad justable locking rod (marked with a black/ yellow str iped label) is fu rnished fa ctory-connect ed to the interphase drive lever. Turn the associated ¼ -20 locknuts as required to raise or lower the interphase drive lever enough to facilitate insertion of the stainless steel pin.
STEP 15. After the pin is installed, remove the lower ¼ -20
locknut that retains the ad justable locking rod, and then remove and discard the adjustable locking rod and locknuts. See Figure 14.
Adjustable locking rod (marked with a black / yellow striped label)
¼ -inch–20 locknut
Figure 14. Attach the Uni-ball coupling to the interphase drive lever.
Interphase drive lever
Uni-ball coupling
¾ -inch stainless steel pin and cotter pin
18 S&C Instruction Sheet 716-502
Page 19
Connecting Conductors
STEP 16.
DANGER
Conductors must be de-energized and grounded in accordance with standard system operating practice. Failure to do so can result
in serious injury or death.
Attach the high-voltage conductors to their respective circuit­switcher terminal pads using  exible-conductor connections. Observe the terminal-pad loading limits speci ed on the catalog drawing. Use the following procedure for attaching the conductors:
(a) Thoroughly wire-brush the current-transfer
surfaces of each connector and immediately apply a liberal coating of Penetrox® A (available from Burndy Corporation) or other suitable aluminum connector compound to the brushed surfaces.
(b) Wire-br ush each ter minal pa d and apply a coating of
Penetrox A. T hen, bolt the con nector s to the ter min al pads.
(c) Prepare the conductors using established
procedures and clamp them in their respective connectors.
Installation
Shield
Figure 15. Remove the shield for the pressure-relief device.
Removing the Interrupter Containers
STEP 17. Remove the container from each interrupter as
follows:
(a) Remove and discard the -16 zinc-plated serrated
hex nuts that run the length of the container.
(b) Remove and discard the -16 × -inch and two
-16 × 1-inch zinc-plated hex-head cap screws and  at washers that attach the upper container half to the coupling end casting of the interrupter. Also, remove and discard the -16 × -inch and two -16 × 1-inch zinc-plated hex-head cap screws and  at washers that attach the upper container half to the indicator-end casting of the interrupter.
(c) Pr y the container halves apart with a  at-head
screwdriver or other sturdy pry tool. The upper container half can now be removed and discarded. Slotted holes are provided so a rope or lifting sling can be attached and the container half more safely lowered to the ground.
(d) Remove and discard the -16 × -inch hex-head
cap screw and  at washer that attach the lower container half to the coupling-end casting of the interrupter, and the -16 × -inch hex-head cap screw a nd  a t washer th at atta ch the lower contai ner half to the indicator-end casting of the interrupter. Then, discard this container half.
(e) Remove and discard the foam-core inner liner
wrapped around the interrupter.
(f) Finally, remove the shield for the pressure-relief
device. See Figure 15.
STEP 18. Remove and discard the wrappers from each
insulating support column.
S&C Instruction Sheet 716-502 19
Page 20
Installation
operation counter
Control-source
circuit fuse holder
Setting up the Operator and Checkout
STEP 19.
CAUTION
Unauthorized changes should not be made in the wiring of the operator. Should a control­circuit revision appear desirable, it should be made only on the authority of a revised wiring diagram that has been approved by both the user and S&C Electric Company.
Do not apply control voltage to the operator at this time!
Perform the following set-up procedure on the
operator. (See Figures 16 through 18.)
(a) To avoid accidentally energizing the operator after
the external connections have been completed, open the control power KNIFE switch, and then swing the KNIFE switch retainer ar m out of the way
by putti ng pressur e on the red insu lated ret ainer and the black nylon retainer nut. The KNIFE switch retainer arm will “pop up” and can then be swung out of the way. See Figure 17 on page 22.
(b) Mark the conduit-entrance location for the control-
circuit wiring on the conduit-entrance plate in the bottom of the operator enclosure. See Figure 16. Remove the pla te and cut out the nece ssar y opening. Apply sealant and replace the plate. Make up and connect the entrance  ttings, and verify the  ttings are properly sealed to prevent water ingress.
NOTICE
Make sure the polarity of the control circuit is correct on dc-control voltage models. Energizing the switch operator with polarity reversed will cause damage to the operator control circuit and will require repair or replacement of the operator.
Instruction Manual holder
Spare fuses
Manual trip lever
Trip and Close pushbuttons
Position indicating lamps (catalog number supply suffix "-M"
Non-reset electric operation counter
"Charged" and "Discharged" indicators for stored–energy mechanism
Control-source knife switch
Motor-and-closing circuit fuse holder
Figure 16. Interior of the switch operator.
20 S&C Instruction Sheet 716-502
Conduct-entrance plate
Page 21
(c) Connect the external control-circuit wiring
(including the space-heater source leads) to the terminal blocks at the bottom of the enclosure. Refer to the wiring diagram. Observe correct polarity on the dc-control-voltage models. Trip­circuit conductors and motor-closing circuit conductors must be adequately sized for the ampacities indicated on the wiring diagram.
NOTICE
Trip-circuit conductors and motor-and-closing circuit conductors must be adequately sized for the ampacities indicated on the wiring diagram.
DO NOT apply control voltage to the operator at this time.
Installation
Motor contactor
Side access door
Figure 17. The knife switch retainer and knife switch.
Figure 18. Side-access panel of switch operator.
S&C Instruction Sheet 716-502 21
Page 22
Installation
Stop bracket
Spacer
STEP 20. Perform  nal checkout as detailed below:
NOTICE
Check the following. Failure to make the following checks can result to damage to the circuit-switcher when operated.
(a) At each transition box, make sure:
• The interrupter stop bracket and spacer have been removed (see Figure 19)
• The transition lever has been connected to the operating rod link (see Figure 12 on page 17)
• If the optional remote gas-density monitor is present (catalog number suf x “-R”) make sure connections are made according to Instruction Sheet 716-530
(b) At each interrupter, make sure:
• Both shipping-container ha lves and all a ssociated packing and hardware have been removed
• The pressure relief shield has been removed from the target-end of the interrupter (See Figure 15 on page 19)
Stop bracket
Spacer
Adjustable locking rod
Figure 19. Check the transition box and high-speed base for these shipping parts.
22 S&C Instruction Sheet 716- 502
Page 23
(c) In the high-speed base, make sure:
• Each insulated operating rod is connected to the interphase drive (see Figure 20)
• The interphase drive lever has been connected to the operator uni-ball coupling (see Figure 21 on page 24)
• The adjustable locking rod attached to the inter­phase drive lever has been removed (see Figures 19 on page 22 and Figure 21 on page 24)
(d) In the switch operator, make sure:
• Correct polarity has been obser ved on dc-control­voltage models (See Figure 22 on page 24)
• The motor contactor and surge suppressor are fully seated in their mounts (See Figure 23 on page 25)
• Any optional “icebox” style relays (used for cata­log number suf x “-P,” “-T2” and “-U”) are fully seated (See Figure 24 on page 25)
(e) Make sure all other pinned connections have been
made and all bolted connections have been securely tightened.
Installation
Insulated operating rod
Interphase drive
STEP 21. Replace the access cover on the side of each
transition box and securely tighten the associated 5/16 -18 × ¾-inch hex-head stainless-steel cap screws. See Figure 11 on page 17.
STEP 22. Replace the bottom plates to the underside of the
high -speed bas e and securely t ighten the as sociated ½-13 × 1-¼ -inch galvanized-steel cap screws,  at washers, and nuts. See Figure 6 on page 14.
For circuit-switchers rated 161kV and 230 kV:
Attach the six 13 × 3-¼ -inch adjustment plates to the underside of the high-speed base. These plates are used to cover small gaps between the bottom plates, the operator support tube mounting plate, and the mounting pedestal.
Figure 20. Check that each insulated operating rod has been connected to the interphase drive.
S&C Instruction Sheet 716-502 23
Page 24
drive lever
Installation
STEP 23. Insert the motor-and-closing circuit fuse holder.
Then, close the control power KNIFE switch. See Figure 22.
STEP 24. Press the CLOSE pushbutton or send a Close
command to the switch operator. See Figure 16 on page 20. (TRIP and CLOSE pushbuttons are not included on ope rators sp eci ed w ith cat alog number suf x “-J.” In such instances, momentarily touch a jumper between terminals 1 and 3 to close the circuit-switcher.)
The closing latch will release, discharging the closing spring. This action closes the interrupters. The switch-position indicator on the high-speed base will move to the Closed position. See Figure 25 on page 26. If the position-indicating lamp option has been specified, the red lamp will light. See Fig­ure 16 on page 20.
STEP 25. When the circuit-switcher is ready to be placed in
service, the motor and closing circuit fuses can—at the user’s option—be replaced with the slugs furnished. This practice is recommended for increased reliability because low-voltage fuses can be damaged by the repeated inrush current experienced during normal opening operations and can “sneak out,” leaving the circuit-switcher inoperable.
Adjustable locking rod (marked with a
black/yellow striped label)
¾-inch stainless-steel pin
and cotter pin
Interphase drive lever
Un i - b a ll coupling
NOTICE
Before replacing these fuses with slugs, make certain the control-source battery is adequately protected to prevent discharge using fuses or circuit breakers located at the battery bus.
STEP 26. Please complete and mail the Circuit-Switcher
regis tra tion card. T he informat ion reque sted on this card is vital to ensure prompt noti cation in the event  eld modi ca tions are needed.
Figure 21. Check that the interphase drive lever has been con­nected to the uni-ball coupling and check that the adjustable locking rod has been removed.
Figure 22. The motor-and-closing circuit fuse holders and the control-source knife switch.
24 S&C Instruction Sheet 716-502
Page 25
Installation
Surge suppressor out of place. Push the surge support (if present) back into place.
Motor contactors should be fully seated
Figure 23. Check the motor contactor and surge suppressor behind the operator side panel.
Optional relays
Figure 24. Check that all optional “ice cube” style relays are fully seated and that the retaining plate is in place.
Retaining plate
S&C Instruction Sheet 716-502 25
Page 26
Operation
Understanding Trip-Free Operation
The stored-energy mechanism has an instantaneous trip-free capability. If the Series 2000 Circuit-Switcher is closed into a fault sensed by the user-furnished relaying, the mechanism will immediately trip. To accomplish trip-free operation, the stored-energy mechanism uses two spring assemblies: one for closing and one for opening. Both springs are charged by the operator motor before the circuit-switcher can be closed.
Recharging time after a Trip operation is approximately 10 seconds for Model 2040 Circuit-Switchers rated 69 kV through 138 kV and 16 seconds for circuit-switchers rated 161 kV and 230 kV.
Electrical Operation
To Open the circuit-switcher, press the TRIP pushbutton or send a remote trip signal to the switch operator. See Figure 16 on page 20.
The opening latch in the stored-energy mechanism will release, discharging the opening spring. This action trips the interrupters and forces the opening and closing pistons in the mechanism downward, which can be seen in the DIS­CHARGED indicator window inside the operator. See Figure 26 on page 27. The switch-position indicator on the high-speed base will move to the Open position. See Figure 25. Further, if the position-indicating lamp option (catalog number suffix “-M”) has been specified, the green lamp will light.
The motor-driven cam in the stored-energy mechanism will immediately start rising, thereby charging both the opening and closing springs; when the opening spr ing latches, the indi­cator will again be visible at the CHARGED indicator window.
To Close the circuit-switcher, press the CLOSE pushbutton or send a remote close signal to the switch operator. See Figure 16 on page 20.
The motor-driven cam in the stored-energy mechanism will immed iately star t retracting. The closing latch will release, dis­charging the closing spring. This action closes the interr upters. The switch-position indicator on the hig h-speed base wil l move the Closed position. See Figure 25. If the position-indicating lamp option has been specified, the red lamp will light.
The circuit-switcher may also be electrically operated via remotely located control switches. No instructions are included for remote control because control schemes vary with the installation and specific application of the switch.
Figure 25. Switch-position indicator in the OPEN position. Switch-position indicator in the CLOSED position.
26 S&C Instruction Sheet 716- 502
Page 27
Manual Operation
To trip the interrupters, push the manual TRIP lever counterclockwise as indicated by the TRIP lever label. See Figure 16 on page 20. The opening latch in the stored-energy mechanism will release, discharging the opening spring. This action trips the interrupters and forces the openi ng and closing pistons in the mechanism downward, as denoted by movement of the indicator to the DISCHARGED indicator window. (See Figure 26.) The switch-position indicator on the high-speed base will move to the Open position. (See Figure 25 on page 26.) If the position-indicating lamp option has been speci ed—and operator control voltage is available—the green lamp will light.
If operator control voltage is available, the motor-driven cam in the stored-energy mechanism will immediately start rising, charging both the opening and closing springs. When the opening spring latches, the indicator will again be visible at the Charged window.
If operator control voltage is not available, the interrupt­ers will open. The motor-driven cam in the stored-energy mechanism will charge the opening and closing springs when control power is restored to the operator.
Manual closing of the circuit-sw itcher cannot be performed.
Operation
Stored energy indicator
Figure 26. Close -up view of CHARGED and DISCHARGED position indicators.
S&C Instruction Sheet 716-502 27
Page 28
Operation
Safety relief device
(semiphore)
Understanding the Gas-Pressure Indicator and Safety Relief Device
Series 2000 Circuit-Switchers have sealed interrupters containing gas under pressure. Loss of gas pressure may result in improper interrupting action. Low gas pressure is signaled by a red target in the GAS PRESSURE indicator at the upper terminal end of the interrupter.
Figure 27 illustrates a GAS PRESSURE indicator with
acceptable gas pressure.
Figure 28 illustrates a GAS PRESSURE indicator with a red
target, signaling a loss in gas-pressure.
Understanding the Optional Remote Gas­Density Monitor
The remote gas-density monitor provides local and remote indication of the gas density in each interrupter in terms of percent full. The system can be wired to provide remote indication of the gas density of each interrupter via three analog 0 to 1.0 mA dc outputs. The LCD screen provides indication of gas density and alarms for each interrupter. The remote gas-density monitor transmits updated measurements approximately once per hour.
The remote gas-density monitor has three available alarm contacts. The system provides both local and remote indication of ala rms.
Level 1 Alarm indicates an interrupter is leaking. The circuit-switcher can still be operated, but the leaking inter­rupter should be replaced promptly.
Level 2 Alarm indicates an interrupter has lost enough SF6 gas it can no longer clear faults properly.
System Trouble Alarm indicates a problem with the monitoring system. A system trouble alarm will activate when the receiver fails to receive a signal for over 24 hours. The system trouble alarm will also activate when there are approximately three months or less of battery life remaining. At first, a Low-Battery alarm will appear locally. After the battery has completely discharged, an “Error” message will appear in place of the percent-gas-density information, and the system trouble alarm will signal remotely.
For complete instructions on installing, operating, and troubleshooting the optional remote gas-density monitor, refer to S&C Instr uction Sheet 716-530.
Safety relief device
Gas-pressure indicator
Figure 27. The normal gas-pressure indicator and relief device.
Red target (semiphore)
Inspection Recommendations
To ensure the Series 2000 Circuit-Switcher’s continued proper performance, the circuit-switcher should be inspected in accordance with S&C-recommended schedule and procedures contained in S&C Instruction Sheet 716-590.
28 S&C Instruction Sheet 716- 502
Figure 28. The visible “red target” gas pressure indicator.
Loading...