SBC Q.PS-PEL-240x User Manual

Document 27-646; Version ENG01 │ 2015-08-27
Manual
Q.PS-PEL-240x
24 VDC Power Supply Unit
Saia-Burgess Controls AG
1-02
Document versioin
Contents
Document version
Version Changes Published Remarks
ENG01 2015-08-27 2015-08-27 New document
Brands and trademarks
Saia PCD® and Saia PG5® are registered trademarks of Saia-Burgess Controls AG.
Technical modications are based on the current state-of-the-art technology.
Saia-Burgess Controls AG, 2015. © All rights reserved.
Published in Switzerland
Saia-Burgess Controls AG
1-03
1
Document versioin
Datasheet
Datasheet
General
The Q.PS-PEL-240x range of single phase primary switched mode power supplies can tole-
rate a wide range of supply voltage and are distinguished by their at prole ideal for mounting in control panels for building and automation controls. Available in 1.3 A and 4 A DIN rail mounting packages, all units feature overvoltage and short
circuit protection.
Features
● Stabilised and adjustable output voltage
● Power output OK LED
● Parallel connection capability
● Spring-loaded connector system
● DIN rail mounting
Specications
Input
Input rated voltage 100 to 240 Vac. Input voltage range 85 to 264 Vac, Input frequency range 44 to 66 Hz Inrush current limiter <30 A, NTC Recommended 6A, 10A, 16 A circuit
external protection breaker characteristic
B, C
Output
Output rated voltage 24 Vdc ±2%
Output voltage range 22.8 to 26.4 Vdc Overload behavior constant current
Parallel operation yes Serial operation yes Residual ripple 100 mV typical
Saia-Burgess Controls AG
1-4
1
Environment
Datasheet
Environment
Storage temperature –25°C to +80°C Ambient temperature –25°C to +55°C Derating –3%/K >+45°C
Mounting position Vertical on DIN rail TH35 Humidity range 30 to 85 %RH, non-condensing Space for cooling 50 mm above and below
Safety and protection
Protection IP20 High voltage test volts 4.2 kVdc Safety class II (in closed cabinet) Conductors Use Cu only (rated 60°C or 60/75°C) Installation Install in Pollution Degree 2 environment Feedback voltage max. 30 Vdc
Safety standards
Safety EN61558-2-17, EN60950 (SELV) EMC EN61204
UL cURus, cULus GL GL, Germanischer Lloyd
Indication
Output power OK Green LED (DC OK)
Input / output terminals
Connection technology Push in Conductor cross section: single-wire 0.2 … 2.5 mm
2
Conductor cross section: stranded 0.2 … 2.5 mm
2
Conductor cross section: stranded 0.25 … 1.5 mm2 (with ferrules with plastic collar*) Conductor cross section: stranded 0.25 … 2.5 mm2 (with ferrules without plastic collar)
Stripping Length 9 … 10 mm
* a sleeve length of 12 mm is required for twin wire end ferrules
Saia-Burgess Controls AG
1-5
1
Model Dependent Specications
Datasheet
Model Dependent Specications
Model number Q.PS-PEL-2401 Q.PS-PEL-2403
Derating input voltage Max 1 A (<100 Vac)
Max 3.5 A (<100 Vac)
3 A (<90 Vac)
Rated input current (nominal load)
110/230 Vac
0.7/0.5 A 1.6/0.9 A
Internal fuse 2 AT 4 AT Mains drop compensation at nominal
load 110/230 Vac
10/80 ms 18/100 ms
Rated output current
1.3 A <45°C
0.9 A <55°C
4 A <45°C
2.8 A <55°C
Efciency 82% typ. 88% typ.
Current rating at any mounting position Max. 0.9 A Max. 2.4 A Weight 0.17 kg 0.3 kg Dimensions 54 × 89 × 54 mm 90 × 89 × 54 mm
Voltage/Current Characteristic for short circuit and overload
The output of the device is electrically protected against overload and short circuit
U
out
(V)
Output Charac
I
out
(A)
teristic (U/I Charateristic)c
1,1× I
N
N
I
Current overload protection is constant current at 1.1 × nominal current
Output Derating Curve
Q.PS-PEL-2401 Q.PS-PEL-2403
0.5
1
1.3
–25 –10 0 10 20 30 40 50 60–20
0.9
0
45
1.5
100
70
55
Load [A] Load [%]
Temp [°C]
At Input rated voltage 230 VAC
1
3
4
–25 –10 0 10 20 30 40 50 60–20
2.8
0
45
100
70
55
2
Load [A] Load [%]
Temp [°C]
At Input rated voltage 230 VAC
Saia-Burgess Controls AG
1-6
1
Dimensions
Datasheet
Dimensions
H
D1
D2
W
Model Q.PS-PEL-2401 Q.PS-PEL-2403
W 54 mm 90 mm H 89 mm 89 mm
D1 54 mm 54 mm D2 59 mm 59 mm
Saia-Burgess Controls AG
1-7
Connections
Installation
1
Installation
Connections
Input Terminals
LN
Output Terminals
+ + - -
Output Power OK LED
Output Voltage Adjustment
Output Power OK LED:
The green LED lights as soon as the output voltage is present
Output Voltage adjustment:
The output voltage can be altered using a screwdriver (Philips size 00). Turning the adjustment screw anticlockwise reduces the
voltage output.
V
ADJ.
+
Mount/Dismount
Mount unit by placing the DIN rail guide on the upper edge of the DIN rail and snapping
it into place with a downward motion
Dismount unit by levering the lower catch
open with a screwdriver, pulling the lower edge forward, and unhooking from the top of
the DIN rail
Parallel connection
If units have their outputs connected in parallel, their output voltages must be adjusted to the same value (± 100 mV).
Impedances from the units to the star point must be equal Note that leakage current, EMI, inrush current and harmonics can increase using multiple
power supplies.
Saia-Burgess Controls AG
1-8
Safety measures
Installation
1
Installation
Safety measures before installation.
This equipment is to be protected against improper use. Components are not to be bent or
isolation spacing changed, especially through handling and transport.
The contact with electrical components and terminals is to be avoided. Always disconnect the equipment from the mains supply, before commencing installation or wiring. The product description, technical information in this data sheet and the marking on the equipment ratings plate are to be observed.
Installation
Installation must be carried out according to the prevailing local conditions and safety regula­tions (e.g. VDE 0100) national accident prevention regulations (e.g. UVV-VBG4 or BGV A3) and the generally accepted rules of technology. This equipment is a component designed for installation into electrical systems and machines, and fulls the requirements of the low volta­ge guidelines (2014/35/EU).
The required minimum spacing to neighboring components must be observed to guaran­tee the required cooling. When installed into machinery, the normal operation is forbidden until it is determined that the machine fulls the requirements of the machinery guidelines (2014/30/EU). EN 60204 must be observed. The EMC requirements (2004/108/EG) must be fullled before operation is commenced. The observance of the required limitations for the EMC legislation is the responsibility of the manufacturer of the installation or machinery.
Disposal
WEEE Direc ti ve:
At theend of their useful lifethe packaging and productshouldbe disposedofbyasuitable recyclingcentre.
Do not dispose of with normal household waste. Do not burn.
Saia-Burgess Controls AG
1-9
Contact
Annex A
A
Contact
Saia-Burgess Controls AG Bahnhofstrasse 18
3280 Murten, Switzerland Phone +41 26 580 30 00
Fax +41 26 580 34 99
Email support: support@saia-pcd.com Supportsite: www.sbc-support.com SBC site: www.saia-pcd.com