Satec RPT091 Quick Manual

RPT091
Remote Power
Transducer
QUICK GUIDE
RPT091 Remote Power Transducer
QUICK GUIDE
The RPT091 is a compact three-phase AC Remote Power Transducer. The unit operates with a remote master (computer or PLC), and with an optional Remote Display Module (RDM091) for local display/setup. The RDM091 is stand-alone or operable with a remote master, and can be panel-mounted or hand-held. Communications are via an RS-422 or RS­485 line, operable in multi-drop mode for connection of up to 32 instruments to a single line.
IMPORTANT
Please read instructions contained in this manual before performing installation, and take note of the following precautions:
1. Ensure that all incoming AC power and other power sources are turned OFF before performing any work on the instrument.
Failure to do so may result in serious or even fatal injury
and/or
equipment damage.
2. Before connecting the instrument to the power source, check the labels on the side of the instrument to ensure that your instrument is equipped with the appropriate power supply voltage, input voltages, currents, analog output and communication protocol for your application. Also check the correctness of other ordering options.
3. Under no circumstances should the instrument be connected to a power source if it is damaged.
4. To prevent potential fire or shock hazard, do not expose the instrument to rain or moisture.
5. Mount the instrument away from heat sources in a dirt-free environment. Do not operate the instrument in direct sunlight.
6. The secondary of an external current transformer must never be allowed to be open circuit when the primary is energized. An open circuit can cause high voltages, possibly resulting in equipment damage, fire and even serious or fatal injury
. Ensure that the current transformer wiring is made through shorting switches and is secured using an external strain relief to reduce mechanical strain on the screw terminals, if necessary.
7. The RPT091 relays should not
be used for basic (primary)
protection of power lines, transformers or motors, or for protection
of people from injury.
8. Setup procedures must be performed only by qualified personnel familiar with the instrument and its associated electrical equipment.
2
9. DO NOT attempt to open the instrument under any
circumstances.
10. Although designed to operate in an electrically noisy environment, the instrument should not be placed near very high
electric fields. In the event that the instrument is mounted in a harsh, noisy environment with high potential for electromagnetic impulses from heavy switch gears, motors or lightning, it is recommended to install appropriate protective devices such as lightening and over-voltage arresters to all incoming voltage inputs.
LIMITED WARRANTY
The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts from date of dispatch from the distributor. In all cases, this warranty is valid for 36 months from the date of production. This warranty is on a return to factory basis.
The manufacturer does not accept liability for any damage caused by instrument malfunction. The manufacturer accepts no responsibility for the suitability of the instrument to the application for which it was purchased.
Failure to install, setup or operate the instrument according to the instructions herein will void the warranty.
Your instrument may be opened only by a duly authorized representative of the manufacturer. The unit should only be opened in a fully anti-static environment. Failure to do so may damage the electronic components and will void the warranty.
NOTE
The greatest care has been taken to manufacture and calibrate your instrument. However, these instructions do not cover all possible contingencies that may arise during installation, operation or maintenance, and not all details and variations of this equipment are covered by these instructions.
For additional information regarding installation, operation or maintenance of this instrument, contact the manufacturer or your local representative or distributor.
BG0227 Rev. A2
3
Table of Contents
1 Measured Parameters and Outputs_________________4
2 Mechanical Installation___________________________5
3 Electrical Installation ____________________________7
3.1 Power Supply ________________________________7
3.2 Current Inputs________________________________7
3.3 Ground _____________________________________8
3.4 Voltage Inputs________________________________8
3.5 Relays ______________________________________12
3.6 Status Inputs_________________________________13
3.7 Analog Output _______________________________13
4 RDM Display ___________________________________14
5 Setup on the RDM _______________________________18
5.1 Basic Setup Parameters _______________________19
5.2 Communications Port Setup Parameters__________21
6 Communications ________________________________22
7 Troubleshooting ________________________________24
Appendix: Technical Specifications____________________27
Instrument Dimensions
4
1 Measured Parameters and Outputs
’ = averages of 8, 16, or 32 real-time values; ’+’ = real-time values, 1 frequency cycle
Parameter
Commu­nication
Display RDM
Analog Output
Pulsing Relay
Alarm/Con­trol Relay
Voltages and Currents
Voltage (L-n/L-L) per phase
+ +
+
Current per phase
+ • +
+
Neutral (unbalanced) current
• +
Powers
kW per phase
+
kvar per phase
+
kVA per phase
+
Power factor per phase
+
kW total
+ +
kvar total
+ +
kVA total
+ +
Power factor total
+ +
Frequency
+ +
+
Demand
Ampere Demand per phase
Max. Amp. Demand per phase
Accumulated kW Demand
Accumulated kVA Demand
kW Demand
KVA Demand
kW Sliding Demand
KVA Sliding Demand
kW Maximum Sliding Demand
KVA Maximum Sliding Demand
Energy
kWh Import per phase
kvarh Import per phase
kVAh Import per phase
kWh Total Import / Export
kvarh Total Import / Export
kvarh Total Absolute
kVA Total
kvarh net
Harmonic Distortion (RPT091H only)
Voltage THD per phase
+
+
Current THD per phase
+
+
Current TDD per phase
+
+
K- Factor per phase
+
Status
Digital Input Status
Relay Output Status
Alarm Trigger Status
Phase Rotation
Remote Control via Comm.
5
2 Mechanical Installation
Inspect the instrument for physical damage incurred in transit. If the instrument is damaged, inform your local distributor immediately.
Figure 2-1 RDM Cut-out Dimensions
--------------------------------------------------------------------------------------
Figure 2-2 RDM Panel Mounting
STEP 1: Insert RDM into cut-out.
6
STEP 4: Mount RPT on studs. STEP 5: Assemble 4 screws and washers. STEP 6: Fasten RPT to brackets; tighten nuts. STEP 7: Connect RDM to RPT via the 15-pin connectors
using cable supplied.
STEP 1: Insert RDM into cutout.
STEP 2: Mount brackets on studs.
STEP 3: Fasten brackets; do not tighten nuts.
Figure 2-3 Retrofit: Brackets Mounting
Figure 2-4 Retrofit:
RPT Mounting
7
3 Electrical Installation
3.1 Power Supply
The power source can be dedicated-fused, or from a monitored voltage if it is within the transducer power supply range.
AC power supply: line to terminal 12; neutral to terminal 10. DC power supply: positive to terminal 12; negative to terminal 10.
Figure 3-1 Locations of Terminals: Front View
NOTE: Power source connection requires use of the suppression core
provided with the instrument.
IMPORTANT: It is recommended to solder the wire ends
before attaching them to the connectors.
3.2 Current Inputs
To ensure accurate readings, the input current should not exceed
1.2A RMS and 1.76A amplitude for the 1A CT secondary, or 6A RMS and 8.8A amplitude for the 5A CT secondary.
8
If copper wiring is used, its thickness should be 2.5 - 4 mm
2
(13 -
11 AWG).
3.3 Ground
Connect the chassis ground of the RPT091 to the switchgear earth ground using dedicated wire greater than 2 mm
2
/14 AWG.
3.4 Voltage Inputs
Input of 690V (Standard): To ensure accurate readings, the measured voltage between terminals 2-5, 5-8 and 8-2 should not exceed 790V AC RMS, and the measured voltage between terminals 2-11, 5-11 and 8-11 should not exceed 460V AC RMS and 695V amplitude. Use any of the seven wiring configurations shown in Figures 3-2 through 3-8.
Input of 120V (Option U): To ensure accurate readings, the measured voltage between terminals 2-5, 5-8, 8-2, 2-11, 5-11 and 8-11 should not exceed 144V AC RMS and 225V amplitude. 120V input usually implies use of a potential transformer (PT). The PT requires use of any of the four wiring configurations shown in Figures 3-4 through 3-7.
Wiring Configurations ‘Wiring Mode‘ Definition
(See parameter setup instructions in Section 5)
3-wire direct connection using 2 CTs (2-element)
3dir2 (Figure 3-2)
4-wire WYE direct connection using 3 CTs (3-element)
4Ln3 or 4LL3 (Figure 3-3)
4-wire WYE connection using 3 PTs, 3 CTs (3-element)
4Ln3 or 4LL3 (Figure 3-4)
3-wire open delta connection using 2 PTs, 2 CTs (2-element)
3OP2 (Figure 3-5)
4-wire WYE connection using 2 PTs, 3 CTs (2½ -element)
3Ln3 or 3LL3 (Figure 3-6)
3-wire open delta connection using 2 PTs, 3 CTs (2½­element)
3OP3 (Figure 3-7)
4-wire delta direct connection using 3 CTs (3-element)
4Ln3 or 4LL3 (Figure 3-8)
9
LINE
LINE
I
I
+
K
+
K
-
L
-
L
1(A)
2(B)
3(C)
Shorting Switches
+
+
1197
6
431
1210
8
5
2
V
1
V
2
V
N
V
3
1
3
Currents Voltages
LOAD
Figure 3-2 Three Wire Direct Connection Using 2 CTs (2-element) Wiring Mode = 3dir2
LINE
LINE
LINE
I
I
I
+
+
-
K
+
K
K
-
L
L
-
L
1(A)
2(B)
3(C )
Shorting Switches
+
+
+
11976431
1210
8
5
2
V
1
V
2
V
N
V
3
1
2
3
Currents Voltages
LOAD
Figure 3-3 Four Wire WYE Direct Connection using 3 CTs (3-element) Wiring Mode = 4LL3 or 4Ln3
10
LINE
LINE
LINE
+
+
+
+
+
+
+
-
K
+
K
K
-
L
L
-
L
1(A)
2(B)
3(C)
Shorting Switches
+
+
+
1197643112
V
VVV
1
2
3
Currents Voltages
LOAD
N
LINE
LINE
LINE
+
+
+
-
K
+
K
K
-
L
L
-
-
-
-
-
-
-
L
1(A)
2(B)
3(C)
Shorting Switches
+
+
+
10
8
5
2
V
V
V
I
I
I
V
Currents Voltages
LOAD
Figure 3-4 Four Wire Wye Connection Using 3 PTs,3 CTs (3-element) Wiring Mode = 4LL3 or 4Ln3
LINE
LINE
+
+
+
+
+
K
I
I
I
+
K
-
L
-
-
-
-
-
L
1(A)
2(B)
3(C)
Shorting Switches
+
+
11
9
76431
1210
8
5
2
V
1
V
2
V
N
V
3
1
2
3
Currents Vo ltages
LOA D
Figure 3-5
Three Wire Open Delta Connection Using 2 PTs, 2 CTs (2-element) Wiring Mode = 3OP2
11
LINE
LINE
LINE
+
+
+
+
+
+
-
K
+
K
K
-
L
L
-
--
--
L
1(A)
2(B)
3(C)
Shorting Switche s
+
+
+
11976431
1210
8
5
2
V
1
V
2
V
N
V
3
1
2
3
Currents Voltages
LOAD
I
I
I
Figure 3-6 Four Wire Wye Connection Using 2 PTs, 3 CTs (2 ½-element) Wiring Mode = 3LL3 or 3Ln3
[Note: Use this configuration only if voltages are balanced]
LINE
LINE
+
+
-
K
+
K
K
-
L
L
-
L
1(A)
2(B)
3(C)
Shorting Switche s
+
+
+
11976431
1210
8
5
2
V
1
V
2
V
N
V
3
1
2
3
Currents Voltages
LOAD
+++
+
-
-
-
-
I
I
I
Figure 3-7 Three Wire Open Delta Connection Using 2 PTs, 3 CT (2½-element) Wiring Mode = 3OP3
12
2. Line to line voltages: 240V; 240V; 240V.
VOLTAGES DISPLAYED:
N
2
4
0
V
(A)
*
L
120V
L
*
(C)
2
4
0
V
120V
208V
L
*
(B)
delta connectio n
Power Transformer
N
LINE
LINE
LINE
208VAC
240 V AC
240VAC
N
L
3
*
*
*
*
*
*
120VAC
N
L
3
(C)
120VAC
240VAC
2
L
L
1
(A)
2
L
(B)
1
L
+
+
-
K
+
K
K
-
L
L
LOA D
-
L
c98-10008
1(A )
2(B )
3(C)
Shorting Switches
+
+
+
11976431
1210
8
5
2
V
1V2
V
I
II
N
V
3
1
2
3
Currents Voltages
Figure 3-8 Four Wire Delta Direct Connection Using 3 CTs (3 element) Wiring Mode = 4LL3 or 4Ln3
____________________________________________________________
3.5 Relays
Two relays are provided for energy pulsing, alarms or remote control.
Figure 3-9 Relay Output Terminal
13
3.6 Status Inputs
Figure 3-10 Status Inputs Connections
3.7 Analog Output
The RPT091 provides one optically isolated analog output with an internal power supply and current output options of 0-20 mA, 4-20
mA, 0-1 mA and ±1 mA.
Figure 3-11 Analog Output
Stabilization of the analog output after an input change takes up to 250 ms for real time data, and 1 to 6 sec for average data, depending on how the buffer is defined in the setup (see Section
5.1, Basic Setup).
One or two AX-7 analog expanders, DIN-rail mounted and connected via an RS-422 line, can be used for extension of the internal analog output.
Four status inputs are provided for status monitoring, external synchronization input for power demand period, o
r
output selector for multiplexed analog output.
14
4 RDM Display
Upon power up, the RDM assumes the display mode. Displayed parameters are divided into 4 groups. Each group is accessible by pressing the appropriate key, as follows:
Measurement Group: To Display Parameters:
Common default - Press the key that has an
illuminated arrow LED pointing to it (below the lower window). If no LED is lit up, this means that the RDM is displaying the common measurements parameters.
Maximum demands
press MAX. DEMAND key
Harmonic *
press THD/TDD key (RPT091H only)
Energy
press ENERGY key
* Only the RPT091H provides harmonic measurements. The
RDM is the same for both the RPT091 and the RPT091H. In the case of the RPT091, the THD/TDD key is not used.
[Press both arrows simultaneously to return to page 1of the display]
Scrolls display pages back
Scrolls display pages forward
Quits display mode and enters setup mode
Window 1
Window 3
Window 2
15
Table 4-1 Displayed Parameters
Page Window LED 4 Parameter c Digits Unit d
Common Measurements
1 1
V1/V1-2
Voltage L1/L12 4 V/kV
1 2
V2/V2-3
Voltage L2/L23 4 V/kV
1 3
V3/V3-1
Voltage L3/L31 4 V/kV
2 1
A1
Current L1 4 A/kA
2 2
A2
Current L2 4 A/kA
2 3
A3
Current L3 4 A/kA
3 1
kVA
Total kVA 4 kVA/MVA
3 2
PF
Total power factor 4
3 3
kW
Total kW 4 kW/MW
4 1
A NEUT
Neutral current 4 A/kA
4 2
Hz
Frequency 4 Hz
4 3
kvar
Total kvar 4 kvar/Mvar
5 1
Ph.L1
Label
5 2
PF
Power factor L1 4
5 3
kW
kW L1 4 kW/MW
6 1
kVA
kVA L1 4 kVA/MVA
6 2
Ph.L1
Label
6 3
kvar
kvar L1 4 kvar/Mvar
7 1
Ph.L2
Label
7 2
PF
Power factor L2 4
7 3
kW
kW L2 4 kW/MW
8 1
kVA kVA L2
4 kVA/MVA
8 2
Ph.L2
Label
8 3
kvar kvar L2
4 kvar/Mvar
9 1
Ph.L3
Label
9 2
PF
Power factor L3 4
9 3
kW
kW L3 4 kW/MW
10 1
kVA kVA L3
4 kVA/MVA
10 2
Ph.L3
Label
10 3
kvar kvar L3
4 kvar/Mvar
11 1
PHAS.
Label
11 2
rOt.
Label
11 3
Phase rotation(POS/NEG/ERR) 4
12 1
StAt.
Label
12 3
Status inputs #1-#4 4
13 1
rEL.
Label
13 3
Relay status #1-#2
4
16
Page Window LED 4 Parameter c Digits Unit d
Maximum Demands
MAX. DEMAND
1 1
A1
Maximum ampere demand L1 4 A/kA
1 2
A2
Maximum ampere demand L2 4 A/kA
1 3
A3
Maximum ampere demand L3 4 A/kA
2 1
kVA
Max. sliding window kVA demand 4 kVA/MVA
2 3
kW
Max. sliding window kW demand 4 kW/MW
Harmonic Measurements
THD
1 1
V1/V1-2
Voltage THD L1/L12 4 %
1 2
V2/V2-3
Voltage THD L2/L23 4 %
1 3
V3/V3-1
Voltage THD L3 4 %
2 1
A1
Current THD L1 4 %
2 2
A2
Current THD L2 4 %
2 3
A3
Current THD L3 4 %
TDD
3 1
A1
Current TDD L1 4 %
3 2
A2
Current TDD L2 4 %
3 3
A3
Current TDD L3 4 %
Total Energies
1 1
MWh Ac.En.
Label
1 2
IP.
Label
1 3
MWh import 6 MWh
2 1
Mvarh rE.En.
Label
2 2
IP.
Label
2 3
Mvarh import 6 Mvarh
3 1
MVAh AP.En.
Label
3 3
MVAh 6 MVAh
4 1
MWh Ac.En.
Label
4 2
EP.
Label
4 3
MWh export 6 MWh
5 1
Mvarh rE.En.
Label
5 2
EP.
Label
5 3
Mvarh export 6 Mvarh
Phase Energies (if enabled in the BASIC SETUP configuration)
6 1
MWh Ac.En.
Label
6 2
IP.L1
Label
6 3 MWh import L1 6 MWh
7 1
Mvarh rE.En.
Label
7 2
IP.L1
Label
7 3 Mvarh import L1 6 Mvarh
8 1
MVAh AP.En.
Label
8 2
L1
Label
8 3 MVAh L1
6 MVAh
17
Page Window LED 4 Parameter c Digits Unit d
9 1
MWh Ac.En.
Label
9 2
IP.L2
Label
9 3 MWh import L2 6 MWh
10 1
Mvarh rE.En.
Label
10 2
IP.L2
Label
10 3 Mvarh import L2 6 Mvarh
11 1
MVAh AP.En.
Label
11 2
L2
Label
11 3 MVAh L2 6 MVAh
12 1
MWh Ac.En.
Label
12 2
IP.L3
Label
12 3 MWh import L3 6 MWh
13 1
Mvarh rE.En.
Label
13 2
IP.L3
Label
13 3 Mvarh import L3 6 Mvarh
14 1
MVAh AP.En.
Label
14 2
L3
Label
14 3 MVAh L3 6 MVAh
c Display readings for all electrical quantities are sliding average values. d Voltage and current readings with a decimal point are displayed in kV and
kA. Power readings with a decimal point are displayed in MW, Mvar, and MVA. When the value is wider than the window, the right-most digits are truncated.
e The maximum range for energy readings is 999,999,999 kWh/kvarh/kVAh.
Beyond this value, the reading will roll over to zero. Negative (exported) energy readings are displayed without a sign.
18
5 Setup on the RDM
Setup can be performed via the RDM or PComTest software. PComTest is supplied on a disk which includes setup
instructions
1
.
The functions of the RDM keys in the setup mode are shown below:
Figure 5-1 RDM Panel - Setup Mode
Setup Procedure
1. Press
SELECT to enter setup mode.
2a. Press
SELECT again to go to SEE (for viewing only), or
2b. Press SELECT again to go to CHG (for editing setup)
3. Press
ENTER. If a password is required, use ▼ to input the
first digit and press
SELECT to advance to next digit. After all
4 digits are input, press
ENTER.
4. Press
SELECT to choose the menu; press ENTER.
1
All parameters may be set up via either the RDM or PComTest. It is
recommended to use the RDM for Basic and Communications parameters setup, and to use PComTest for setup of all other menus.
Menu
Parameter
Parameter value
To enter a menu/store a value
To move between windows
To return to previous level or quit without saving changes
To scroll through parameter
19
5. Press SELECT to activate the middle window; use ▲ ▼ to
choose the parameter; press
ENTER.
6. Press
SELECT to activate the lower window; use ▼ to
choose the value; press
ENTER (or press ESC to leave value
unchanged).
Menus
Code Full Name Code Full Name
bASc Basic - see Section 5.1 PulS Pulsing Relay *
Port Communications Port -
see Section 4.2
SetP
rtc
Alarm Setpoints *
Real time Clock*
dinP Digital (Status) Inputs * disp Display*
Aout Analog Output * rSt Reset enable/disable *
AEPn Analog Expander * AccS Password enable/disable *
* For full setup instructions for these parameters, see the complete
RPT091 Installation and Operation Manual.
5.1 Basic Setup Parameters
Options / Code Parameter Value Range Description
ConF Wiring Mode 3OP2 3-wire open delta using 2 CTs (2
element)
Default =
3OP3
4Ln3
3dir2
4LL3
3Ln3
3LL3
3-wire open delta using 3 CTs (2½ element)
4-wire Wye using 3 PTs (3 element), line to neutral voltage readings 3-wire direct connection using 2 CTs (2 element) 4-wire Wye using 3 PTs (3 element), line to line voltage readings 4-wire Wye using 2 PTs (2 ½ element), line to neutral voltage readings 4-wire Wye using 2 PTs (2 ½ element), line to line voltage readings
Pt PT Ratio 1.0 to
6500.0
The phase potential transformer ratio. If direct connection, set PT to 1; otherwise, PT= primary voltage/ secondary voltage
Default = 1
20
Options / Code Parameter Value Range Description
Ct CT Primary
Current
1 to 50000 The primary current rating of the
phase current transformer, in A
Default = 5
d.P Demand
Period
1,2,5,10, 15,20, 30,60,E
The length of the demand period for power demand calculations, minutes. E = external synchronization
Default = 15 min
n.dp Number of
Demand Periods
1-15 The number of demand periods to be
averaged for sliding window demands.
Default = 1 = block interval demand calculation
A.dP Ampere
Demand Period
0 to 1800 The length of the demand period for
ampere demand calculations, in seconds. 0 = measuring peak currents
Default = 900 sec
buF Averaging
Buffer Size
8,16,32 The number of measurements for
RMS sliding averaging. Default = 8
rSt RESET
enable/disabl e
diS, En Protects all reset functions either via
the RDM or communications. When set to diS, these functions are disabled. Default = En
Freq Nominal
Frequency
50, 60 The nominal frequency of the
monitored electrical network, in Hz.
Default = 50 Hz NOTE: When measured voltages exist, the nominal frequency is the measured frequency. This parameter is used when measuring currents in the absence of voltages.
LoAd Maximum
Demand Load Current
1-50,000 The maximum demand load current
used in TDD calculations, in A. If
value is unknown, set to CT Primary
Current value.
Default = 5000
Ph.En Phase Energy
Measurement
dis, En Enables/disables measurements of
energies per phase. Default = En
21
5.2 Communications Port Setup Parameters
Options / Code Parameter Value Range Description
Prot Communications
Protocol *
ASCII rtu
dnP3
ASCII protocol
= Default
non-ASCII protocol
rS Interface
Standard
422 485
RS-422 (4 wires) RS-485 (2 wires)
=Default
Addr Address 0-255 Powermeter address:
1-99: ASCII; 1-247: Modbus 255: DNP 3.0, SPA
Default = 1
bAud Baud Rate 110, 300, 110 baud, 300 baud, 600, 1200, 600 baud, 1200 baud, 2400, 4800, 2400 baud, 4800 baud, 9600, 19.2 9600 baud = Default,
19200 baud
dAtA Data Format 7E 7 bits, even parity 8n 8 bits, no parity = Default 8E 8 bits, even parity
* The communications protocol is selected by a short between
terminals 13 and 14 on the RPT091 (see Section 6). The protocol may be modified after a cold restart of the RPT091.
22
6 Communications
Figure 6-1 Terminal Block - ASCII
--------------------------------------------------------------------------------
Figure 6-2 Terminal Block - Non-ASCII
Both the RS-422 and RS-485 standards enable connection of up to 32 instruments on one multi-drop line for a distance of up to 1200 meters.
The RPT091 provides two green LED indicators TXD and RXD, which show activity on the RS-422/RS-485 communication port. The TXD indicator flashes when the instrument sends out data. The RXD indicator flashes when the instrument receives data.
Figures 6-3 through 6-6 illustrate all RS-422 and RS-485 cable configurations and wiring connections.
A full description of the communications software is found in the RPT091 Communications Manual.
NOTE
Where an RS-232/RS-422 converter is used, R1 is not applicable (see Figures 6-3 and 6-4) since it is built in to the converter.
+TX Transmit Data Plus +RX Receive Data Plus
-TX Transmit Data Minus
-RX Receive Data Minus
PROT Communication Protocol
23
#1
#32
Tx
Tx
Tx
Tx-
Tx-
Tx-
Rx
Rx
Rx
Rx-
Rx-
Rx-
#2
2
15
16
17
14
4
5
3
Shield
Shield
POWERMETERS
IBM PC/COMPATIBLE
RS-422/RS-485
R1
R1, R2: 200 - 500 Ohm
RxD
RT S
RxD-
RT S-
TxD
CTS
TxD-
CTS-
R2
OR RS-232/RS-422 CONVERTER
25 PIN DB25 FEMALE CONNECTOR
Figure 6-3 RS-422 Multidrop
Connection, 25-Pin PC Port
#32
Tx
Tx
Tx
Tx-
Tx-
Tx-
Rx
Rx
Rx
Rx-
Rx-
Rx-
#2
8
6
7
2
4
5
9
3
Shield
Shield
Shield
POWERMETERS
IBM PC/COMPATIBLE
RS-422/RS-485
R1
R1, R2: 200 - 500 Ohm
RxD
RTS
RxD-
RTS-
TxD
CTS
TxD-
CTS-
R2
9 P IN DB9 FEM ALE CONNE CT
O
Figure 6-4 RS-422 Multidrop
Connection, 9-Pin PC Port
#32
Tx
Tx
Tx
Tx-
Tx-
Tx-
Rx
Rx
Rx
Rx-
Rx-
Rx-
#2
2
15
16
17
14
4
5
3
Shield
Shield
Shield
POWERMETERS
IB M P C/ CO M PATI B LE
RS-422/RS-485
R1
R2
R1, R2: 200 - 500 Ohm
RxD
RT S
RxD-
RT S-
TxD
CTS
TxD-
CTS-
OR RS-232/RS-422 CONVERTER
25 PIN DB25 FEMALE CONNECTOR
Figure 6-5 RS-485 Multidrop
Connection, 25-Pin PC Port
#32
Tx
Tx
Tx
Tx-
Tx-
Tx-
Rx
Rx
Rx
Rx-
Rx-
Rx-
#2
Shield
Shield
Shield
POWERMETERS
IBM P
C
/COMPATIBLE
RS-422/RS-485
R1
R2
R1, R2: 200 - 500 Ohm
RxD
RT S
RxD-
RT S-
TxD
CTS
TxD-
CTS-
OR RS-232/ RS-422 CONVERTER
25 PIN DB25 FEMALE CONNECTOR
8
6
7
2
4
5
9
3
Figure 6-6 RS-485 Multidrop
Connection, 9-Pin PC Port
Use a shielded, 0.33 mm2/22 AWG twisted pair cable for each communication link; terminate the ends of multi-drop line with 200-500 Ohm resistors. Connect the cable shield to the ground input.
24
7 Troubleshooting
Problem Probable Cause What to do
Code other than ‘8’on RDM panel LED
Self-diagnostic test negative result
Note the code and call your distributor
Power LED on RPT not lit
Insufficient power supply
Check voltage level on power supply inputs (10,12)
Display LED on RDM not lit
Faulty cable connection
Check RDM cable connections
Varying line-to-line voltages
Incorrect voltage inputs connections
Check voltage inputs connections
Non-positive phase rotation
1. Concrete load has negative sequence
2. Incorrect voltage inputs connections
3. One or two phase voltages not connected
Check voltage inputs connections
One or more phase currents not displayed
Incorrect current inputs connections
Check current inputs connections
Phase active powers or power factors unequal or values do not correspond to actual load
Incorrect voltage or current inputs connections
Check voltage and current inputs connections; check polarity of CT connections
Cannot proceed past the first RDM menu
Incorrect password Check that your
password is correct. If you cannot provide the correct password, call your distributor for instructions on overriding password protection.
RDM window continues to flash after pressing ENTER
Value has been entered incorrectly or is incompatible with other setup parameters.
Check that parameter definition is correct.
25
Problem Probable Cause What to do
Alarm setpoints or analog output channels disabled
Setup parameters that affect voltage/current/ power were changed
Define these setup parameters (wiring mode, PT ratio, CT primary current) prior to setting up alarm setpoints/analog channels.
Status inputs setup not accepted
1. The analog selector inputs and the external synchronization pulse input overlap.
2. Allocated inputs for the analog output selector are not contiguous and do not start from input #1.
Check that all inputs are allocated correctly
Cannot store pulsing output setup
1. You assigned a
parameter to a relay output with zero number of unit-hours per pulse
2. You selected an
output parameter already assigned to another relay output.
1. Check that no. unit­hours is within allowed range (1-
9999)
2. Check that output parameters are assigned correctly.
Cannot store setpoint setup
Setpoint action is directed to a relay already allocated for pulsing
Check definition of setpoint actions
Cannot enter reset menu
1. Reset function disabled
2. You are at SEE
level (viewing only)
1. Enable reset function in BASIC setup
2. Go to CHG (editing) level
No phase energy readings displayed
Phase energy not enabled in BASIC setup
Enable phase energy measurement
TXD LED flashes continuously after turning on instrument
Analog expander AX-7 outputs are allocated
If analog expander not used, analog outputs must be cancelled
26
Problem Probable Cause What to do
PCOMTEST program works continuously but TXD LED of PC COMPORT does not flash
1. PC COMPORT number is not correct
2. PC COMPORT setting uncorrected
3. PC COMPORT is damaged
Change COMPORT number (setup of PCOMTEST);
Check COMPORT card setting;
Change COMPORT card
Instrument RXD LED does not flash
Communication cable not connected properly
Check cable
Instrument TXD LED does not flash
Instrument COMPORT setting is not correct
Check that instrument & PC COMPORT settings match: RS Standard Address Data Format Baud rate Protocol name (ASCII or non-ASCII)
PC COMPORT RXD LED does not flash
Communication cable not connected properly
Check cable
Instrument does not respond more than 1% of sessions in the ASCII or non­ASCII test
1. ON the
communication line there are a few instruments with the same address or instruments with address zero
2. Analog expander outputs are allocated on the one of the instruments
1. Check every instrument separately
2. Cancel the analog outputs if analog expander is not used
PCOMTEST receives reply from the instrument with an incorrect check sum
Problems with the communication lines
Check the communication line:
Wires must be more
than 0.33 mm
2
/ 22
AWG Grounded screen Terminated resistors Communication line Distance < 1200 m
27
Appendix: Technical Specifications
Input and Output Ratings
3 Galvanically Isolated Voltage inputs
120 V: INPUT USING PT (up to 120V+20% line-to-line
voltage) Burden: <0.15 VA
690 V: DIRECT INPUT (up to 690V +15% line-to-line
voltage) Burden: <0.5 VA INPUT USING PT - Burden: <0.15 VA
3 Galvanically Isolated Current inputs
1 A:
INPUT VIA CT with 1A secondary output Burden: <0.02 VA Overload withstand: 2A RMS continuous, 50A RMS for 1 second
5 A: INPUT VIA CT with 5A secondary output
Burden: <0.1 VA Overload withstand: 10A RMS continuous, 250A RMS for 1 second
Voltage and Current Input terminals
UL recognized Maximum wire section: 4 mm
2
(10 AWG)
Optically Isolated Communication Port
EIA RS-422 and RS-485 standards Maximum wire section: 2.5 mm
2
(12 AWG)
2 Relay Outputs Relay rated at 5A, 250 VAC/ 5A, 30 VDC
2 contacts (SPST Form A)
4 Optically Isolated Digital Inputs
Dry Contact
Optically Isolated Analog Output 4-20 mA default
0-20 mA (option)
±
1 mA (option)
Accuracy 0.5%, Non-linearity 0.2%
Load up to 510 Ohm for 20 mA Load up to 10kOhm for 1 mA
Display (optional)
3 high-brightness seven-segment digital LEDs
Power Supply
Galvanically isolated Power supply (factory set)
120&230 V AC and 110&220 V DC option 12 V DC option 24 V DC option 48 V DC
85 - 265V AC 50/60 Hz and 88 - 290V DC Burden 10 W
9.6 - 19 VDC 19 - 37 VDC 37 - 72 VDC
28
Environmental Conditions
Operating temperature
-20°C to +60°C (-4°F to +140°F)
Storage temperature
-25°C to +80°C (-13°F to +176°F)
Humidity 0 to 95% non-condensing
Construction
Instrument body Case enclosure: Aluminum, anodized
Dimension: 186x75x109 mm (7.33 x 2.95 x 4.30 “) Mounting: 35 mm DIN rail or wall mount or 4-inch
panel mount
Instrument weight 0.94 kg (2.1 lb.)
Display body Display body: plastic
Front Panel: plastic ABS/PC blend Dimension: 114.3x114.3x20.0 mm (4.5x4.5x .787”) Mounting: wall mount
Display weight 0.2 kg (0.44 lb.)
Standards Compliance
Standards
UL File # E129258 CE-EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC CE-SAFETY: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC
Harmonized standards to which conformity is
declared: EN55011:1991; EN50082-1:1992; EN61010­1:1993; A2/1995 ANSI C37.90.1 1989 Surge Withstand Capability (SWC) ANSI C62.41 - 1991 Standard Surge EN50081-2 Generic Emission Standard - Industrial Environment EN50082-2 Generic Immunity Standard - Industrial Environment EN55022: 1994 Class A EN61000-4-2 ENV50140: 1983 ENV50204: 1995 (900MHz) ENV50141: 1993 EN61000-4-4:1995 EN61000-4-8: 1993
Measurement Specifications
Accuracy, % Range Display Resolution (%Rdg) d
Parameter Full Scale Rdg FS Conditions
@
range
Voltage
120V×PT
@ 120V
380V×PT
@ 660V
208V×PT
@ 120V
660V×PT
@ 660V
0.25 10% to 120% FS 0 to 999,000 V
1 V @ 1V to 9,999 V
0.1%
@
10,000 V to 999,000 V
Starting voltage 1.5% FS
Line current CT PRIMARY CURRENT 0.25 2% to 120% FS 0 to 60,000 A
1 A @ 1A to 9,999 A
0.1%
@
10,000 A to 60,000 A
Starting current 0.5% FS
Active power
0.36
×PT×CT @ 120V input
1.2
×PT×CT @ 690V input
0.5
|PF| 0.5 c
-2,000,000 to +2,000,000 kW
1 kW @ 1kW to 9,999 kW
0.1%
@
10 MW to 2,000 MW
Reactive power
0.36
×PT×CT @ 120V input
1.2
×PT×CT @ 690V input
0.5
|PF| 0.9 c
-2,000,000 to +2,000,000 kvar
1 kvar @ 1kvar to 9,999 kvar
0.1%
@
10 Mvar to 2,000 Mvar
Apparent power
0.36
×PT×CT @ 120V input
1.2
×PT×CT @ 690V input
0.5
|PF| 0.5 c
0 to 2,000,000 kVA
1 kVA @ 1kVA to 9,999 kVA
0.1%
@
10 MVA to 2,000 MVA
Power factor 1 1
|PF| 0.5
-0.999 to +1.000 0.001
Frequency 0.1 45.00 to 65.00 Hz 0.01 Hz
For Ln reading and for 3OP2/3OP3 wiring
modes
For LL reading except 3OP2/3OP3 wiring modes
or
or
Accuracy, % Range Display Resolution (%Rdg) d
Parameter Full Scale Rdg FS Conditions
@
range
Neutral (unbalanced)
current
CT PRIMARY CURRENT 0.5 2% to 120% FS 0 to 60,000 A
1 A @ 1A to 9,999 A
0.1%
@
10,000 A to 60,000 A
Ampere demand same as for current
kW demand (block & sliding) same as for kW
kVA demand (block & sliding ) same as for kVA
K-Factor 999.9 5
typical
1.0 to 999.9 0.1 (via communication)
Total harmonic distortion THD U (I), % U
1
(I1)
100
1.5
1% FS @ U(I) 10%
FSU (FSI)
0 to 100 0.1
Total Demand harmonic distortion
TDD (I), %
100
1.5
1% FS @ I 10% FSI
0 to 100 0.1
Active energy Import & Export
according to power accuracy
e
0 to 999,999 MWh
1 kWh @ 1 to 999999 kWh
10 kWh
@
1000 to 9,999 MWh
100 kWh
@
10 to 99.999 GWh
1MWh @ 100 to 999.9 GWh
Reactive energy Import & Export
according to power accuracy
e
0 to 999,999 Mvarh
1 kvarh @ 1 to 999999 kvarh
10 kvarh
@
1000 to 9,999 Mvarh
100 kvarh
@
10 to 99.999 Gvarh
1Mvarh @ 100 to 999.9 Gvarh
Accuracy, % Range Display Resolution (%Rdg) d
Parameter Full Scale Rdg FS Conditions
@
range
Apparent energy
according to power accuracy
e
0 to 999,999 MVAh
1 kVAh @ 1 to 999999 kVAh
10 kVAh
@
1000 to 9,999 MVAh
100 kVAh
@
10 to 99.999 GVAh
1MVAh @ 100 to 999.9 GVAh
PT = external potential transformer ratio CT, CT PRIMARY CURRENT = primary current rating of external current transformer FSU = full scale voltage FSI = full scale current U
1
= voltage fundamental I1 = current fundamental
c @ 10% to 120% of voltage FS and 2% to 120% of current FS d Higher resolution is achievable via communications
e Where the current is > 10% FS, the energy accuracy is better than 1.5% Rdg.
Additional Notes
1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not include inaccuracies introduced by the
user's potential and current transformers.
2. Specifications assume: voltage and current waveforms with THD
5% for kvar, kVA and PF; reference operating temperature: 20 - 26 °C.
3. Ordinary measurement error is considerably less than the specified accuracy which indicates maximum error.
Loading...