USER MANUAL
Si-Manifold App
Application for Si-RM3, Si-RM13 and Si-RV3
5 Commonwealth Ave5 Commonwealth Ave5 Commonwealth Ave5 Commonwealth Ave Woburn, MA 01801Woburn, MA 01801Woburn, MA 01801Woburn, MA 01801 Phone 781-665-1400Phone 781-665-1400Phone 781-665-1400Phone 781-665-1400 TollTollTollToll Free 1-800-517-8431Free 1-800-517-8431Free 1-800-517-8431Free 1-800-517-8431
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com
Table of contents
1. Safety instructions.............................................................................................................................................................................4
1.1. Use...........................................................................................................................................................................................4
1.2. Warning....................................................................................................................................................................................4
1.3. Environment protection............................................................................................................................................................5
2. Presentation......................................................................................................................................................................................6
2.1. Minimum required versions.......................................................................................................................................................6
2.2. Operating modes......................................................................................................................................................................6
2.3. Screens description...................................................................................................................................................................6
2.3.1. Manifold screens..............................................................................................................................................................6
2.3.2. Vacuum probe screens......................................................................................................................................................7
2.3.3. Tightness screens.............................................................................................................................................................8
3. Technical features of the instruments.................................................................................................................................................9
3.1. Si-RM3 / Si-RM13.....................................................................................................................................................................9
3.2. Si-RV3.................................................................................................................................................................................... 10
4. Instruments description...................................................................................................................................................................11
4.1. Si-RM3 / Si-RM13...................................................................................................................................................................11
4.2. Si-RV3.................................................................................................................................................................................... 11
5. Pair the probes................................................................................................................................................................................ 12
6. Set the application..........................................................................................................................................................................14
6.1. Set the target values...............................................................................................................................................................14
6.2. Set the probes........................................................................................................................................................................14
6.3. Set the temperature probes....................................................................................................................................................15
6.4. Set the operator.....................................................................................................................................................................15
6.5. Set the units...........................................................................................................................................................................15
6.6. About.....................................................................................................................................................................................15
7. Perform a measurement..................................................................................................................................................................16
7.1. Perform an auto-zero in open air............................................................................................................................................16
7.2. Carry out a measurement with the Manifold...........................................................................................................................16
7.3. Perform a measurement with the Vacuum probe.....................................................................................................................17
7.4. Perform a tightness measurement...........................................................................................................................................18
8. Select a refrigerant gas...................................................................................................................................................................20
9. Manage the values records.............................................................................................................................................................22
9.1. Activate the record, make a pause, stop, save..........................................................................................................................22
9.2. Access to the saves.................................................................................................................................................................22
9.3. Resume the measurements from a dataset saved....................................................................................................................23
9.4. Export the records..................................................................................................................................................................23
10. Display the different views of the measured values........................................................................................................................25
10.1. Display the “Graph” view.....................................................................................................................................................25
10.2. Display the “Values table” view............................................................................................................................................25
10.3. Display the “Gauge” view....................................................................................................................................................26
10.4. Select the values to display...................................................................................................................................................26
11. Probes information........................................................................................................................................................................27
11.1. Modify the name of the probe..............................................................................................................................................27
11.2. Update the probe.................................................................................................................................................................27
11.3. Disconnect the probe............................................................................................................................................................28
12. Maintenance.................................................................................................................................................................................29
12.1. Change batteries..................................................................................................................................................................29
12.2. Clean the instrument............................................................................................................................................................29
12.3. Measurement accuracy.........................................................................................................................................................29
13. Notes............................................................................................................................................................................................30
3
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com

1. Safety instructions

Before using the device, please read carefully this user manual. It delivers important information about the device operating, maintenance and reprocessing.

1.1. Use

Interior or exterior use.
This device has been developed for the pressure and temperature measurements and settings on stationary or mobile
refrigeration equipment. It must not be used in any other purpose.
This device has been developed, produced and sold exclusively to trained and qualied experts in the eld of HVACR. Appropriate training is necessary in order to guarantee a riskless use of this instrument. Sauermann is not responsible for any possible accident during its use.
In case of improper use, gases leak can occur and be dangerous towards the user or the environment. Please always use the device in accordance with its intended use and within parameters described in the technical features in order not to compromise the protection ensured by the devices.
When installing the device, the safety of the system integrating the device is the responsibility of the system assembler.
Only the accessories provided with the device or available as an option must be used.
Maximum operating pressure: 60 bar (945 psi)
Do not use the device if it is damaged or if it operates abnormally. Inspect the device before every use. In case of doubt,
please contact the Sauermann's After-sales service.
Always wear protective glasses and gloves when using the Manifold in order to protect your eyes and skin when operating
refrigerant gases. The vapours of refrigerant gases are extremely cold. Do not expose your skin to these vapours.

1.2. Warning

Do not authorise pressures beyond the device limits. Please refer to the technical features described in this user manual.
Never use a refrigerant gas that is not listed in the refrigerant gases menu of the application. Several refrigerant gases have
been excluded for safety reasons. Use of other unapproved gases can damage the device.
The refrigerant gases database of the application includes refrigerant gases classied as inammable. If these gases are selected, the operator must compulsory have an additional training or qualication. Please consult the competent legal authorities and fully respect their directives.
The device must not be exposed to rain or any other humid environments (> 80%RH).
Do not use the device next to explosive gases, vapour or dust.
The device must not be used in ATEX zones according to applicable standards.
In any case the device can be used as a pressure regulator, especially using the N2 nitrogen.
The device must not be used with the ammoniac refrigerant gas (NH3 / R717).
Do not use this device on systems containing chemical leaks clogging. They can break into the device and dry inside the
instrument causing irreversible damages.
Do not perform contact measurements on non-insulated or under voltage parts.
Do not store the device with solvents. Do not use desiccants.
The device does not contain any internal part repairable by the user. Do not open the device. The maintenance must be
4
Safety instructions
performed by Sauermann only.
If the device falls or in case of similar inconveniences, the hoses for refrigerants can break. The stop valves can be damaged too and create internal damages than can not be identied from the outside. Therefore, the hoses for refrigerants must be replaced every time the device falls or similar mechanical load. Please send back the device to Sauermann After-sales service for a technical check and to ensure your own safety.
This device allows to connect several inputs, including electrical and mechanical ones. Be careful in order to avoid any risk of electrical shock. Do not use the device if you are not able to detect any electrical failure.

1.3. Environment protection

The refrigerant gases can affect the environment. Please apply the environmental current regulations.
Send back the device at its end of working life in a waste collection centre for electrical and electronic components (according
to local regulations), or send it back to Sauermann to ensure a required waste collection in the respect of the environment.
Safety instructions
5
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com

2. Presentation

This user manual describes the Si-Manifold application operating with the Si-RM3, the Si-RM13 Manifold and the Si-RV3 vacuum probe.

2.1. Minimum required versions

In order to ensure the application operation, the device requires the following minimum versions:
Android 4.4
IOS 8.0
BLE 4.0

2.2. Operating modes

The Manifold indicates the operating high and low pressures and temperatures of a refrigerating plant. It also allows maintenance and troubleshooting on the equipment uid circuit. According to the type of probe it is necessary to select an operating mode in the application. These operating modes are:
Manifold mode: used with Si-RM3, Si-RM13 and the temperature clamps
Vacuum probe mode: used with Si-RV3 and Si-RM3 low pressure and Si-RM13 low pressure
Tightness mode: used with Si-RM3 high pressure and Si-RM13 high pressure
Press , or to access the required mode.

2.3. Screens description

2.3.1. Manifold screens

In Manifold mode, the screen will be different according to the mobile or tablet orientation.
1. Perform a screenshot
2. Create and export a report
3. Access to the application conguration parameters
4. Name of the selected gas and access to the gases list
5. Display different views: table or graph
6. Save, pause, stop a dataset
7. Measured or calculated parameters with the low pressure probe
8. Measured or calculated parameters with the high pressure probe
9. Access to the measuring modes and saves
6
Presentation
Manifold mode
Vacuum probe mode
Tightness mode
Portrait mode

 
1. Wireless connection reception and battery levels
2. Perform an auto-zero, access to the connected probe information

2.3.2. Vacuum probe screens

With the Si-RV3 vacuum probe:
1. Perform a screenshot
2. Create and export a report
3. Access to the application conguration parameters
4. Display different views: table or graph
5. Wireless connection reception and batteries level
6. Save, pause, stop a dataset
7. Access to the connected probe information
8. Vacuum probe measurements
9. Fixed values
10. Access to the measuring modes and saves
With the Si-RM3 low pressure probe:
1. Perform an auto-zero, access to the connected probe information
Presentation
7
Landscape mode
Portrait mode
Landscape mode
Landscape mode
Portrait mode

 
 
 
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com

2.3.3. Tightness screens

1. Perform a screenshot
2. Create and export a report
3. Access to the application conguration parameters
4. Display different views: table or graph
5. Wireless connection reception and batteries level
6. Save, pause, stop a dataset
7. Perform an auto-zero, access to the connected probe information
8. Pressure probe measurements
9. Access to the measuring modes and saves
8
Presentation
Landscape mode
Portrait mode

 
 
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com

3. Technical features of the instruments

3.1. Si-RM3 / Si-RM13

Pressure
Pressure valves 2 valves Measuring range From -1 to 60 bar (-14 to 870 psi) Pressure sensing accuracy* ±0.5% of full scale Available units psi, MPa, kPa, bar, foot of head Resolution 0.1 psi, 0.001 MPa, 1 kPa, 0.01 bar, 1 foot of head Overload 65 bar (943 psi) Burst pressure 150 bar (2175 psi) Operating temperature (handle) From -20 to 50°C (-4 to 122°F) Storage temperature (handle) From -20 to 60°C (-4 to 140°F)
Temperature
Number of probe 2 clamp probes Temperature sensors High accuracy NTC thermistors Temperature sensor range** From -40 to 150°C (-40 to 302°F) Temperature accuracy* ±1.3°C (±2.4°F)*** Maximum operating temperatures Jaws: 150°C (302°F) - Cable: 105°C (221°F) - Handle : 90°C (194°F) Available units °C, °F, K Resolution 0.1°C, 0.1°F, 0.1 K Pipes diameter From 6 to 42 mm (0.2'' to 1.7'') Cable 2 m length with strengthened Jack connector
3 points, Ø3.2 mm, in PVC, max. temperature 105°C (221°F)
Operating temperature (handle) From -20 to 50°C (-4 to 122°F) Storage temperature (handle) From -20 to 60°C (-4 to 140°F)
Device
Environmental conditions of use Hygrometry: in non-condensing condition (< 80% RH)
Maximumaltitude: 2000 m (6561') Non-corrosive or combustible gases
Battery life 250 h (for one measurement every seconds @ 20°C / 68°F) Wireless connection Class 1 BLE 4.2 Wireless connection range Up to 30 m (98 ft) - Depending on smartphone and tablet wireless
connection radio strength.
Superheat and subcooling Automatically calculated by the Manifold app Refrigerant database 126 refrigerant gases
Measurable products: CFC, HFC, HCFC, N, CO2, H20
Connections To installation: female ¼’’ FFL with Schrader® depressor
To exible: male ¼’’ MFL with Schrader® valve
Standards 2011/65/EU RoHS II; 2012/19/EU WEEE; 2014/30/EU EMC;
2014/53/EU RED
* All accuracies specied in this document were conducted under laboratory conditions & can be guaranteed for measurement carried out in the same conditions, or carried out with calibration compensation. ** The temperature only concerns the sensors operating range, do not use the handle or cables outside the indicated temperature. *** The temperature accuracy is given for the -20 to 80°C (-4 to 176°F) range.
Technical features of the instruments
9

3.2. Si-RV3

Vacuum
Measurement and discharge valves 2 valves Measuring range From 5 to 25,000 microns Pressure sensing accuracy* ±10% of the measured value ±10 microns** Available units micron, Pa, hPa, mbar, Torr, mmHg, inHg, inH2O Resolution 1 micron from 0 to 1000 microns
10 microns from 1000 to 2000 microns 100 microns from 2000 to 10,000 microns 500 microns from 10,000 to 25,000 microns
Overload 10 bar (145 psi) Burst pressure 27.5 bar (400 psi) Operating temperature From -10 to 50°C (-4 to 122°F) Storage temperature From -20 to 60°C (-4 to 140°F)
Device
Environmental conditions of use Hygrometry: in non-condensing condition
Maximumaltitude: 2000 m (6561') Non-corrosive or combustible gases
Battery life 250 h (for one measurement every three seconds @ 20°C / 68°F) Wireless connection Class 1 BLE 4.2 Wireless connection range Up to 30 m (98 ft) - Depending on smartphone and tablet wireless
connection radio strength.
Connections To installation: female ¼’’ FFL with Schrader® depressor
To exible: male ¼’’ MFL with Schrader® valve
Standards 2011/65/EU RoHS II; 2012/19/EU WEEE; 2014/30/EU EMC;
2014/53/EU RED
*All accuracies specied in this document were conducted under laboratory conditions & can be guaranteed for measurement carried out in the same conditions, or carried out with calibration compensation. **The pressure accuracy is given for the 100 to 2000 microns range.
10
Technical features of the instruments

4. Instruments description

4.1. Si-RM3 / Si-RM13

1. Female connector ¼’’ FFL with Schrader® depressor
2. Identication label (see below)
3. Male connector ¼’’ MFL with Schrader® valve
4. Cap
5. Input for temperature clamp probe
6. Operating led
7. On/Off button

4.2. Si-RV3

1. Female connector ¼’’ FFL with Schrader® depressor
2. Identication label (see below)
3. Male connector ¼’’ MFL with Schrader® valve
4. Cap
5. Operating led
6. On/Off button
Instruments description
11
 
 
 
Example of label
Example of label
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com

5. Pair the probes

Before using the Si-RV3, Si-RM3 probes and temperature clamps with the Si-Manifold application, it is compulsory to pair the probes for their rst use. Follow the following procedure to pair a probe. The following procedure is described using the Si-RM3 low pressure probe as example.
Launch the application from the smartphone or the tablet.
The following screen is displayed.
Press “Connection to probe” on the left-hand corner of the screen.
The following screen is displayed.
Turn on the low pressure probe of the Si-RM3 for a few seconds.
The green light of the probe quickly blinks.
Press “Search for probes”.
This step takes a few seconds. The application searches for turned-on-probes next to the device and then displays them on the screen:
1. Grey: indicates a Si-RM3 probe
2. Yellow: indicates a Si-RV3 probe
3. Blue: indicates a low pressure probe
4. Red: indicates a high pressure probe
12
Pair the probes
 
Select the probe to pair and then press “Pair” on the right-hand corner of the screen.
Pairing is a compulsory step only for the rst use. If “Always link this probe to the low pressure” is activated, the probe is directly displayed.
Immediately, the measured values are displayed on the screen and the green light of the probe blinks slowly.
Follow the same procedure for the high pressure probe of the Si-RM3 and the vacuum probe of the Si-RV3.
In case of a connection loss with the probe, the following message is displayed:”...”
The probe stores automatically the 60 last measured values in its buffer memory.
Come closer to the probe with the smartphone or the tablet. The application launches an automatic research of the probe. When the connection is restored, the measurements carry on.
Pair the probes
13
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com

6. Set the application

Before performing a measurement, it is possible to set different parameters in the application. These settings concern:
the target values
the probes
the operator
the units
From this screen, it is also possible to consult the user manual, the application version and the licences.
Press “Parameters” in the right-hand corner of the screen.
The following screen is displayed.

6.1. Set the target values

This part allows users to set the values that will be materialised on the application. In Manifold mode:
Activate the display of the target values by pressing the button.Set the target value for the overheat between 0 and 60°C (32 and 140°F).Set the target value for the subcooling between 0 and 60°C (32 and 140°F).Set the target value of the low pressure between -1 and 60 bar (-14 and
870 psi).
Set the target value for the high pressure between 0 and 60 bar (-0 and 870
psi).
In Vacuum probe mode:
Set the target value for the vacuum pressure between 5 and 25000microns then set the delay time, i.e. how long
the pressure stays at this dened target value until the “Target reached” message is displayed above the measured value.

6.2. Set the probes

In the “Probes” part:
Select the operating mode: summer or winter.Select a time before the probe auto shut-off between 1 minute and 4 hours.Set the measurement rate between 1 second and 2 minutes.Delete the saved probe: delete all the probes that have been paired with
the application.
Inform the atmospheric pressure value between 600 and 1200hPa (17 and
35 inHg).
Activate the visual assistance of the auto-zero: activated, this function
allows to automatically ask if an autozero must be performed before a measurement.
14
Set the application

6.3. Set the temperature probes

When pairing a Manifold probe, the following screen displays:
Select the temperature probe type: temperature clamps or Velcro® probe for high diameter
pipes.
To not display this message again, tick “Don't ask me again”.Press validate.
In “Temperature probes” part:
Activate the pipe temperature compensation: activated, this function allows to take into
account the ambient temperature and the pipe temperature to get the refrigerant uid temperature.
Select the type of probe used:
temperature clamps
or
Velcro® temperature probe for high diameter pipes. ➢ Tick “Don't ask me again” to memorize the selected probe.Untick “Don't ask me again” to reactivate the automatic display of this
message.

6.4. Set the operator

In the “Operator” part:
Inform a name in the “Operator name” eld.Inform an accreditation number in the “Accreditation number”
eld.
Inform the name of the society.

6.5. Set the units

In the “Units” part:
Select the temperature unit: °C, °F or KSelect the pressure unit for the Manifold and Tightness modes: bar, psi,
Mpa, kPa or Feet of head
Select the pressure unit for the Vacuum mode: microns, mmHg, Torr,
mbar, hPa, inH2O, inHg, or Pa

6.6. About

This part allows to obtain information about the application:
User manualApplication version number User licences
Set the application
15

7. Perform a measurement

Before any measurement with the Manifold, perform an auto-zero of the probe in open air.
Only a trained and qualied technician can perform the following operations.
The Manifold or Vacuum probe must be paired with the application (see previous chapter).

7.1. Perform an auto-zero in open air

Before any measurement with the Manifold, perform an auto-zero of the probe in open air. From the measurement screen:
Press to perform an auto-zero of the low pressure probe.
A message is displayed to conrm the autozero.
Press “YES”.
A message with a picture is displayed indicating that the probe must be disconnected from the network before launching the autozero.
Press “Validate” to perform the autozero.Press to perform an auto-zero of the high pressure probe.

7.2. Carry out a measurement with the Manifold

Activate the “Manifold” mode by pressing
For pressure measurements:
Connect the low pressure probe on the equipment to verify.Connect the high pressure probe on the equipment to verify.
16
Perform a measurement
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com
Read the measured values on the application.
For the temperature measurements:
Connect the temperature clamp on the pressure probe.Position the temperature clamp on the pipe.
1. Low pressure probe measured or calculated values
2. Circuit low pressure measurement
3. Evaporation temperature: calculated value depending on the selected refrigerant gas
4. Overheat: calculated value corresponding to T° T1 contact – evaporation T°
5. High pressure probe measured or calculated values
6. Circuit high pressure measurement
7. Condensation temperature: calculated value depending on the selected refrigerant gas
8. Subcooling: calculated value corresponding to
9. Condensation T° – T° T2 contact
1. T° T1 contact: contact temperature probe 1
2. Ambient T°: ambient temperature probe 1
3. T° T2 contact: contact temperature probe 2
4. Ambient T°: ambient temperature probe 2

7.3. Perform a measurement with the Vacuum probe

Activate the “Vacuum probe” mode by pressing
Connect the Vacuum probe or the low pressure probe on the equipment to verify.Read the measured values on the application.
Example with a Vacuum probe:
1. Vacuum measurement
2. Indication of the dened target value
3. Ambient T°: ambient temperature
4. Water evap. T°: water evaporation temperature
Perform a measurement
17
Portrait mode
 
 
 
 
Landscape mode
 
 
Portrait mode
If the Vacuum probe is connected but that the measured values are beyond the measuring range, “Atmo is displayed:
When the target value is reached, the message “Target reached” is displayed:
Example with a Si-RM3 low pressure probe:
1. Measured value by the low pressure probe

7.4. Perform a tightness measurement

With a Manifold probe, it is possible to perform a tightness measurement on the equipment to verify.
Activate the “Tightness” mode by pressing
18
Perform a measurement
Landscape mode
Landscape mode
Portrait mode
Landscape mode
Portrait mode
Landscape mode
Connect the Si-RM3 high pressure probe on the equipment to verify.Read the measured values on the application.
1. Value measured by the high pressure probe
2. Ambient T°: ambient temperature
3. P1: measured value of pressure when launching the record
4. P2: measured value of pressure when stopping the record
5. Delta P: calculated value corresponding to P1 – P2
Perform a measurement
19
Landscape mode
Portrait mode
 
 
Portrait mode

8. Select a refrigerant gas

The application contains the 126 following refrigerants:
R12 R227ea R410A R444A R601a R-407D R-441A
R13 R236ea R413A R445A R718 R-407E R-444B
R13b1 R236fa R414B R448A R723 R-410B R-446A
R14 R245fa R416A R449A R744 R-411A R-447A
R22 R290 R417A R450A R744A R-411B R-501
R23 R401A R417C R452A RE170 R-412A R-504
R32 R401B R420A R453A R-11 R-414A R-507A
R41 R402A R421A R455-A R-21 R-417B R-508
R114 R402B R422A R50 R-113 R-418A R-508A
R123 R403B R422B R500 R-115 R-419A R-509
R1150 R404A R422C R502 R-116 R-419B R-509A
R1234yf R406A R422D R503 R-124 R-421B R1233zd
R1234ze R407A R424A R507 R-141b R-422E
R125 R407B R427A R508B R-143a R-423A
R1270 R407C R434A R511A R-218 R-425A
R134a R407F R437A R513A R-245ca R-426A
R142b R408A R438A R600 R-401C R-428A
R152a R409A R442A R600a R-403A R-439A
R170 R409B R443A R601 R-405A R-440A
From the “Manifold” measurement screen:
Press to display the refrigerant gases list.
The following screen is displayed. The bookmarked refrigerants are displayed on top of the list and in alphabetical order.
20
Select a refrigerant gas
Tick the box of the required refrigerant.Press “Validate”.
Signication of the several elements relative to the refrigerants:
1. Box to tick to select the refrigerant
2. Name of the refrigerant
3. Indicates that the refrigerant is ammable
4. If the star is empty: press it to bookmark the refrigerant. If the star is full, press it to remove the bookmark on the refrigerant.
It is possible to bookmark up to 10 refrigerants.
Select a refrigerant gas
21
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com

9. Manage the values records

It is possible to launch a record of the measured values, make a pause, stop the record and save it.

9.1. Activate the record, make a pause, stop, save

All these actions are available thanks to the buttons on top of the measurement screen:
Activate the values record
Make a pause on the record
Stop the record
Once the record activated, a chronometer is displayed on top of the screen.
Press “Stop” to stop the record. The application asks a conrmation to stop the record: select “Yes” or “No”.
If Yes, the application asks to save the dataset:
If No: the application restores the measurement screen.
If Yes: the dataset is saved in the mobile device.
If No, the application restores the measurement screen.

9.2. Access to the saves

Press “Saves” at the bottom of the screen.
The following screen is displayed with the folders containing the saved datasets classied by date.
Select the required folder.
The following screen is displayed with the saved datasets.
22
Manage the values records
Select the required dataset.
The application displays the dataset.
Then it is possible to:
resume the measurements (see chapter 9.3)
export the dataset (see chapter 9.4)

9.3. Resume the measurements from a dataset saved

From the saved datasets screen:
Select the required dataset from which the measurements must restart.Press button.
The application displays the probes used during previous measurements.
Turn on the probes.
The application and probes connect to each other. The following screen is displayed:
Press “Continue”.
The application returns to the measurements screen and the chronometer restarts when it stopped.
When probes and application are connected each other, an autozero will be asked if the “Autozero help” parameter has been activated.

9.4. Export the records

When a dataset is saved in the mobile device or when a current dataset is stopped, it is possible to export it in PDF, XML, CSV format or export it directly in the clipboard.
To export a dataset without saving it beforehand:
Stop the dataset by pressing “Stop”
Press “Export” on top of the screen
The following screen is displayed:
Manage the values records
23
Fill in the elds.Select the format: PDF, CSV, XML or clipboard.Select or not to add graphs, tables of values, screenshots, photos.
Press “Export”
The les are exported in a folder created automatically called “Si-Manifold” located at the root of the mobile device.
To export a dataset saved in the device:
Select the required dataset (see 9.2 for the saved datasets management) then follow the previous procedure.
To display a dataset saved in the device:
Press “Saves” at the bottom of the screen.
The screen with the saved datasets list is displayed.
24
Manage the values records

10. Display the different views of the measured values

It is possible to display the measured values according to three different views:
“Gauge” view “Graph” view “Values table” view

10.1. Display the “Graph” view

Press
The following screen is displayed.

10.2. Display the “Values table” view

Press
The following screen is displayed.
Display the different views of the measured values
25
Portrait mode
Landscape mode
Portrait mode
Landscape mode

10.3. Display the “Gauge” view

Press
The following screen is displayed.

10.4. Select the values to display

It is possible to select the values to display.
The values selection is possible only with the Manifold mode.
These values are:
Overheat target (for the low pressure probe only)
Sub-cooling target (for the high pressure probe only)
Pressure target
Pressure (real time, minimum, maximum, average)
Contact temperature (real time, minimum, maximum, average)
Ambient temperature (real time, minimum, maximum, average)
Delta T1T2
Overheat (minimum, maximum, average) for the low pressure probe only
Sub-cooling (minimum, maximum, average) for the high pressure probe only
Evaporation temperature (real time, minimum, maximum, average)
Condensation temperature (real time, minimum, maximum, average)
To display the required values:
Press two times on the required zone to modify the measurement to display on this location.
The list of values to display appears.
Tick the box of the value to display.For the targets: inform the target value.Press “Validate”.
26
Display the different views of the measured values
Landscape mode
Portrait mode

11. Probes information

From the measurements screen in Manifold, Vacuum probe or Tightness mode:
Press
The following screen is displayed.
This screen presents the following information:
Name of the probe
Type of probe
Serial number of the probe
Firmware version number of the probe
Updates research for the probe

11.1. Modify the name of the probe

Press the eld of the probe name.Fill in the new name.Press “Validate”.

11.2. Update the probe

To update a probe, the tablet or smartphone must be connected to a Wi-Fi network.
Press .
The application automatically searches for available updates.
If an update is available:
Press «Firmware update» button.
The application displays the following message: “The operation will takes several minutes and will
prevent any measurement”.
Press “Continue” button.
The following screen is displayed.
During this preparation step of the update, the led ashing stops.
Probes information
27
After few seconds, the following screen is displayed and shows the update progression:
During the update, it is imperative not to disconnect the wireless connection between the probe and the smartphone or tablet.
When the update is nished, the application backs on the probe information screen and the probe ashes again.
If there is no update available: “Firmware update” button will be replaced by “No update available” button. This button will be shaded.

11.3. Disconnect the probe

From the probe information screen:
Press “Disconnection”.
The application disconnect the probe of the device.
This operation will stop the current record of the dataset.
28
Probes information

12. Maintenance

12.1. Change batteries

Check that the device is turned off.Remove the batteries cover.Remove the power supply block containing batteries.Replace used batteries by three new AAA-LR03 1.5 V batteries.Put back the power supply block observing proper polarity.Put back the batteries cover.Dispose of used batteries according to your local regulations.
The device must be turned off during the batteries replacement.
In order to prevent battery leakage and damages to the coupler, it is recommended to replace batteries as soon as they are at and to not leave them within the device.

12.2. Clean the instrument

Use a soft cloth slightly dampened with soapy water.
Clean up is possible with isopropyl alcohol.
Do not use alcohol or solvent.
Check regularly the cleanliness of the connections.The block and hoses must be free of residual oil. Use a cloth inside and compressed air outside.
Remaining uids in the block or hoses must be recovered thanks to a uids recovery system.

12.3. Measurement accuracy

In order to guarantee the measurements accuracy, it is recommended to yearly return the device to the Sauermann after­sales service.
Maintenance
29
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, Woburn, MA 01801
TestEquipmentDepot.com
NTang – Si-Manifold-App – 03/02/2021 – Non-contractual document – We reserve the right to modify the characteristics of our products without prior notice.
Register now to get your additional 1 year manufacturer warranty!
Enregistrez-vous maintenant pour bénécier d'une année supplémentaire
de garantie fabricant !
Registrieren sie sich jetzt für ein zusätzliches Jahr Herstellergarantie!
¡Regístrese ya para obtener 1 año adicional de garantía!
Registrati ora ed ottieni 1 anno di garanzia supplementare!
Registe-se já para obter um ano de garantia adicional do fabricante!