Saxby Lighting 46429 User Manual

Operation
• This unit works in maintained mode. The fitting can
be switched separately on or off. The unit will charge automatically (LED is green). A single LED remains on when the supply is interrupted.
• Locate the flying lead on the inver ter and plug into
the connector.
• Replace fuse or circuit breaker and switch on.
Ensure that the source is mains (240V ~ 50Hz).
• Verify that the Green LED is illuminated; this confirms
that the batteries are charging.
Battery Replacement
• If after routine operation check, the lamp does not
remain lit for the set period, a new battery may be required.
• Switch off the electricity at the mains, allow batteries
to fully discharge then reconnect to supply and allow to charge for 24 hours.
• Test again for two hours, if light does not remain lit
change the inverter / battery unit as follows:
• Charge the battery for at least 24 hours before first
use.
• If the LED is not illuminated then there may be no a.c.
supply, the battery has not been connected properly or the internal circuit may have failed.
• The battery should be re-charged and checked every
three months.
• The battery should be discharged and the duration
of the lamp in emergency mode checked every six months.
• Obtain a replacement battery / inverter unit. make a
note of the wiring, and remove from plate and refit the new one.
• Perform full operation check and update test record.
• Refit the shade. Ensure that the seal is correctly
located.
• Restore power and allow to charge for 24 hours.
Instruction leaflet
Vigor EM LED Bulkhead
46429
Fitting/replacing bulbs
This system contains non-replaceable parts and
cannot be serviced. If damage occurs the part should
We recommend cleaning with a soft dry cloth. Do not use solvents or abrasive cleaners as these could damage the finish.
be scrapped.
Recycling advice
Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.
For your safety, always switch off the supply before cleaning.
www.saxbylighting.com
Iss.1 11122012
Saxby Lighting Ltd. BH23 3PE
Thank you for purchasing this light fitting. Please read the instructions carefully before use to ensure safe and satisfactory operation of this product. Please retain these instructions for future reference.
Warning
This is a Class 1 product and must be earthed.
Please read these instructions carefully before commencing any work.
This unit must be fitted by a competent and qualified electrician.
Install in accordance with IEE Wiring regulations and
current Building Regulations.
To prevent electrocution switch off at mains supply before installing or maintaining this fitting. Ensure other persons cannot restore the electrical supply without your knowledge. If you are in any doubt, please consult a qualified electrician.
This light fitting should be connected to a circuit with a
30mA RCD fitted.
If replacing an existing fitting, make a careful note of the connections.
This system contains non-replaceable parts and cannot be serviced. If damage occurs the part should be scrapped.
Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your local authority or retailer for recycling advice.
This product is rated at IP44.
This product is not suitable for dimming.
These products should not be fitted to PIR circuits or
short duration timed switches.
Installation
Existing fittings must be completely removed before installation of a new product. Before removing the existing fitting, carefully note the position of each set of wires.
• Unscrew the shade and set aside.
• Hold the product in place and mark the position of
the holes.
• Ensure the wall is capable of holding the weight
of the product, or if fitting to a ceiling, ensure there is a joist at the point of fixing to support the
Wiring
Having correctly identified the wiring from your existing light fitting, connect to the connection block inside the
SUPPLY
NEUTRAL
weight of the product. Take care to avoid damaging any concealed wiring and pipes. The correct fixings should be used for brick, cavity walls or plasterboard.
• Pierce a hole in the grommet, and pull the cable
through.
• Fix into position.
• Wire as detailed below
product in the following way:
LIGHT FITTING
BLUE (N)
Specification
Voltage : 240V ~ 50Hz Lamp : 16W SMD 5630 LED's IP rating : 44 Lumens : 120lm in EM mode Duration : 3 hours (180 minutes)
Operating Temperature : 10˚C to 50˚C
Layout
• Plan the desired layout of this fitting carefully,
ensuring the cables will reach the distance between the junction box and the light fitting.
• Avoid locating any cables in positions that would
cause a hazard. Position cables and junction boxes (not supplied) away from areas where they may be at risk from being cut, trapped or damaged.
Maximum Operating Humidity : 90%
Change over Time : Approximately 1s Battery Specification : 3.7V 1.3Ah Lithium Battery Charge Time : 24 hours
• The mains supply cable must have a minimum cross
sectional area of 1.0mm².
• Cables must be protected using suitable conduit or
plastic trunking.
• The products can be wall or ceiling mounted. If wall
mounting ensure that the power supply is at the bottom.
EARTH (GREEN/YELLOW)
SWITCHED LIVE
PERMANENT LIVE
Check that...
You have correctly identified the wires
The connections are tight
Commissioning
• Ensure that the screws and cable entry points are
sealed to maintain the IP rating of the product.
• Refit the shade, ensuring that the seals are correctly
GREEN/YELLOW
BROWN (L)
BROWN (L)
No loose strands have been left out of the connection
block.
located.
• Replace fuse or circuit breaker and switch on. Your
light is now ready for use.
Loading...