KDB-GOM
Series
- 1 -
1. Specifications of the KDB-GOM series
1.1 Kyungdong Boiler Product Features and Functions
1.2 Specifications
2. Operating Types/Constructions/Schematic Diagram
2.1 Operating Types
2.2 Constructions of the Boiler
2.3 Schematic Diagram of Operating
3. Equipment Protection and Personal Safety
4. Specifications and Functions of the Major Components
4.1 Main Heat Exchanger
4.2 Fan Assembly
4.3 Circulation Pump
4.4 Modulating Gas Control Valve
4.5 3-Way Valve
4.6 Expansion Tank
4.7 Air Pressure Switch
4.8 Hot Water Flow Sensor
4.9 High Limit Sensor(Bimetal Type)
4.10 High Limit Fuse(Fuse Type)
4.11 Heating Temperature Sensor
4.12 Ignition Transformer
4.13 Power Transformer
4.14 Domestic Hot Water Heat Exchanger
4.15 Burner Assembly
4.16 Nozzle Holder Assembly
4.17 Wiring Diagram
4.18 Main Controller
I.
Technical Information
KDB-GOM
Series
- 2 -
THE KDB -GOM
THE KDB -GOMTHE KDB -GOM
THE KDB -GOM
KYUNGDONG BOILER’S VARIABLE-CAPACITY-MULTI-PURPOSE
82%+ HYDRONIC HEATING SYSTEM
How does it work?
The KDB-GOM provides 2 different heating functions that operate independently from the same boiler. One mode
provides space heating water to heat the home. The other mode provides a continuous circuit of hot water for domestic
use eg, bath, laundry, etc. Both circuits are separate and operate at different temperature ranges.
The space-heating water is controlled by the FR-5 thermostat. A special thermostat has been provided that enables the
user to either set the room temperature required of set the heating water temperature. In some cases this thermostat may
not be suitable for multi-system applications. (The installing contractor will make this determination and install suitable
alternative controls.
The domestic hot-water is controlled by the user. Because the KDB-GOM is a multi-purpose design, it can provide hot
water on demand, there is no storage tank to hold hot water, when there is no use for it. The KDB-GOM will only produce
hot water when you use it : instantaneous. The modulating gas burner allows water to heat up as evenly as it is being
used. The KDB-GOM will continue to heat the water until the source or sources are shut off. This on-demand-use also
helps to prevent water being held in the boiler for long periods of time.
IMPORTANT:
A thermostatic mixing valve should be installed on the domestic water supply pipe to control the supply water
temperature and prevent any possibility of scalding.
Domestic hot water priority
The GOM prioritizes bath water over space-heating water and will immediately stop producing space-heating water the
moment a hot water valve is opened anywhere in the home. Once the valve has been turned off, the boiler will return to
the home-heating function again.
The seal-combustion process
The KDB-GOM is designed with a special sealed-combustion venting process. Both sides of the combustion process
(inlet oxygen and outlet carbon monoxide) are isolated from each other and are totally sealed-off from the air supply within
the home. This reduces drafts, caused by infiltration, by as much as 82% making the KDB-GOM one of the safest, most
comfortable and clean-burning boilers in the world.
1. Specifications of the KDB-GOM series
1. 1 KyungDong GOM Product Features and Functions
A. Continuous Hot Water
Its On Demand! KyungDong Boiler makes running-out-of-hot-water obsolete.
B. Everything Built-in
Installs in half the time. We tried to think of all the parts and accessories you’ll need (plus a few you might have
forgotten) and built them into this multi-purpose hydronic heating system. You’ll spend less time driving to all the supply
houses.
KDB-GOM
Series
- 3 -
C. Baked-in Beauty
The high quality porcelain finish is bake on and keeps the exterior looking new and lustrous for years to come.
D. System Timer
Save energy during times the home is unoccupied. Just set and activate the timer and leave. The unit turns off for
pre-programmed intervals until you return.
E. Room Thermostat FR-5
Convenient and accurate, large digital display is easier to read, easier to use. Our new room thermostat gives the
consumer digital control over several heating function.
F. Performance Indicator
With the use of the FR-5 electronic room thermostat, the (LED) will conveniently display the current operating
condition of the unit such as temperature of heating water, room temperature, normal operation, etc.
G. Continuous-Discharge Ignition(C.D.I.)
Direct ignition design requires no wasteful pilot burner and offers fuel savings.
H. Combustion Safety Protection
If the unit fails to ignite after the “ON” switch is pressed, or if the flame is extinguished due to a gas shortage, the
flame sensor will shut down the unit.
I. Always Balanced Operation
Despite fluctuating wind conditions, changes in atmospheric pressure and other external disturbances, the
variable-speed combustion blower provides steady performance.
J. Exhaust Safety Protection
While operating, the exhaust-discharge fan is continuously monitored. The units will be immediately stopped to
prevent fumes from entering the home if the wind gusts become excessive or if the flue exhaust has been clogged.
K. Smart Re-Start
Should the unit’s flame fail due to strong winds or temporary low gas pressure, the unit will automatically restart. In
cold weather climates, manual resets could cause freeze damage.
L. Safety Protection during Power Outages
When the power fails, the gas is automatically shut down and the units are stopped.
M. Automatic Fill & Refill
If for any reason the water level in the system drops to an unsafe level, makeup water will automatically fill to the
appropriate levels.
N. Automatic Air Bleed
Each unit has 2 built-in air bleed devices. One is manual and used for quick fill and venting convenience; the other
is air-activated and operates and automatically.
O. Removal of Impurities
Each unit come equipped with a built-in, clearable, heavy duty, particulate water filter for trapping impurities and
preventing the clogging of pipes. This is a maintenance item.
P. Air-Ratio Controller
Air ratio is monitored, adjusted and controlled prior to and during each operating cycle and will automatically adjust
the combustion rate. The air-ratio controller guarding against unsafe operating conditions also senses excessive
gusts of wind filling the flue system.
Q. Proportional Temperature Control
This control is designed to continually analyze water flow and usage while maintaining the outgoing water at a
constant, even temperature.
KDB-GOM
Series
- 4 -
1.2 Specifications
GAS WALL-MOUNT
FRONT
View
A
Full, Dual Function Heating Design.
Natural and Propane Gas M odels.
B
Pow er-Vent, 2-Pipe C ombustion Process.
Modulating Gas for Precis ion Tem peratures.
REA R
Built-in Circulation Pump Assembly .
View
Built-in Ex pans ion Tank. Quiet, Vibration-Free Operation.
A
Built-in Freez e Protection.
Digitally Controlled, Full-Logic T hermostat.
C
Funct ion
ew
CENTR AL HEATING WATER
(LEFT
Const ructi on of Heat Exchanger
Heat Output (kcal/hr)
Max.Effici ency (%) 82 82 83 84
(wall)
Temperature Setting Range (℃)
Maxim um Working Pressur e (kgf/cm2)
Pre- Charged Ex pansion Tank (l iter ) 6.5 6.5 8.5 8.5
Circulation Pump
Freeze Protection Device
DOMESTIC HOT WATER
Heat Output (kcal/hr)
Max.Temperature Setting (℃)
Conti nuous DHW product ion
△T = 25 ℃
(liter )
10.7 13.3 16.7 20.0
Conti nuous DHW product ion △T = 33 ℃ (liter )
8 10.0 12.5 15.0
Conti nuous DHW product ion △T = 40 ℃ (liter )
6.7 8.3 10.4 12.5
C
Conti nuous DHW product ion △T = 50 ℃ (liter )
5.3 6.7 8.3 10.0
ew
Maxim um Working Pressur e (kgf/cm2)
(RIGHT)
OTHER DATA
Gas Type
Gas Consumption - LP (kg/hr)
1.58
1.98 2.48 2.97
(wall ) Gas Consumption (natural gas) (kcal/hr ) 19,000 23,700 29,700 35,600
Gas Inlet Supply Pressur e (natural: kPa) ( min - max)
Manifold Pressure (kPa) 0.16 ~ 0.92 0.16 ~ 0.96 0.25 ~ 0.94 0.14 ~ 0.96
Usage ( Heating & H ot Water )
Water Storage Capacity (liter) 0.7 0.7 0.8 0.8
Power (volts/cycle)
Power Consumption (watts)
Ignition
NOx Emi ssions
(Ref:0%, O2 in flue gas natural gas, ppm)
E F G D
Temp. of Exhaust Gas (℃)
WEIGHT AN D DIMENSIONS
Net Weight (l bs) 31 31 39 39
A Physi cal Dimensions: Hei ght (mm) 630.0 630.0 685.0 685.0
View
B Wi dth (mm) 485 485 525 525
C Depth (mm) 235 235 250 250
D C onnection: Gas Inlet 15A, 1/2" 15A, 1/2" 20A, 3/4" 20A, 3/4"
E C onnection: Heating Water Supply/Return
B
F C onnection: Domestic H ot Water Supply/Return
(front) G C onnection: Primary Power (AC220V-50Hz)
H F lue Diameter (Intake / Exhaust) (mm)
TOP
H
Specif ication s s ubject to c hange with out prior not if ication
View ( wall )
- 2865 PELLISSIER PLACE - W HITTIER, CA 90601 - (562) 463-0880
15A, 1/2"
15A, 1/2"
70 / 75
28 (l ess than)
150 (l ess than)
20A, 3/4"
Dual
AC 220V- 50Hz
120 ~ 160
ELECT RONIC
80
17.5
Liquefied Petroleum ( L.P.) or Natural Gas
0.98 ~ 2.45
40 ~ 80
3
Self Pr imi ng
Ther mis tor
MODEL NUMBER
Combo Boiler
Stainl ess Steel / Copper
161 GOM 201 GOM 251 GOM 301 GOM
w ith 1-Year on Parts.
KYUNGDONG BOILER SPECIFICATIONS
C on trols Bo th Water F unction s Separ ately .
On-Demand Hot Water Delivery.
Com pact, Space-sav ing Design.
Limited Warranty on Heat Exc hanger
---- KEY FEATURES
Prov ides Hi-Temp Water for Heating the Home.
Pr ov ide s Hot Wate r fo r B athing & Wa s hing.
KDB - 161 / 201 / 251 / 301 GOM
Residential Gas Hydronic Heating System
GAS FIRED, WALL-MOUNT ED, MULT I-PURPOSE, HYDRONIC HEATING SYS T EMS
MODEL RAN GE : 16, 000 ~ 30,000 kcal/hr
KDB-GOM
Series
- 5 -
2. Operating Types/Constructions/Schematic Diagram
2.1 Operating Types
Item Specification
Installation
Wall Mount Type
Flue Type
Both Use FF and FE
Usage
Both Use Heating and Domestic Water (Single Pipe, 2 Waterways)
Water Supply for
Heating
Maintain normally at a constant water pressure by pressure reducing valve
(Auto / Manual)
Control Method
Proportional Control Method by MICOM
Heat Exchanger Type
Single Dry Type (131/161/201GOM) and Single Wet Type (251/301/351GOM)
Combustion Method
Air Intake Method by Semi-Bunsen Burner
Gas Flow Control
Current Proportional Control Method by Thermistor
Heat Exchange
Method of Hot Water
y Heat Exchange Method : Indirect Heat Exchange by Secondary Heat Exchanger
y Heat Exchange Type : Plate Formed Brazing Heat Exchange
y Heat Exchange Circuit : Parallel Circuit
Ignition Method
Continuous Discharge, Direct Ignition Method
Heating
/
Domestic Water
Changeover
Heating Priority, Changeover to Domestic Water Circuit by 3-way Valve
Domestic Water Signal
Detect Flow by Flow Switch
y Motor : Condenser Type
y Casing : Engineering Plastic
Circulator Pump
y Impeller and Shaft Coupled : Magnetic Type
Expansion Tank
y Type : Expansion Tank
y Volume:6.5Liter(161/201GOM), 8.5Liter(251/301GOM)
Pressure Reducing /
Flow Limiting Control
and Water Hammering
Prevention
Control Pressure Reduction/Flow Limit and Prevent Water Hammering
by Diaphragm
KDB-GOM
Series
- 6 -
2.2 Constructions of the Boiler
■
Model : KDB
Model : KDB Model : KDB
Model : KDB – 251 / 301 GO M
251 / 301 G OM 251 / 301 G OM
251 / 301 G OM
■
Model : KDB – 161 / 201GOM
KDB-GOM
Series
- 7 -
2.3 Schematic Diagram of Operating
2.3.1 Schematic Diagram at the Heating Water Supply
High Limit Fuse
Fan Assembly
Heating Temperature
Sensor
Hot Water Flow Switch
Modulating
Gas Control Valve
Expansion Tank
Air Pressure Switch
Nozzle Holder Assembly
Burner Assembly
Flame Detector
Electrode
High Limit Sensor
②
Main Heat Exchanger
Exhaust Duct
③
3-Way Valve
Gas Inlet
Domestic Water Outlet
Tap Water Inlet
⑥
Heating Return
④
Heating Supply
⑦
Heating Strainer
①
Circulator Pump
Flue Exhaust
Heating Flow Sensor
Combustion Air Inlet
Domestic Water
Heat Exchanger
①
Circulator Pump → ② Main Heat Exchanger → ③ 3-Way Valve → ④ Heating Supply
⑦
Heating Strainer → ⑥ Heating Return → ⑤ Room Heating(Heating Coil, Radiator)
KDB-GOM
Series
- 8 -
2.3.2 Controls of the Heating Temperature
2.3.2.1 When the heating water temperature is selected
- Setting Temperature: 40 ~ 80
℃
- To stop the run, turns the “HEATING WATER
TEMP.” dial to “OFF” position.
2.3.2.2 When the heating is controlled by the room
temperature
- Setting Temperature: 10 ~ 40
℃
- To stop the run, turns the “ROOM TEMP.” dial to
“OFF” position.
2.3.2.3 When the heating with the repetition time
(TIMER)
- The timer sets the stop time between 0 to 4-hours.
- Press the “TIMER” button, the boiler runs for 20minutes and stops for the time set by the timer.
- The temperature of the heating water is
automatically set at 80 ℃ and the temperature
indicator displays the room temperature.
※
If the range of control has been exceeded due to the change in the set temperature or to abrupt change in
flow, the set temperature will be reached through the proportional control with the delay of 30±3 seconds.
If 83 ℃ is exceeded, the delay of 30±3 seconds will not be performed.
Control Range
Setting Temperature,
“T” set
ON OFF
Over 78
℃
63±2.0
℃
83±2.0
℃
70 ~ 77
℃
“T” set – (14±2.0)
℃
“T” set – (6±2.0)
℃
60 ~ 69
℃
“T” set – (12±2.0)
℃
“T” set – (6±2.0)
℃
50 ~ 59
℃
“T” set – (10±2.0)
℃
“T” set – (5±2.0)
℃
Below 49
℃
“T” set – (10±2.0)
℃
“T” set – (5±2.0)
℃
KDB-GOM
Series
- 9 -
2.3.3 Schematic Diagram at the Domestic Water Supply
Fan Assembly
Heating Temperature
Sensor
②
Hot Water Flow Switch
Modulating
Gas Control Valve
ⓐ
Expansion Tank
Air Pressure Switch
Nozzle Holder Assembly
Burner Assembly
Flame Detector
Electrode
High Limit Sensor
ⓒ
Main Heat Exchanger
High Limit Fuse
Exhaust Duct
ⓓ
3-Way Valve
Gas Inlet
Domestic Water Outlet
Tap Water Inlet
Heating Return
Heating Supply
Heating Strainer
ⓑ
Circulator Pump
Flue Exhaust
Heating Flow Sensor
Combustion Air Inlet
③
Domestic Water
Heat Exchanger
③
Domestic Water
Heat Exchanger
Domestic Water Line
Heating Water Line
ⓒ
Main Heat Exchanger
④
Domestic
Water Outlet
②
Hot Water
Flow Switch
①
Tap Water Inlet
ⓓ
3-Way Valve
ⓑ
Circulator Pump
ⓐ
Expansion Tank
KDB-GOM
Series
- 10 -
2.3.4 Controls of the Domestic Water Temperature
2.3.4.1 Possible use of hot water in heating/not-at-home mode and hot water exclusive mode, according to the
flow volume detection of the hot water sensor.
2.3.4.2 Indirect control of the hot water temperature based on the heating water temperature.
2.3.4.3 Control at 80℃ when using hot water during heating.
2.3.4.4 Control at 70℃ when not-at-home or hot water exclusive mode
2.3.4.5 Stand by after hot water use
y when stopped after hot water use, the fan does not perform post purge and maintain the ON status for 90
seconds.
y the pump stops after the post purge (60 seconds)
y when using hot water again and after the hot water sensor detects the flow volume
pre-ignition Æ fuel supply Æ flame detection Æ post-ignition
y return to the before-hot-water-use status 90 seconds after the use of hot water.
2.3.4.6 Combustion in progress while in stand-by for hot water (90 seconds) or after 12 seconds of the post purge
time ( while in heating mode after the hot water sensor if “OFF”). Hot water stand-by time in progress separately.
3. Equipment Protection and Personal Safety
A. Ignition Failure
If the ignition fails, the gas supply is automatically cut off. An error code will appear as a flashing 2-digit code on the room
thermostat(models FR-5 only). The error codes are discussed in the troubleshooting section of the installation manual.
B. Flame Detection
If the fails and/or the re-ignition attempt fails, the gas supply is automatically cut off. An error code will appear on the room
thermostat(models FR-5 only).
C. Power Interruption
When the power is restored after a power failure, the boiler will automatically start and return to normal
operation(Manual reset is not required).
D. Excessive Air Pressure
Occasionally an excessive gust of wind from outside may be forced into the flue pipe. The air-ratio control module
will detect these strong back-drafts. To prevent any products of combustion from re-entering the building through the
open flue, the gas supply will be automatically cut off. An error code will appear on the room thermostat(models FR5 only).
E. Explosive Re-ignition Protection
Abrupt, noisy startups and backfires are prevented by means of soft ignition, a trademark of our air-ratio control
module.
F. Overheat Protection
Any overheating of the burners or heat exchanger will automatically shut down the supply of gas to the burners.
An error code will appear on the room thermostat(models FR-5 only).
G. Low Water-Level Safety
Water levels in the heating pipes are continuously monitored to prevent the boiler from operating if there is no
water or a restricted flow through the piping. The boiler will automatically shut down and an error code will appear
on the room thermostat(models FR-5 only).
KDB-GOM
Series
- 11 -
H. Automatic Water Fill
Should the water level in the system drop too low, a sensor will automatically activate the re-fill circuit.
I. Freeze Protection
During the heating season, a sensor inside the boiler will automatically detect and initiate safe heating cycles to prevent internal
equipment damage from occurring should freezing temperatures surround the boiler.
Note !
- When there is no gas supply
available, the circulating pump will automatically start up to guard the pipes from freezing (available only in boilers equipped with a
circulation pump).
J. Gas Pressure Control
To prevent internal damage from rupture, each boiler is protected from occasional surges in gas pressure by a regulating governor
device located in the gas valve.
K. Short-Circuit Protection
Any short-circuits occurring inside the boiler’s electrical circuit will immediately ‘blow’ the internal glass fuse(s)
and automatically cut off the gas supply.
L. Lightening Protection
Each boiler is specially grounded inside and out to protect against lightening strikes.
M. Combustion air flow control
When the combustion airflow is disrupted due to a defective, obstructed or an abnormal back-pressure of the
flue, the combustion is shut off safely.
N. Thermostat Control Failure
Should the thermostat fail to function properly, as a safeguard, the boiler’s gas supply will be automatically shut
down.
KDB-GOM
Series
- 12 -
4. Specifications and Functions of the Major Components
4.1 Main Heat Exchanger
Item
161GOM 201GOM 251GOM 301GOM
Typ e
Single Dry Type Single Wet Type
Structure
Copper Fin+Copper pipe Brazing
Function
- For use of heating and hot water, absorb generated heat from main burner and
then transmit it to heating pipe and hot water heat exchanger.
Number of Heat Fin
72 Fin 80 Fin 106 Fin 112 Fin
Material & Dimension
- Copper Pipe:C1220T-H(φ15.88).
- Heat Fin:C1220P-1/4H(t=0.4)
Heat Exchange Method
Instantaneous Method
KDB – 251 / 301 GOM
KDB – 161/201GOM
KDB-GOM
Series
- 13 -
4.2 Fan Assembly
Item
161GOM 201GOM 251/301GOM
Fan Type
Phase Controlled Air Intake Fan
Motor Type
Shading Coil Induction Motor Condenser Induction Motor
Blower Dimension
(mm)
φ
100 X 40L X 45 Fin
φ
134 X 40L X 60 Fin
Function
- Supply air needed for combustion and exhaust the remained gas before and after
combustion in order to prevent explosion in advance.
Bell Mouth(mm)
φ
60
φ
70 -
Rated Voltage
AC 220V, 50Hz
Power Consumption
Max.: 36.4 W, Min.: 14.0 W Max.: 75 W, Min.: 30 W
Casing
ALDC12
Blower
AL 5052
Material
Venture
ALDC12
KDB – 161 / 201GOM
KDB – 251 / 301GOM
KDB-GOM
Series
- 14 -
4.3 Circulation Pump
Item
All GOM models
Pump Type
Magnet Type
Motor Type
Single Phase, 2 Pole Induction Motor
Function
- Transmit the absorbed heat from main heat exchanger to heating pipe by
circulating heating water when use heating.
- Transmit the absorbed heat from main heat exchanger to hot water heat
exchanger by circulating heating water inside of boiler when use hot water.
Maximum Pump Head
10M(at 0 gal/ min )
Rated Voltage
AC 220V, 50Hz
Power Consumption
90 W
Condenser Capacity
2.5
㎌
Weight
2.45 kg
KDB-GOM
Series
- 15 -
4.4 Modulating Gas Control Valve
Item
All GOM models
Model No.
UP 33 –06 (TIME CO.)
Rated Voltage
AC 220V, 50 / 60Hz
Power Consumption
8 W
Function
y Controls the flow of gas supply by the current value received from main
controller.
y Cut off the gas to prevent danger by the signal of sensor when happen troubles
caused by improper combustion.
Magnet Valve Proportional Valve
Schematic Diagram
SV1
(UV3)
SV2
(UV3)
PV
(UP2)
(SV1)
(SV2)
(PV)
Secondary pressure
Adjust Screw
Gas flow diagram
KDB-GOM
Series
- 16 -
4.5 3-Way Valve
Item
All GOM models
Rated Voltage
AC 220V, 50 / 60Hz
Power Consumption
3 W
Body Material
NYLON 66
Function
- Block the passage of heating water by the flow detection in flow switch and flow
heating water into the hot water heat exchanger when use hot water, and lead to
exchanging the heat of hot water with heating water in the hot water heat
exchanger. (When stop using hot water, the water passage is changed over to
the way of heating pipe automatically.)
Heating → Hot Water 10 ± 2 sec
Operating Time
Hot Water → Heating 10 ± 2 sec
Wire Identification
y RED : Heating, y BLUE : Hot Water y BLACK : Common
Model
Motor Speed
2.5 ~ 3 RPM
Direction of Motor
Rotation
CCW
KDB-GOM
Series
- 17 -
4.6 Expansion Tank
NO. Part Name Material Remarks
1 Body SBHG1 , 2.0t
2 Bracket SBHG1 , 2.0t
3 Diaphragm BUTYL , 2.0t
4 Nipple S10C , PF3/8”
Item KDB – 161 / 201GOM KDB – 251 / 301GOM
Vol um e
6.5 Liter 8.5 Liter
Body Material
SBHG 1
Charging Gas
Nitrogen
Charging Pressure
1.0 kg/cm2 (14.2 psig)
Function
y Vent the generated air in the heating pipe.
y Absorbs pressure generated in the pipe by the expansion of heating water due to
increasing temperature of heating water.
y Maintain the water volume in the boiler at a constant by low water level sensor.
Nitrogen gas
Charging point
KDB-GOM
Series
- 18 -
4.7 Air Pressure Switch
Item All GOM Model
Electric Rating
0.1A –125V AC, 0.1A –30V DC (Micro Switch)
Typ e
Differential Pressure Type (Vertical Type), Normal Close Type
Body Material
Nylon 66 (GF 30%)
Function
- Stop the combustion safely and automatically by monitoring the high pressure
or the adverse wind in the flue.
Contact Arrangement
ON more than 2.0 mmH2O
ON / OFF Operating
Pressure
OFF 7.0 ± 2 mmH
2
O
Reference
- Normal Close Type : The contact is always connected, and if the wind
pressure switch is operated by adverse pressure, this contact is opened and
stop the combustion in the boiler.
P3 (COM)
P1 (NC)
P2 (NO)
KDB-GOM
Series
- 19 -
4.8 Hot Water Flow Switch
Item All GOM models
Body Material
Nylon 66 (GF 30%)
ON 2.3 ± 0.3 liter / min
Operating Flow
OFF 1.5 ± 0.5 liter / min
Installation Type
Horizontal Installation
Function
- When use hot water, detect the flow of hot water and transmit the signal to
controller, and operate 3-way valve to usable hot water.
- Reduce the pressure of discharging hot water in case of high water pressure
area (water supply pressure : more than 1.5 kgf/㎠) and maintain the optimum
condition of hot water use through flow limited by reduced pressure.
Reducing Pressure
Capability
P1 : 0.3 ~ 10 kgf/
㎠
→ P2 : 0.3
~
3.0 kgf/
㎠
Contact Rating
10 VA (W)
Maximum Contact Current
AC, DC 0.5A
Contact Resistance
less than 300 m
Ω
KDB-GOM
Series
- 20 -
4.9 High Limit Sensor (Bimetal Type)
Function
- When the bimetal plate in the high limit sensor detects the increase in the
heating water temperature or in causing surface temperature, it is
transformed to move the shaft and to let the contact “OFF”
- The “OFF” signal from the high limit sensor is sent to the controllers so that
the check lamp on the room thermostat comes “ON” and the failure code
NO. 16 is displayed on the temperature indication. When the running is
resumed, only the check lamp is kept “ON”.
- In case of reduced discharge of combustion exhaust or overheat of heat
exchangers, the high limit sensor automatically cut off the gas control valve to
close it when the send the sensed the temperature of the heat exchanger
reaches 95 ℃ or higher. The check lamp on the room thermostat is lit and
failure code NO. 1 is indicated on the indication panel.
Model MS-1, Manual Reset
Type Bimetal Type
Operating Temp. 95
℃
Structure
Recovery Temp.
80
℃
Voltage Rating 125 ~ 250 V
Electric Rating
Current Rating 15 A
[Automatic, MS-1]
KDB-GOM
Series
- 21 -
4.10 High Limit Fuse (Fuse Type)
Function
- In case of abnormal overheat of heat exchanger, the temperature of sensor
part will be more than 195 ℃, high limit fuse will cut off the power of
modulating gas control valve to close the modulating gas control valve and
secure the safety.
- Check lamp will on in the room thermostat and failure code # 03 will be
indicated.
Type Fuse Type
Structure
Operation Temp. OFF point: 195
℃
Electric Rating
Resistance
61.1 Ω at 20
℃
KDB-GOM
Series
- 22 -
4.11 Heating Temperature Sensor
Item All GOM models
Model No.
DKS - 902ET - 330C
Resistance
R50 = 3.485 ㏀ ± 3%
B Constant
R0 / R100 = 3449 K ± 1%
Thermal Radiation Constant
0.7
mW /
℃
Thermal Time Constant
Within 10 seconds
Function
- Detect the temperature of heating water and transmit the signal
to main controller. The main controller controls the flow of air /
gas needed for achieving and maintaining the setting
temperature.
KDB-GOM
Series
- 23 -
4.12 Ignition Transformer
Function
- Electric energy provides high voltage and current to the main burner for
ignition of gas.
Primary Rating AC 220 V , 50 / 60 Hz
Secondary Rating 19 kVo-p±2
Power Requirement
Secondary Current
7 mA±2
Casing Non-Combustible ABS
Structure
Cable Silicon
KDB-GOM
Series
- 24 -
4.13 Power Transformer
Function
- Supply the power source to boiler.
Input Rating AC 220 V , 50 / 60 Hz
AC 220 V # 8-BLACK, # 9-GRY
AC 34.0 V # 2-RED, # 6-RED
AC 18.4 V # 1-ORANGE, # 5-BLUE
Power Requirement
Output Rating
AC 12.0 V # 4-WHITE, # 7-BROWN
Casing Non-Combustible ABS
Structure
Cable Silicon
KDB-GOM
Series
- 25 -
4.14 Domestic Hot Water Heat Exchanger
Item
161GOM 201GOM 251GOM 301GOM
Material
STS 304
Capacity
10 Pieces 12 Pieces 16 Pieces 18 Pieces
Function
- When use hot water, supply the heating water heated in main heat exchanger to hot water
heat exchanger and heat-exchange water (water supply) with heating water supplied in
hot water heat exchanger to be usable hot water.
Domestic Water
Outlet
Heating
Supply
Tap Water
Inlet
Heating
Return
KDB-GOM
Series
- 26 -
4.15 Burner Assembly
Item
161 / 201GOM 251 / 301GOM
Quantity of Secondary Nozzle
10 EA 15 EA
Material of Secondary Nozzle
ALSTAR
Slit (Flame Holder) Material
STS 430
Front Bracket
SBHG 1
Rear Bracket
STS 430
Function
- Supply heat sources by mixing and combusting the supplied gas and
air.
KDB-GOM
Series
- 27 -
4.16 Nozzle Holder Assembly
Item
161GOM 201GOM 251GOM 301GOM
Quantity of Primary Nozzle
10 EA 15 EA
Material of Primary Nozzle
C3602 BD
Material of Nozzle Holder
A6063S
LNG
φ
1.33
φ
1.46
φ
1.37
φ
1.50
Diameter of
Nozzle(mm)
LPG
φ
0.92
φ
1.06
φ
0.95
φ
1.06
Function
- Supply gas needed for combustion according to demands.
Secondary
gas pressure
measuring hole
KDB-GOM
Series
- 28 -
4
.17 Wiring Diagram
4
NO Function NO Function
1, 3
Gas Valve 1
7, 12
Ignition Transformer
2, 3
Gas Valve 2
8, 12
3-Way Hot Water
4, 11
AC 220V
9,13
3-Way Heating
5, 6
Circulation Pump
10
Ground
NO Function NO Function
1, 11
Water Filling
9, 20
Room Thermostat
2, 12
Fan
3, 13
Control Voltage
4
RPM Power Sourc e
14
RPM Input
5, 15
Heating Temp.
Sensor
15
RPM Ground
6 16
Flame Detector
7, 20
Air Pressure
Switch
17
Heating Flow Sensor
8, 20
Hot Water
Flow Switch
18, 19
Overheat
NO Function NO Function
1,5
AC 20V
4,7
AC 12V
2,6
AC 40V
8,9
AC 220V
3
AC 200V
4.17.3.3 21 Pin Wiring Connecting Diagram
4.17.3.2 9 Pin Wiring Connecting Diagram
4.17.3.1 13 Pin Wiring Connecting Diagram
4.17.3 Wiring Connecting Diagram
4.17.1 Fault repair codes (room thermostat, FR-5)
NO ON OFF
1
Trial Run Normal
2
Forced Max.
Combustion
Normal
3
Forced Min.
Combustion
Normal
4
FE FF
5
L.P. Gas Natural Gas
6
Close-Air Type Open Tank System
7
50 Hz 60 Hz
NO
161GOM 201GOM 251GOM 301GOM
8
OFF OFF ON OFF
9
ON ON OFF OFF
10
ON OFF ON ON
4.17.2 DIP S/W Setting on Main Controller
FND
No.
Problems FND
No.
Problems
01
Overheat
10
Air pressure failure
02
Low water level
11
Water level detection failure
03
Ignition failure
12
Flame failure in combustion
04
Flame sensor
(Lower gas pressure)
13
Heating water switch failure
05
Heating sensor wire
disconnected
14
Gas alarm(optional)
06
Short circuit of
heating sensor
15
MICOM failure
07
Hot water sensor wire
disconnected
16
Mechanical overheat
08
Short circuit of
hot water sensor
17
DIP switch setting error
09
Fan R.P.M. failure
18
KDB-GOM
Series
- 29 -
4.17.3 Wiring Diagram
WHT : WHITE
ORG : ORANGE
AC34V
AC220V
AC18.4V
IGNITION TRANS
LEGEND
GRY : GRAY
RED : RED
BLK : BLACK
BLK
2)BRN: Secondary valve
2)BLK: Currency
.
.
Modulation
YEL : YELLOW
BLU : BLUE
1)BLU : Primary valve
TIME UP 33-06
GAS VALVE
BLU
BLK
EV 1
BLU
BLU
RED
.
.
BRN
BRN
EV 2
HIGH LIMIT FUSE
2)BLK,BLU : HOT WATER
1)BLK,RED : HEATING WATER
THREE WAY VALVE
.
.
GRN
RED BLK
BLU
EARTH
AIR PRESSURE
: DC 5V : DC 5V
SWITCH
INPUT SIGNAL
HEATING FLOW
SWITCH
INPUT SIGNAL
: DC 20V
THERMOSTAT
INPUT SIGNAL
ROOM
: DC 5V
HOT WATER
FLOW SWITCH
INPUT SIGNAL
WHT
RED
SUPPLY POWER
BLK
WHT
FUSE , 3A - 2EA
PUMP
POWER TRANSFORMER
1)WHT : AC 5V
BLK
BLK
INPUT SIGNAL
: AC 200V
3)BLK : Ground
2)RED : DC 12V
FLAME
DETECTOR
EARTH
SUPERVISION
FAN ROTATION
BLK
RED
BLK
: DC 20V
YELYEL
GRN
PREVENTION
INPUT SIGNAL
OVERHEAT
SKYSKY
BLUBLU
ORG
BLK
RED
GRY
AC220V
: DC 5V
TEMPERATURE
HEATING WATER
INPUT SIGNAL
WHT
FAN
RED
RED
BLK
BLU
RED
RED
BLU
: DC 5 - 20V
68
F
50
176
3
86
99 4
F
2
Hrs
1
0
140
104
ORGORG
ALARM WIRE
INPUT SIGNAL
GAS LEAKAGE
BLK
BLK
RED
( - )
(+)
[13 PIN]
.
.
1
2
3
4
GRN : GREEN
BRN : BROWN
9
7
8
10
11
[9 PIN]
[21 PIN]
20
BLU
AC18.4V
RED
BRN
YEL
WHT
AC34V
AC12V
AC200V
AC12V
5
6
1
2
3
4
12
13
5
8
6
7
9
1
2
3
4
6
7
8
5
13
11
12
14
15
17
16
18
19
9
10
21
KDB-GOM SERIES WIRING DIAGRAM
AC220V, 50/60Hz
220VAC 50Hz
AC220V, 50Hz
AC220V, 50Hz
AC 220V, 50/60Hz
AC 220V, 50/60Hz
Operating Temp. : 156
°
C
KDB-GOM
Series
- 30 -
4.18 Main Controller
Voltage , Frequency AC 220V , 50 / 60 Hz
Voltage Range +10% to –15%
Ambient Temp. -15℃ to 70
℃
Electric Spec.
Ambient Humidity 45 – 90 %
Structure
Casing ABS
Model
KDC – 208-1M
4.18.1 DIP switch setting on main controller
4.18.2 Functions of Main Controllers
4.18.2.1 Pre-Purge
When the boiler operates, the function is to operate blower (fan) first and exhaust the remained air in the combustion
chamber before combustion starts, in order to prevent from immoderate ignition. Pre-Purge time is by achieving the fan’s
light-up RPM ± 200 rpm with more time than 4 ± 1 seconds.
4.18.2.2 Pre-Ignition
After Pre-Purge, the function is to operate ignition transformer previously in order to light up easily before supplying the
fuel (gas) for combustion. Pre-Ignition time is from ON time of ignition transformer till ON time of fuel supply device (gas
valve 2).
DIP Switch adjust part
Max. adjust screw
for secondary gas
pressure
NO ON OFF
1
Trial Run Normal
2
Forced Max.
Combustion
Normal
3
Forced Min.
Combustion
Normal
4
FE FF
5
L.P. Gas Natural Gas
6
Close-Air Type Open Tank System
7
50 Hz 60 Hz
NO
161GOM 201GOM 251GOM 301GOM
8
OFF OFF ON OFF
9
ON ON OFF OFF
10
ON OFF ON ON