RDT 300: Electronic controller for ventilation and air- condi t i oning
How energy efficiency is improved
Areas of application
Weather-compensated flow temperature control in 2- and 4-pipe systems for heating/cooling. Activa­tion of intelligent unitary controllers.
Features
Clearly-laid-out operating unit with large LCD display and generously proportioned keypad
6 controller models
Plug-in memory for copying and documenting system parameters
Fast commissioning thanks to preset parameters
Room user panel with display available as accessory
Weekly and annual switching program
Automatic summertime/wintertime changeover
Sealable sliding switch for selection of operating mode
Technical description
Housing 144 x 96 mm made of flame-retardant, pure white thermoplastic (RAL 9010)
4 universal inputs and 2 analogue inputs
2 independent PI controllers
3 continuous outputs and 6 relay outputs
Reset, sequencing and limiting functions, as well as alarm and time functions
Suitable for fitting on walls, in panels and on top-hat rails
Electrical connection in base with screw terminals for wires up to 2.5 mm²
PI
Y06366
Type 1)
Setting range
°C
Control modes Power supply Weight
kg
RDT 300 F001
–30...150 P, PI 230 V~ 0,67
Ranges (depend­ing on transmitter)
Temperature
°C or K
Percentage % Rel. humidity
%rh
Abs. humidity
g/kg
Enthalpy
kJ/kg
No unit of
measurement
Setpoint Xs –30...150 °C 0...100 0...100 0.0...20 0...100 –4999...4999 P-band 0.1...180 K 0.1...200 0.1...100 0.1...100 0.1...100 10...4999
4 universal inputs 3)
2 analogue inputs
Temperature Ni1000 (DIN 43760)
2× temperature
2) 3)
Ni1000 (DIN 43760)
Voltage
0(2)...10 V; R
i
= 100 k
0...1 V, R
i
= 500 k
Outputs
3)
Current
0(4)...20 mA, R
i
= 50
3 continuous
0(2)...10 V, load > 5 k
Potentiometer
2 k (min.1 kΩ)
4 relays 5(2) A, 250 V~
2 relays 5(2) A, 24/250 V~
Power supply 230 V~ +10/–15%; 50...60 Hz Degree of protection IP 30 (EN 60529) Power consumption 5 VA Protection class F001 230V II (IEC 60730)
P-band Xp 0,1....180 K
Integral action tim e Tn 0....9990 s Wiring diagram A09432
Dimension drawing M368900 Cycle time 1 s Fitting instructions MV 505711 Permissible am bi ent temp.
0...45 °C Operating instructions
Ambient humidit y
5...80 %rh For end users 7000927 (Part 1)
non-condensing Commissioning 7000928 (Part 2)
Accessories
RDB 300
Remote-con trol unit see Section 46
0313516 . . .
Additional operating instruc t i ons (7000927 and 7000928) German 001, French 002, English 003, Italian 004.
0369746 001
Cover plate for the whole front; of transparent thermoplastic; seal abl e
0226187 002*
Plug-in dummy for memory slot
0226187 003*
Plug-in memory for flexotron
*)
Dimension drawing or wiring diagram are available under the same number
1) Since several languages are available, please order the operating instructions as an accessory.
2) Can also be used as a binary input (gold contacts).
3) Protected against short-circuiting and excess voltage up to 24 V a.c. Current input for max 70 mA.
7146102003 04
46.102/2
RDT 300
Sauter Components
Operation
The RDT 300 controller has software modules with fixed configurations and captive standard parameters. The software modules have definite links given by the control model. There are also modules for min./max. limitation. All user parameters can be stored in the optional memory for documentation purposes or for copying when installations are similar. All parameters are captive. The sliding switch (Hand/Automatic/Service) controls the operating modes. Service In this mode, the controller can be matched to the control task by selecting the appropriate control model, and the inputs, outputs and additional functions can be configured. Automatic Control mode with setpoints as per weekly programme. Manual The current positioning signals are adopted on entering this mode. They can be set by hand between 0 and 100%. Any necessary adjustments to the control parameters and to the time programme can be made in this mode.
Additional technical data
Radio suppression EN 55014 and 55022 Storage and transport temp. –25. . .+65 °C EMC EN 50082 -1 Conformity EN 12098 and CE
Complies with:- Directive 2006/95/EC EN 60730-1/ EN 60730-2-9 EMC directive 2004/108/EC EN 61000-6-1/ EN 61000-6-3 EN 61000-6-4
Wiring diagram
Printed in Switzerland Right of amendment reserved N.B.: A comma between cardinal numbers denotes a decimal point © Fr. Sauter AG, CH-4016 Basle 7146102003 04
0...1 V
6543
Rel. 6
Ni1000
0...10 V
0...20 mA
1
2
X4 X3 X2 X1
RDT 300 F001
17
1112131516181920
X1 X2 X3 X4 Y1 Y2 Y3
xi2 xi3 xi4 y1 y2 y3xi5
Rel. 5
Rel. 4
Rel. 3
8109
Rel. 2
Rel. 1
230V~; 5(2)
14
X5 X6
xi6xi1
xi
Ni1000
Input X5; X6
24/230V~; 5(2)A
230~
L
N
xi xi xi
Ni1000
0(2)...10V Ri=100k
0...1V
Ri=500k
xi
0(4)...20mA
Ri=50
Input X1... X3
Input X4
xi
0...10V
Ri=100k
A09432d
21222324
A B
15V
RDB 300
21222324
xi xi xi
Ni1000
0(2)...10V Ri=100k
0...1V
Ri=500k
xi
0(4)...20mA
Ri=50
Input X4, Modell 1
Key X1 Supply temperatures, heating X6 Floor temperature X2 Supply temperatures, cooling Y1 Heating or heating/cooling X3 Outside temperature Y2 Cooling X4 Relative humidity or universal input Y3 E.g. measuring amplifier X5 Temperature for calculating the dew point
Accessories
Dimension drawing
M00689a
memory
9,411,4
226187 369857
13,4
7,2
15,5
66
72
144
16
92
96
min. 155
7
4
,
5
7,5
74
60 18
92
+0,8/0
138
+1/0
max. 5
138 x 92 DIN 43700
35 x 7,5 EN 50022
M368900a