Saunier Duval SEMIA CONDENS F30E Installation, Use and Servicing Instruction

Page 1
HIGH EFFICIENCY CONDENSING COMBINATION BOILER
Instructions for use Installation and servicing
Semia Condens F24 E G.C. 47-920-51 Semia Condens F30 E G.C. 47-920-52
Page 2
Page 3
Instructions for use
1 Important information ...........................................................2
2 Guarantee registration ..........................................................3
3 Appliance use ........................................................................4
4 Servicing ................................................................................4
5 Recycling ...............................................................................4
6 Operating the boiler (user instructions) .............................5
6.1 Control panel ................................................................................5
6.2 Commissioning and lighting .........................................................5
6.3 To program daily timeclock ...........................................................5
6.4 Temperature adjustment ...............................................................6
7 Turn the boiler off ..................................................................6
8 Fault finding ...........................................................................6
9 Frost protection .....................................................................9
9.1 Boiler frost protection ...................................................................9
9.2 Frost protection activation ............................................................9
Instructions for Use
10 Maintenance/After Sales Service .........................................9
1
Page 4
1 Important information
WARNINGS
Gas Leak or Fault
Turn off the gas emergency control valve immediately. Eliminate all sources of ignition, i.e. smoking, blowlamps, hot air
guns, etc. Do not operate electrical lights or switches either on or off. Open all doors and windows, ventilate the area.
Sheet Metal Parts
This boiler contains metal parts (components) and care should be taken when handling and cleaning, with particular
regard to edges.
Sealed Components
Under no circumstances must the User interfere with or adjust sealed parts.
Gas Category
This boiler is for use only on G20 natural gas, but the 30cxi may be converted for use on G31 gas (Propane L.P.G.).
Gas Safety (Installation and Use) Regulations
In your own interests and that of safety, it is the Law that ALL gas appliances are installed by a competent person in accordance with the current issue of the above regulations.
Testing and Certifi cation
This boiler is tested and certifi cated for safety and performance. It is, therefore, important that no alteration is made to the boiler, without permission, in writing, by Saunier Duval.
Any alteration not approved by Saunier Duval, could invalidate the certifi cation, boiler warranty and may also infringe the current issue of the statutory requirements.
CE Mark
This boiler meets the requirements of Statutory Instrument, No. 3083 The Boiler (Effi ciency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the effi ciency requirements for new hot water boilers fi red with liquid or gaseous fuels.
Type test for purposes of Regulation 5 certifi ed by: Notifi ed body
0087. Product/production certifi ed by: Notifi ed body 0086. The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonisation of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
Insulation Pads / Ceramic Fibre
These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to
irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal
good hygiene and wash your hands before eating, drinking or going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Electrical Supply
The boiler must be earthed. All system components shall be of an approved type and all wiring
to current I.E.E. wiring regulations. External wiring must be correctly earthed, polarised and in accor-
dance with the relevant standards. In GB this is BS 6891. In IE this is the current edition of I.S.813 “Domestic Gas Installa-
tions”. The boiler must be connected to a permanent 230V ac, 50Hz sup-
ply. Connection of the whole electrical system of the boiler, including
any heating controls, to the electrical supply must be through one common isolator and must be fused 3 Amp maximum.
Isolation should be by a double pole switched fused spur box, with a minimum gap of 3mm for both poles. The fused spur box should be readily accessible and preferably adjacent to the appliance. It should be identifi ed as to its use.
Alternatively connection can be made through an unswitched shut­tered socket and 3A fused 3-pin plug both to the current issue of BS 1363 may be used, provided they are not used in a room containing a bath or shower.
Wiring to the boiler must be PVC 85°C insulated cable, not less than
0.75mm2 (24/0.20mm).
2
Page 5
2 Guarantee registration
Thank you for installing a new Saunier Duval appliance in your home.
Saunier Duval appliances’ are manufactured to the very highest standard so we are pleased to offer our customers’ a
Comprehensive Guarantee.
This product is guaranteed for 24 months from the date of installation or 30 months from the date of manufacture,
whichever is the shorter, for parts. In addition this product is guaranteed for 12 months from the date of installation
or 18 months from the date of manufacture, whichever is the shorter, for labour.
The second year of the parts guarantee, from the beginning of the 13th month onwards after installation, is conditional
upon the boiler having been serviced by a CORGI registered gas installer, in accordance with the manufacturer’s
recommendations. We strongly recommend regular servicing of your gas appliance, but where the condition is not met, any
chargeable spare parts of components issued within the applicable guarantee period still benefi t from a 12 month warranty
from the date of issue by the manufacturer.
We recommend you complete and return as soon as possible your guarantee registration return literature, supplied in
the document envelope.
If your guarantee certifi cation return literature is missing you can obtain a copy by telephoning
the Saunier Duval Customer Service number 00 44 (0)1773 525914.
REGISTER YOUR SAUNIER DUVAL APPLIANCE DIRECTLY BY CALLING
00 44 (0)870 240 3413
Instructions for Use
Customer service:
Saunier Duval GB Great Britain:
Tel. 00 44 (0)1773 525914
Fax. 00 44 (0)1773 828070
Saunier Duval,
Nottingham Road, Belper, Derbyshire. DE56 1JT
Saunier Duval IE Ireland:
Tel. 00 3531 4508120
Taney Distribution
Unit 4, Riverside Industrial Estate
Bluebell Avenue
Dublin 12
Technical Advice Line:
Tel. 00 44 (0)1773 828400
General and Sales enquires:
Tel. 00 44 (0)870 606 4351
Fax. 00 44 (0)1773 820569
3
The code of practice for the installation,
commissioning & servicing of gas central heating
Page 6
3 Appliance use
4 Servicing
Saunier Duval’s appliances are manufactured according to the latest technical evolutions and current safety regulations.
This appliance is used to produce hot water using gas. Any other use is considered inappropriate and is forbidden.
The manufacturer shall not be responsible for any damage caused by another use. In that case the user shall be the responsible party.
Clean the case of the appliance with wet soapy cloth.
Do not use any abrasive cleaning product as they could damage the housing or plastic parts.
Also see section 12 & 35.
5 Recycling
The appliance comprises many recyclable parts. The packaging, the appliance and the content of the package shall not be thrown together with domestic waste but eliminated according to the current regulations.
4
Page 7
6 Operating the boiler (user instructions)
6.1 Control panel
5
1
9
8
234
10
Legend 1 Operating indicator 2 Operating mode selection 3 Heating temperature adjustment 4 DHW temperature adjustment 5 Display of the temperature /
error codes
6.2 Commissioning and lighting
Make sure that:
the boiler is connected to the electrical
­supply (the green indicator [1] blinks).
7
6
6 Pressure gauge 7 Safety lockout indicator 8 Timeclock 9 Timeclock toggles 10 Timeclock mode selector
6.3 To program daily timeclock
Set the current time, by turning the dial [8] clockwise until the current time is shown against the indicator ‘
’.
Instructions for Use
the gas service cock is open.
­Turn the selector [2] bringing it in the
• SUMMER The operating indicator [1] on the control panel turns on: the boiler is ready to run.
Turn the selector [2] to modify the
• operating mode of the boiler:
0
reset
or WINTER position.
Central heating and domestic hot water
Domestic hot water only
Installer mode
Stand-by and appliance frost protection
Push in plastic toggles [9] against the time you wish the heating to be off.
The timeclock can operate in three positions: automatic ‘ ’, heating permanently off ‘0’, and heating permanently on ‘1’.
To select, move the lever [10] to the desired position.
NOTE: In case the electrical supply fails
the timeclock will not operate as it has no back-up battery backup. Therefore, it will be necessary to reset the current time once electrical supply is restored.
5
Page 8
6.4 Temperature adjustment
6.4.1 Domestic hot water temperature
adjustment
Turn the knob
• domestic hot water max temperature.
6.4.2 Heating temperature adjustment
[4] to adjust the
7 Turn the boiler off
Turn the selector [2] on the 0 / reset
position
blinks).
We advise you to turn off the appliance gas supply if you leave home for a long period.
(the green indicator [1]
Turn the knob
• heating system temperature.
[3] to change the
8 Fault finding
GREEN LED [1]
The green led can be off, fl ashing (slowly or rapidly) or on.
OFF: the boiler is electrically disconnected. In these conditions the boiler obviously
doesn’t work. The Automatic Anti Freezing and Anti Blocking functions can’t be acti­vated (prevents damage to boiler during long period of inactivity). The external general switch could be off.
FLASHING (slowly): the boiler has power but the SUMMER/WINTER Selector is in central
position (0). The boiler will not provide heating or hot water but the boiler protection systems are operating (Anti Freezing and Anti Blocking functions may ignite the boiler and as such require the gas supply to be open).
FLASHING (rapidly): the Chimneysweep Function (which is reserved for the installer)
is on by mistake.
Turn it off bringing the SUMMER/WINTER selector on the central position (0) until
the green led fl ashes slowly.
ON: the boiler is on and the SUMMER/WINTER selector is in the SUMMER
the WINTER
Position. The boiler will provide heating and hot water on demand.
5
1
7
Position or in
6
9
8
234
10
6
Page 9
RED LED [7] - FAULT CODES AND LOCKOUTS
The red led [7] can be off, fl ashing or on.
Led OFF: the boiler is functioninging correctly. Led FLASHING: signals a boiler fault. The display [5] will show a fault code:
Fault code “06” - the heating system temperature sensor (inside the boiler) is
damaged. Call a Qualifi ed Technician to repair.
Led ON - The display [5] shows a fl ashing code. Things to try:
Code “01” - If the boiler has just been installed, or adjustments have been made
to the gas pipes.
If the air-gas mix ratio is incorrect then this will prevent combustion and can
force the boiler into a state of lockout. In order to correct the mix you should repeat the ignition process several times with the SUMMER/WINTER Selec-
tor on the 0 /
reset position until the red led turns off.
Code “01” - Ignition problems if no work has been carried out.
Ensure that the SUMMER/WINTER selector is on the 0 / reset position until the
red led turns off. If this does not happen or the boiler goes back into lockout please ask your installer to check the following points:
Check the CO
levels of the boiler are correct. Please refer to Technical Data
2
table in the section reserved for installers (in this manual);
Check the fl ue outlet for leaks and inspect general condition clearliness. Please refer to “Flue connection” in the section reserved for installers (in this manual).
Instructions for Use
Technical Note for the TECHNICIAN: if the Flame Control Unit is not detecting a fl ame
it could be due to one of the following reasons:
• the fl ame has not ignited;
• the fl ame control unit has become disconnected from the burner.
7
Page 10
Code “05” - The boiler is overheating and the Safety Thermostat has triggered.
Move the SUMMER/WINTER Selector on the 0 /
led turns off (this may take a while to allow the boiler to cool). Once the led is off move the selector to the desired position (Summer If the boiler locks out again please call the group service for assistance.
Code “05” - The boiler fl ue is overheating and the Flue Safety Thermostat has
triggered;
The thermostat must be replaced by the installer. Please try the following
process, if it does not work then call group service for assistance.
Move the SUMMER/WINTER Selector on the 0 /
led turns off (this may take a while to allow the boiler to cool). Once the led is off move the selector to the desired position (Summer If the boiler locks out again please call the group service for assistance.
Code “21” - You have insuffi cient water pressure (0.5 bar or lower).
Repressurise the system to the optimum pressure of between 1-1,5 bar
(cold) by following the procedure outlined in the paragraph “Commissioning” in the section reserved for installers (in this manual).
If a system continues to lose pressure it would suggest a system leak and
the system should be inspected for water loss. Also check that all radiators bleed points are closed or have not been recently opened before checking the system.
reset position until the red
or Winter ).
reset position until the red
or Winter ).
8
Page 11
9 Frost protection
9.1 Boiler frost protection
In case of frost risk, do as follows:
Make sure the boiler is supplied with electrical power and gas.
Turn the selector [2] on the 0 / position (the green indicator blinks).
The frost protection system operates the boiler as soon as the temperature in the heating circuit is under 5°C. The boiler stops as soon as the water temperature in the heating circuit reaches 30°C.
9.2 Frost protection activation
If you leave home for a few days, select
• the minimum heating temperature on the control panel of the boiler and just decrease the setpoint temperature on your room thermostat.
reset
[1]
10 Maintenance/After Sales Service
Please note that an incorrectly serviced appliance can affect the safety of the appliance and can lead to injury.
To ensure the continued effi cient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, refer to guarantee registration.
If this appliance is installed in a rented property there is a duty of care imposed on the owner of the property by the current issue of the Gas Safety (Installation and Use) Regulations, Section 35. Servicing/ maintenance should be carried out by a competent person in accordance with the rules in force in the countries of destination. To obtain service, please call your installer or Saunier Duval service team.
Instructions for Use
If you leave home for a long period, see
• chapter “Draining of the appliance” in
the section reserved for installers (in this manual).
9
Page 12
Installation and servicing
1 Comments on the instructions ..........................................12
2 Appliance description .........................................................12
2.1 Data label ...................................................................................12
2.2 Mandatory WARNING for EEC countries ...................................12
2.3 Block diagram .............................................................................13
3 Appliance location ..............................................................13
4 Safety instructions and regulations ..................................14
4.1 Safety instructions ......................................................................14
4.2 Regulations ................................................................................15
5 Appliance installation .........................................................16
5.1 Recommendations before mounting ..........................................16
5.2 Dimensions .................................................................................17
5.3 List of delivered equipment ........................................................18
5.4 Fixing to the wall .........................................................................18
5.5 Gas and water connection ..........................................................19
5.6 Connection to the condensate trap ............................................20
5.7 Flue connection ..........................................................................22
5.7.1 Flue restrictor .............................................................................22
5.7.2 Horizontal concentric flue Ø 60/100 (C13 type installation) ......24
5.7.3 Vertical concentric flue Ø 60/100 (C33 type installation) ...........24
5.7.4 Twin flue 2 x Ø 80 (C53 type installation) ...................................25
5.8 Electrical connection ..................................................................25
5.8.1 External controls .........................................................................26
5.9 Wiring diagram ...........................................................................28
6 Commissioning ...................................................................29
7 Specific adjustments ..........................................................29
7.1 Pump speed ...............................................................................29
7.2 Personalizing the boiler’s functioning .........................................31
8 Draining of the appliance ...................................................32
8.1 Heating circuit .............................................................................32
10
Page 13
9 Gas valve / Output power settings ....................................33
9.1 Gas valve setting ........................................................................33
9.2 Central heating output setting ....................................................34
9.3 Domestic hot water flow rate setting ..........................................34
9.4 Slow opening setting ..................................................................35
9.5 Changing gas type .....................................................................35
10 Fault finding .........................................................................35
11 Control / Commissioning ...................................................38
12 User information .................................................................38
13 Spare parts ..........................................................................38
14 Maintenance ........................................................................39
14.1 Casing ........................................................................................39
14.2 Combustion chamber .................................................................39
14.3 Burner .........................................................................................39
14.4 Heat exchanger ..........................................................................39
14.5 Reassembly of parts removed for servicing ...............................40
14.6 Flue system ................................................................................40
14.7 Operation of fan ..........................................................................40
15 Replacement of parts ..........................................................40
15.1 To replace fan .............................................................................40
15.2 To replace air pressure switch ....................................................40
15.3 To replace pump .........................................................................41
15.4 To replace gas valve ...................................................................41
15.5 To replace domestic heat exchanger ..........................................42
15.6 To replace thermistor ..................................................................42
15.7 To replace overheat thermostat ..................................................42
16 Technical data .....................................................................43
16.1 Burner pressure tables ...............................................................44
17 Boiler schematic .................................................................45
Installation and servicing instructions strictly reserved for qualifi ed gas installers
11
Page 14
1 Comments on the instructions
Please give all of the instructions to
• the user. The user shall keep them for future reference.
We accept no liability in case of damage due to the non-compliance of the instruction manual.
2 Appliance description
2.1 Data label
The data label certifi es the origin where the product was manufactured and the country for which it is intended. Warning! The appliance shall only be used with the gas types indicated on the data label.
Member States relating to appliances burning gaseous fuels.
Directive 73/23/EEC on the
­harmonisation of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
Directive 89/336/EEC on the
­approximation of the Laws of the Member States relating to electromagnetic compatibility.
IMPORTANT. With regards to the Manual Handling Operations, 1992 Regulations, the following lift operations are recommended as the appliance weight exceeds a one-man lift.
Clear the route before attempting the
• lift.
2.2 Mandatory WARNING for EEC countries
This appliance is designed, approved and inspected to meet the requirements of the intended market. The data label indicates where the product was manufactured and the country for which it is intended.
This appliance meets the requirements of Statutory Instrument, No. 3083 The Appliance (Effi ciency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the effi ciency requirements for new hot water appliances fi red with liquid or gaseous fuels.
Type test for purposes of Regulation 5 certifi ed by: Notifi ed body 0063. Product/ production certifi ed by: Notifi ed body
0086.
The CE mark on this appliance shows compliance with:
Directive 90/396/EEC on the
­approximation of the laws of the
Ensure safe lifting techniques are used
- keep back straight - bend using legs. Keep load as close to body as possible.
• Do not twist - reposition feet instead.
• If two persons performing lift, ensure
• co-ordinated movements during lift.
Always use assistance if required.
Manufacturer’s instructions must not be taken as overriding statutory requirements. Reference in these instructions to British standards and statutory regulations/ requirements apply only to the United Kingdom. For Ireland the current edition of I.S.813 «Domestic Gas Installations» must be used.
This appliance certifi cated to the current issue of EN 483: 2000 for performance and safety. It is important that no alteration is made to the appliance, without permission, in writing, from Saunier Duval. Any alteration that is not approved by Saunier Duval could invalidate the warranty and could also infringe the current issue of the Statutory Requirements.
12
Page 15
2.3 Block diagram
1 Drain valve 2 Pressure gauge / thermometer 4 By-pass 5 Pump 6 Heating system safety valve 3 bar 7 Expansion vessel 8 Overheat thermostat 9 Condense syphonic trap 10 Automatic air vent 11 Recuperator 12 Flue overheat safety thermostat 13 Air pressure switch 14 Fan 15 Flue hood 16 Primary heat exchanger 17 Burner 18 Thermistor 19 Hydraulic 3-way valve 20 Water valve 21 Domestic plate to plate
heat exchanger 22 Gas valve 23 low pressure sensor
CONDENSE
(orange)
FLUE
WARNING: This schematic is for information only.
3 Appliance location
This appliance is not suitable for
• outdoor installation.
This appliance may be installed in any
• room, although particular attention is drawn to the installation of an appliance in a room containing a bath or shower where reference must be made to the relevant requirements. In GB this is the current I.E.E. WIRING REGULATIONS and BUILDING REGULATIONS.
GAS
FLOW
(green)
RETURN HEATING
In IE reference should be made to the
(green)
INLET
(black)
OUTLET
DOMESTIC
WATER
(white)
(white)
current edition of I.S.813 «Domestic Gas Installations» and the current ETCI rules.
Make sure you keep the minimum clearances to ensure total accessibility for servicing. Top: 150 mm; bottom: 200 mm; side: 5 mm.
The appliance must be mounted on a
• fl at wall, which is suffi ciently robust to take its weight.
Installation and servicing instructions strictly reserved for qualifi ed gas installers
13
Page 16
The appliance is room sealed, so when
• it is installed in a room or space, a permanent air vent is not required.
Do not install the appliance above
• another appliance that could damage it (for example, above a cooker that might emit steam or grease) or in a room, which has a lot of dust in the atmosphere which is corrosive.
to provide information on substances hazardous to health. The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
In the event of the appliance overheating the safety devices will cause a safety shutdown. If this happens, call your installation/servicing company.
4 Safety instructions and
regulations
This appliance is tested and certifi cated for safety and performance. It is, therefore, important that no alteration is made to the appliance, without permission, in writing, from Saunier Duval. Any alteration not approved by Saunier Duval, could invalidate the certifi cation, appliance warranty and may also infringe the current issue of the statutory requirements.
4.1 Safety instructions
If the gas pressure at the input of the appliance is outside the range specifi ed, you shall not start the appliance. If the cause of the problem cannot be found nor solved, please contact the Gas Utility company.
Warning! This appliance must be earthed. This appliance must be wired in accordance with these instructions. Any fault arising from incorrect wiring cannot be put right under the terms of the Saunier Duval guarantee.
The following safety instructions must be imperatively followed during the maintenance and the replacement of spare parts.
Stop the appliance (see chapter “Turn
• the boiler off” in the “Instructions for use” section, in this manual).
Deactivate the appliance from the
• mains power supply with the socket or the double-pole switch (with a minimum gap of 3mm for both poles).
Turn off the gas control valve.
Warning! Incorrect installation can cause electric shock or appliance damage.
When making the connections, locate
­the sealing washers properly so as to avoid any gas or water leakage.
Never use a wire brush or stiff-bristle
­scrubbing brush to clean the heat exchanger as this could damage the appliance.
Under no circumstances must the User
­interfere with or adjust sealed parts.
Under Section 6 of The Health and Safety at Work Act 1974, we are required
14
Close the shut off valves located on the
• connection sockets.
Drain the appliance when you want
• to change the hydraulic parts of the appliance.
Let the appliance cool down before
• undertaking any maintenance operation.
Protect all the electrical components
• from water when you achieve any operations.
Use only new O-rings and gaskets.
Page 17
After having carried out work on the
• gas carrying components check that they are correctly fi tted and sealed by checking for leaks.
When the work is complete check the
• boiler operates correctly.
4.2 Regulations
When installing and commissioning the appliance, the regulations below shall be observed in their current version:
In your own interests and that of safety, it is the Law that ALL gas appliances must be installed by a competent person only, in accordance with the current issue of the above regulations.
In GB the installation of the appliance must be carried out by a competent person as described in the following regulations:
The manufacturer’s instructions
­supplied.
The Gas Safety (Installation and Use)
­Regulations.
The appropriate Buildings Regulations
­either The Building Regulations, The Building Regulations (Scotland), The Building Regulations (Northern Ireland).
The Water Fittings Regulations or
­Water byelaws in Scotland.
reference should be made to the current ETCI rules for Electrical Installation.
In GB the following Codes of Practice apply: BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593, BS7671. In IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.
Where no British Standard exists, materials and equipment should be fi t for their purpose and of suitable quality and workmanship. The installation of this appliance must be carried out by a competent person in accordance the rules in force in the countries of destination. Manufacturer’s instructions must not be taken as overriding statutory requirements.
If the appliance is to be installed in a timber frame building it should be fi tted in accordance with the Institute of Gas Engineers document IGE/UP/7/1998. If in doubt seek advice from the local gas undertaking or Saunier Duval.
The installation is subject to building regulation approval, notify the Local Authority of intention to install.
The Health and Safety at Work Act,
­Control of Substances Hazardous to Health (COSHH).
The Current I.E.E. Wiring Regulations.
-
Where no specifi c instructions are given, reference should be made to the relevant British Standard Code of Practice. In IE, the installation must be carried out by a competent person and installed in accordance with the current edition of I.S.813 «Domestic Gas Installations», the current Building Regulations and
Installation and servicing instructions strictly reserved for qualifi ed gas installers
15
Page 18
5 Appliance installation
All the dimensions in this chapter are expressed in mm.
5.1 Recommendations before mounting
5.1.1 Domestic hot water circuit design
The circuit should be designed to avoid any unnecessary fl ow losses (decrease the number of elbows).
The boiler will operate with a minimum supply pressure but with a low fl ow. Optimum performance will be achieved with a pressure of 1 bar (cold).
5.1.2 Heating circuit design
SEMIA CONDENS boilers can be used for any kind of installation: serial or derivated double tube, single tube, under fl oor heating, etc... Heating surfaces can be made up with heaters, convectors or unit heaters.
Warning: If the materials used are of a different type, some corrosion can occur. In that case, we advise you to add an inhibitor to the heating circuit water (according to the manufacturer’s recommendations) that could avoid gas production and oxide formation.
The pipework sections should be fi xed by using the following fl ow/pressure curve (see chapter “Heating circuit adjustment”). The system will be calculated according to the fl ow corresponding to the power
that is really required without taking into account the maximum power that the boiler can supply. Nevertheless, we advise you to have a fl ow big enough so that the temperature difference between outgoing and return is under or equal to 20°C. The minimum fl ow rate is indicated in the chapter “Technical Data” at the end of this instruction manual.
The piping route should be designed in such a way that it avoids any air locks and make purging of gas from the system easier. Bleeders should be placed at each high point of the system as well as on any radiators.
Total water volume accepted by the heating circuit depends, amongst other things, on the cold static load. The expansion tank fi tted in the boiler is delivered set in plant (see chapter “Technical Data” at the end of this instruction manual). At commissioning, it is possible to change this pressure in case of a larger static load. We advise you to provide a drain valve at the lowest point of the system.
If thermostatic radiator valves are used, we advise you not to fi t in a room where a room thermostat is fi tted.
In case of an old installation, the
• system should be fl ushed. See section
5.1.4. If the boiler is not immediately set,
• protect all the pipe fi ttings so as to avoid that any plaster element or paint could impede the connection.
16
Page 19
5.1.3 Water treatment
In the case of an existing installation, it is Essential that prior to installing the new boiler the system is thoroughly fl ushed. For optimum performance after installation of a new system, the boiler and its associated central heating system should also be fl ushed. Flushing should be carried out in accordance with BS7593: 1992 using a cleanser such as Sentinel X300 or X400, Fernox Superfl oc or Salamander corrosion guard cleaner.
For long-term corrosion protection, after fl ushing, an inhibitor suitable for stainless steel heat exchangers should be used, refer to the current issue of BS 5449 and BS 7593 on the use of inhibitors in central heating systems. Examples are Sentinel X100 Fernox or Salamander corrosion guard inhibitor.
5.2 Dimensions
F Cold water inlet (white) T Room thermostat L Electrical power supply G Gas (white)
400 347
116
284
223
R Heating return (green) M Heating fl ow (green) SC Condense outlet
(orange) (fl exible pipe)
C Hot water outlet (black)
RM
SC
52 52 88 39
TLFCG
403046 53
CONNECTIONS FOR FLUE
116
750
735
2
1
13
941_2
1 Flue products outlet
2 Air inlet for concentric system
223
942_1
17
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 20
5.3 List of delivered equipment
The boiler is delivered in two packages:
The boiler
-
One isolating valve pack:
-
- 2 heating isolating valves
- 1 domestic cold water isolating valves
- 1 gas isolating valves
One safety discharge pipe pack:
-
- 1 safety discharge pipe
- 1 1/2 in. gasket
One installation and documentation
-
pack:
- 1 user and installation manual
- 1 guarantee envelope
- 1 gas conversion instructions sheet
- 1 log book
- 1 condense drain pipe
- a set of 1/2 in. gaskets
- a set of 3/4 in. gaskets
One pipe pack:
-
- 2 central heating pipes
- 2 gas/cold water pipes
- 1 hot water pipe
- a set of 1/2 in. gaskets
- a set of 3/4 in. gaskets
- 1 wall template
- 1 hanging bracket
The fl ue is supplied separatly and will depend upon the confi guration of the installation.
5.4 Fixing to the wall
Make sure the material you use fi ts
• those of the appliance.
Chose the location of the appliance.
• See chapter “Appliance location”.
18
1033_R01
GREEN
GREEN
BLACK
ORANGE
WHITE
WHITE
Page 21
The hanging bracket will be adapted to
• the features of the bearing wall and will have to take into account the weight of the boiler (please refer to Technical Data table in this manual);.
Drill the holes for the fi xing screws
• in accordance to the diagram below and to the size of the wall template delivered with the appliance.
The heating safety discharge valve must be connected, using not less than 15mm o.d. pipe, to discharge, in a visible position, outside the building, facing downwards, preferably over a drain.
The pipe from the safety discharge valve must not discharge above an entrance, window or any type of public access area.
Place the boiler above the hanging
• bracket.
Slowly lower the boiler.
• Set the seals on the different pipe
• fi ttings.
Make connections to boiler, gas,
• water and heating cocks with the tube assemblies supplied in piping pack.
5.5 Gas and water connection
Before undertaking any operation,
• carefully clean the pipes with an appropriate product in order to remove impurities such as fi lings, welds, different oils and greases that may be present. These foreign bodies may enter the boiler and disrupt the operation.
The pipe must have a continuous fall and be routed to a position so that any discharge of water, possibly boiling, or steam cannot create any danger to persons, damage to property or external electrical components and wiring.
To ease future servicing it is advisable to use a compression type fi tting to extend the safety discharge valve tube.
Warning! Relief valve connections should not be used for any other purpose.
Do not use any solvents that could
• damage the heating circuit.
Do not brase the nozzles set on place:
• this operation could damage the seals and the taps tightness.
Only use the genuine seals delivered
• with the appliance.
Check that there is no leakage. Repair
• if need be.
Installation and servicing instructions strictly reserved for qualifi ed gas installers
19
Page 22
5.6 Connection to the condensate
trap
Connect the fl exible pipe to a discharge
• system leading to the sewer in compliance with the instructions below:
Use the condensate drain fl exible
• connection pipe supplied.
Ensure there is a conbinual fall of 2.5°
• (44 mm/m).
Do not let the condensate drain fl exible
• connection fall into the trap.
Do not use copper pipes.
Important notice: The fl oat in the condensate trap also ensures fume tightness. Therefore, it is not necessary to add water in the condensate trap.
OK
OK
20
Page 23
1041_R00
Installation and servicing instructions strictly reserved for qualifi ed gas installers
21
Page 24
5.7 Flue connection
Different fl ue outlet confi gurations can be carried out.
Consult your supplier for more information about the other possibilities and associated accessories.
Warning! You can only use fl ue accessories approved for the SEMIA CONDENS.
Saunier Duval’s horizontal fl ue automatically provides a 3° angle that enables the return of the condensates to the appliance.
Whatever the kind of fl ue system
• chosen, observe the minimum distances indicated in the chart on the next page to position the fl ue terminals.
5.7.1 Flue restrictor
Depending on the length of the fl ue system, it may be necessary to install the fl ue restrictor “D”. The length of the system is specifi ed for each fl ue confi guration.
Then, install the plastic adaptor “A”.
A D
22
Page 25
R
S
Position Horizontal flues
A
B
C
D below gutter, drain/soil pipe 25 E below eaves 25 F below a balcony or car port
G
H
Position of the flue terminal
directly below an opening, air brick, opening windows
above an opening, air brick, opening windows
horizontally to an opening, air brick, opening windows
from vertical drain pipes and soil pipes
from internal/external corners
mm
300
300
300
25 25
25
H*
I
J
K facing terminals 1200
L
M vertical from a terminal 1500 N horizontally from a terminal 300
Vertical flues
P from another terminal 600
Q above roof level 300 R
S from adjacent wall to flue 300
to a boundary alongside the terminal
above adjacent ground or balcony level
from surface or a boundary facing the terminal
from opening (door/ window) in car port into dwelling
from adjacent opening window
300
300
600
1200
1000
Installation and servicing instructions strictly reserved for qualifi ed gas installers
23
Page 26
H*: This dimension comply with the building regulations, but it may need to be increased to avoid wall staining and nusance from pluming depending on site conditions.
5.7.2 Horizontal concentric fl ue Ø 60/100 (C13 type installation)
IMPORTANT: turn the coaxial socket 45°
(as shown in the picture) when horizontal concentric fl ue Ø 60/100 is used.
45°
1035_R01
A Plume mangement kit can be installed at the extremity of the duct.
Every time a 90° elbow is used (or 2 off 45°), the length (L) should be reduced by 1 m.
5.7.3 Vertical concentric fl ue Ø 60/100 (C33 type installation)
L
L
1
72
1034_R00
Legend 1 Gasket
Maximum fl ue index: 150 Pa
This value is reached with the length of the maximum duct (L) + 1 90° elbow.
Flue model
Ø 60/100
horizontal
Boiler model
F24 E 4 m < 2 m F30 E 3 m < 1 m
Max.
length L
Restrictor
if length
Maximum fl ue index: 150 Pa
This value is reached with the length of the maximum duct (L) + 1 90° elbow.
Flue model
Ø 60/100
vertical
Boiler model
F24 E 5 m < 2 m F30 E 4 m < 1 m
Max.
length L
Restrictor
if length
Every time an extra 90° elbow is used (or 2 off 45°), the length (L) should be re­duced at by 1 m.
24
Page 27
5.7.4 Twin fl ue 2 x Ø 80 (C53 type installation)
Warning!
-
Any duct that goes through a wall and whose temperature is over 60°C from the room temperature will be thermally insulated at this passage. The insulation will be composed of an appropriate insulating material whose thickness is ≥ 10 mm and thermal conductibility λ ≤ 0.04 W/m.K.
For separator correct and wrong positions, refer to the following diagram:
1043_R00
L2
L1
L1
188
Maximum fl ue index: 150 Pa
This value is reached with 2 elbows, the separator and the maximum duct length (L1+L2).
Flue model
Ø 80
twin
Boiler model
F24 E 10 (9) m always F30 E 10 (9) m always
Max.
length
L1+L2 (L2)
Restrictor
if length
L1+L2
5.8 Electrical connection
Warning! Incorrect installation can cause electric shock or appliance damage.
Connect the power cable of the boiler to
• the 230 V single-phase + earth network.
Observe the phase and neutral
• connection on the boiler.
Important: A skilled professional should achieve the electrical connection of the appliance.
Isolation should be by a double pole switched fused spur box, with a minimum gap of 3mm for both poles.
The fuse of the PCB must be connected to the neutral.
Every time an extra 90° elbow is used (or 2 off 45°), the length (L) should be re­duced by 0.5 m.
Installation and servicing instructions strictly reserved for qualifi ed gas installers
25
Page 28
5.8.1 External controls
The boiler will work for heating AS DELIVERED without a room thermostat fi tted provided the two wires on the integral external controls lead REMAIN LINKED TOGETHER.
ANY EXTERNAL HEATING CONTROL MUST BE POTENTIAL FREE (see Figure 1). ON NO ACCOUNT MUST ANY ELECTRICAL VOLTAGE BE APPLIED TO EITHER OF
THE TERMINALS OF THE WHITE EXTERNAL CONTROLS LEAD WARNING: This boiler must be wired in accordance with these instructions. Any
fault arising from incorrect wiring may invalidate the terms of the guarantee.
1) INTERNAL TIME CLOCK WITH EXTERNAL ROOM THERMOSTAT
If a room thermostat is required it must be connected to the external controls lead as shown in fi gure 1, using a suitable electrical connection.
POTENTIAL
FREE ROOM
THERMOSTAT
617R01
Figure 1
FUSED MAINS
SPUR OR
FUSED 3 PIN
PLUG
BLACK MAINS LEAD WHITE EXTERNAL CONTROL LEAD
BOILER
Internal time clock (factory fitted)
External potential-free room thermostat
2) CONNECTION WITH EXTERNAL PROGRAMMER
Any eventual external programmer must be connected in series with the room thermostat (see fi gure 2)
IMPORTANT: the boiler time clock must be linked across (see the REMARK below)
FUSED MAINS
SPUR OR
FUSED 3 PIN
PLUG
PROGRAMMER
BOILER
ROOM
THERMOSTAT
Figure 2
BLACK MAINS LEAD WHITE EXTERNAL CONTROL LEAD
Internal time clock (factory fitted) disconnected
External potential-free room thermostat
External potential-free programmer
26
617A
Page 29
3) CONNECTION WITH EXTERNAL CHRONOTHERMOSTAT
As an alternative solution it is possible to connect a single external chrono-thermostat which makes the double function of a room thermostat and a programmer (see fi gure 3)
IMPORTANT: the boiler time clock must be linked across (see the REMARK below)
FUSED MAINS
SPUR OR
FUSED 3 PIN
PLUG
BOILER
BLACK MAINS LEAD WHITE EXTERNAL CONTROL LEAD
CHRONOTHERMOSTAT
Figure 3
Internal time clock (factory fitted) disconnected
External potential-free chrono-thermostat
617B
REMARK: In case of installation of an external programmer (see fi gure 2 and 3) the internal time clock (factory fi tted) must be excluded acting in the following way:
1. Remove the front panel of the boiler;
2. Gain access to the PCB;
3. Disconnect the two low voltage wires connected to the clock and make a link by using the “wiring link” supplied in the Documentation Pack as shown in fi gure 4.
Figure 4
220 Vac
from PCB
(M1 2-4)
Time clock low voltage terminals from PCB (M6 18-19)
220 Vac
from PCB
(M1 2-4)
Time clock low voltage terminals from PCB (M6 18-19) to link across
27
“wiring link”
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 30
5.9 Wiring diagram
C Pump PSA Loss of water pressure switch
(“NO” contact closed = in pressure) MOD Modulating coil S Thermistor MP Water valve microswitch CA Ignition and fl ame control unit EA Ignition electrodes ER Flame sense electrode F1 Fuse (2 A) TA Voltage-free contact for room Thermo-
stat or Cronothermostat
Colour abbreviations:
BK Black BN Brown BU Blue GN Green GNYE Green-Yellow GY Grey OG Orange RD Red VT Violet WH White
TC Syphonic condensate trap
with overfl ow sensor TF Flue Overheat thermostat TS Overheat thermostat MV Fan MPV Air pressure switch AO Timeclock power supply CO Timeclock microswitch SD Display board (SE) External temperature sensor (optional)
28
Page 31
6 Commissioning
Turn the mode selector to the WINTER
• position.
The green operating indicator on the control panel turns on: the boiler is ready to operate.
Open the isolating valves located on
the pipes: they will be placed in the direction of the fl ow.
Open the automatic bleeders of the
system. Open the fi lling loop valve situated
under the boiler until you obtain a 1 bar pressure on the indicator (cold).
Bleed each radiator to remove the air,
re-tighten bleed screws.
7 Specific adjustments
7.1 Pump speed
1
2
3
4
Legend 1 Speed III 2 Speed II 3 Speed I 4 Speed selector of pump
Leave the cap on the pump auto air
vent open. Flush the domestic hot water system by
opening the hot water taps for several minutes.
Make sure the display indicates a
system pressure of between 1 and 2 bars. Re-fi ll system as necessary.
Make sure the condense syphon works
properly. It ensures the seal only when it’s fi lled with condense (or water).
Turn the selector (4) to choose pump
• speed I, II or III in relation to the output/ pressure curve (see next page).
29
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 32
Output/pressure curve
6
O
2
5,5
5
4,5
Pressure m. H
4
3,5
3
2,5
2
1,5
1
0,5
0
0 200 400 1000 1200600 800 1400
Semia Condens F24 E
977 R00
Water fl ow l/h
Semia Condens F30 E
7
O
2
6,5
6
5,5
Pressure m. H
5
4,5
4
3,5
3
2,5
2
1,5
1
0,5
0
0 200 400 1000 1200600 800 1400
1038
R00
Water fl ow l/h
30
Page 33
7.2 Personalizing the boiler’s functioning
(for professional and After Sales Service use only)
The SEMIA CONDENS models are equipped with a Microprocessor P.C.B., with an array of 8 microswitches (SW3 / 1-8) which allow to make personalizing actions for the boiler’s functioning. The fi rm arrangements are underlined.
Disconnect the power supply before touching the microswitches. Restore the
power supply only after you have closed the back cover of the control panel.
Note: the changes to the microswitches have no effect until the boiler is electrically
connected.
SW3
OFF
ON
ON
12876543
706_SMC_R00
.
31
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 34
SW3 / 1 – Natural gas Functioning = OFF. LPG Functioning = ON. All the operations to
change the gas type are described on a separate document provided with the boiler.
SW3 / 2 – Heating Flow Temperature Range: OFF = normal (+30°C/+80°C); ON = reduced
(+25°C/+45°C). The reduced arrangement is used for low temperature systems, but the best results with this type of system are gained with the normal arrangement, using the suitable optional Low Temperature Kit.
SW3 / 3 – Gives a 3 minute delay (anti-cycling) preventing ignition after the heating set
temperature has been exceeded. OFF = Delay ON (for normal systems or radiators);
ON = Delay OFF (for fan coil systems).
SW3 / 4 – It determines the extinction and new ignition temperature for DHW: OFF = Burner
OFF at 75°C and burner ON at 70°C; ON = burner OFF at the arranged temperature for DHW (T.SET) + 5°C, and burner ON at T.SET (this arrangement is suggested for water with a high percentage of scale and not treated)
SW3 / 5 and 6 – Pump working mode (during heating):
5 OFF – 6 OFF: intermittent for normal applications (with or without delay, see
SW3/3)
5 OFF – 6 ON: always turned off (with outside circulators) 5 ON – 6 Unimportant (OFF or ON): always on (for high thermic inertia systems)
SW3 / 7 and 8 – In SEMIA CONDENS boilers they must be OFF.
8 Draining of the appliance
8.1 Heating circuit
Open the drain cock provided at the system low point.
• Provide an air intake by opening a radiator bleed screw.
• In order to drain only the water in the boiler, fi rst shut off the heating fl ow and return
• isolating valves.
32
Page 35
9 Gas valve / Output power settings
9.1 Gas valve setting
— Check that the inlet pressure is correct for
G20 gas;
3 4
Move the Summer/Winter Selector to Chimney Sweep the selector return to the Summer green led fl ashes rapidly and the burner ignites at maximum rate for a defi ned period of time to allow all of the checks to be made. The produced heat is carried off by the heating system;
Wait for at least 10 seconds and check that the pressure corresponds to the highest value indi­cated in the “Power Pressure” table of the specifi c model. If it is necessary to correct the pressure, use the following procedure:
position for at least 3 seconds, then let
position. The
• make sure that the modulation coil is energised;
remove protection cap “C”. Take off the silicon tube from the “VENT” on the gas valve (item 3 in the fi gure);
• adjust maximum pressure by turning knob “B”, with a 10 mm. spanner. Clock­wise to increase, counterclock wise to decrease;
1
2
892_R00
1 = Pressure tapping point
for gas outlet
2 = Pressure tapping point
for gas inlet
3 = Vent (mod. SE)
C
B
A
remove electrical connector on modulation coil;
keeping knob “B” locked, adjust minimum pressure unscrewing screw “A” very slowly, using a 4 mm screwdriver;
refi t electrical connector on the modulator and check settings;
turn off the burner by turning the Summer/Winter selector to the central position. The green led fl ashes slowly.
• Refi t the silicon tube in the “VENT” on the gas valve (item 3 in the fi gure). ATTEN­TION: after this operation, the value indicated by pressure gauge could decrease due to pressure compensation. This is normal and does not require any adjustment.
Important: lock the adjustment device after any setting operation.
Installation and servicing instructions strictly reserved for qualifi ed gas installers
33
Page 36
9.2 Central heating output setting
The central heating output can be set in accordance with the system requirements. To adjust the burner pressure, proceed as follows, referring to “Burner pressure tables” paragraph (in this manual):
- Gain access to the PCB, see diagram above.
- Set the ‘summer/winter’ switch to the ‘winter’ position
- Light the burner and check the gas pressure
- Adjust the pressure using potentiometer P1 MAX.R. on the PCB.
- Refi t cover to controls housing.
CONTROLS HOUSING
701_1_R00
9.3 Domestic hot water fl ow rate setting
The domestic hot water fl ow rate is factory set. However, after installation, it may be necessary to adjust the do­mestic hot water fl ow rate, proceed as follows:
PCB
704_R01
- Fully open a domestic hot water tap.
- Using a suitable water fl ow gauge, adjust water fl ow by turning the adjuster screw on the water valve (see photo).
34
Page 37
9.4 Slow opening setting
To adjust the slow opening, proceed as follows:
- switch off the boiler;
- Gain access to the PCB as described on previous page
NOTE: you will have 8 seconds to regulate the slow opening pressure, and after this the
burner pressure increases to the highest value. To increase this period of time to 30 seconds, turn the trimmer P1 MAX.R. fully anticlockwise (it will be necessary to reset the Max Heating output after this operation).
- turn on the boiler and open a cold water tap, the burner will light and the slow opening setting pressures can be checked.
The setting pressure is: 7 mbar (71 mm w.g.) Turn the trimmer P4 RLA (clockwise to increase the pressure and anticlockwise to
decrease the pressure)
CONTROLS HOUSING
701_1_R00
PCB
704_R01
9.5 Changing gas type
All the operations to change the gas type are described on a separate document provided with the boiler.
10 Fault finding
You will fi nd the list of the fault codes in the User Instructions section. Fault fi nding must be carried out by a skilled professional and if need be by SAUNIER DUVAL’s After Sales Service.
Important: a central heating system cannot operate effi ciently if it is not fi lled with water and if the air has not been completely removed. If those requirements are not fulfi lled, the boiler could possibli generate unwanted noise.
35
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 38
- To carry out electrical continuity tests across the components make sure: a) electrical supply is OFF and the multimeter is set to the :
position,
b) the connectors of the component to check are disconnected
- During checks, verify the integrity of the wirings and their correct electrical connections
TURN THE MAIN SELECTOR TO THE POSITION “STAND-BY”
a) Is the Has the main
green led
flashing?
NO
electrical supply
connector 230 V
NO
YES
- Check the 230 V electrical supply circuit
- PCB fuse blown
across L and N ? - PCB faulty
YES
TURN THE MAIN SELECTOR TO “SUMMER”, SET THE HOT WATER KNOB AT MAXIMUM, TURN OFF TAPS
b)Is the green led permanently on?
YES
NO
- Replace PCB
c) Is the Is the
red led
off?
NO
red led
permanently - Insufficient water pressure (below 0,5 bar)
on ?
YES
d) Does
NO
Is there continuity on
NO
YES
- If the red led is flashing, NTC sensor faulty
- Low water pressure switch faulty
NO
- Replace PCB the boiler DHW flow microswitch ? - Check, on the PCB, switches 7 and 8 are off stay off? terminals 16 and 20 )
YES
(PCB-M6 connector, across)
YES
- Domestic hot water flow switch faulty
TURN ON THE HOT WATER TAP AT THE MAXIMUM FLOW RATE
e) Does the water Is the main
come
through the tap?
YES
NO
NO
water supply
turned on?
YES
- Turn on valves or check the water supply feeding system
- Flow rate regulator turned off or boiler inlet filter dirty
f) - Clean or replace the diaphragm inside domestic water priority valve
- If not continuity on PCB-M6 across terminals 16-20, flow switch faulty
- PCB faulty
- Ignition unit faulty
NO
If the fan is not running:
- Air pressure switch faulty, if there is not continuity across C and NC
- Fan faulty, if there is 230 V across fan connectors
- Ignition unit faulty, if there is not 230 V across fan connectors
Does the boiler If the fan is running:
start working Does - Air pressure switch tubes disconnected or obstructed
and the burner boiler - Air pressure switch faulty, if there is not continuity across C and NO
ignite after
a few seconds?
NO
Lock- - Replace PCB if all the above checks did not produce successful result
out?
If the burner does not ignite:
- Insulating gas valves turned off
- Ignition electrode dirty or broken
YES
- Gas valve faulty, if the ignition unit has 230V across terminals 14 - N
during the ignition phase
- Overheat thermostat faulty or boiler temperature over 100°C
- Flue thermostat faulty or in open circuit
- Minimum gas pressure to be adjusted on the gas valve ( see manual )
If the burner ignites:
- Life and neutral reversed polarity
- Ionisation electrode dirty or broken.
- Condensate siphon is not draining or ionization wiring disconnected
- Ignition unit faulty ( no ionization )
YES
36
Page 39
YES
g) Does
the
NO
- Check if pump is blocked
- Pump faulty, if there is 230 V across pump terminals
pump run? - PCB faulty, if not power is supplied to the pump
YES
h) Does the flame
rise up
NO
- Check and adjust the gas pressures on the gas valve as indicated in the manual
- Gas valve modulator faulty, if there is nearly 5 v = across the modulator terminals
after 8 seconds? - PCB faulty, if there is not power to the modulator or the voltage is less than 3V =
YES
i) Is Is the domestic hot
the water warming up to the tap? indicated in the manual ?
YES
NO
NO
water flow rate - Check gas valve for correct gas regulation
greater than the one
YES
- Domestic hot water exchanger dirty
- Reduce the hot water flow rate to the tap
DECREASE THE HOT WATER FLOW RATE TO APPROXIMATELY 5 LITER PER MINUTE
j) Does Check resistance NTC values In case of difficulty:
the flame
modulate
a few seconds ?
YES
of the NTC sensor and if necessary,
NO
replace
the NTC
0°C = 33 k: 20°C = 12,5 k:
60°C = 2,5 k: 80°C = 1,3 k:
- Check the gas valve for correct gas pressure
- Check on the PCB the after switches 7 and 8 are set to OFF
TURN OFF THE HOT WATER TAP
TURN THE MAIN SELECTOR TO “WINTER”, SET THE HEATING KNOB AT MAXIMUM, TIME-CLOCK TO “1”
k) Does
the
NO
boiler calling for
Is the room
thermostat Make a link on the PCB-M10 across terminals 39 and 40:
NO
YES
- Set the temperature on the room thermostat
- Room thermostat faulty, if the boiler starts working
work? heating? - Faulty time-clock,if no continuity across switch terminals
- PCB faulty, if the boiler does not operate
YES
l) Does the pump start ?
YES
m) Do radiators heat up? turned on ?
YES
n) Is the water
pressure
stable on the when temperature
NO
Are the switches 5 and 6
on the PCB
in position OFF ?
NO
NO
Are all the
valves of the system
Does the pressure rise up over 2 bar
NO
YES
NO
YES
NO
YES
- Set switches 5 and 6 to the off position
- Replace PCB
- Turn on all the radiator valves and insulating valves
- Bleed air out of the radiators
- Verify the filling check valves are turned off
- Pressurize the expansion vessel. If leaks occurs from
pressure gauge? is above 50°C the valve, replace the expansion vessel
YES
END OF THE TEST
Guide for the correct electrical reading
37
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 40
11 Control / Commissioning
13 Spare parts
Once the appliance is installed, check whether it operates correctly:
Start the appliance according to the
• indications of the operating instructions and check whether it operates correctly.
Check the appliance for leaks (gas
• and water) and eliminate any leakage found.
Check that the ignition is correct and
• that the fl ames of the burner are uniform.
Check that the fl ue exhausts properly.
Check the full control and safety devices, their setting and their operating states.
In order to guarantee the reliability and quality of the individual components and the correct functioning of the boiler, only authentic spare parts from SAUNIER DUVAL should be used when repairing and servicing the appliance.
12 User information
It is your responsability to ensure that the user knows how to use the appliance. Points to explain:
Explain to the user the appliance operating principles and demonstrate if required.
Have a look at the operating instructions together and answer any questions if need be.
Give the user all of the manuals and documents concerning the appliance and tell the user to keep them near the appliance.
Explain more precisely the safety principles they should observe.
Remind the user to regularly service the appliance (every 12 months recommended).
38
Page 41
14 Maintenance
14.3 Burner
Warning!
Before performing the maintenance on the appliance, read carefully the “Safety instructions” chapter.
14.1 Casing
1. Unscrew the screws [1] and slide back
the catches [2] to release the front cas­ing [3];
2. Push the front casing [3] upwards and
remove it;
3. Unscrew the two screws [4] and pull
down the control panel [5];
700_R01
3
- Undo main gas supply nut from burn­er.
- Pull main burner forward, pull off the ignition and fl ame sense leads from the electrodes and remove burner from boiler.
Note: The washer between main burner and
main burner gas supply must be kept for use on reassembly.
1
2
6
4
6
5
14.2 Combustion chamber
- Unscrew and remove 6 screws securing sealed chamber cover to the boiler. Pull cover forward and off boiler.
- Remove ignition and fl ame sense elec­trodes from burner.
- Unscrew and remove four injector bar retaining screws and separate injector bar from burner.
- Examine and clean injectors as neces­sary.
Note: DO NOT use a wire or sharp instru-
ment on the holes.
14.4 Heat exchanger
- Locate the heat exchanger inside the sealed chamber.
- Gain acces to heat exchanger by remov­ing fan and fl ue hood.
- Examine heat exchanger for any block­ages or build up of deposits.
- Clean heat exchanger with soft brush or vacuum cleaner.
39
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 42
14.5 Reassembly of parts removed for servicing
- Slacken, but do not remove, two screws securing fan to rear of fl ue hood.
All parts are replaced in reverse order to removal.
14.6 Flue system
- Check externally to make sure that fl ue is not blocked
- Inspect fl ue system to make sure that all fi ttings are tight and secure.
14.7 Operation of fan
- Switch on electrical supply and turn on gas.
- Set selector switch to ‘Winter’ tion.
- Light burner by operating external con­trols (if fi tted) to call for heat.
posi-
- Supporting fan, unscrew and remove two screws securing fan to front of fl ue hood.
- Lower fan from top of boiler then tilt base of fan to right hand side. Gently ease fan forwards and out of boiler.
- Transfer fl ue sensing probe assembly onto replacement fan.
- Fit replacement fan in reverse order to removal.
Note: Ensure white air sensing tube is con-
nected to upper probe and red tube to lower probe.
15.2 To replace air pressure switch
- Locate air pressure switch in upper right hand corner of sealed chamber.
- Do not light the boiler without the sealed chamber cover fi tted
- Check that fan operates when burner lit and stops when it goes out.
15 Replacement of parts
Warning!
Before starting the replacement of parts, read the “Safety instructions” chapter carefully.
15.1 To replace fan
- Slide fl ue sensing probe insulating boot away from fan.
- Pull off both red and white sensing probe tubes.
- Disconnect power supply and earth leads to fan.
- Pull off plastic tubes from base of switch.
- Remove electrical connections from switch.
- Unscrew and remove two screws secur­ing switch to upper panel and remove switch.
- Fit electrical connections to replacement switch as follows:
NO - BROWN NC - BLACK C - BLUE
- Fit replacement switch in reverse order to removal.
Important: Refi t red tube to right hand connector and white tube to left hand connector.
40
Page 43
15.3 To replace pump
15.4 To replace gas valve
- Drain down boiler heating circuit as fol­lows:
- From below boiler, close isolating valves on fl ow and return connections.
- Open boiler drain valve to right of pump.
Note: It is not necessary to drain down entire
heating circuit to carry out this work.
- Gain access to the pump by lowering the controls panel.
- Pull off electrical connection to pump.
- Supporting pump, unscrew pump con­nection nuts at top and rear of pump. Remove pump by lifting forward and out of boiler.
- Fit replacement pump in reverse order to removal.
1
- Isolate boiler from gas supply.
- Gain access to the gas valve by lower­ing the controls panel.
- Remove clear plastic sensing pipe from gas valve.
- Unscrew and remove upper screw (1) holding gas valve ignition box onto gas valve body.
- Carefully pull off ignition box, leaving electrical wiring connected, and move clear of gas valve.
- Remove electrical connections to gas valve modulating coil.
- Disconnect gas inlet cock from boiler.
- Open isolating valves on fl ow and return connections,
- Refi ll, vent and pressurise boiler. Check for leaks.
- Undo nuts on gas valve to burner sup­ply pipe and swing pipe clear of gas valve.
- Unscrew and remove two screws secur­ing gas valve to boiler lower frame.
- Fit replacement gas valve in reverse order to removal.
Note: When refi tting electrical connections
to gas valve modulating coil, the polarity is not important.
41
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 44
15.5 To replace domestic heat exchanger
- Open isolating valves on fl ow and return connections, refi ll, vent and pressurise boiler. Check for leaks.
BC
F
- Drain down heating circuit of boiler as described previously.
- Drain down hot water circuit of boiler as follows:
- From below boiler, close cold water inlet isolating valve.
- Open a hot tap to drain hot water cir­cuit.
- Remove clip (A) and pull off microswitch assembly
- Undo connections (B), (C), (D) and (F) on 3 way valve
- Grasp 3 way valve and lift upwards releasing ‘O’ ring joint (E)
- Remove 3 way valve and domestic heat exchanger assembly (G) from boiler.
Important: Take care not to drip water
into PCB housing when removing assembly.
EGD
H
A
- Open cold water isolating valve. Check for leaks.
15.6 To replace thermistor
- Locate thermistor clipped onto fl ow pipe behind and to the right of the pump.
- Pull off clip from fl ow pipe.
- Remove electrical connections from thermistor.
- Fit replacement thermistor in reverse order to removal.
Note: 1) No heat sink compound is
required.
2) The polarity of the connections is not important.
15.7 To replace overheat thermostat
- Locate overheat thermostat on left hand side of main heat exchanger at rear.
- Remove electrical connections from overheat thermostat.
- Unscrew and remove two screws securing overheat thermostat to heat exchanger.
- Fit replacement overheat thermostat in reverse order to removal.
Note: 1) No heat sink compound is
required.
2) The polarity of the connections is not important.
- Fit replacement heat exchanger (G) in reverse order to removal.
42
Page 45
16 Technical data
Boiler type B22-C12-C32-C42-C52-C62-C82
Description Unit
SEMIA CONDENS
F24 E
Gas category ll
2H3+
SEMIA CONDENS
F30 E
ll
2H3+
Heating output at 80°C/60°C (Hi) kW 18.1 - 24.5 11.1 - 28.6 Efficiency calculated on net calorific value
% 94.9 - 95.8 95.2 - 97.1
at 80/60°C Heating output at 50°C/30°C (P) kW 19.2 - 26.2 15.9 - 30.6 Efficiency calculated on net calorific value
% 101.1 - 102.2 100.5 - 103.8
at 50/30°C Heat input (Hs) (heating) kW 21.08 - 28.4 17.76 - 32.74 Heat input (Hs) (DHW) kW 11.65 - 28.4 13.3 - 32.74 Maximum hot water temperature °C 80 80
Heating
Heating temperature range (standard) 30 - 80 30 - 80 Heating temperature range (low temp.) 25 - 45 25 - 45 Expansion vessel, useful capacity l 8 8 Expansion tank initial pressure bar 1 1 Safety valve, maximum service pressure
(PMS)
bar 3 3
Domestic hot water
Hot water temperature range °C 30-70 30-70 Specific flow rate (D) (ΔT 25°C) l/min 14.0 16.4 Specific flow rate (D) (ΔT 30°C) l/min 11.7 13.7 Specific flow rate (D) (ΔT 35°C) l/min 10.0 11.7 Threshold flow rate l/min 3 3 Maximum supply pressure bar 6 6 Minimum operating pressure bar 0.8 0.8
Combustion
Product outlet flow rate g/s 15.9 16.4 Product outlet temperature °C 85 70 Values of product outlet (measured on nominal heating output with G20 reference gas):
CO ppm 38.0 54.8
CO2 % 6.40 7.20
NOx balance
mg/
kWh
163.1 122.0
43
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 46
Description Unit
Dimensions:
Height mm 750 750 Width mm 400 400 Depth mm 347 347 Net weight kg 41.5 43 Supply voltage V/Hz 230/50 230/50 Maximum absorbed power W 145 150 Electric protection IP X4D IP X4D CE number 0694 BN 3710 0694 BN 3710
SEMIA CONDENS
F24 E
SEMIA CONDENS
F30 E
Technical data depending on the gas type
Natural gas G 20 (1)
Flow rate at maximum input Flow rate at minimum input Inlet pressure mbar 20 20
Burner injector diameter mm 1.25 1.30
(1) 15 °C, 1013,25 mbar
Unit SEMIA CONDENS
F24 E
m m
3
/h
3
/h
2.71 3.12
1.11 1.27
SEMIA CONDENS
16.1 Burner pressure tables
SEMIA CONDENS F24 E
HEAT OUTPUT PRESSURE
kW Btu/hr mbar
9.5 32566 2.1 10 34120 2.3
11 37532 2.7 12 40944 3.2 13 44356 3.7 14 47768 4.3 15 51180 4.9 16 54592 5.5 17 58004 6.1 18 61416 6.8 19 64828 7.5 20 68240 8.2 21 71652 9.0 22 75064 9.8 23 78476 10.6 24 81888 11.4
24.5 83594 11.6
SEMIA CONDENS F30 E
HEAT OUTPUT PRESSURE
kW Btu/hr mbar
11.1 37832 2.2 12 40944 2.6 13 44356 3.0 14 47768 3.4 15 51180 3.9 16 54592 4.4 17 58004 4.9 18 61416 5.5 19 64828 6.1 20 68240 6.7 21 71652 7.3 22 75064 7.9 23 78476 8.6 24 81888 9.3 25 85300 10.0 26 88712 10.8 27 92124 11.5 28 95536 12.3
28.6 97735 12.7
F30 E
44
Page 47
17 Boiler schematic
1
23 22
21
2 3
4 5
6 7
8 9
10
11
12
945_2_R00
24
25
20
19 18
1 Overheat thermostat (manual reset control) 2 Air pressure switch 3 Automatic air vent 4 Fan 5 Flue hood 6 Expansion vessel 7 Primary heat exchanger 8 Flame sense electrode 9 Ignition electrode 10 Burner 11 Water valve 12 Gas valve 13 Syphonic condensate trap
13
1416 15
14 Domestic plate to plate heat exchanger 15 Hydraulic 3-way valve 16 Low pressure sensor 18 Condense outlet pipe 19 Drain valve 20 Pump 21 Thermistor 22 Recuperator 23 Flue overheat thermostat (probe) 24 Overheat thermostat 25 Pressure relief valve (3 bar)
45
Installation and servicing instructions strictly reserved for qualifi ed gas installers
Page 48
Page 49
Page 50
982790002/000
Page 51
Page 52
Saunier Duval, Nottingham Road Belper,Derbyshire DE56 1JT Tel. 00 44 (0)1773 525914 Fax. 00 44 (0)1773 828070 www.saunier-duval.co.uk
10/2005 - 982.160099/001
Loading...