Recon LED Recessed Exit Box
13738

Thank you for purchasing this light fitting.
Please read the instructions carefully before use to ensure safe and satisfactory operation of this product.
Please retain these instructions for future reference.
SUPPLY
LIGHT FITTING
Warning
This is a Class 1 product and must be earthed.
Live Voltages may be present in this unit even when turned of or when completely disconnected.
Please read these instructions carefully before commencing any work.
This unit must be fitted by a competent and qualified electrician.
Install in accordance with IEE Wiring regulations and current Building Regulations.
To prevent electrocution switch off at mains supply before installing or maintaining this fitting. Ensure other persons
cannot restore the electrical supply without your knowledge.
This light fitting should be connected to a fused circuit.
If replacing an existing fitting, make a careful note of the connections.
This system contains non-replaceable parts and cannot be serviced. If damage occurs the part should be scrapped.
This product is not suitable for dimming.
Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist.
Check with your local authority or retailer for recycling advice.
These products should not be fitted to PIR circuits or short duration timed switches.
Before cutting a mounting hole, ensure ceiling surface is flat to ensure a good fit.
This product is suitable for mounting in a suspended ceiling only.
Specification
Power: 1.5W(15 LED’s)
Continuous Illumination: >3 hours
Battery: 3.6V 900mah
Recharge time: approximately 24 hours
Over-discharge Protection: Yes
SWITCHED LIVE
PERMANENT LIVE
EARTH (GREEN/YELLOW)
NEUTRAL
LIVE TERMINAL
EARTH TERMINAL
NEUTRAL TERMINAL
Check That
You have correctly identified the wires.
The connections are tight.
No loose strands have been left out of the connection block.
Commisioning
6. Push the unit up until firmly in position, ensuring that the cable is not trapped.
7. Adjust the cable so it does not get snagged.
8. Tighten the fixing bolts to secure the unit in place.
9. Fit the green exit sign. Refit the cover using the screws, taking care not to over tighten.
10. Replace fuse or circuit breaker and switch on. Your light is now ready for use.
Installation
Existing fittings must be completely removed before installation of a new product. Before removing the existing
fitting, carefully note the position of each set of wires.
1. Undo the two screws on the end of the cover, pop the charging LED out of its holder, and the cover aside.
2. Cut a mounting hole in the ceiling taking care not to foul any pipes or mains cables beneath the surface. The hole
size should be 325mm x 115mm to fit the product into.
3. Ensure free movement of air around the fitting by removing any roof void insulation from at least 100mm
around the hole.
Under no circumstances must these fittings be covered with insulating matting or similar
material.
4. Using the side plate as a template, mark and drill the fixing holes.
5. Unscrew the 2 screws that hold the LED tray in place. Flip the tray up and wire into the terminal block as
detailed below. Then connect the battery.
Wiring
This unit is capable of being wired in both Maintained and Non Maintained configurations.
Maintained Wiring:
To allow the unit to be switched separately, this link must be removed, and this terminal blocked connected to
the switched live.
Identify the permanent live and switched live and connect to the connection block inside the product in the
following way:
Operating Instructions
Non Maintained LED’s are normally on and battery is on automatic charge (green charging LED is on) when the
mains supply is present. Fitting automatically switches the LED’s to emergency mode when the
supply is interrupted.
Maintained LED’s can be off or on as the unit can be switched separately and battery is on automatic charge
(green charging LED is on) when the mains supply is present. Fitting automatically switches the
LED’s to emergency mode when the permanant supply is interrupted.
1. Connect the unit to the mains (220-240V a.c.). Verify that the charging LED is illuminated; this confirms that
the batteries are charging.
2. The battery requires charging for at least 24 hours before first use.
3. When the unit is installed a green LED indicates that mains power is present and the battery is being charged.
4. If the charging LED is not illuminated then there may be no A.C. supply, the battery has not been connected
properly or the internal circuit may have failed.
5. The battery should be re-charged and checked every three months.
6. The battery should be discharged and the duration of the lamp in emergency mode checked every six months.
Non Maintained Wiring:
Leave in the link provided between the permanent live and the switched live to allow the LED’s to remain on.
Identify the permanent live and connect to the connection block inside the product in the following way:

Battery Replacement
If after routine operation check, the lamp does not remain lit for the three hour period, a new battery pack may be
required.
1. Switch off the electricity at the mains.
2. Allow batteries to fully discharge then reconnect to supply and allow to charge for 24 hours.
3. Test again for 3 hours, if light does not remain lit change the battery pack as follows:
4. Undo the two screws on end of the diffuser and lift off. Push the clasps in to release the gear tray, the tray
will spring up. Remove the gear tray carefully.
5. Unplug the battery lead from the circuit board. Pull the battery pack away from the gear tray.
6. Write current date on the new battery pack.
7. Fit new battery pack using self adhesive pads or similar. Plug battery pack into circuit board.
8. Close and secure gear tray and replace diffuser.
9. Restore power and allow to charge for 24 hours.
10. Perform full operation check and update test record.
Care and Cleaning
We recommend cleaning with a soft dry cloth.
Do not use solvents or abrasive cleaners as these could damage the finish.
Recycling Advice
Waste electrical products should not be disposed of with household waste. Please recycle where
facilities exist. Check with your Local Authority or retailer for recycling advice.
Safety Information
Live Voltages may be present in this unit even when turned of or when completely disconnected.
For your safety, always switch off the supply before changing lightbulbs, or cleaning.
This system contains non-replaceable parts and cannot be serviced. If damage occurs the part should be scrapped.
Saxby Lighting Ltd. BH23 3PE
040915