Description of operation
Display symbol Procedure
Set the duration of the backlight of the display
Factory setting: 15 seconds
Determines the time period for which the display is illuminated
after operation.
Setting range: 0 to 30 seconds (in 5-second steps)
Display the status of the output signal
Factory setting: 0
When the output for thermal actuators is active, the heating or
cooling symbol flashes slowly. If this output is inactive, the symbol
is displayed continuously.
0 = deactivated
1 = activated
Set the direction of operation of the room controller (NC or NO)
Factory setting: 0
The direction of operation of the room controller and the connected
thermal actuators can be defined.
0 = normally closed (NC)
1 = normally open (NO)
Set the frost-protection temperature
Factory setting: 5 °C
Activates the frost-protection facility when the temperature falls
below the set temperature.
Setting range: 5 °C to 10 °C
Activate the optimised time programme function
Factory setting: 0
If the optimised time programme function is activated, the setpoint is reached at the defined time. In order to reach the setpoint,
heating or cooling mode is initiated in good time ahead of the defined time.
0 = deactivated
1 = activated
Set the cycle time for the valve protection facility
Factory setting: 14 days
Prevents the plug from sticking inside the valve.
Setting range: 0 to 28 days
Define the actuation duration while the valve protection facility
is active
Factory setting: 5 minutes
The actuation time can be optimised depending on the running
time of the thermal actuator.
Setting range: 0 to 10 minutes.
Define the pilot timer output
Factory setting: 0
0 = pilot timer output active acc. to time programme
1 = pilot timer output inactive acc. to time programme
pilot timer output active when “ECO” operating mode is
selected;
pilot timer output active when “Switch-off” operating mode is
selected.
Note: When parameter P230 =1, the time programme can be used
for local decreasing.