SBM 262 XLA Technical Instructions

Page 1
XLA BROODERS
TECHNICAL INSTRUCTIONS
N° 05000300/6
GAS HEATING FOR POULTRY AND LIVESTOCK
1. TECHNICAL SPECIFICATIONS
2. INSTALLATION
3. LIGHTING THE BROODERS
4. SHUT-OFF
5. MAINTENANCE
6. GAS CONVERSION
7. SPARE PARTS
Manufacturer :
SBM Service Commercial France Export Department 3, cottages de la Norge Tél : 03.80.76.74.70 Tel : (+33) 3.80.76.74.84 21490 CLENAY Fax : 03.80.76.74.69 Fax : (+33) 3.80.76.74.89 FRANCE e-mail : sbm.france@sbm.fr e-mail : sbm.com@sbm.fr http://www.sbm.fr http://www.sbm-international.net
1
1312
Page 2
Power supply
G31 (Propane)
- Inlet pressure
6
0 to 180 mbar (nominal 148 mbar)
208
212
216
8.100
11.500
15.500
kW
0.588
0.
827
1.
122
kg/h
none
G20 (Natural gas)
- Inlet pressure 60 to 180 mbar (nominal 148 mbar)
208
212
216
8.100
11.500
15.500
kW
0.773
1.098
1.477
m3/h
1 x 200
208
212
216
308 mm
575 mm
X
1. TECHNICAL SPECIFICATIONS
Refer to the rating plate on the filter box holder (see example opposite)
X (mm) 272 398 522 Weight (kg) 7.00 8.00 9.00
230V (+10% -15%) / 50Hz - 60Hz / 2 x 0.1A
certificate number 1312 AR 1201 Nominal capacity (inlet pressure = 148 mbar) ∑Qn (Hs) (Nominal heat input) ∑Qn (Hi) 7.452 10.580 14.260 kW Maximum capacity (inlet pressure = 180 mbar) ∑Qm (Hs) 8.932 12.682 17.093 kW (Maximal heat input) ∑Qm (Hi) 8.218 11.668 15.726 kW Gas consumption (inlet pressure = 148 mbar) M (Mass flow rate) (inlet pressure = 180 mbar) M 0.649 0.912 1.237 kg/h Ø orifices (1/100e mm) primary orifice (restrictor) none none secondary orifice (injector) 2 x 70 2 x 78 2 x 95 Combustion air 7.452 10.580 14.260 m3/h
certificate number 1312 AR 1201 Nominal capacity (inlet pressure = 148 mbar) ∑Qn (Hs) (Nominal heat input) ∑Qn (Hi) 7.293 10.355 13.957 kW Maximum capacity (inlet pressure = 180 mbar) ∑Qm (Hs) 8.932 12.682 17.093 kW (Maximal heat input) ∑Qm (Hi) 8.043 11.420 15.392 kW Gas consumption (inlet pressure = 148 mbar) V (Volumetric flow rate) (inlet pressure = 180 mbar) V 0.852 1.210 1.629 m3/h Ø orifices (1/100e mm) primary orifice (restrictor) 1 x 135 1 x 180 secondary orifice (injector) 2 x 115 2 x 135 2 x 150 Combustion air 7.293 10.355 13.957 m3/h
Hi = Net calorific value - Hs = Gross calorific value
The proper operation of the heaters requires the renewal of 1 m3/h fresh air per kW of operating capacity.
2
Page 3
2 3
2. INSTALLATION
2.1 RULES AND REGULATIONS
The brooders must be installed in compliance with current local regulations,
by a qualified installer.
The brooders must be installed in sufficiently ventilated premises.
The brooders are not authorised for use in domestic premises.
2.2 ASSEMBLING OF BROODER
1
3
Page 4
S h 0.6m MINIMUM
216 : 0.40m to 0.44m
25° to 30°
2.3 INCLINATION OF BROODER
2.4 MINIMUM SAFETY CLEARANCES
208 : 0.28m to 0.32m 212 : 0.34m to 0.38m
CEILING
(see table below)
WALL
(see table below)
FLOOR
Ceiling S (m)
Inflammable ceiling (plastic) (max. surface temperature : 70°C)
0.80
Non inflammable ceiling (metal) 0.30
Brooder size 208 212 216
h (m) 0.80 1.00 1.00
For recommended hanging heights H, please contact your local SBM specialist.
4
Page 5
XL
A
230V AC
3. LIGHTING THE BROODERS
3.1 STANDARD INSTALLATION
RCD 16A - 30mA (Residual Current Device)
Sensor cable
RP32 + 2 x 0.25A fuses
Valve B10F or valve NPT
2 chains 2.5m
Clik CL10
or CLT
brooder
Sensor A1 (supplied with VisioLon)
G6A or G10A
Optional plugs (not supplied)
VisioLon Elv-T
KIT MODULE ENCLOSURE 2 ZONES
Gas filter
Ground terminal
Enclosure
Main gas valve
G31 (Propane) - 1.5 bar G20 (Natural gas) - 1.5 bar
3.2 IGNITION
IMPORTANT : preheat the building 24 hours before the animals arrive.
Set the G6A-G10A MINI gas regulator to position 1. Set the G6A-G10A MAXI gas regulator to position 8 (Summer)
or position 10 (Winter).
Open the main gas valve. Open the individual gas valves. Switch on the power supply. Adjust the VisioLon Elv-T set point to the temperature required by the animals.
Ignition of the brooders is automatically activated by the VisioLon Elv-T.
4. SHUT-OFF
Close the main gas valve. Switch off the power supply.
5
Page 6
air jet
5. MAINTENANCE
ONCE A WEEK (or whenever a blue flame appears), CLEAN THE AIR FILTER.
Take out the metal filter
Blow out the metal filter with compressed air
Compressed air jet
Compressed
Replace the metal filter in the filter holder
Compressed air jet
6
Page 7
Unplug igniters
2
4
ONCE A YEAR (or whenever a blue flame appears), CLEAN THE BROODER.
Remove the injector block.
1
Unscrew thermocouples (completely)
Unscrew (completely) the locking screws
3
Pull the injector block
Clean the injector block Remove the filter box holder and
with compressed air. blow it with compressed air.
Compressed air jet (3 to 5 bar max.)
Pull the filter box holder
Blow the inside of the 2 burners Blow the surface of the ceramic
with compressed air. plaques with compressed air.
Joints
Compressed air jet (3 to 5 bar max.)
Compressed air jet (3 to 5 bar max.)
Do not aim at the joints between the ceramic plaques.
7
Page 8
B E F G H
J' K K' L M N C D
After cleaning the brooder, make sure that the brooder (surface of the ceramic
plaques, hanging bracket) has not experienced mechanical damage.
ONCE A YEAR, PERFORM A VISUAL INSPECTION OF ALL FLEXIBLE GAS HOSES, ESPECIALLY AROUND THE HOSE CLAMPS.
6. GAS CONVERSION
The brooders are designed to operate with the following gases :
CATEGORY : GAS : PRESSURE : I3P GB/IE/TR G31 (LPG propane) 148 mbar I2H GB/IE/TR G20 (Natural gas) 148 mbar
The equipment is adjusted for the type of gas and the pressure as displayed on the rating plate. For any change of the gas used, please contact your local SBM specialist.
7. SPARE PARTS
REP. SPARE PARTS
BR 208XL LEFT
A
BR 212XL LEFT BR 216XL LEFT
BR 208XL RIGHT
BR 212XL RIGHT
BR 216XL RIGHT METAL FILTER 300 METAL FILTER HOLDER 300 THERMOCOUPLE FA 10 LOCKING SCREW 6X100/30 (supplied by packs of 10) INJECTOR BLOCK CAP MAGNETIC HEAD 11.5 BLOCK 200 XLA T10
I
BLOCK 200 XLA 14G
BLOCK 200 XLA T11
BLOCK 200 XLA 12G
J
PRIMARY ORIFICE M9x1 (please specify the number marked on the end of the orifice) ORIFICE (please specify the number stamped on the side of the orifice) IGNITER EARTH PIN L3-NUT BA BRACKETS (2) BA BLOCK BA NUT
8
Page 9
For any spare part order, please specify :
C B
D
A E G H
I
J F N
L M J'
K'
K
- brooder type and serial number
- type of gas
- operating pressure These informations are displayed on the rating plate, attached to each brooder.
9
Page 10
TO BE DISPLAYED
NEXT TO THE CONTROL UNIT
Page 11
air jet
XLA BROODERS
INSTRUCTIONS FOR USE
No. 05000300/6
(TO BE DISPLAYED NEXT TO THE CONTROL UNIT)
A U T O M A T I C C O N T R O L
VisioLon Elv-T module and G6A or G10A gas regulation
LIGHTING THE BROODERS :
Set the G6A / G10A MINI gas regulator to position 1. Set the G6A / G10A MAXI gas regulator to position 8 (Summer) or position 10 (Winter). Open the main gas valve. Open the individual gas valves. Switch on the power supply. Adjust the VisioLon Elv-T set point to the temperature required by the animals. Ignition of the brooders is automatically activated by the VisioLon Elv-T.
SHUT-OFF :
Close the main gas valve. Switch off the power supply.
OPERATION IN CASE OF POWER FAILURE : A SBM AUTOMATIC SYSTEM CAN OPERATE WITHOUT ELECTRICITY
BROODERS OPERATING AT MINI Adjust the heating level manually using the MINI regulator of the G6A / G10A. After the power comes back, reset the MINI regulator to its original position.
BROODERS "OFF" Set the MINI regulator of the G6A / G10A to 10. Press the push-button while holding a flame against the ceramic surface of one burner. Keep pressing the push-button during 30 seconds. Repeat this operation for the second burner. After the power comes back, reset the MINI regulator to its original position.
MAINTENANCE :
ONCE A WEEK (or whenever a blue flame appears), CLEAN THE AIR FILTER :
Take out the metal filter Blow out the metal filter with compressed air
Do not hold your face close to the ceramic plaques during ignition.
Compressed air jet
Compressed
Compressed air jet
Page 12
Unplug igni
ters
2
box holder
between
4
Replace the metal filter in the filtre holder
ONCE A YEAR (or whenever a blue flame appears), CLEAN THE BROODER :
Remove the injector block. Clean the injector block with compressed air
Unscrew thermocouples
1
(completely)
Unscrew (completely)
3
the locking screws
Pull the injector block
Compressed air jet (3 to 5 bar max.)
Remove the filter holder box Blow the inside of the 2 burners Blow the surface of the ceramic plaques and blow it with compressed air. with compressed air. with compressed air.
Joints
Compressed air jet
Pull the filter
After cleaning the brooder, make sure that the brooder (surface of the ceramic plaques, hanging bracket) has not
experienced mechanical damage.
ONCE A YEAR, PERFORM A VISUAL INSPECTION OF ALL FLEXIBLE GAS HOSES, ESPECIALLY AROUND THE HOSE CLAMPS.
Manufacturer :
(3 to 5 bar max.)
Do not aim at the joints the ceramic plaques.
Installer's stamp :
SBM 3 cottages de la Norge 21490 CLENAY FRANCE
Compressed
air jet
(3 to 5 bar max.)