Satel INT-SK, INT-S Quick Installation Manual

Page 1
®
INT-SK
PARTITION KEYPAD
int-sk_sii_en 12/15
Quick installation guide
Full manual is available on www.satel.eu
The INT-SK partition keypad offers control of one par access control features. The device can be used in conjunction with the INTEGRA and INTEGRA Plus control panels.
The keypad is designed for indoor installation. The place of installation should be readily accessible to the system users.
1. Open the keypad enclosure.
2. Set the partition keypad address (see “Setting address”).
3. Place the enclosure base on the wall and mark the location of mounting holes.
4. Drill the holes for wall plugs (screw anchors).
5. Run the wires through the opening in the enclosure base.
6. Using wall plugs (screw anchors) and screws, fasten the enclosure base to the wall.
7. Connect the CLK, DTA and COM terminals to the appropriate terminals of the control panel expander bus (see the control panel installer manual). It is recommended that an unshielded non-twisted cable be used for making the connection. If you use the twisted­pair type of cable, remember that CLK (clock) and DTA (data) signals must not be sent through one twisted-pair cable. The wires must be run in one cable.
8. If the partition keypad is to control an electric strike, electromagnetic lock or another door actuator, connect corresponding wires to the NO terminals (see Fig. 1). It is not recommended that the door actuator be powered from the same source as the partition keypad.
tition in the alarm system and provides
Fig. 1. Connecting wires to NO terminals of the keypad.
9. Connect the wires of door status sensor to the IN and COM terminals. If the door status is not to be monitored, connect the IN terminal to the keypad COM terminal or, when configuring the keypad, set value 0 for the M
AX. DOOR OPEN TIME
parameter.
Page 2
2 INT-SK SATEL
10. Connect the power wires to the +12V and COM terminals. The keypad may be powered directly from the control panel, from an expander with power supply or from a power supply unit.
11. Close the keypad enclosure.
12. Power on the alarm system.
13. Start the identification function in the control panel (see the control panel installer manual). The keypad will be identified as “INT-S/SK”.

Setting address

To set address, use the switches 1-5 of the DIP-switch package. A numerical value is assigned to each switch. In OFF position, the value is 0. Numerical values assigned to individual switches in ON position are shown in Table 1. The sum of numerical values assigned to switches 1-5 means the address set on the module. The address must be different from that on the other modules connected to the communication bus of the control panel.
DIP-switch number 1 2 3 4 5 Numerical value 1 2 4 8 16
Table 1.
Fig. 2. Examples of partition keypad address setting.

Description of terminals

NO - relay output IN - door status monitoring input (NC) COM - common ground +12V - power input DTA - data (expander communication bus) CLK - clock (expander communication bus)
The declaration of conformity may be consulted at www.satel.eu/ce
SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND
tel. 58 320 94 00
www.satel.eu