Guidelines for the electrician
Product Description1
The SAUTER EY-RU483F001 communicating sensor and balancing tool for VAV is specifi cally designed to work with the EY-RC415 and EY-RC416 controller product lines. This device provides precision local temperature sensing and it allows occupants to adjust the local setpoint and view the occupancy status, local space temperature, outside air temperature and operation mode.
Maintenance personnel have access to a password-protected advanced mode that allows them to perform air balancing on a connected EY-RC415 or EY-RC416, send service pin messages for commissioning and toggle temperature units between °C and °F.
The SAUTER EY-RU483F001 can be permanently installed on a wall or used as a hand-held air balancing tool that can be connected through a standard wall-mounted room sensor. Using the SAUTER EY-RU483F001 as a hand-held unit, technicians can directly perform VAV balancing right near the point of control.
The SAUTER EY-RU482F001 communicating sensor is specifi cally designed to work with the EY-RC402 and EY-RC403 controller product line. This device provides precision local temperature sensing and it allows occupants to adjust the local setpoint and fan speed and view the local space temperature.
Content
1 Product Description 1 2 General Installation Requirements 2 3 General Wiring Recommendations 2 4 Mounting Instructions 2 5 Device Wiring 4 6 Maintenance 8 7 Disposal 8 8 Troubleshooting guide 8 9 Hardware Installation Guide 9
EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications
2/9
P100002807 A
The modern, sleek profile enclosure is suitable for classrooms, hotels, executive areas, office spaces & other commercial areas. Mounting hardware with a separate sub-base is provided with the device for installation on dry wall or on a electrical junction box.
This document describes the hardware installation procedures for the following devices: SAUTER EY-RU482F001 and SAUTER EY-RU483F001.
Unless otherwise indicated, the term VAV will be used in this document to represent all models of the EY-RC415 or EY-RC416 controller product lines. Likewise, the term EY-modulo4 Room Operating Unit will be used to represent the SAUTER room units type EY-RU482F001 and SAUTER EY-RU483F001.
General Installation Requirements2
For proper installation and subsequent operation of the EY-modulo4 Room Operating Unit, pay special attention to the following recommendations:
Upon unpacking the product, inspect the contents of the carton for shipping damages. Do • not install damaged devices. Allow for proper clearance of device enclosure and wiring terminals for easy access, • hardware configuration and maintenance. The device is designed to operate under the following environmental conditions:•
Ambient temperature from 5°C to 40°C•
Relative humidity from 0% to 95%, non-condensing. • Ensure proper ventilation of device and avoid areas where corroding, deteriorating or • explosive vapors, fumes or gases may be present. The device must be oriented with the ventilation slots towards the top to permit proper heat dissipation.
Take reasonable precautions to prevent electrostatic discharges to the device when installing, servicing or operating the device. Discharge accumulated static electricity by touching one’s hand to a securely grounded object before working with this device.
General Wiring Recommendations3
WARNING
Danger of electrocution
Turn off power before any kind of servicing. f
All wiring must comply with electrical wiring diagrams as well as national and local electrical • codes. To connect the wiring to the device, use the terminal connectors which are located inside • the device’s enclosure. Use a small flat screwdriver to tighten the terminal connector screws once the wires have been inserted. The board connectors accept wires or flat cables ranging from 22 to 14AWG • (0.644-1.630mm diameter) per pole.
Mounting Instructions4
The EY-modulo4 Room Operating Unit has been specially designed for easy installation. However, certain conditions apply when choosing a suitable location for the device:
The device should not be installed on an exterior wall.• The device should not be installed near a heat source• The device should not be installed near an air discharge grill.•
3/9
P100002807 A
The device should not be installed in a place were it can be affected by the sun.• Install the device in an area that provides proper device ventilation. Nothing must restrain air • circulation to the device.
NOTICE
The EY-RU481 has not been designed for outdoor use.
Installation procedure4.1
Remove the security screw from the device (Figure 1). 1.
Open the device by pressing in the two (2) tabs on the bottom of the device and pulling 2. the bottom side of the front plate outwards.
Flip the printed circuit board over to access the mounting hole. 3.
Pull all cables 6” out of the wall, and insert them through the central hole of the back plate. 4.
Align the back plate with the wall and mark the location of the two mounting holes on the 5. wall. Make sure to orient the proper side of the back plate facing upwards.
Remove the back plate and drill holes in the wall if necessary. 6.
Install anchors in the wall if necessary. 7.
Make sure that the mounting surface is flat and clean. 8.
Screw the back plate onto the wall. Do not over tighten. 9.
Strip each wire 6 mm and insert each one according to the wiring diagrams shown in this 10. document.
Gently push excess wiring back into the wall. 11.
Flip the printed circuit board back into place. 12.
Reattach the front plate and make sure it clips tightly into place. 13.
Install security screw.14.