Satron Instruments SATRON VC Installation And Setting-up Instructions

Page 1
1
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
Contents:
1. INSTALLATION
1.2 Installing the transmitter s. 3
1.3 Dimensions of the transmitter s. 5
1.4 Electrical connections s. 6
2 SETTING-UP
2.1 Setting-up with Satron VoAdvisor Service Software s. 8
2.2 Setting-up with local switches s. 8
2.3 Setting-up with remote unit s. 9
3 USER GUIDE FOR MENUS
3.1 Confi guration s. 10
3.2 New sample s. 12
3.3 Calibration s. 12
3.4 Diagnostics s. 13
4 SETTINGS
4.1 Basic settings s. 15
4.2 Collect sample s. 15
4.3 Laboratory values s. 15
4.4 Start-Up calibration s. 16
4.5 1-point calibration s. 16
4.6 2-point calibration s. 16
4.7 Offset adjustment s. 17
4.8 Gain adjustment s. 17
4.9 Time and Date settings s. 17
Satron Instruments Inc.
P.O.Box 22, FI-33901 Tampere, Finland
Tel. +358 207 464 800, Telefax +358 207 464 801
www.satron.com, info@satron.com
Installation and Setting-Up Instructions
We reserve the right for technical modifi cations without prior notice. HART® is the registered trademark of Hart Communication Foundation. Hastelloy® is the registered trademark of Haynes International. Tefl on® E.I. is the registered trademark du Pont de Nemours & Co. Viton® is the registered trademark DuPont Down Elastomer.
DOCUMENTS
Technical Specifi cations: BCs220 Installation and Setting-Up Instructions: BCs220AV
Page 2
2
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
Figure 1-1 Recommended mounting location
Minimum 2 x D
Minimum 1 x D
Minimum 1 x D
Minimum 2 x D
Minimum 1 x D
400
1. INSTALLATION
1.1 Mounting location
Installation recommendations: Figure 1-1
- transmitters should be installed as a general rule
turbulence fl ow.
- Recommended installation location
- An alternative mounting location
1
2
2
1
The mounting angle of the coupling 15°
Page 3
3
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
Figure 1-2a Mounting the transmitter on the coupling
1. Ensure that the installation valve is clean from process media which could dam­age the transmitter prior to inserting the transmitter into it.
2. Insert the transmitter into the valve and turn to fasten the valve coupler. Tighten­ing torque 40 Nm.
3. Align the installation tool slots (C1 and C2) with the transmitter slots and connect the installtion tool.
4. Turn the installation ball valve fully open and insert the trasmitter into the process, by turning the installation tool lever clockwise.
C1
C2
1.2 Installing the transmitter
Page 4
4
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
Figure 1-2b Mounting the transmitter on the coupling
5. Turn the installation tool level until the transmitter is fully inserted into the process.
6. Fasten the transmitter in place with the locking nut E, Tightening torque 40Nm.
7. Remove the installtion tool.
8. To remove the transmitter from the process, reverse the steps shows for inserting the transmitter.
E
E
Page 5
5
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
Dimensions Satron VCT
Standard 5 m Optional 10 m
Satron VC with L-housing
Dimensions Satron VCF
312
20
Ø24
Ø36
373
Ø25
Ø36
110
95
PG9 std.Ø6,2
90
120
159
Page 6
6
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
Figure 1-11 Wiring Housing with M12-connector, code HT
Figure 1-13 Wiring housing with PLUG DIN 43650-connector, code HS
Figure 1-12 Wiring
Housing with PLUG DIN43650- and M12-connector, test
connector box, codes HT and HS
1.2 Electrical connections
Supply voltage and load of the transmitter according to the Figure 1-10.
We recommend shielded twisted-pair cable as signal cable.
The signal cable should not be installed near high­voltage cables, large motors or frequency converters.
The shield of the cable is grounded at the power supply end or according to the recommendations of the manufacturer of the used control system.
Figure 1-10 Supply voltage and load capacity
Position selection 3 x 90°
1. Remove screw
2. Open
Figure1-9 Removing the PLUG junction box
Tighten the screw
Page 7
7
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
Figure 1-14 Wiring Remote electronics housing with display, code L
Page 8
8
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
2.2 Setting-up with local switches
The additional instruction of display menus is enclosed to this manual. See chapter 4
2 SETTING-UP
2.1 Setting-up with Satron-VoAdvisor Service Software
When you want to have all the operations of the Smart transmitter, we recommend the use of Satron-VOadvisor Service Software program. Satron Instruments Inc. will deliver you the program, HART-modem and HP-2133 Mini Note PC according the order.
Figure 2-1 VOadviser software
Figure 2-2 VC transmitter with display
Housing with display, code N
Keyboard :
Esc = Press Esc move back towards the top of the main menu.
= Use the UP arrow key to move up on the current menu level
or to increase the selected parameter value.
= Use the DOWN arrow key to move down on the current menu
level or to decrease the selected parameter value. Enter = Press ENTER to move to a lower level in a menu or to accept a command or parameter valu
Page 9
9
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
2.3 Setting-up with remote unit.
The Satron VC transmitter remote unit can be provided with a wall box which is capable of having a 20m cable between the Sensing unit and the Display unit. Inside the Display unit is a terminal where up to 3 binary inputs, 3 relay outputs and 2 analog milliamp loops can be connected. All connections can be used simultaneously. The signal cable between the Display unit and Sensing unit should not be installed near high-voltage cables, large motors or frequency converters.
Figure 2 - 3 Remote Connections
Figure 2 - 4 VC Sensing connections.
Inside the Sensing element is a dipswitch and a USB port. This is only used for updating the fi rmware.
DO NOT USE THE USB PORT UNLESS THERE NEEDS TO BE A NEW FIRMWARE INSTALLED.
Page 10
10
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
3. USER GUIDE FOR MENUS
The user interface for the series VO analyzers, housing option N, consists of display and operating keys. Among other things, the user interface allows you to set process variables in the desired units on the display and to confi gure the analyzer e.g. by setting the lower and upper range-values. In addition, you can perform diagnostic routines and view de­vice information through the user interface.
The 8-character liquid crystal display (LCD) with backlight allows you to display information with letters and num­bers.
OPERATING KEYS: With the UP/DOWN arrow keys and the ENTER and ESC you can move in the menus.
ENTER: Press ENTER to move to a lower level in a menu or to accept a command or parameter value.
UP: Use the UP arrow key to move up on the current menu level or to increase the selected parameter value.
DOWN: Use the DOWN arrow key to move down on the current menu level or to decrease the selected parameter value.
ESC: Press the ESC to move back towards the top of the main menu or cancel the current action.
3.0 MEASUREMENTS VALUES MENU:
When the analyzer is powered up, it immediately shows the MEASUREMENT VALUES.
Use the UP/DOWN keys to move in the menu. The menu does not have any variables adjustable by the user. Pressing DOWN shows you the following parameters in order.
the user calibrated information (% Cs)
the value of the fi rst mA loop
the temperature of the sensor head
the temperature of the electronics
active recipe name
Under the main menu are 6 submenus: Confi guration, New Sample, Calibration, Diagnostics and Advanced. To enter these
submenus press ESC for 3 seconds.
3.1 Confi guration
The transmitter confi guration settings
RCP SEL
Active recipe selection menu. RECIPE 1 Recipe selected options RECIPE (1 ... 4). The basic factory tuning is stored in the recipe 1.
To perform a new calibration is recommended to
use a new recipe.
MAOUTPUT
The current output (mA circuit) settings. LRV Lower range value (4 mA) URV Upper range value (20 mA) DAMPING:
Time constant, in seconds for output damping. The range is 0.000s to 60s. Set the value with the UP/DOWN keys and accept it with ENTER or press ESC if you do not want to change the value.
AVERAGE:
Time constant in Hz for averaging the output. The range is 1Hz to 50Hz. . Set the value with the UP/DOWN keys and accept it with ENTER or press ESC if you do not
want to change the value.
ALARMTYP: The alarm current (3,7 mA or 22,5 mA).
SYSTEM CONFIGURATION
(confi gure parameters that have an effect on the system like
e.g. language and date.)
TAG:
Tag code. You can enter free-format text one character at a time. When you select this option with ENTER the cursor will be at the left. Select characters with ENTER (to the right) and ESC (to the left). You can view the se­lectable characters one character at a time with the UP/ DOWN keys until the desired character is found. When the cursor is at the right edge you can go back to the SYSTCONF menu either by accepting the new tag code with ENTER or by pressing exiting without changing the tag code by pressing the ESC key when asked to accept your entry. Apostrophe indicates the cursor position; at point, however, the cursor will disappear. A great deal of special characters are available besides letters and numbes.
al
al
al
ue
ue
ue
20
20
20
A)
A)
A)
Page 11
11
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
MANUFACTURER:
Manufacturer’s name. (SATRON) Cannot be changed.
DEVICE TYPE: The type code of device. Cannot be changed.
VERSION:
Version numbers of the transmitter’s electronics and software. Press ENTER to select this item. Press ESC to exit. With the UP/DOWN keys you can select either CPU HW, CPU SW, ADC HW, ADC SW or MAN REV (manual revision) revision number or CPU ID-number
from this submenu.
ASSEMBLY NUMBER:
The analyzers assembly number. Press ENTER to select this item. Press ESC to exit. For instance, assembly number 0901 shows that the transmitter was made in
week 01 of the year 2009.
SERIAL NUMBER:
Serial number. Cannot be changed.
OPERATION TIME:
The value of the operation time save at 1 hour intervals. When the value of the counter is < 100 hours so value save 1- minute intervals. The value of the operation time counter on the display : HH :MM :SS when the value of counter is <100 hours HHHH : MM when the value of counter is <100000 hours
HHHHHHHH when the value of counter is ≥100000 hours
I/O CONFIGURATION
Confi gure parameters that have an effect on the INPUT and OUTPUT relays (VC transmitters with N- and L-housing) Satron highly recommends the use of the software package
VOadviser to alter these settings!
Settings menu for input / output
, I/O 1...3 (housing type N) or input PIN 1...3, output DOUT 1...3 and IO2 (housing type L)
TYPE: Select the function (housing type N) When "NONE" is selected in the I / O is turned off. To use the digital input to select DIN1. To use the digital outputs, select the DOUT1. To use the second current output confi gurable external input IO2 select EXT (only I / O 2). To use the second current outputs confi gurable to select IO2 (only I / O 3)
FUNCTION: The digital input / output function settings
HI LIMIT
the digital output will change its state depending on the HI VALUE.
LO LIMIT
the digital output will change its state depending on the LO VALUE.
SETCLOCK: Aika ja pvm(pp.kk.vvvv -hh.mm.ss) asetukset
HART: Tässä valikossa tehdään Multidrop-toiminnan ase-
tukset. Multidrop-toiminnassa kaikkien multidrop­väylään asetettujen lähettimien lähtöviesti asettuu 4 mA:iin. Osoit teel la 0 on käy tössä 4...20 mA:n vir tasil muk ka, jolloin lähetin toimii normaalisti 4...20 mA signaalilla.
DISPLAY:
In this menu you can select the looks in which the dis­play will be read.
BACKLGHT: Select the intensity of the backlighting from OFF, LOW, MEDIUM and HIGH. ANGLE: lets you select the angle of the text. NORMAL: From left to right. Transmitter mounted hori-
zontally with process connection directed to the right. ROTATED: Rotates the text 180 degrees from NOR-
MAL.
PASSWORD:
From this menu you can set a password (0…999) for the analyzer. If a password has been specifi ed, you cannot set any parameters or make any other settings on the analyzer unless you enter the correct ID number in this menu. Password is not in use when PASSWORD is 000 after reset. You enter the PASSWORD in the same way as TAG. PASSWORD will be on when you defi ne a value between 1 and 999. If you forget password get on
to Satron Instruments Inc.
FACTORY:
Restore Factory settings. After entering this menu you will get a warning message that the confi gurations will be lost after this point. To cancel the procedure press
ESC.
LANGUAGE:
Select the Display language.
ENGLISH, FRENCH.
T UNIT: Selected the temperature unit from this menu. The unit can be Celsius (°C) or Fahrenheit (°F).
PV UNIT: Selected the unit for process value in the display from this menu. (mg/l, % CS ...)
LED CURR: (the LED intensity settings) Select the amount of current, which is used for LED (%)
INFO
You can select the device information menu from the Main Menu level with the ENTER key. Use the UP/DOWN keys to view these items. Press ESC key to return to the Main Menu
level. You cannot change the data displyed in this menu.
VO
Page 12
12
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
ERROR AL the digital output will change its state
when there is an error.
WARNG AL the digital output will change its state
when there is a warning.
ERWNG AL the digital output will change its state
when there is a error and/or warning.
HOLD when the digital input is ON the whole
unit will be in a hold until the input is
OFF. NONE no function. OFT ACKN the digital input mode [ON] setting off a
timer to overfeed. RECIPE+1 digital input status [ON] RECIPE+2 increase the number of active pre-
scription for one (RECIPE 1) or two
(RECIPE 2) if the recipe is I / O SEL. TRB ZERO the digital input mode [ON] to reset the
value of the consistency of the factory. DATA LOG the digital input mode is [ON] storing
data logging is permitted if the DATA
LOG parameter is set to DIGITAL I /
O. FLSH ON the digital input mode [ON] to set the
fl ush mode to [ON]. FLSH OFF the digital input mode [ON] to set the
fl ush mode [OFF]. FLSH OVT digital output is for fl ushing guidance.
SOURCE:
Select the source to which the digital output will change its state.
PV is the process value selected by the user. (value which is behind “U” on the display). MA is the 1st current loop ST is the sensor temperature located 5 millimeter behind the optical lens RANGE-% this will show a 0 to 100 % value correlating
to 4…20mA.
ON DELAY:
On delays can be used to delay digital output state from OFF > ON transitions. The time can be selected in seconds in the range of 0…300s. By default the off delay is not used.
OF DELAY:
Off delays can be used to delay digital output state from ON > OFF transitions. The time can be selected in seconds in the
range of 0…300s. By default the off delay is not used.
OF TIMER:
Overfeed timer limits the time that the digital output can be continuously in ON state. The time can be selected in seconds in the range of 1…60000s. By default the overfeed timer is not used. Note: overfeed timer does not function if digital output is over­ridden by HOLD function, when performing a I/O test in the DIAGNOST menu or with HART CPU Control/ DOOverride.
IO2 SOURCE: The source for 2 nd mA out (PV,ST, ET, ...).
IO2 LRV: The lower range value for 2 nd mA out (4 mA).
IO2 URV: The upper range value for 2 nd mA out (20 mA).
IO2 DAMPING: The time constant for 2 nd mA out (0 ... 60 s).
3.2 NEW SAMPLE
The new sample menu
START: Store a new sample to memory.
SAMPLE H2O: Restore the water point to memory.
3.3 CALIBRATION
The calibration menu.
RECIPE: The settings for active recipe.
OFFSET: The offset correction for calibration (default 0.0)
GAIN
:
The gain correction for calibration (default 1.0)
USER.PNTS: The number of points for multipoint calibration. POINT.CNT calibrated count the number of points 1 ... 16.
Their point of entry is given a number in either the keyboard (EDIT) or by saving the real-time mea­surement (SAMPLE). Point out the value of the pair (user selectable unit) is given a number in the keypad. See the section of this manual for an example of tuning to get more information on the complete re-calibration.
USER MODE: Select the method of interpolation between the
points.
INTERPL Select a linear interpolation. SPLINE Select the spline curve with interpola
tion.
TEXT
:
Select the user name for the recipe.
Page 13
13
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
SAMPLES: The history of the sample (10). Laboratory values input.
SAMPLE 01: Upload a sample 1.
SAMPLE 09: Upload a sample 9.
SAMPLE H2O: The water value
CALIBRATE: Calibration with sample (1/2-point).
SAMPLE 01:
SAMPLE 09:
SAMPLE H2O:
The calibration list of suitable samples (samples recorded fed laboratory value).
CALIBRATION HISTORY: Transmitter calibration history.
The date / time stamped list of calibrations.
3.4 DIAGNOSTICS
(This submenu allows you to examine the transmitter’s internal errors and faults, to set the transmitter to give out a fi xed current, and to calibrate the transmitter.)
STATUS: Here you can display and reset accumulated errors one at a time. The text OK will be displayed if there are no errors. Possible error messages (alarm means a serious fault/error that also puts the current signal in fault status and makes the display blink). Table 1, the content of error word 1, page 18.
LOOPTEST: The transmitter can be set to give out a fi xed current sig­nal for testing the mA output. The fi rst ENTER will switch the transmitter off from normal mode (AUTO OFF), the second ENTER will set it for 4 mA output, and the third ENTER for 20 mA output. The next ENTER after that will give default value 12 mA, which can be changed as desired with the UP/DOWN keys. The last ENTER will switch the transmitter back to normal mode (AUTO ON). The purpose of this test is to test the accuracy of the
transmitter’s current output with a reference meter.
TRB TRIM: The transmitter calibration factory units (FU).
TRB ZERO measurement of zero Calibration of measurement by two points LRW.TRIM calibration of the lower point UPR.TRIM calibration of the upper point REMOVE delete of calibration
SENSOR TEMPERATURE TRIM: Sensor Temperature Trim. Here you are able to calibrate the temperature probe which is placed in the head of the analyzer. (Maximum by 10 degrees.)
LOOP CALIBRATION: Here you can calibrate the current signal given by the transmitter. The fi rst ENTER will switch the transmitter off from normal mode (AUTO OFF). The next ENTER will make the transmitter give out a signal which it assumes to be 4 mA. Use the UP/DOWN keys to change this value in accordance with the reading on the reference meter. Then press ENTER for 20 mA output, which you must also set in accordance with the reference meter. Press ENTER to accept the new reading. Note: Use a suffi ciently accurate reference meter.
I/O TEST: The digital inputs and outputs, as well as the power out­put of the second test. Income status is displayed on the screen and change the status of the outputs
HARDWARE:
VOLTAGES the voltage diagnostics I/O COMM device I / O communication diag-
nostic diagnostics (only housing type L)
LOG:
ADD TXT text (8 characters) increase in the
event log
DATA LOG data log mode: CYCLIC continuous (default) DIC I/O selected with digital inputs OFF off
O
TR
Th
th
tr
of
to
Th
O
Th
sc
Page 14
14
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
MAIN MENU
Page 15
15
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
Place the decimal separator with the [ ac ] [ ] and press the ENTER-button.
Press the ESC-button to enter the menu.
Select CONFIGURATION and press the ENTER-button.
Press [
]-button and select MAOUTPUT
and press the ENTER-button.
Select LRV (mA-output lower range value 4mA) and press the ENTER-button.
Insert lower range value (4 mA) with the [ se ] [
] and press ENTER-button, until upper separator reaches the right end of display.
Press ENTER-button to store the lower range value for mA-output.
Press the [ ]-button and select URV (mA-output upper range value 20mA) and press ENTER-button.
Place the decimal separator with [ ] [ ]-buttons and press ENTER­button.
Insert upper range value (20 mA) with the [
] [
er
er
] and ENTER-buttons, until upper separator reaches the right end of display.
Press ENTER-button to store the upper range value for mA-output.
Press the [ ]-button and select DAMP­ING (time constant for mA-output damp­ing) and press the ENTER-button.
Press the ENTER-button to store the alarm current value.
Press the ESC-button to return to the main measuring screen.
Set the time constant with the [ ] [ ]-button and press the ENTER­button.
Press the ENTER-button to store the time constant for mA-output damping.
Press [ ]-button and select ALARMTYP and press the ENTER-button.
Set alarm current with the [ ] [ ]-but­tons (3.7 or 22.5mA) and press the ENTER-button
Press the [ ]-button and select NEW SAMPLE and press the ENTER-button.
Press the ENTER-button and activate sampling.
The screen will blink SAMPLING text dur­ing sampling process. Press the ENTER­button when sample has been taken to end sampling.
The sampling time stamp, average and min and max cs-values during the sampling process are shown on display. Press the ENTER-button to store the sample or press ESC to cancel.
Press the ESC-button to enter the menu.
Press the [ ]-button and select SAM­PLES and press the ENTER-button.
Press the ESC-button to enter the menu.
Press the [ ]-button and select CALI­BRATION and press the ENTER-button.
Select with the [ ] [ ]-buttons the desired sample point to which labora­tory value will be inserted and press the ENTER-button.
Place the decimal separator with [ ac ] [
th
th
]-buttons and press the ENTER-
button.
Insert the laboratory value with the [ ] [
se
] and the ENTER-buttons and press the ENTER-button until upper separator reaches the right end of display.
Press the ESC-button to return to the main measuring screen.
Page 16
16
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
2-point calibration with water and one sample point
Press the [ ]-button and select the SAMPLEH2O to be the 1st calibration point and press the ENTER-button
Press the [
]-button and select the sec­ond point for calibration (SAMPL 01...09) and press the ENTER-button. The display rolls the new calculated OFFSET, GAIN values. Press the ENTER-button to store values or press the ESC-button to cancel. Press the ESC-button to return to measuring screen
Press the [ ]-button and select CALI­BRATE and press the ENTER-button
Press the ESC-button to enter the menu
Press the [
]-button and select CALI­BRATION and press the ENTER-button
Press the [ ]-button and select CALI­BRATE and press ENTER-button
Press the [ ]-button and select the sample point (SAMPL 01...09) for 1-point calibration and press the ENTER-button.
Press the ESC-button (1-point calibra­tion, no second point). The display rolls the new calculated OFFSET, GAIN values. Press the ENTER-button to store or the ESC-button to cancel. Press the ESC-button to return to the main measur­ing screen.
Press the ESC-button to enter the menu
Press [
]-button and select CALIBRA-
TION and press the ENTER-button
2-point calibration with two sample points
Select with the [
][ ] -buttons the fi rst
sample point for calibration (SAMPL
01...09) and press the ENTER-button
Press the [ ]-button and select CALI­BRATE and press the ENTER-button.
Press the ESC-button to enter the menu.
Press the [
]-button and select CALI-
BRATION and press the ENTER-button
Select with the [ ][ ] -buttons the sec­ond sample point for calibration (SAMPL
01...09) and press the ENTER-button. The display rolls the new calculated OFFSET, GAIN values. Press the EN­TER-button to store or the ESC-button to cancel. Press the ESC-button to return to the main measuring screen.
Page 17
17
SATRON VC Optical Consistency Transmitter
BCs220AV
Revision 2
15.10.2014
Select RECIPE and press the ENTER­button.
Select OFFSET and press the ENTER­button.
Place the decimal separator with [
] [ ]-buttons and press ENTER-
button.
Insert the OFFSET value with the [
] [ ] and ENTER-buttons, until up­per separator reaches the right end of display.
Press the ENTER-button to store the OFFSET value.
Press the ESC-button to return to main measuring screen.
Press the ESC-button to enter the menu.
Press the [
]-button and select CALI-
BRATION and press the ENTER-button.
Select RECIPE and press the ENTER­button.
Place the decimal separator with [ ] [ ]-buttons and press ENTER­button.
Press the ESC-button to enter the menu.
Press the [
]-button and select CALI-
BRATION and press the ENTER-button.
Press the [ ]-button and select GAIN and press the ENTER-button.
Insert the GAIN value with the [ ] [ ] and ENTER-buttons, until up­per separator reaches the right end of display.
Press the ENTER-button to store the GAIN value.
Press the ESC-button to return to main measuring screen.
Insert date with the [ ] [ ] -buttons (dd.mm.yyyy), press the ENTER-button to move dd->mm->yyyy and press the ENTER-button.
Insert time with the [ ] [ ] -buttons (hh.mm.ss), press the ENTER-button to move hh->mm->ss and press the ENTER-button.
Press the ESC-button to enter the menu.
Press the [ ]-button and select CON­FIGURATION and press the ENTER­button.
Press the [
]-button and select SYST-
CONF and press the ENTER-button.
Press the [
]-button and select SET-
CLOCK and press the ENTER-button.
Press the ESC-button to return to main measuring screen.
Page 18
18
BCs220AV
Revision 2
15.10.2014
SATRON VC Optical Consistency Transmitter
Satron Instruments Inc.
www.satron.com
P.O.Box 22, FI-33901 Tampere, Finland
Tel. +358 207 464 800, Telefax +358 207 464 801
Table 1. The content of error word 1
(EW1=0…15)
Bit
Error message
Description
0 TU ER Process value error
1 ST ER Sensor temperature (ST) error
2 ET ER Electronics temperature (ET) error
3 RANGE ER Percentage of output under -10% or over 110% error
4 OUTSA WA Output current saturated
5 ADCR ER ADC converter runtime error
6
7
8 ADCS ER ADC converter startup error
9 EEPRR ER EEPROM checksum error
10 EEPRW ER EEPROM write error
11 EECAL ER EEPROM calibration error
12 HART ER HART communication error
13 INTRN ER Internal system error
14 OFTMR WA Overfeed timer warning
15