Satec PM172P, PM172E, PM172EH, PM174 Series Installation And Operation Manual

Series PM172 Powermeters
PM172P/PM172E/PM172EH
Installation and Operation Manual
2 Series PM172 Powermeters
LIMITED WARRANTY
The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts from date of dispatch from the distributor. In all cases, this warranty is valid for 36 months from the date of production. This warranty is on a return to factory basis.
The manufacturer does not accept liability for any damage caused by instrument malfunction. The manufacturer accepts no responsibility for the suitability of the instrument to the application for which it was purchased.
Failure to install, set up or operate the instrument according to the instructions herein will void the warranty.
Only a duly authorized representative of the manufacturer may open your instrument. The unit should only be opened in a fully anti-static environment. Failure to do so may damage the electronic components and will void the warranty.
The greatest care has been taken to manufacture and calibrate your instrument. However, these instructions do not cover all possible contingencies that may arise during installation, operation or maintenance, and all details and variations of this equipment are not covered by these instructions.
For additional information regarding installation, operation or maintenance of this instrument, contact the manufacturer or your local representative or distributor.
WARNING
Read the instructions in this manual before performing installation, and take note of the following precautions:
Ensure that all incoming AC power and other power sources are turned OFF before
performing any work on the instrument. Failure to do so may result in serious or even fatal injury and/or equipment damage.
Before connecting the instrument to the power source, check the labels on the back of the
instrument to ensure that your instrument is equipped with the appropriate power supply voltage, input voltages and currents.
Under no circumstances should the instrument be connected to a power source if it
is damaged.
To prevent potential fire or shock hazard, do not expose the instrument to rain or
moisture.
The secondary of an external current transformer must never be allowed to be open circuit
when the primary is energized. An open circuit can cause high voltages, possibly resulting in equipment damage, fire and even serious or fatal injury
. Ensure that the current transformer wiring is secured using an external strain relief to reduce mechanical strain on the screw terminals, if necessary.
Only qualified personnel familiar with the instrument and its associated electrical
equipment must perform setup procedures.
Do not open the instrument under any circumstances when it is connected to a power
source.
Do not use the instrument for primary protection functions where failure of the device can
cause fire, injury or death. The instrument can only be used for secondary protection if needed.
Read this manual thoroughly before connecting the device to the current carrying circuits. During operation of the device, hazardous voltages are present on input terminals. Failure to observe precautions can result in serious or even fatal injury or damage to equipment.
All trademarks are property of their respective owners.
Copyright © 2005-2008
Series PM172 Powermeters 3
Table of Contents
Chapter 1 General Information......................................................... 6
Chapter 2 Installation...................................................................... 10
Mechanical Installation ...................................................................................10
Panel Mounting........................................................................................................10
DIN Rail Mounting....................................................................................................13
Remote Display Installation............................................................................ 14
Mechanical Installation .............................................................................................14
Electrical Connection ................................................................................................16
Electrical Installation....................................................................................... 17
Typical Installation...................................................................................................17
Terminals ................................................................................................................18
Power Source Connection .........................................................................................18
Chassis Ground Connection.......................................................................................19
Wiring Diagrams ......................................................................................................19
I/O Connections............................................................................................... 24
Relay Outputs..........................................................................................................24
Digital Inputs...........................................................................................................24
Analog Outputs........................................................................................................25
Analog Inputs ..........................................................................................................25
Communications Connections....................................................................... 26
COM1 RS-232 Connection.........................................................................................26
COM1 RS-422/485 Connection..................................................................................27
COM1 Dial Up Modem Connection.............................................................................28
COM1 Ethernet Connection.......................................................................................28
COM1 Profibus Connection........................................................................................29
COM2 RS-422/485 Connection..................................................................................30
Chapter 3 Display Operations........................................................ 32
Indicators and Controls .................................................................................. 32
Display Diagnostics ..................................................................................................32
Numeric LED Display................................................................................................32
Load Bar Graph........................................................................................................33
Energy Pulse LED.....................................................................................................33
Port Activity LEDs.....................................................................................................33
Navigation Buttons...................................................................................................33
Data Display..................................................................................................... 33
Display Features ......................................................................................................33
Navigation Buttons...................................................................................................34
Simple Reset of Accumulated Data............................................................................35
Common Measurements Display................................................................................35
Min/Max and Max. Demands Display .........................................................................36
Harmonics Display....................................................................................................37
Energy Display.........................................................................................................38
Status Display.................................................................................................. 39
Using the Menus.............................................................................................. 40
Navigation Buttons...................................................................................................40
Selecting Menus.......................................................................................................40
Entering the Password ..............................................................................................41
Selecting a Menu Entry.............................................................................................41
Viewing and Changing Setup Items...........................................................................41
Menu Operations ............................................................................................. 42
Basic Device Settings................................................................................................42
4 Series PM172 Powermeters
Device Options.........................................................................................................43
Transformer Correction.............................................................................................44
Communication Ports ...............................................................................................45
Network Address......................................................................................................46
Counters Setup........................................................................................................47
Relay Output Setup..................................................................................................47
Control Setpoints Setup............................................................................................48
Analog Inputs Setup.................................................................................................49
Analog Outputs Setup...............................................................................................50
Analog Expander Setup ............................................................................................51
Timers Setup ...........................................................................................................52
Display Setup...........................................................................................................52
Meter Security..........................................................................................................53
Setting the Device Clock...........................................................................................54
Resetting Accumulators and Maximum Demands........................................................55
Chapter 4 PAS Application Software............................................. 56
Configuration Database.................................................................................. 56
Setting up Communications........................................................................... 56
Communicating through a Serial Port ........................................................................57
Communicating through a Dial-up Modem .................................................................58
Communicating through the Internet.........................................................................58
Setting Up the Meter........................................................................................ 59
Downloading Setup to the Meter...............................................................................59
Uploading Setup from the Meter ...............................................................................59
Authorization.................................................................................................... 59
Configuring Communications in your Meter ................................................ 60
Setting Up Communication Ports...............................................................................60
Setting Up the Ethernet............................................................................................61
Configuring GE EGD Production Exchanges................................................................62
General Meter Setup........................................................................................ 64
Basic Meter Setup ....................................................................................................64
Device Options.........................................................................................................65
Transformer Correction.............................................................................................67
Local Settings ..........................................................................................................68
Using Digital Inputs..................................................................................................69
Using Relay Outputs.................................................................................................70
Programming Analog Inputs .....................................................................................72
Programming Analog Outputs ...................................................................................74
Programming the Analog Expander ...........................................................................75
Using Counters ........................................................................................................76
Using Periodic Timers...............................................................................................77
Using Control Setpoints ............................................................................................78
Configuring Summary Energy and TOU Registers...................................... 83
Setting up Total and Tariff Registers ......................................................................... 83
Configuring the Daily Tariff Schedule.........................................................................84
Configuring the Season Tariff Schedule .....................................................................85
Configuring Recorders.................................................................................... 87
Configuring Device Memory ......................................................................................87
Configuring the Event Recorder.................................................................................88
Configuring the Data Recorder..................................................................................89
Configuring the Waveform Recorder..........................................................................91
Configuring Communication Protocols ........................................................ 94
Configuring Modbus .................................................................................................94
Configuring DNP3.....................................................................................................95
Remote Device Control................................................................................. 100
Remote Relay Control.............................................................................................100
Event Flags............................................................................................................100
Device Diagnostics .................................................................................................101
Series PM172 Powermeters 5
Updating the Clock.................................................................................................102
Resetting Accumulators and Clearing Log Files.........................................................102
Administration ...............................................................................................103
Changing a Password .............................................................................................103
Upgrading Device Firmware......................................................................... 103
Monitoring Devices........................................................................................ 106
Viewing Real-time Data ..........................................................................................106
Viewing Min/Max Log .............................................................................................106
Viewing Real-time Waveforms.................................................................................106
Viewing Harmonic Spectrum and Synthesized Waveforms.........................................107
Viewing Recorded Files ................................................................................ 107
Retrieving Logs Files...............................................................................................107
Viewing Options..................................................................................................... 107
Viewing the Device Event Log.................................................................................108
Viewing the Data Log .............................................................................................109
Viewing Waveforms................................................................................................ 109
Viewing Synchronized Waveforms...........................................................................114
COMTRADE and PQDIF Converters ............................................................ 116
Manual Converting .................................................................................................116
Automatic Converting.............................................................................................117
Appendix A Technical Specifications.......................................... 118
Appendix B Analog Output Parameters...................................... 124
Appendix C Setpoint Triggers and Actions ................................125
Appendix D Parameters for Data Log and Monitoring............... 128
Appendix E Data Scales ............................................................... 282H136
134HAppendix F Device Diagnostic Codes......................................... 283H137
Chapter 1 General Information
6 Series PM172 Powermeters
Chapter 1 General Information
The PM172 is a compact, multi-function, three-phase AC powermeter specially designed to meet the requirements of users ranging from electrical panel builders to substation operators.
Bright 3-row LED display provides easy local meter readings. The display module is freely detachable and can be located at a distance of up to 1000 meters from the device.
Two communication ports allow local and remote automatic meter readings and setup though the supplemental communication or user data acquisition software. Different communication options are available for remote communications with the meter including public telephone lines, LAN and the Internet.
The PM172 Series product line includes three models of devices:
PM172P – basic model – offers all standard metering and control capabilities of the PM172 Series
PM172E – adds to above an energy meter, an event recorder and a multi-channel data recorder.
PM172EH – adds to above extended harmonic analysis and incorporates a fast waveform recorder with the voltage disturbance monitor.
Features:
3 voltage and 3 current transformer-isolated AC inputs for direct connection to power line or via potential and current transformers
Multi-function 3-phase meter (true RMS, volts, amps, power, power factor, neutral current, voltage and current unbalance, frequency)
Embedded harmonic analyzer, voltage and current THD, current TDD and K-Factor, up to 40th order harmonic
Voltage and current harmonic spectrum and angles, harmonics power and energy (PM172EH)
Ampere/Volt/THD/TDD demand meter
Class 0.2 four-quadrant energy meter
Time-of-Use, 8 totalization and tariff energy/demand
registers x 8 tariffs, 4 seasons x 4 types of days, 8
Chapter 1 General Information
Series PM172 Powermeters 7
tariff changes per day, easy programmable tariff schedule
Automatic daily profile for energy and maximum demand readings (total and tariff registers)
Embedded programmable controller; 16 control setpoints; programmable thresholds and delays; relay output control; 1-cycle response time
Event recorder for logging internal diagnostics events, control events and I/O operations (PM172E, PM172EH)
Eight data recorders; programmable data logs on a periodic basis and on any internal and external trigger (PM172E, PM172EH)
Two waveform recorders; simultaneous 6-channel AC recording in a single plot; sampling rate of 32 and 128 samples per cycle; 20 pre-fault cycles; up to 30 seconds of continuous recording at a rate of 32 samples per cycle (PM172EH)
Real-time waveform capture and monitoring; simultaneous 6-channel 4-cycle capture at 128 samples per cycle (PM172EH)
Easy to read 3-row (2x4 characters + 1x6 characters) bright LED display, adjustable update time, auto­scroll option with adjustable page exposition time, auto-return to a default page
LED bar graph showing percent load with respect to user-definable nominal load current
Detachable display module with a 3-wire RS-485 interface; up to 1000 meters operation
2 digital inputs for monitoring external contacts, and receiving pulses from energy, water and gas meters
2 relay outputs for alarms and controls, and for output energy pulses
2 optional optically isolated analog outputs with an internal power supply; options for 0-20mA, 4-20mA, 0-1mA, and ± 1mA output
2 optional optically isolated analog inputs with an internal power supply; options for 0-20mA, 4-20mA, 0-1mA, and ± 1mA input
Optional analog expander providing additional 2 x 8 analog outputs; options for 0-20mA, 4-20mA, 0-1mA, and ± 1mA
25/50/60/400 Hz operation
Precise internal clock with battery backup
1 Mbyte RAM with battery backup for long-term data
and waveform recording
Two communication ports; communications options available:
COM1:
RS-232/RS-422/RS-485 56K Dial-up modem
Ethernet 10/100BaseT, eXpertPower enabled Profibus DP
Chapter 1 General Information
8 Series PM172 Powermeters
COM2:
RS-422/RS-485
Modbus RTU, Modbus/TCP, DNP3, DNP3/TCP, GE EGD producer, Profibus DP and proprietary ASCII communication protocols
Easy field upgrading device firmware through any communication port
Measured Parameters
Parameter Display Comm. Analog Pulse Alarm
1-cycle Real-time Measurements
RMS Voltage per phase
3 3
3
RMS Current per phase
3 3
3
kW per phase
3
3
kvar per phase
3
3
kVA per phase
3
3
Power Factor per phase
3
3
Total kW
3 3
3
Total kvar
3 3
3
Total kVA
3 3
3
Frequency
3 3
3
Neutral Current
3 3
3
Total Power Factor
3 3
3
Voltage & Current unbalance
3
3
1-sec Average Measurements RMS Voltage per phase
3 3 3
3
RMS Current per phase
3 3 3
3
kW per phase
3 3
3
kvar per phase
3 3
3
kVA per phase
3 3
3
Power Factor per phase
3 3
3
Total kW
3 3 3
3
Total kvar
3 3 3
3
Total kVA
3 3 3
3
Total Power Factor
3 3 3
3
Frequency
3 3 3
3
Neutral Current
3 3 3
3
Voltage & Current unbalance
3 3
3
Amps & Volt Demands Ampere & Volt Demand per phase
3
3
Ampere Maximum Demand per phase
3 3
3
Voltage Maximum Demand per phase
3 3
3
Power Demands
E, EH
kW Accumulated Demand Import & Export
3 3
3
kvar Accumulated Demand Import & Export
3 3
3
kVA Accumulated Demand
3 3
3
kW Demand Import & Export
3
3
kvar Demand Import & Export
3
3
kVA Demand
3
3
kW Sliding Demand Import & Export
3
3
kvar Sliding Demand Import & Export
3
3
kVA Sliding Demand
3
3
kW Predicted Demand Import & Export
3
3
kvar Predicted Demand Import & Export
3
3
kVA Predicted Demand
3
3
kW Maximum Demand Import
3 3
kW Maximum Demand Export
3
kvar Maximum Demand Import
3 3
kvar Maximum Demand Export
3
kVA Maximum Demand
3 3
Total Energy
E, EH
Total kWh Import & Export
3 3
3
Total kvarh Import & Export
3 3
3
Total kvarh Net
3
Chapter 1 General Information
Series PM172 Powermeters 9
Parameter Display Comm. Analog Pulse Alarm
Total kVAh
3 3
3
Energy per Phase
E, EH
kWh Import per phase
3 3
kvarh Import per phase
3
kVAh per phase
3 3
TOU Registers
E, EH
8 TOU energy registers (kWh and kvarh import & export, kVAh, 2 pulse sources)
3 3
8 TOU maximum demand registers
3
8 tariffs, 4 seasons x 4 types of day
3
3
Harmonic Measurements Voltage THD per phase
3 3 3
3
Current THD per phase
3 3 3
3
Current TDD per phase
3 3 3
3
K-factor per phase
3 3 3
3
Voltage harmonics per phase up to order 40
3
EH
3
EH
Current harmonics per phase up to order 4 0
3
EH
3
EH
Voltage harmonic angles up to order 40
3
EH
Current harmonic angles up to order 40
3
EH
Total Harmonic Powers
EH
Total Harmonic kW
3 3
3
Total Harmonic kVA
3 3
3
Total Harmonic Energy EH
Total Harmonic kWh Import & Export
3 3
Total Harmonic kVAh
3 3
Fundamental Component Voltage and Current per phase
3
kW, PF per phase
3 3
kvar, KVA per phase
3
Total kW, PF
3 3
Total kvar, KVA
3
Min/Max Logging
Min/Max A, V, total kW, kvar, kVA, PF
3 3
Min/Max Frequency, Neutral current
3 3
Min/Max THD, TDD, K-Factor per phase
3
Voltage Disturbance
EH
3
Phase Rotation
3
3
Voltage and Current Phase Angles
3 3
Day and Time
3 3
3
Pulse Counters
3 3
3
Analog Inputs (optional)
3 3
3
Digital Inputs
3 3
3
Relay Outputs
3 3
3
Remote Relay Control
3
Alarm Triggers/Setpoints
3
3
Self-diagnostics
3
Designations used in the manual:
E - available in the PM172E and PM172EH EH - available in the PM172EH
Chapter 2 Installation Mechanical Installation
10 Series PM172 Powermeters
Chapter 2 Installation
Mechanical Installation
Panel Mounting
Figure 2-1 Dimensions
Figure 2-2 STEP 1 (ANSI 4" round cutout): Mount the display module in cutout
Chapter 2 Installation Mechanical Installation
Series PM172 Powermeters 11
Figure
2-3 STEP 1 (DIN 92x92mm square cutout): Mount the display module in cutout
Figure 2-4 STEP 2: Assemble the four locating studs
Chapter 2 Installation Mechanical Installation
12 Series PM172 Powermeters
Figure 2-5 STEP 3: Slide and position the meter on locating studs
Figure 2-6 STEP 4: Affix the meter using the thumb nuts
Chapter 2 Installation Mechanical Installation
Series PM172 Powermeters 13
DIN Rail Mounting
The PM172 can be mounted on a 35-mm DIN rail. The display module is mounted separately on the switchboard panel and is connected to the meter by a communication cable (see “Remote Display Installation”).
BG0386-1
FRONT VIEW SIDE VIEW
Figure 2-7 Dimensions
DIN RAIL
BG0386-2
Figure 2-8 DIN rail mounting
Chapter 2 Installation Remote Display Installation
14 Series PM172 Powermeters
Remote Display Installation
Mechanical Installation
Standard Cutouts (ANSI 4" round or DIN 92x92 mm square)
Figure 2-9 Display cutout dimensions
STEP 1: Insert the display module into cutout. STEP 2: Fasten washers and nut on screws.
Figure 2-10 ANSI 4" or DIN 92x92 mm display mounting
Special Cutout
Chapter 2 Installation Remote Display Installation
Series PM172 Powermeters 15
Figure 2-11 Panel cutout dimensions
Figure 2-12 Display mounting
Electrical Connection
The remote display is connected to the meter via a 3-wire or 5-wire communication cable provided with two 15-pin D-type connectors.
At distances of up to 3 m, the display can receive power through the communication cable directly from the meter. Connect pins 1 and 8 on both sides as shown in Figure 2-13.
At distances above 3 m, power should be provided from a separate 12V DC power source (a 12V AC/DC adapter can be used). Connect the positive wire to pin 1 and the negative wire to pin 8 as shown in Figure 2-14.
Pin Signal
1 +12V 5 RS-485 + (plus) 7 RS-485 – (minus) 8 GND
15 Chassis ground
Chapter 2 Installation Remote Display Installation
16 Series PM172 Powermeters
Figure 2-13 Self-powered remote display connection
Figure 2-14 Remote display powered from a 12V DC power source
If required, the remote display may be connected to one of the regular meter ports COM1 or COM2 via a three-wire RS-485 communication cable using a separate 12V DC power source as shown in Figure 2-14. See
Communications Connections for connector pin-outs and connection
diagrams. The meter port settings must be as follows: Modbus RTU protocol, RS-485 interface, 19200 baud, 8-bits/no parity.
Chapter 2 Installation Electrical Installation
Series PM172 Powermeters 17
Electrical Installation
Before installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
Typical Installation
COM.1
DIGITAL INPUTS
COM.2
RELAYS
-
ANALOG OUTPUTS
ANALOG INPUTS
+
1
2
+
-
Figure 2-15 Typical Installation
Chapter 2 Installation Electrical Installation
18 Series PM172 Powermeters
Terminals
+RX
16
RS-422/RS-485
POWER SUPPLY
-RX-TX +TX
VN
9 6
1413 15
11
5
V
3
8
Handle Only at
COM.1
1
Workstations
Static-Safe
COM.2
Static-Sensitive Devices
ATTENTION
17
N/-
L/+
12
10
9
2
1
10-16VDC 18-36VDC 36-72VDC
2V
5
(24) (48)
(12)
O
S/N
S
N
LOW DC
CT.
I
1A
T
DIGITAL INPUTS
90-264VAC 50/60Hz
85-290VDC
POWER SUPPLY
V
1
2
10W
O P
ANALOG OUTPUTS
2018 19
12
23
+
21 22
+
262524
3
7
6
2
4
1
-
3
RELAYS
+
1
2928
27
21
ANALOG INPUTS
ANALOG IN/OUT :
+1mA
-
0-20mA
4-20mA
0-1mA
+
+
-
-
--
CALIBRATED AT : 25 Hz
60 Hz
50 Hz
400 Hz
COM.1 :
RS-232/422/485 STANDARD
ETHERNET MODEM PROFIBUS
690V
OPT.U
STANDARD
CT.
5A
Figure 2-16 Terminals - Rear View
Power Source Connection
Before connecting your meter to the power source, check the label on the back of the device to ensure that it is equipped with the appropriate power supply.
The power source can be dedicated-fused, or from a monitored voltage if it is within the instrument power supply range.
AC power supply: connect the line wire to terminal 12 and the neutral wire to terminal 10.
DC power supply: connect the positive wire to terminal 12 and the negative wire to terminal 10.
Chassis Ground
A
C Voltage Inputs
Digital Inputs
A
nalog Inputs/Outputs Relay Outputs
A
C Current Inputs
COM1 Port COM2 Port Power Supply
Chapter 2 Installation Electrical Installation
Series PM172 Powermeters 19
Chassis Ground Connection
Connect the chassis ground of the device to the switchgear earth ground using a dedicated wire greater than 2 mm
2
/14 AWG.
Wiring Diagrams
For AC input ratings, see “Technical Specifications” in Appendix A.
The following wiring configurations are available in the meter:
Wiring Configuration
(See Basic Device Settings in Chapter 3)
Setup Code Figure
3-wire 2-element Direct connection using 2 CTs 3dir2 2-17 4-wire Wye 3-element direct connection using 3 CTs 4Ln3 or 4LL3 2-18 4-wire Wye 3-element connection using 3 PTs, 3 CTs 4Ln3 or 4LL3 2-19 3-wire 2-element Open Delta connection using 2 PTs, 2 CTs 3OP2 2-20 4-wire Wye 2½ -element connection using 2 PTs, 3 CTs 3Ln3 or 3LL3 2-21 3-wire 2½ -element Open Delta connection using 2 PTs, 3 CTs 3OP3 2-22 4-wire 3-element Delta direct connection using 3 CTs 4Ln3 or 4LL3 2-23 3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs 3bLn3 or 3bLL3 2-24
Figure 2-17 3-Wire 2-Element Direct Connection Using 2 CTs.
Wiring Mode = 3dir2
Chapter 2 Installation Electrical Installation
20 Series PM172 Powermeters
Figure 2-18 4-Wire Wye 3-Element Direct Connection Using 3 CTs.
Wiring Mode = 4LL3 or 4Ln3
Figure 2-19 4-Wire Wye 3-Element Connection Using 3 PTs, 3 CTs.
Wiring Mode = 4LL3 or 4Ln3
Chapter 2 Installation Electrical Installation
Series PM172 Powermeters 21
Figure 2-20 3-Wire 2-Element Open Delta Connection Using 2 PTs, 2 CTs.
Wiring Mode = 3OP2
Figure 2-21 4-Wire Wye 2½-Element Connection Using 2 PTs, 3 CTs.
Wiring Mode = 3LL3 or 3Ln3
This configuration provides accurate power measurements only if the voltages are balanced.
Chapter 2 Installation Electrical Installation
22 Series PM172 Powermeters
Figure 2-22 3-Wire Open 2½-Element Delta Connection Using 2 PTs, 3 CTs.
Wiring Mode = 3OP3
Figure 2-23 4-Wire 3-Element Delta Direct Connection Using 3 CTs.
Wiring Mode = 4LL3 or 4Ln3
Chapter 2 Installation Electrical Installation
Series PM172 Powermeters 23
Figure 2-24 3-Wire 2½-Element Broken Delta Connection Using 2 PTs, 3 CTs.
Wiring Mode = 3bLn3 or 3bLL3
Chapter 2 Installation I/O Connections
24 Series PM172 Powermeters
I/O Connections
For I/O ratings, see “Technical Specifications” in Appendix A.
Relay Outputs
2
1
2
V
5
O
S/N
CT.
I
1A
T
DIGITAL INPUTS
90-264VAC 50/60Hz
85-290VDC
POWER SUPPLY
V
1
2
10W
O
P
ANALOG OUTPUTS
2018 19
12
23
+
21 22
+
262524
6
2
4
1
-
3
RELAYS
+
1
2928
27
21
ANALOG INPUTS
ANALOG IN/OUT :
+
-
--
CALIBRATED AT : 25 Hz 60 Hz
50 Hz
400 Hz
690V
OPT.U
STANDARD
CT.
5A
LOAD LOAD
N
10A FUSE
LINE
Figure 2-25 Relay Output Connection
Digital Inputs
O
S/N
CT.
I
1A
T
DIGITAL INPUTS
90-264VAC 50/60Hz
85-290VDC
POWER SUPPLY
V
1
2
10W
O
P
ANALOG OUTPUTS
2018 19
12
23
+
21 22
+
262524
6
2
4
1
-
3
RELAYS
+
1
2928
27
21
ANALOG INPUTS
ANALOG IN/OUT :
+
-
--
CALIBRATED AT : 25 Hz 60 Hz
50 Hz
400 Hz
690V
OPT.U
STANDARD
CT.
5A
2
1
2V
5
Figure 2-26 Digital Input Connection
Chapter 2 Installation I/O Connections
Series PM172 Powermeters 25
Analog Outputs
LOAD
SHIELD
_
+
2
1
2
V
5
O
S/N
CT.
I
1A
T
DIGITAL INPUTS
90-264VAC 50/60Hz
85-290VDC
POWER SUPPLY
V
1
2
10W
O P
ANALOG OUTPUTS
2018 19
12
23
+
21 22
+
262524
6
2
4
1
-
3
RELAYS
+
1
2928
27
21
ANALOG INPUTS
ANALOG IN/OUT :
+
-
--
CALIBRATED AT : 25 Hz 60 Hz
50 Hz
400 Hz
690V
OPT.U
STANDARD
CT.
5A
PROTECTIVE
GROUND
+
_
Figure 2-27 Analog Output Connection
Maximum current loop load:
510 Ohm for 0-20 mA and 4-20 mA options 5 kOhm for 0-1 mA and ±1 mA options
Analog Inputs
SENSOR
SHIELD
_
+
2
1
2V
5
O
S/N
CT.
I
1A
T
DIGITAL INPUTS
90-264VAC 50/60Hz
85-290VDC
POWER SUPPLY
V
1
2
10W
O
P
ANALOG OUTPUTS
2018 19
12
23
+
21 22
+
262524
6
2
4
1
-
3
RELAYS
+
1
2928
27
21
ANALOG INPUTS
ANALOG IN/OUT :
+
-
--
CALIBRATED AT : 25 Hz 60 Hz
50 Hz
400 Hz
690V
OPT.U
STANDARD
CT.
5A
PROTECTIVE
GROUND
+
_
Figure 2-28 Analog Input Connection
Chapter 2 Installation Communications Connections
26 Series PM172 Powermeters
Communications Connections
Several communication options are available for the PM172:
COM1 (check the label on the back of your meter):
RS-232/RS-422/RS-485 56K Dial-up modem Ethernet 10/100BaseT Profibus DP
COM2:
RS-422/RS-485
The RS-232/RS-422/RS-485 port is a standard port for COM1. Other options are ordered separately. Connections to the Ethernet RJ45 connector and to the telephone RJ11 connector are made through a cable adaptor provided with your meter (if ordered).
A full description of the communication protocols is found in the PM172 protocol guides provided with your meter.
COM1 RS-232 Connection
0-1mA
0-20mA
V
-
+1mA
LOW DC
N
(24) 18-36VDC (48) 36-72VDC
S
2
(12) 10-16VDC
+
7
3
9
6
5
1
-4-20mA
9
8
COM.1 :
ATTENTION
Devices
Static-Sensitive
Static-Safe Workstations
Handle Only at
POWER SUPPLY
RS-422/RS-485
16
+RX
COM.2COM.1
11
V
1513 14
69
N
1
5
-TX +TX-RX
V
MODEM PROFIBUS
ETHERNET
RS-232/422/485 STANDARD
3
17
12
L/+
N/-
10
ANALOG IN/OUT :
Connector 9-pin D-type female:
Pin Signal
1 RS-232 RTS 2 RS-232 RxD 3 RS-232 TxD 4 RS-232 CTS 5 RS-232 Signal ground
PM172 RS -232 MALE CON.
PM172 RS-232 MALE CON.
Chapter 2 Installation Communications Connections
Series PM172 Powermeters 27
RS232
PM 172 MALE CON.
IBM PC/COM PATIBLE
25-PIN DB25 FEM ALE C ON .
IBM PC/COMPATIBLE
MALE CON.
RS232
PM172
9-PIN DB9 FEM ALE CO N .
RS-232 SIMP LE 3-WIRE CONNECTION 25-PIN CONNECTION 9-PIN
RS-232 SIMP LE 3-WIRE
Figure 2-29 COM1: RS-232 Cable Drawings
COM1 RS-422/485 Connection
0-1mA
0-20mA
V
-
+1mA
LOW DC
N
(24) 18-36VDC (48) 36-72VDC
S
2
(12) 10-16VDC
+
7
3
9
6
5
1
-4-20mA
9
8
COM.1 :
ATTENTION
Devices
Static-Sensitive
Static-Safe Workstations
Handle Only at
POWER SUPPLY
RS-422/RS-485
16
+RX
COM.2COM.1
11
V
1513 14
69
N
1
5
-TX +TX-RX
V
MODEM PROFIBUS
ETHERNET
RS-232/422/485 STANDARD
3
17
12
L/+
N/-
10
ANALOG IN/OUT :
Connector 9-pin D-type female:
Pin Signal
6 RS-422/485 +RxD 7 RS-422/485 +TxD 8 RS-422/485 –TxD 9 RS-422/485 –RxD
RS-422
TO SATEC
CONVERTER
PM172
COM1
+T
+R
-R
-T
8
1
6
2
7
3
9
4
5
(MALE)
DB9
+T
+R
-T
-R
RS-422 CABLE
5
4
3
2
1
Figure 2-30 COM1: Connection to the RS-422/485-RS-232 Converter
Chapter 2 Installation Communications Connections
28 Series PM172 Powermeters
COM1 Dial Up Modem Connection
05-12001-3
AC0140
Figure 2-31 COM1: Telephone Line Connection
Connector 9-pin D-type female:
Pin Signal
6 Ring 8 Tip
COM1 Ethernet Connection
AC0139
05-12001-4
RJ45
Figure 2-32 COM1: Ethernet Connection
Chapter 2 Installation Communications Connections
Series PM172 Powermeters 29
Connector 9-pin D-type female:
Pin Signal
6 +Rx 7 +Tx 8 –Tx 9 –Rx
COM1 Profibus Connection
-
4-20mA
9
8
COM.1 :
ATTENTION
Devices
Static-Sensitive
Static-Safe Workstations
Handle Only at
POWER SUPPLY
RS-422/RS-485
16
+RX
COM.2COM.1
11
V
1513 14
69
N
1
5
-TX +TX-RX
V
MODEM PROFIBUS
ETHERNET
RS-232/422/485 STANDARD
3
17
12
L/+
N/-
10
ANALOG IN/OUT :
0-1mA
0-20mA
V
-
+1mA
LOW DC
N
(24) 18-36VDC (48) 36-72VDC
S
2
(12) 10-16VDC
+
7
3
9
6
51
Connector 9-pin D-type female:
Pin Signal
1 N/C 2 N/C 3 B-Line, Positive RS485 RxD/TxD 4 RTS, Request To Send 5 GND BUS 6 +5V BUS 7 N/C 8 A-Line, Negative RS485 RxD/TxD 9 N/C
Chapter 2 Installation Communications Connections
30 Series PM172 Powermeters
COM2 RS-422/485 Connection
-4-20mA
9
8
COM.1 :
ATTENTION
Devices
Static-Sensitive
Static-Safe Workstations
Handle Only at
POWER SUPPLY
RS-422/RS-485
16
+RX
COM.2COM.1
11
V
1513 14
69
N
1
5
-TX +TX-RX
V
MODEM PROFIBUS
ETHERNET
RS-232/422/485 STANDARD
3
17
12
L/+
N/-
10
ANALOG IN/OUT :
0-1mA
0-20mA
V
-
+1mA
LOW DC
N
(24) 18-36VDC
(48) 36-72VDC
S
2
(12) 10-16VDC
+
7
3
9
6
5
1
Connector removable, captured-wire, 5 terminals:
Terminal Signal
13 -TxD 14 -RxD 15 +TxD 16 +RxD 17 Ground
-4-20mA
9
8
COM.1 :
ATTENTION
Devices
Static-Sensitive
Static-Safe Workstations
Handle Only at
POWER SUPPLY
RS-422/RS-485
16
+RX
COM.2COM.1
11
V
1513 14
69
N
1
5
-TX +TX-RX
V
MODEM PROFIBUS
ETHERNET
RS-232/422/485 STANDARD
3
17
12
L/+
N/-
10
ANALOG IN/OUT :
0-1mA
0-20mA
V
-
+1mA
LOW DC
N
(24) 18-36VDC (48) 36-72VDC
S
2
(12) 10-16VDC
+
7
3
4 WIRE CONNECTION
RS-485/422 COMMUNICATION PORT
TO COMMUNICATION
SYSTEM
_ +
+
_
Rx
Tx
Figure 2-33 COM2: RS-422/485 4 Wire Connection
Chapter 2 Installation Communications Connections
Series PM172 Powermeters 31
-
4-20mA
9
8
COM.1 :
ATTENTION
Devices
Static-Sensitive
Static-Safe Workstations
Handle Only at
POWER SUPPLY
RS-422/RS-485
16
+RX
COM.2COM.1
11
V
1513 14
69
N
1
5
-TX +TX-RX
V
MODEM
PROFIBUS
ETHERNET
RS-232/422/485 STANDARD
3
17
12
L/+
N/-
10
ANALOG IN/OUT :
0-1mA
0-20mA
V
-
+1mA
LOW DC
N
(24) 18-36VDC (48) 36-72VDC
S
2
(12) 10-16VDC
+
7
3
-
+
RS-485 COMMUNICATION PORT
2 WIRE CONNECTION
R
S
-
4
8
5
P
C
(
P
L
C
)
D
E
V
I
C
E
S
Figure 2-34 COM2: RS-485 2 Wire Connection
Chapter 3 Display Operations Indicators and Controls
32 Series PM172 Powermeters
Chapter 3 Display Operations
Indicators and Controls
Display Diagnostics
The display may indicate a connection error as shown on the left picture if it fails to establish a connection with the meter. Check the connection between the display module and the meter body. If the error message is still displayed, contact your local distributor.
Numeric LED Display
The meter has a simple user interface that allows you to view numerous measurement parameters by scrolling through different display pages. The
Load Bar Graph
Wh/varh Pulse LED
Measurement Units
Port Activity LEDs
Navigation Buttons
Displayed Parameters
diSP
Con.Err
Chapter 3 Display Operations Data Display
Series PM172 Powermeters 33
numeric LED display shows up to three parameters at a time. Small rectangular or triangular LEDs at right and below the display indicate the displayed parameters and their measurement units.
The display layout may change depending on the meter type and mode of operation. There are three modes of display operation: data display, status display, and programming mode display.
Load Bar Graph
The load bar graph displays the amount, in percent (40% to 110%), of the present current load with respect to user-defined nominal load current. The reference nominal current can be set up in amps through the Display Setup menu. If it is set to 0 (default), the current load is referenced to the specified CT primary current.
Energy Pulse LED
The PM172E and PM172EH have a red “Energy Pulse” LED. It flashes at a constant rate when a load is applied to the meter. There are two modes of LED operation: normal and test. In normal mode, the LED pulses indicate imported Wh at a rate of 1,000 pulses per kWh in secondary units. In test mode, the LED pulses indicate either imported Wh, or imported (inductive) varh at a rate of 10,000 pulses per kWh/kvarh. The energy test mode can be enabled through the Display Setup menu. When in test mode, the energy and demand accumulators do not account for consumed energy.
Port Activity LEDs
The meter has two yellow LEDs “COM1” and “COM2”, which indicate activity on the two communication ports. The port’s LED flashes when the port is receiving or transmitting data. With the Ethernet or Profibus option, the “COM1” LED flashes constantly regardless of the port activity.
When the display module is connected remotely through a 3-wire RS-485 interface, the “COM1” LED indicates the display port activity, while the “COM2” LED is not operational.
Navigation Buttons
The PM172 is provided with six push buttons that are normally used to navigate between different measurement displays. In programming mode, the buttons access the device setup menus and the default factory-set device settings can be changed.
Data Display
In data mode, the display is normally updated once per second; you can adjust the display update rate via the Display Setup menu.
Display Features
Measurement Units
Currents are always displayed in amperes with two decimal places.
Measurement units for voltage and power depend on the connection scheme of the meter:
When direct wiring is used, voltages are displayed in volts with one decimal place, and power in kilowatts with three decimal places.
Chapter 3 Display Operations Data Display
34 Series PM172 Powermeters
When wiring via PT is used, for the PT ratio up to and including 4.0, voltages are displayed in volts, and power in whole kilowatts.
For the PT ratio above 4.0, voltages are displayed in kilovolts, and power in megawatts with three decimal places.
The small round “Kilo” and “Mega” LEDs light up showing the appropriate measurement units for a displayed page.
Primary and Secondary Volts
Volts can be displayed in primary (default) or secondary units. The volts display mode can be changed through the Display Setup menu.
Phase Power Readings
In configurations with the neutral wire, in addition to total three-phase powers, the meter can show per-phase power readings. By default, they are disabled. See Display Setup on how to enable per-phase power readings in your meter.
Fundamental Component
The meter can display total power factor and active power for the fundamental component if it is enabled through the Display Setup menu. Whenever phase power readings are allowed, the PM172 also displays per­phase power factor and active power for the fundamental component.
Auto Return
If no buttons are pressed for 30 seconds while the display Auto Return option is enabled, the display automatically returns to the main screen from any other measurement display or programming mode.
The Auto Return option can be enabled through the Display Setup menu
Auto Scroll
If no buttons are pressed for 30 seconds while in the common measurements display, and the Auto Scroll option is enabled in the meter, the display automatically scrolls through all available pages. The scroll interval can be adjusted through the Display Setup menu.
To stop auto scrolling, press briefly the SCROLL button.
Navigation Buttons
In Data Display mode, the navigation buttons function as follows.
The MIN/MAX button switches to the Min/Max - Maximum Demands display pages. When briefly pressed again, it switches back to the common measurements display.
The THD/TDD button in the PM172P and PM172E switches to the Total Harmonics display. The similar H/ESC button in the PM172EH switches between different harmonic displays: Total Harmonics, Individual Harmonics, Harmonic Powers, and Harmonic Energies. When briefly pressed once again, it switches back to the common measurements display
The UP and DOWN arrow buttons, labeled by arrowheads, scroll forwards and backwards through the display pages. Pressed briefly, they move one page forward or backward. If you hold down the button, the display pages are scrolled at rate of a twice per second.
ENERGY
ENTER
THD/TDD
ESC
S
T
MIN MAX
SELECT
Chapter 3 Display Operations Data Display
Series PM172 Powermeters 35
Pressing both the UP and DOWN arrow buttons together returns to the first page within the current display.
The SELECT button operates once it’s released. The button has two functions:
When pressed briefly, it switches to programming mode.
When pressed together with the ENTER button for more
than 5 seconds, it resets Min/Max records, maximum demands, or energies depending on the currently displayed page. If the meter is password protected and a simple reset of data from the display is not allowed, the action has no effect.
The ENERGY button switches to the Energy display in the PM172E and PM172EH. In the PM172P, the button is not operational. If TOU registers are configured in the meter, you can repeatedly press this button to scroll through all available TOU registers. When briefly pressed once again, it switches back to the common measurements display
Simple Reset of Accumulated Data
When the meter is not password protected, or the simple reset of data is allowed from the display regardless of the security setting (see “Display Setup”), the meter allows the simple “two-button’ reset of the Min/Max registers, maximum demands, energies, and counters from the data display mode without entering the reset menu:
1. Select a display page where the data you want to reset is displayed:
Min/Max log - select a Min/Max page from the Min/Max Display. Ampere and volt maximum demands - select the ampere or volt
maximum demand page from the Min/Max Display. Power maximum demands - select the power maximum demand
page from the Min/Max Display. Total and phase energies - select a total energy, or phase energy
page from the Energy Display. Counters – select a counter page from the Status Display
2. While holding the SELECT button, press and hold the ENTER
button for about 5 seconds. The displayed data is reset to zero.
Common Measurements Display
Scroll through pages with the UP and DOWN arrow buttons.
Common Measurements (Main Display)
1
L
V12 V23 V31
Line-to-line volts
2
P
V1 V2 V3
Line-to-neutral volts (in 4LN3, 3LN3, 3BLN3 configurations)
3 I1
I2 I3
Amps
4 kVA/MVA
PF kW/MW
Total VA Total PF Total W
5 In
Hz kvar/Mvar
Neutral current Frequency Total var
6 Ph.L1
PF kW/MW
Phase L1 powers (if enabled)
S
T
Chapter 3 Display Operations Data Display
36 Series PM172 Powermeters
Common Measurements (Main Display)
7 kVA/MVA
Ph.L1
kvar/Mvar
Phase L1 powers (if enabled)
8
Ph.L2
PF kW/MW
Phase L2 powers (if enabled)
9 kVA/MVA
Ph.L2
kvar/Mvar
Phase L2 powers (if enabled)
10 Ph.L3
PF kW/MW
Phase L3 powers (if enabled)
11 kVA/MVA
Ph.L3
kvar/Mvar
Phase L3 powers (if enabled)
12 H01
PF kW/MW
Fundamental total powers (if enabled)
13 H1.L1
PF kW/MW
Fundamental phase L1 powers (if enabled)
14 H1.L2
PF kW/MW
Fundamental phase L2 powers (if enabled)
15 H1.L3
PF kW/MW
Fundamental phase L3 powers (if enabled)
16 An.In
AI1 AI2
Analog inputs (optional)
Min/Max and Max. Demands Display
Press the MIN/MAX button. The MIN/MAX LED, or MAX DEMAND LED in the PM172EH, is illuminated when in the MIN/MAX display. Use the UP and DOWN arrow buttons to scroll through the Min/Max and Max. Demand pages.
Note that volts readings are line-to-neutral in 4LN3, 3LN3 and 3BLN3 wiring modes, and line-to-line in other modes.
Min/Max and Maximum Demands
1
Lo
V1/V12 V2/V23 V3/V31
Minimum volts
2
Lo
I1 I2 I3
Minimum amps
3
Lo
kVA/MVA PF kW/MW
Minimum total VA Minimum total PF (absolute) Minimum total W
4
Lo
In Hz kvar/Mvar
Minimum neutral current Minimum frequency Minimum total var
5
Hi
V1/V12 V2/V23 V3/V31
Minimum volts
6
Hi
I1 I2 I3
Maximum amps
7
Hi
kVA/MVA PF kW/MW
Maximum total VA Maximum total PF (absolute) Maximum total W
8
Hi
In Hz kvar/Mvar
Maximum neutral current Maximum frequency Maximum total var
S
T
MIN MAX
Chapter 3 Display Operations Data Display
Series PM172 Powermeters 37
Min/Max and Maximum Demands
9
Hd
V1/V12 V2/V23 V3/V31
Maximum volt demands
10
Hd
I1 I2 I3
Maximum ampere demands
11
Hd
kVA/MVA PF kW/MW
Maximum VA demand PF at maximum VA demand Maximum W demand
Harmonics Display
Press the THD/TDD, or H/ESC in the PM172EH, button. The THD/TDD LED is illuminated. In the PM172EH, press the button again to move to the individual harmonics, or to the harmonic power and energy displays. Use the UP and DOWN arrow buttons to scroll through harmonics measurements.
Note that voltage harmonics readings are line-to-neutral in the 4LN3, 3LN3, 3BLN3, 4LL3, 3LL3 and 3BLL3 wiring modes, and line-to-line in all other modes.
Total Harmonics
1
thd.
V1/V12 THD V2/V23 THD V3/V31 THD
Voltage THD
2
thd.
I1 THD I2 THD I3 THD
Current THD
3
tdd.
I1 TDD I2 TDD I3 TDD
Current TDD
4
HF
I1 K-Factor I2 K-Factor I3 K-Factor
Current K-Factor
Individual Voltage Harmonics
1
02H
V1/V12 HD% V2/V23 HD% V3/V31 HD%
Order 2 harmonic distortion
2
03H
V1/V12 HD% V2/V23 HD% V3/V31 HD%
Order 3 harmonic distortion
39
40H
V1/V12 HD% V2/V23 HD% V3/V31 HD%
Order 40 harmonic distortion
Individual Current Harmonics
1
02H
I1 HD% I2 HD% I3 HD%
Order 2 harmonic distortion
2
03H
I1 HD% I2 HD% I3 HD%
Order 3 harmonic distortion
39
40H
I1 HD% I2 HD% I3 HD%
Order 40 harmonic distortion
Harmonic Powers
1 kVA/MVA
kW/MW
Total harmonic VA Total harmonic W
S
T
S
T
H ||| |
ESC
S
T
THD/TDD
ESC
H ||| |
ESC
H ||| |
ESC
Chapter 3 Display Operations Data Display
38 Series PM172 Powermeters
Harmonic Energies
1
Ac.En. IP.
MWh
Harmonic Wh import
2
Ac.En. EP.
MWh
Harmonic Wh export
3
AP.En.
MVAh
Harmonic VAh
Energy Display
Press the ENERGY button. The MVAh, Mvarh, or MWh LED is illuminated. If TOU registers are configured in the meter, press the button again to scroll through all active TOU registers. Use the UP and DOWN arrow buttons to scroll through energy pages.
Along with total energies, per phase energy accumulators are displayed if phase energy calculation is enabled in the Device Options menu.
Total and Phase Energies
1
Ac.En. IP.
MWh
Total Wh import
2
rE.En. IP.
Mvarh
Total varh import
3
AP.En.
MVAh
Total VAh
4
Ac.En. EP.
MWh
Total Wh export
5
rE.En. EP.
Mvarh
Total varh export
6
Ac.En. IP.L1.
MWh
Phase L1 Wh import
7
rE.En. IP.L1.
Mvarh
Phase L1 varh import
8
AP.En. L1.
MVAh
Phase L1 VAh
9
Ac.En. IP.L2.
MWh
Phase L2 Wh import
10
rE.En. IP.L2.
Mvarh
Phase L2 varh import
11
AP.En. L2.
MVAh
Phase L2 VAh
12
Ac.En. IP.L3.
MWh
Phase L3 Wh import
13
rE.En. IP.L3.
Mvarh
Phase L3 varh import
14
AP.En. L3.
MVAh
Phase L3 VAh
S
T
S
T
ENERGY
ENTER
H ||| |
ESC
Chapter 3 Display Operations Status Display
Series PM172 Powermeters 39
TOU Energy Register 1
1
rEG.1 trF.1
MWh
Tariff 1 reading
2
rEG.1 trF.2
MWh
Tariff 1 reading
8
rEG.1 trF.8
MWh
Tariff 8 reading
TOU Energy Register 8
1
rEG.8 trF.1
MWh
Tariff 1 reading
2
rEG.8 trF.2
MWh
Tariff 1 reading
8
rEG.8 trF.8
MWh
Tariff 8 reading
Status Display
The meter has separate status information pages accessible through the primary device menu. The Status Display shows rarely used information that is especially helpful when connecting the meter inputs and outputs to external equipment. For information on navigating in the menus, see “Using the Menus”.
To enter the Status Display:
1. From the Data Display, press the SELECT button to enter the primary device menu. The “StA” window is highlighted.
2. Press ENTER to enter the Status Display. Use the UP and DOWN arrow buttons to scroll through the status pages.
To exit the Status Display:
1. Press ESC to return to the primary device menu.
2. Press ESC to return to the Data display.
Status Display
1
PhS rot
POS/nEG/Err
Phase rotation order
2
AG.
V1 angle V2 angle V3 angle
Voltage angles (±180°, referenced to V1)
3
AG.
I1 angle I2 angle I3 angle
Current angles (±180°, referenced to V1)
4 U.Unb
V% unb
Voltage unbalance, percent
5 C.Unb
I% unb
Current unbalance, percent
6
rEL
1.2.
00
Relay status
7
St.In
1.2.
00
Status inputs
S
T
S
T
S
T
ENERGY
ENTER
ENERGY
ENTER
StA
CHG
OPS
SELECT
ENERGY
ENTER
Chapter 3 Display Operations Using the Menus
40 Series PM172 Powermeters
Status Display
8
Cnt.1
Counter #1
9
Cnt.2
Counter #2
10
Cnt.3
Counter #3
11
Cnt.4
Counter #4
12
batt
nor/Lo
Backup battery status (Normal/Low)
Using the Menus
Navigation Buttons
The PM172 has a menu-driven setup. To enter the menus, press and release the SELECT button.
The SELECT button selects (highlights) an active window in which you can select or change a desired menu item. The button operates once it’s briefly pressed and released.
The UP and DOWN arrow buttons scroll through menu items in the highlighted window forwards and backwards, and allow changing a highlighted item when entering numbers.
The ENTER button confirms the selection of a menu item or a number in the highlighted window, thus allowing to enter a submenu or to store a changed item.
The ESC button is “Escape” leaving the highlighted item unchanged or returning to the upper level menu.
Selecting Menus
To access the meter menus, press and release the SELECT button. The primary meter menu is open as shown below. The menu has three entries:
StA - Status Display entry (see ”Status Display” above)
OPS – Main setup menu entry allowing to review setup options
CHG – Main setup menu entry allowing to change setups
To enter the Status Display:
1. If the StA window is not highlighted, use the SELECT button to activate it.
2. Press the ENTER button to enter the Status Display
To review the meter setup options:
ENERGY
ENTER
THD/TDD
ESC
S
T
SELECT
St
A
CHG
OPS
SELECT
StA
CHG
OPS
SELECT
ENERGY
ENTER
Chapter 3 Display Operations Using the Menus
Series PM172 Powermeters 41
1. Press the SELECT button to activate the OPS window.
2. Press the ENTER button to enter the main menu.
To change the meter setup, or to clear the accumulated values:
1. Press the SELECT button to activate the CHG window.
2. Press the ENTER button to enter the main menu.
Entering the Password
The Setup Change menu can be secured by a four-digit user password. The meter is primarily shipped with the password preset to 0 and password protection disabled. You can change the password and enable password protection through the Access Control menu (see Meter Security).
If authorization is not required, just press the ENTER button to move to the Main menu; otherwise you should enter a correct password to be authorized to access the meter setup.
To enter the password:
1. Adjust the first digit with the UP and DOWN arrow buttons.
2. Press the SELECT button to advance to the next digit.
3. Adjust the remaining password digits in the same manner.
4. Press ENTER to confirm the password.
If the password entered is correct, you move to the Main menu, otherwise you return to the previous menu.
Selecting the OPS or CHG entry moves you to the Main menu that is represented by two entries: the upper window displays a secondary menu list, while the bottom item is an assisting exit window.
Selecting a Menu Entry
To select a menu entry from the menu list:
1. Highlight the upper item by pressing the SELECT button.
2. Scroll through the menu list by pressing briefly the UP and DOWN arrow buttons until the desired menu entry appears.
3. Press the ENTER button.
Viewing and Changing Setup Items
A second level menu normally consists of three items: the upper static window indicates the menu name, while the middle window represents a list of setup parameters you can scroll through, and the lower item shows the present parameter value.
To select a parameter you want to view or change:
PASS
0000
ENERGY
ENTER
PASS
0201
S
rSt
ESC
S
bASc
ESC
ENERGY
ENTER
Chapter 3 Display Operations Menu Operations
42 Series PM172 Powermeters
1. Highlight the middle window by pressing the SELECT button.
2. Scroll through the parameter list with the UP and DOWN buttons until the desired parameter name appears.
To change the selected parameter:
1. Press the SELECT button to highlight the lower item.
2. If a number represents the parameter, adjust it to the desired value with the UP and DOWN arrow buttons. When briefly pressed, the button increments or decrements the number by one. When the button is pressed continuously, the number is changed approximately twice per second.
3. If a name represents the parameter, select the desired option with the UP and DOWN arrow buttons.
4. To store your new selection, press the ENTER button.
5. To leave the parameter unchanged, press the ESC button.
You will return to the parameter list to select another parameter or return to the main menu.
To exit the menu, press ESC.
Menu Operations
Basic Device Settings
This menu allows you to configure the basic meter settings that define the general operating characteristics of the device. To enter the menu, select the “baSc” entry from the main menu, and then press the ENTER button.
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired option.
3. Press ENTER to confirm your changes and to store your new setting, or press ESC to discard changes.
To exit the menu, press ESC.
The following table lists available options.
bASc
4Ln3
ConF
bASc
4Ln3
ConF
S
bASc
1.0
Pt
bASc
1.0
Pt S
bASc
200.0
Pt
ENERGY
ENTER
SELECT
bASc
200.0
Pt
THD/TDD
ESC
Chapter 3 Display Operations Menu Operations
Series PM172 Powermeters 43
Label Parameter Options Default Description
ConF Wiring connection
(configuration) mode
See “Basic Meter Setup” in Chapter 4
4Ln3 The wiring connection of the
device
Pt PT ratio 1.0-6500.0 1.0 The phase potential
transformer’s primary to secondary ratio
Pt.F PT Ratio multiplier ×1, ×10 ×1 PT Ratio multip lication factor.
Used in extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks.
U.SEC Nominal secondary
voltage
EH
10-690 V 120 V The nominal secondary line-to-
neutral or line-to-line voltage. Used as a reference voltage for the disturbance monitor.
Ct CT primary current 1-20,000 A 5 A The primary rating of the phase
current transformer
d.P Power block demand
period
E
1, 2, 3, 5, 10, 15, 20, 30, 60 min, E=external sync
15 min The length of the demand
period for power demand calculations. If the external synchronization is selected, a pulse front on the digital input DI1 denotes the start of the demand interval.
nd.P The number of blocks in
the sliding window
E
1-15 1 The number of blocks to be
averaged for sliding window demands
Ad.P Ampere, volt and THD
demand period
0-1800 sec 900 sec The length of the demand
period for ampere, volt and THD demand calculations
Freq Nominal frequency 50,60,25,
400 Hz
60 Hz The nominal line frequency
LoAd Maximum demand load
current
0-20,000 A 0 The maximum demand load
current (0 = CT primary)
Ì Always specify the wiring mode and transformer ratings prior to setting up
setpoints and analog outputs.
Ì The maximum value for the product of the phase CT primary current and PT ratio
is 57,500,000. If the product is greater, power readings are zeroed.
Device Options
This menu allows you to change the user-configurable device options or put the meter into energy test mode. To enter the menu, select the “OPtS” entry from the Main menu, and then press the ENTER button.
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired option.
3. Press ENTER to confirm your changes and to store your new setting, or press ESC to discard changes.
To exit the menu, press ESC.
OPtS
rEAc
P.cAL
Chapter 3 Display Operations Menu Operations
44 Series PM172 Powermeters
The following table lists available options.
Label Parameter Options Default Description
P.cAL Power
calculation mode
rEAc (reactive power), nAct (non-active
power)
Reactive The method used for
calculating reactive and apparent powers
roLL Energy roll
value
E
10.E4=10,000
10.E5=100,000
10.E6=1,000,000
10.E7=10,000,000
10.E8=100,000,000
10.E9=1,000,000,000
10.E9 The value at which energy counters roll over to zero
Ph.En Phase energy
option
E
diS = disabled En = enabled
Disabled Enables phase energy
calculations
Hr.En Harmonic
energy option
EH
diS = disabled En = enabled
Disabled Enables harmonic
energy calculations
bAtt Backup battery
mode
OFF = switched OFF On = switched ON
OFF Allows to conserve a
battery while the meter is out of operation
tESt Energy test
mode
E
OFF = disabled Ac.Ei = Wh pulses rE.Ei = varh pulses
Disabled Setting this option puts
the meter into the energy test mode
An.EP Analog
expander option
1
nonE = disabled 0-20 = 0-20 mA 4-20 = 4-20 mA 0-1 = 0-1 mA
-1-1 = ±1 mA
Disabled Enables outputs for the
AX-8 analog expanders through port COM2. See “Analog Expander Setup”
C.Str Starting
Current, %FS
0.1-2.0
0.1%FS Specifies the low current measurement limit in percent of the full scale current (1A, 5A). Available in the PM172P/E V13.1.19 and later.
1
Do not enable the analog expander output if you do not have the analog expander
connected to the meter, otherwise it will disturb the computer communications.
Transformer Correction
This menu is available in the PM172P/E with firmware V13.1.19 and later, or V13.71.12 and later.
Transformer correction allows you to compensate ratio and phase angle inaccuracies of the user voltage and current instrument transformers. To enter the menu, select the “t.Cor” entry from the Main menu, and then press the ENTER button.
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired option.
3. Press ENTER to confirm your changes and to store your new setting, or press ESC to discard changes.
To exit the menu, press ESC.
The following table lists available options.
t.Cor
1.000
U1.rt
Chapter 3 Display Operations Menu Operations
Series PM172 Powermeters 45
Label Parameter Options Default Description
U1.rt U2.rt U3.rt
V1-V3 voltage transformer ratio correction factor
0.900 to 1.100 1.000 The ratio of the true transformer ratio to the marked ratio.
U1.AG U2.AG U3.AG
V1-V3 transformer phase angle error, minutes
-600 to 600
(-2700 to 2700 with V13.7X.XX)
0 The phase
displacement, in minutes, between the primary and secondary values. The phase angle of a voltage transformer is positive when the secondary value leads the primary value.
C1.rt C2.rt C3.rt
I1-I3 current transformer ratio correction factor
0.900 to 1.100 1.000 The ratio of the true transformer ratio to the marked ratio.
C1.AG C2.AC C3.AG
I1-I3 transformer phase angle error, minutes
-600 to 600
(-2700 to 2700 with V13.7X.XX)
0 The phase
displacement, in minutes, between the primary and secondary values. The phase angle of a current transformer is positive when the secondary value leads the primary value.
Communication Ports
These two menus allow you to configure parameters for communication ports COM1 and COM2. To enter the menu, select “Prt.1” for COM1 or “Prt.2” for COM2 from the Main menu, and then press the ENTER button.
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired option.
3. Press ENTER to confirm your changes and to store your new setting, or press ESC to discard changes.
To exit the menu, press ESC.
The following tables list available port options.
COM1 Settings
Label Parameter Options Default Description
Prot Communications
protocol
ASCII = SATEC ASCII rtu = Modbus RTU
2
dnP3 = DNP3
2
dtE = DTE PrFb = Profibus DP
Modbus RTU
The communications protocol supported by the port
rS
Port interface
1
232 = RS-232 485 = RS-485 422 = RS-422 dial = Dial-up Modem Eth.= Ethernet PrFb = Profibus DP
Depends on the order
For non-serial interfaces
- not changeable; automatically detected by the meter
Prt.1
rtu
Prot
Chapter 3 Display Operations Menu Operations
46 Series PM172 Powermeters
Label Parameter Options Default Description
Addr Device address SATEC ASCII: 0-99
Modbus RTU: 1-247 DNP3: 0–65532 DTE: 1-65532 Profibus DP: 0-126
1 (126 for Profibus)
Device network address
bAud Baud rate 300-115200 bps 19200 bps The port baud rate dAtA Data format and
parity
7E, 8N, 8E 8N 7E data format should
not be used with the Modbus RTU and DNP3 protocols
H.Sh
Handshaking (flow control)
nonE=no flow control SOFt=software (XON/XOFF) HArd=hardware (CTS)
None
rtS
RTS mode
nonE = not used Forc = RTS is permanently asserted CtrL = RTS is asserted during the transmission
None
1
The meter automatically detects a replaceable communication module and does not allow you to change the interface, baud rate or data format for the Dial-up modem, and for the Ethernet or Profibus port.
2
Selecting the DNP3 protocol on the Ethernet port launches the DNP3/TCP server along with the Modbus/TCP server allowing simultaneous connections on both TCP ports. Selecting the Modbus protocol for the port disables the DNP3/TCP server.
COM2 Settings
Label Parameter Options Default Description
Prot Communications
protocol
ASCII = SATEC ASCII rtu = Modbus RTU dnP3 = DNP3 dtE = DTE
Modbus RTU
The communications protocol supported by the port
rS Port interface
485 = RS-485 422 = RS-422
RS-485
Addr Device address
SATEC ASCII: 0-99 Modbus RTU: 1-247 DNP3: 0–65532 DTE: 1-65532
1 Device network address
bAud Baud rate 300-115200 bps 19200 bps The port baud rate dAtA Data format and
parity
7E, 8N, 8E 8N 7E data format should
not be used with the Modbus RTU and DNP3 protocols
Network Address
This menu allows you to configure the device IP address and the default gateway address for the Ethernet port. To enter the menu, select “nEt” from the Main menu, and then press the ENTER button.
To change the IP Address and Default Gateway:
1. To change the device IP address, select the “A” entry in
the upper window with the UP and DOWN arrow buttons. To change the default gateway address, select the “G” entry.
2. Press the SELECT button to activate the first address
digit.
3. Use the UP and DOWN arrow buttons to adjust the digit.
4. Press the SELECT button to advance to the next digit.
5. Adjust the remaining address digits.
A. 192.
000.203
168.
G. 192.
000.001
168.
Chapter 3 Display Operations Menu Operations
Series PM172 Powermeters 47
6. Press ENTER to confirm your new setting, or press ESC
to discard changes.
To exit the menu, press ESC.
Counters Setup
The PM172 has four six-digit counters that can count pulses delivered through the device digital inputs with a programmable scale factor, or events that trigger setpoint operations. This menu allows you to link digital inputs to the counters and define a pulse multiplier for each counter. To enter the menu, select the “Cnt” entry from the Main menu and press the ENTER button.
The menu uses three entries:
1. The upper window indicates a counter number.
2. The middle window selects a digital input to be linked to
the counter.
3. The lower window defines a counter multiplier.
Use the UP and DOWN arrow buttons to scroll to the desired counter.
To change the counter options:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to link a digital
input to the counter or to disable the counter input.
3. Press the SELECT button to activate the lower window.
4. Use the UP and DOWN arrow buttons to enter the desired
multiplier.
5. Press ENTER to confirm your changes and to store your
new settings, or press ESC to discard changes.
6. You are returned to the upper window to select another
counter or exit the menu.
To exit the menu, press ESC.
The following table lists available counter options.
Parameter Options Default Description
Pulse source None = disabled
Inp.1 = DI1 Inp.2 = DI2
None Links a digital input to the counter
Multiplier 1-9999 1 The value added to the counter
when a pulse is detected on the pulse source input, or the counter is incremented through a setpoint action
Relay Output Setup
To enter the menu, select the “rEL” entry from the Main menu and press the ENTER button.
Use the UP and DOWN arrow buttons to scroll to the desired relay.
To select a relay parameter:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the
desired parameter.
To change the parameter value:
1. Press the SELECT button to activate the lower window.
Cnt.1
1
Inp.1
rEL
ESC
Chapter 3 Display Operations Menu Operations
48 Series PM172 Powermeters
2. Use the UP and DOWN arrow buttons to select the
desired value.
3. Press ENTER to confirm the new parameter setting, or
press ESC to discard changes.
4. You are returned to the middle window to select and
configure another parameter, or confirm the settings and exit the menu.
To store your new settings:
1. When the middle window is highlighted, press the ENTER
button.
2. You are returned to the upper window to select another
relay or exit the menu.
To exit the menu, press ESC.
The following table lists available relay options.
Label Parameter Options Default Description
tYPE Operation
mode
UnLt = Unlatched Ltch = Latched PLS.A = Pulse PLS.C = KYZ pulse
UnLt See Using Relay Outputs
in Chapter 4
Polr Polarity nor = Normal (N.O.)
InS = Inverting (N.C.)
nor See Using Relay Outputs
in Chapter 4
rtnt Retentive
mode
diS = Disabled En = Enabled
diS See Using Relay Outputs
in Chapter 4
PuLS Pulse width 20-1000 ms 100 ms The actual pulse width is
a multiple of the 1-cycle time rounded to the nearest bigger value.
The pause time between pulses is equal to the pulse width.
Src Pulse source nonE
Ac.Ei = kWh IMP Ac.EE = kWh EXP rE.Ei = kvarh IMP rE.EE = kvarh EXP rE.Et = kvarh TOT AP.Et = kVAh
NONE Links a pulse relay to the
internal energy pulse source. The relay must be set into either pulse, or KYZ mode.
Unit Pulse rate,
kWh/Pulse
0.1-1000.0 1.0 kWh/Pulse
Defines the pulse weight in kWh units per pulse
Control Setpoints Setup
The PM172 provides 16 control setpoints with programmable operate and release delays. Each setpoint evaluates a logical expression with up to four arguments using OR/AND logic. Whenever an expression is evaluated as “true”, the setpoint performs up to four concurrent actions that send a command to the output relays, increment or decrement a counter, or trigger a recorder. For more information on setpoints operation, see “Using Control Setpoints” in Chapter 4.
This menu configures setpoints through the front display. To enter the menu, select the “SEtP” entry from the Main menu, and press the ENTER button.
The menu uses three entries:
1. The upper window indicates a setpoint number.
2. The middle window selects a setup parameter to view or change.
3. The lower window displays the parameter value.
SEtP
ESC
rEL.1
PulS
tYPE
rEL.1
nor
Polr
rEL.1
100
PuLS
rEL.1
Ac.Ei
Src
rEL.1
1.0
Unit
rEL.1
diS
rtnt
Chapter 3 Display Operations Menu Operations
Series PM172 Powermeters 49
Use the UP and DOWN arrow buttons to scroll to the desired setpoint.
To select a setpoint parameter:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired parameter.
To change the parameter value:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired value.
3. Press ENTER to confirm the new parameter setting, or press ESC to discard changes.
4. You are returned to the middle window to select and configure another parameter, or confirm the setpoint settings and exit the menu.
To store your new setpoint settings after you configured all setpoint parameters:
1. When the middle window is highlighted, press the ENTER button.
2. You are returned to the upper window to select another setpoint or exit the menu.
To exit the menu, press ESC.
The following table lists available setpoint options. For a list of available setpoint triggers and actions, see “Using Control Setpoints” in Chapter 4.
Label Parameter Options Description
LGC.2­LGC.4
Logical operator
OR, AND
Combines setpoint triggers in a logical expression
TrG.1-TrG.4 Trigger
parameter #1­#4
See Appendix C
The analog or digital value that is used as an argument in a logical expression
On.1-On.4 Operate limit
The threshold (in primary units) at which the conditional expression would be evaluated to true. Not applicable for digital triggers.
OFF.1­OFF.4
Release limit
The threshold (in primary units) at which the conditional expression would be evaluated to false. Defines the hysteresis for analog triggers. Not applicable for digital triggers.
Act.1-Act.4 Setpoint action
#1-#4
See Appendix C
The action performed when the setpoint expression is evaluated to true (the setpoint is in operated state)
On d Operate delay
0-999.9 sec
The time delay before operation when the operate conditions are fulfilled
OFF d Release delay
0-999.9 sec
The time delay before release when the release conditions are fulfilled
Analog Inputs Setup
This entry appears only if the meter is ordered with optional analog inputs. For more information on configuring analog inputs in your meter, see “Programming Analog Inputs” in Chapter 4.
To enter the menu, select the “A.In.1” or “A.In.2” entry from the Main menu for the AI1 and AI2 input respectively, and press the ENTER button.
SP.1
rtHi.C1
trG.1
SP.1
200
On.1
SP.1
180
OFF.1
SP.1
Or
LOG.2
SEtP
rEL.1
A
ct.1
SP.1
rtHi.C2
trG.2
SP.1
200
On.2
SP.1
180
OFF.2
Chapter 3 Display Operations Menu Operations
50 Series PM172 Powermeters
To change the analog input options:
1. Use the UP and DOWN arrow buttons to scroll to the desired parameter.
2. Press the SELECT button to activate the lower window.
3. Use the UP and DOWN arrow buttons to adjust the parameter value.
4. Press ENTER to confirm the new parameter setting, or press ESC to discard changes.
5. You are returned to the middle window to select another parameter, or store your new settings and exit the menu.
To store new settings and exit the menu:
1. When the middle window is highlighted, press the ENTER button.
2. You return to the main menu.
To exit the menu without saving your changes, press ESC.
The following table lists available analog input options.
Label Parameter Options Description
Lo Zero scale
0-999,999
The low engineering scale (in primary units) for the analog input corresponding to a lowest (zero) input current (0 or 4 mA)
Hi Full scale
0-999,999
The high engineering scale (in primary units) for the analog input corresponding to a highest input current (1 or 20 mA)
dEc.P Number of
decimal places
0-3
The number of decimal digits in a fractional part of the scaled engineering value
Analog Outputs Setup
This entry appears only if the meter is ordered with optional analog outputs. For more information on configuring analog inputs in your meter, see “Programming Analog Outputs” in Chapter 4.
To enter the menu, select the “A.Ou.1” or “A.Ou.2” entry from the main menu for the AO1 and AO2 output respectively, and then press the ENTER button.
To change the analog output options:
1. Use the UP and DOWN arrow buttons to scroll to the desired parameter.
2. Press the SELECT button to activate the lower window.
3. Use the UP and DOWN arrow buttons to adjust the parameter value.
4. Press ENTER to confirm your new parameter setting, or press ESC to discard changes.
5. You are returned to the middle window to select another parameter, or store your new settings and exit the menu.
To store new settings and exit the menu:
1. When the middle window is highlighted, press the ENTER button.
2. You return to the main menu.
To exit the menu without saving your changes, press ESC.
The following table lists available analog output options. For a list of the available output parameters and their scales, see “Programming Analog Outputs” in Chapter 4.
A
.In.1
ESC
A.In.1
0
Lo
A.In.1
230
Hi
A.In.1
1
dEc.P
A
.Ou.1
ESC
A.Ou.1
rt.U1
OutP
A.Ou.1
0
Lo
A.Ou.1
230
Hi
Chapter 3 Display Operations Menu Operations
Series PM172 Powermeters 51
Label Parameter Options Description
OutP Output
parameter
See Appendix B
Selects the measured parameter to be transmitted through the analog output channel.
Lo Zero scale
Low engineering scale (in primary units) for the analog output corresponding to a lowest (zero) output current (0 or 4 mA)
Hi Full scale
High engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA)
Analog Expander Setup
The meter can provide 16 additional analog outputs via two optional AX-8 analog expanders that are connected through a serial RS-422 interface to the meter port COM2. Each expander has its own address 0 or 1 on the serial interface.
This menu allows you to assign parameters for the expanded analog outputs and to specify their scales. For more information on configuring the analog expander outputs in your meter, see “Programming the Analog Expander” in Chapter 4.
To enter the menu, select the “AEPn” entry from the Main menu, and press the ENTER button.
The expanded analog outputs are labeled in the following manner: analog output channels A1-1 through A1-8 are associated with the analog expander with address 0, while outputs A2-1 through A2-8 are associated with the analog expander with address 1.
The menu uses three entries:
1. The upper window indicates an analog expander’s output channel.
2. The middle window selects a setup parameter to view or change.
3. The lower window displays the parameter value.
Use the UP and DOWN arrow buttons to scroll to the desired analog expander channel.
To select a setup parameter:
1. Press the SELECT button to activate the middle window.
3. Use the UP and DOWN arrow buttons to scroll to the desired parameter.
To change the parameter value:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired value.
3. Press ENTER to confirm the new parameter setting, or press ESC to discard changes.
4. You are returned to the middle window to select and configure another parameter, or confirm the analog output settings and exit the menu.
To store your new settings after you configured all parameters:
1. When the middle window is highlighted, press the ENTER button.
A
EPn
ESC
A1-1
Ar.U1
OutP
A-1
0
Lo
A1-1
120
Hi
Chapter 3 Display Operations Menu Operations
52 Series PM172 Powermeters
2. You are returned to the upper window to select another analog output or exit the menu.
To exit the menu, press ESC.
The following table lists available analog output options.
Label Parameter Options Description
OutP Output
parameter
See Appendix B
Selects the measured parameter to be transmitted through the analog expander channel.
Lo Zero scale
Low engineering scale (in primary units) for the analog output corresponding to a lowest (zero) output current (0 or 4 mA)
Hi Full scale
High engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA)
Ì Analog expander outputs will not be operational until you globally enable the
analog expander option in your meter through the Device Options menu.
Timers Setup
The PM172E and PM172EH are provided with two interval timers. When enabled, a timer generates periodic events in predefined intervals that can trigger setpoints to produce periodic actions like periodic data trending. To enter the menu, select the “t-r” entry from the Main menu and press the ENTER button.
Use the UP and DOWN arrow buttons to scroll to the desired timer.
To change the time period for the timer:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to enter the desired interval value in seconds. Intervals from 1 to 9999 seconds are allowed. Resetting the interval to 0 disables the timer.
3. Press ENTER to confirm your changes and to save the new settings, or press ESC to discard changes.
4. You are returned to the middle window to select another timer or exit the menu.
To exit the menu, press ESC.
Display Setup
This menu allows you to configure options for the meter display, and view display and device firmware versions. To enter the menu, select the “diSP” entry from the Main menu and press the ENTER button.
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired option.
3. Press ENTER to confirm your changes and to save the new setting, or press ESC to discard changes.
To exit the menu, press ESC.
t-r
0
t-r.1
diSP
1.0
UPdt
Chapter 3 Display Operations Menu Operations
Series PM172 Powermeters 53
The following table lists available options.
Label Parameter Options Default Description
UPdt Display update rate 0.1-10.0 sec 1 sec Defines the interval betw een
display updates
ScrL Auto scroll interval None,
2-15 sec
None Defines the scroll interval for
the main data display or disables auto scroll
rEtn Auto return to the
main screen
diS = disabled,
En = Enabled
Enabled Enables automatic return to
the main display if no buttons are pressed for 5 minutes
bAr
Reference load current for LED bar graph
0-20,000A (0 = CT primary current)
0 Defines the nominal load
(100%) level for the bar graph display
Uolt Primary/Secondary
volts units
Pri, SEc Primary Selects primary or secondary
units for volts display
Ph.P Phase powers
display mode
diS, En Disabled Disables or enables phase
powers in the main display
Fund. Fundamental
component display mode
diS, En Disabled Disables or enables
fundamental values in the main display
dAtE Date order dnY, ndY,
Ynd (d=day, n=month, y=year)
mm.dd.yy Defines the date order in the
RTC display
rSt Simple reset mode PASS =
password required
En = enabled
PASS PASS = the simple reset is not
allowed when password protection is enabled
En = enables the simple reset buttons regardless of password protection
SoFt. Display firmware
version
N/A N/A Shows display firmware
version, like 1.2.8
SoFt. Device firmware
version
N/A N/A Shows device firmware
version, like 15.01.09
Meter Security
The Access Control menu allows you to change the user password and enable or disable password protection. To enter the menu, select the “AccS” entry from the main menu and press the ENTER button.
The password in your meter is preset to 0 at the factory, and password protection is disabled.
To change the password:
1. Select the “PASS” entry in the upper window with the UP and DOWN arrow buttons.
2. Press the SELECT button to activate the first password digit.
3. Use the UP and DOWN arrow buttons to adjust the digit.
4. Press the SELECT button to advance to the next digit.
5. Adjust the remaining password digits.
6. Press ENTER to confirm your new password.
Ì Your new password is effective for both the display and communication ports.
To enable or disable password protection:
PASS
0000
A
ccS
ESC
Chapter 3 Display Operations Menu Operations
54 Series PM172 Powermeters
1. Select “CtrL” in the upper window using the UP and DOWN arrow buttons.
2. Press the SELECT button to activate the middle window.
3. Use the UP and DOWN arrow buttons to select the desired option. “On” enables password protection, “OFF’ disables password protection.
4. Press ENTER to confirm your new setting, or ESC to discard changes.
To exit the menu, press ESC.
Ì
When password protection is enabled in your meter, you are not able to change
the device settings through the display or communications unless you provide a correct password. If you cannot provide a proper password, contact your local distributor for the appropriate password to override password protection.
Setting the Device Clock
To enter the menu, select the “rtc” entry from the Main menu and press the ENTER button. This menu allows you to set up the device clock and to configure your local time zone settings.
To select a setup option, use the UP and DOWN arrow buttons from the upper window.
To change the time, date, or daylight savings setting:
1. Highlight an item you want to change by pressing briefly the SELECT button. When you enter the time setup display, the hours and minutes are frozen to allow you to adjust them.
2. Adjust the selected item with the UP and DOWN arrow buttons.
3. Highlight the next item you want to change and adjust it in the same manner.
4. Press ENTER to confirm your changes, or press ESC to leave the clock settings unchanged. If you confirm the time change while the seconds are highlighted, the seconds are zeroed; otherwise they stay unchanged.
To exit the menu, press ESC.
The following table lists available options.
Label Option Format/Range Description
hour Time hh.mm.ss The time is displayed as hh.mm.ss, where
the hours and minutes are shown in the middle window separated by a dot, and the seconds - in the lower window.
dAte Date YY.MM.DD,
MM.DD.YY, DD.MM.YY
The date is displayed as per the user definition, where the first two items are shown in the middle window, and the last one - in the lower window. For instructions on how to select the date format, see “Display Setup”.
dAY Day of week Sun = Sunday
Πon = Monday tuE = Tuesday UEd = Wednesday thu = Thursday Fri = Friday Sat = Saturday
The day of the week is displayed in the lower window. It is set automatically when you change the date.
CtrL
On
hour
25.
17.43.
dAtE
05.
01.23.
Chapter 3 Display Operations Menu Operations
Series PM172 Powermeters 55
Label Option Format/Range Description
dSt Daylight saving
time option
diS = disabled En = enabled
When DST is disabled, the RTC operates in standard time only. When enabled, the device automatically updates the time at 2:00 AM at the pre-defined DST switch dates.
dSt.S DST start date Month-week-
weekday Week = 1
st
, 2nd, 3rd,
4
th
or LSt (last week
of the month)
The date when Daylight Saving Time begins. The DST switch point is specified by the month, week of the month and weekday. By default, DST starts at 2:00 AM on the second Sunday in March of each year.
dSt.E DST end date Month-week-
weekday Week = 1
st
, 2nd, 3rd,
4
th
or LSt (last week
of the month)
The date when Daylight Saving Time ends. The DST switch point is specified by the month, week of the month and weekday. By default, DST ends at 2:00 AM on the first Sunday in November of
each year. dSt.S Hour
DST start hour 1-6 The time when Daylight Saving Time
begins. dSt.E Hour
DST end hour 1-6 The time when Daylight Saving Time
ends.
Resetting Accumulators and Maximum Demands
To enter the menu, select the “rst” entry from the Main menu, and then press the ENTER button.
The Reset menu allows you to separately reset minimum/maximum log records, maximum demands and counters.
To reset the desired registers:
1. Highlight the middle window by pressing briefly the SELECT button.
2. Select the desired entry by scrolling through the list with the UP and DOWN arrow buttons until the desired entry appears.
3. Press the SELECT button briefly to highlight the lower item.
4. Press and hold the ENTER button for 5 seconds.
5. Release the button. The “do” entry is replaced with “done” showing the operation is complete.
The following table shows available options.
Label Description
Lo.Hi Clears Min/Max log A.dnd Clears maximum ampere, volt and harmonic demands P.dnd Clears maximum power demands dnd Clears all maximum demands Enr Clears all total energies tOU.d Clears summary and TOU maximum demands tOU.E Clears summary and TOU energy registers Cnt Clears all counters Cnt1 – Cnt4 Clears counter #1-#4
rSt
do
Lo.Hi
Chapter 4 PAS Application Software Configuration Database
56 Series PM172 Powermeters
Chapter 4 PAS Application Software
Supplemental PAS software can be used for configuring the PM172 through communication ports, for retrieving real-time and recorded data, and for remote upgrading device firmware.
For information on how to install PAS on your PC, see the “PAS Getting Started” guide supplied on the installation CD.
Configuration Database
To communicate with your meters, create a separate site database for each device. All communication and configuration data for your meter is stored in this database. During configuration, store all setups to the site database so that PAS recognizes device properties regardless of whether the device is online or offline.
To create a new database for your meter:
1. Select Configuration from the Tools menu, and then click the Sites button on the right-hand side.
2. From the “Look in” box, select the directory where a new database will be stored. By default, it will be the “Sites” directory. Type a site name for your device in the “File name” box, click New, and then click OK.
3. On the Instrument Setup tab, select “PM172-N” for the PM172P and PM172E, or select “PM172EH-N” for the PM172EH, in the “Model” box. PAS automatically selects the appropriate instrument options for your meter.
4. Select a correct CT secondary current (5A or 1A) for your meter. If you have the analog expander connected to the meter, select an appropriate output current option for the analog expander.
5. If you wish to add any comments for your meter, type them into the “Comment” box.
Setting up Communications
You can communicate with the meter via a changeable COM1 communication port, or through a second factory set serial RS-485/RS-422 COM2 port. Depending on what was ordered, your meter’s COM1 port can
Chapter 4 PAS Application Software Setting up Communications
Series PM172 Powermeters 57
be equipped with an RS-232/RS-422/RS-485 serial interface, with a dial-up modem for communicating through public telephone lines, with an Ethernet module for communicating through the Internet, or with a Profibus port. PAS does not support communications through Profibus.
To configure your communications with the PM172:
1. Select Configuration from the Tools menu. Under the Communication group on the Instrument Setup tab, select the type of a connection for your device.
2. Set the device communication address you assigned to the PM172.
3. In the “Sampling Rate” box, select a rate at which PAS updates data on your screen when you continuously poll the device in the PAS Data Monitor.
The communication protocol and port settings in PAS must match the settings made in your device.
Communicating through a Serial Port
Select Serial Port/Modem Site on the Configuration tab, and then click on the Connection tab to configure your serial port settings.
Configuring a Serial Port
1. On the Connection tab, select a COM port from the “Device” box, and then click Configure.
2. Specify the baud rate and data format for the port. Choose the same baud rate and data format as you have set in the device, and then click OK. The default settings for the local RS-232 and RS-422/485 ports are 19200 baud, 8 bits with no parity.
Selecting the Communications Protocol
1. On the Connection tab, click Protocol.
Chapter 4 PAS Application Software Setting up Communications
58 Series PM172 Powermeters
2. In the “Protocol” box, select the same communications protocol as you have in your meter. The default protocol setting in your meter for all ports excluding the Profibus port is Modbus RTU.
For more information on configuring the protocol parameters, refer to the “PAS Getting Started” guide.
Communicating through a Dial-up Modem
Configuring a Modem
1. On the Connection tab, select a local modem installed on your PC.
2. Click on Phones to add the phone number of the remote meter to the phone list.
3. Type the phone number in the “Phone number” box, add comments if you desire, click Add, and then click OK.
4. From the “Phone number” box on the Connection tab, select the phone number from the list, and then click OK.
Selecting the Communications Protocol
On the Connection tab, click Protocol, and then select the protocol settings as shown above for a serial port.
Communicating through the Internet
If you are communicating through the Ethernet port, you should define the IP address of your meter on the network.
1. On the Instrument Setup tab, select Internet Site.
2. Click on the Connection tab.
3. Click on the “IP address” and type in the IP address of your meter. The default IP address preset at the factory is
192.168.0.203.
4. In the “Protocol” box, select the communications protocol for the TCP port. The meter can provide Modbus/TCP connections on TCP port 502 and DNP3/TCP connections on port 20000. The host port is set automatically as you
Chapter 4 PAS Application Software Setting Up the Meter
Series PM172 Powermeters 59
select the protocol. Select “Modbus RTU” for Modbus/TCP or “DNP3” for DNP3/TCP.
5. In the “Wait for answer” box, adjust the time that PAS will wait for a connection before announcing an error and the number of retries PAS will use to receive a response from the device if communications fail.
Setting Up the Meter
PAS allows you to prepare setup data for the meter off-line without the need to have it connected to your PC.
Select the device site from the list box on the PAS toolbar, and then select the desired setup group from the Meter Setup menu. Click on the tab with the setup you want to create or modify, and then fill in the boxes with the desired configuration data for your device. Click on the “Save as…” button to store your new data to the site database.
Ì
Always set up and store the Basic Setup data to the site database first. PAS uses
this data as a reference when arranging other meter setups.
To save your setup to another site database, select it from the file pane. Click OK.
To reuse setups from another site, copy them to your present site database. Click Open, select the desired site database, and then click OK. The opened setup is copied to your site database.
You can also copy all setups from one site database into another site's database. Select a device site from the list box on the toolbar from which you want to reproduce setups, and then select “Copy to...” from the Meter Setup menu. Select the site database to which to copy setups, and click OK.
Downloading Setup to the Meter
You can update each setup in your meter one at a time or download all setups together from the site database.
To update a particular setup in your device, check the On-line button on the PAS toolbar, select a meter site from the list box on the toolbar, and then select the desired setup group from the Meter Setup menu. Click on the tab of the setup you want to download to the meter, and then click Send.
To download all setups to your device at once, check the On-line button on the toolbar, select the device site from the list box on the toolbar, and then select Download Setups from the Meter Setup menu.
Uploading Setup from the Meter
To upload the setup from the device to the site database, check the On-line button on the toolbar, select the device site from the list box on the toolbar, and then select Upload Setups from the Meter Setup menu.
Authorization
If communications with your device is secured, you are prompted for the password when you send new setup data to the meter.
Chapter 4 PAS Application Software Configuring Communications in your Meter
60 Series PM172 Powermeters
Enter the password and click OK. If your authorization was successful, you are not prompted for the password again until you close the dialog window.
Configuring Communications in your Meter
This section describes how to configure communication ports in your meter through PAS.
Setting Up Communication Ports
To enter the setup dialog, select the device site from the list box on the PAS toolbar, select Communications Setup from the Meter Setup menu, and then click on the Serial Ports Setup tab. In the Port box, select the desired device port.
To change the port settings in your meter, select desired port parameters, and then click Send. For the available communication options, see “Communication Ports” in Chapter 3.
NOTES
1. The meter provides the permanent Modbus TCP server on port 502. Selecting the DNP3 protocol launches the DNP3 TCP server in addition to the Modbus server allowing simultaneous connections on both ports. Selecting the Modbus protocol disables the DNP3 TCP server.
2. When you change the COM1 settings through the Ethernet port, the device port restarts so communications
Chapter 4 PAS Application Software Configuring Communications in your Meter
Series PM172 Powermeters 61
will be temporarily lost. You may need to wait some additional time until PAS restores a connection with your device.
Setting Up the Ethernet
To enter the Setup dialog, select the device site from the list box on the PAS toolbar, select Communications Setup from the Meter Setup menu, and then click on the Network Setup tab.
The following table lists available network options.
Parameter Options Default
Device IP Address 192.168.0.203 Network Subnet Mask 255.255.255.0 Network Default Gateway 192.168.0.1 TCP Service Port 502 = Modbus/TCP
20000 = DNP3/TCP
502
Ì
The TCP service port can also be changed trough the COM1 serial port setup:
changing the protocol for the port automatically changes the TCP port for the Ethernet.
To change the Ethernet settings in your meter, select desired parameters, and then click Send.
NOTES
1. The meter provides the permanent Modbus TCP server on port 502. Selecting the DNP3 TCP service port launches the DNP3 TCP server in addition to the Modbus server allowing simultaneous connections on both ports. Selecting the Modbus TCP port disables the DNP3 TCP server.
2. When you change the device network settings through the Ethernet port, the device port restarts so communication will be temporarily lost. You may need to wait some
Chapter 4 PAS Application Software Configuring Communications in your Meter
62 Series PM172 Powermeters
additional time until PAS restores a connection with your device.
Configuring GE EGD Production Exchanges
The PM172 provides a GE EGD (Ethernet Global Data) data producer that supports four data exchanges. Each data exchange is individually configurable and can produce and send data to the same or to different consuming nodes. For EGD implementation and configuration details, see the PM172 GE EGD Communications Protocol Reference Guide.
To enter the Setup dialog, select the device site from the list box on the PAS toolbar, select Communications Setup from the Meter Setup menu, and then click on the GE EGD Producer Setup tab.
To configure an EGD exchange:
1. Select a desired exchange ID.
2. Specify a destination IP address of the data-consuming node.
3. Specify the production period for the exchange. The PM172 exchanges provide production rates from 70 ms to 10 minutes in 10 ms increments. Though lower settings are allowed, the actual production period in most cases will not be less than 70 ms.
4. Select “Enabled” in the Exchange Status box to enable the exchange operations.
5. Define address ranges for the points to be sent via the exchange and the data element type for each address range. Up to 30 point ranges can be selected for each exchange that may identify a single point or a range of contiguous points.
Specify the data ranges using the range start point and end point identifiers (ID) in decimal notation. For the available device data points and their IDs, refer the
Chapter 4 PAS Application Software Configuring Communications in your Meter
Series PM172 Powermeters 63
PM172 GE EGD Communications Protocol Reference Guide.
Select a desired data type for the point range. Data transferred through the exchange can be represented in word (16-bit) or double word (32-bit) integer format, or in IEEE single precision floating-point format.
As you specify an address range for the exchange, PAS immediately shows you the data offset in bytes in the production data area for the following range. Each exchange can send a total of 480 bytes of production data. PAS automatically truncates your range if you specify more data than the exchange can accommodate.
To indicate the end of the address range list, put a zero start point ID in the range following the last range you specified.
6. Click on Send to download your new setup to the meter. The device will reject your setup if you specified an inexistent start point ID for one of the address ranges. If you specified more points in a range than the device can provide, it truncates the range to the maximum number of points available.
From this dialog box, you can also temporarily put a configured exchange into the pending (disabled) state, and then resume (enable) it whenever needed.
NOTE
When you change the consumer IP address for an exchange through the Ethernet, the device port restarts so communications will be temporarily lost. You may need to wait some additional time until PAS restores a connection with your device.
Chapter 4 PAS Application Software General Meter Setup
64 Series PM172 Powermeters
General Meter Setup
This section describes how to configure the PM172 for your particular environment and application using PAS.
Basic Meter Setup
Before operating your meter, provide the device with basic information about your electrical network.
To enter the Setup dialog, select the device site from the list box on the PAS toolbar, and then select General Setup from the Meter Setup menu.
The following table lists available device configuration options.
Parameter Options Default Description
Basic Configuration
Wiring mode See Table below 4LN3 The wiring connection of the device PT ratio1
1.0-6500.0 1.0 The phase potential transformer’s primary to secondary ratio
PT Ratio multiplier ×1, ×10 ×1 PT Ratio multiplication factor. Used in
extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks.
CT primary current 1-20,000 A 5 A The primary rating of the phase
current transformer
Nominal voltage EH
10-690 V 120 V The nominal secondary line-to-neutral
or line-to-line voltage. Used as a reference voltage for the disturbance monitor.
Maximum demand load current
0-20,000 A 0 The maximum demand load current
(0 = CT primary current)
Nominal frequency 50,60,25,400 Hz 60 Hz The nominal line frequency
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 65
Parameter Options Default Description
Demand Setup
Power block demand period
E
1, 2, 3, 5, 10, 15, 20, 30, 60 min, E=external sync
15 min The length of the demand period for
power demand calculations. If the external synchronization is selected, a pulse front on the digital input DI1 denotes the start of the demand interval.
Number of blocks in sliding demand
E
1-15 1 The number of blocks to be averaged
for sliding window demands
Volt/Ampere/THD demand period
0-1800 sec 900 sec The length of the demand period for
ampere, volt and THD demand calculations
1
PT Ratio is defined as a relation of the potential transformer’s primary voltage rating to its secondary rating. For example, for the 14,400 V transformer’s primary rating and 120 V secondary rating, the PT Ratio = 14400/120 = 120.
Available wiring modes are listed in the following table.
Wiring
Mode
Description
3OP2 3-wire Open Delta using 2 CTs (2 element) 4LN3 4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings
3DIR2 3-wire Direct Connection using 2 CTs (2 element)
4LL3 4-wire Wye using 3 PTs (3 element), line-to-line voltage readings 3OP3 3-wire Open Delta using 3 CTs (2½ element) 3LN3 4-wire Wye using 2 PTs (2½ element), line-to-neutral voltage readings
3LL3 4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings
3BLN3 3-wire Broken Delta using 2 PTs, 3 CTs (2½-element), line-to-neutral
voltage readings
3BLL3 3-wire Broken Delta using 2 PTs, 3 CTs (2½-element), line-to-line voltage
readings
Ì
In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltage readings for min/max volts and volt demands represent line-to-neutral voltages; otherwise, they will be line-to-line voltages. The voltage waveforms and harmonics in 4LN3, 4LL3, 3LN3, 3LL3, 3BLN3 and 3BLL3 wiring modes represent line-to-neutral voltages; otherwise, they will be line-to-line voltages.
Device Options
This setup allows you to enable or disable optional calculations and redefine user-selectable device options.
To enter the setup dialog, select the device site from the list box on the PAS toolbar, and then select Device Options from the Meter Setup menu.
The following table lists available device options.
Parameter Options Default Description
Power Calculation Mode
S=f(P, Q) (using reactive power),
Q=f(S, P) (using non-active power)
S=f(P, Q) The method used for calculating
reactive and apparent powers (see “Power Calculation Modes” below)
Energy Roll Value 1000.0 kWh
10000.0 kWh
100000.0 kWh
1000000.0 kWh
10000000.0 kWh
100000000.0 kWh
100000000.0 The value at which energy counters roll over to zero
Chapter 4 PAS Application Software General Meter Setup
66 Series PM172 Powermeters
Parameter Options Default Description
Phase Energy Calculation
Disabled, Enabled Disabled Enables phase energy calculations
Harmonic Power/Energy Calculation
Disabled, Enabled Disabled Enables harmonic power and
energy calculations
Analog Expander Option
1
Disabled 0-20 mA 4-20 mA 0-1 mA ±1 mA
Disabled Enables outputs for the AX-8
analog expanders through port COM2. See “Programming the Analog Expander”
Backup Battery OFF = switched OFF
On = switched ON
OFF Allows to conserve a battery while
the meter is out of operation
Energy Test Mode
E
OFF = disabled Wh pulses varh pulses
Disabled Setting this op tion puts the meter
into the energy test mode
Volts Scale, V 10-828 V 144 V The maximum voltage scale
allowed, in secondary volts. See
Data Scales
in Appendix E.
Amps Scale, A
2 × nominal CT secondary current (2A, 10A)
2A/10 A The maximum current scale
allowed, in secondary amps. Not changeable. See
140HData Scales in
Appendix E.
Starting Current, %FS
0.1-2.0 0.1%FS Specifies the low current measurement limit in percent of the full scale current (1A, 5A). Available in the PM172P/E, V13.1.19 and later.
1
Do not enable the analog expander output if you do not have the analog expander
connected to the meter, otherwise it will disturb the computer communications.
150BPower Calculation Modes
The power calculation mode option allows you to change the method for calculating reactive and apparent powers in presence of high harmonics. The options work as follows:
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 67
1. When the reactive power calculation mode is selected, active and reactive powers are measured directly and apparent power is calculated as:
22
QPS +=
This mode is recommended for electrical networks with low harmonic distortion, commonly with THD < 5% for volts, and THD < 10% for currents. In networks with high harmonics, the following method is preferable.
2. When the non-active power calculation mode is selected, active power is measured directly, apparent power is taken as product S = V x I, where V and I are the RMS volts and amps, and reactive power (called non-active power) is calculated as:
22
PSN =
Transformer Correction
This setup is available in the PM172P/E with firmware V13.1.19 and later, or V13.71.12 and later.
Transformer correction allows you to compensate ratio and phase angle inaccuracies of the user voltage and current instrument transformers.
To enter the setup dialog, select the device site from the list box on the PAS toolbar, and then select Transformer Correction from the Meter Setup menu.
The following table lists available options.
Parameter Options Default Description
Ratio Correction Factor
0.900 to 1.100 1.000 The ratio of the true transformer ratio to the marked ratio.
Chapter 4 PAS Application Software General Meter Setup
68 Series PM172 Powermeters
Parameter Options Default Description
Phase Angle Error, minutes
-600 to 600
(-2700 to 2700 with V13.7X.XX)
0 The phase displacement, in
minutes, between the primary and secondary values. The phase angle of a transformer is positive when the secondary value leads the primary value.
Local Settings
This setup allows you to specify your time zone and daylight saving time options.
To configure the time zone options for your device, select the device site from the list box on the PAS toolbar, select General Setup from the Meter Setup menu, and then click on the Local Settings tab.
The available options are described in the following table:
Parameter Options Default Description
Country Default, or country
name
Default Defines calendar setting. The default
setting stands for the U.S.A.
Daylight saving time Disabled
Enabled
Disabled When DST is disabled, the RTC
operates in standard time only. When enabled, the device automatically updates the time at 2:00 AM at the
pre-defined DST switch dates. DST start month DST start week DST start weekday
Month-week­weekday
Week = 1
st
, 2nd, 3rd,
4
th
or Last (last week
of the month)
Second Sunday in March
The date when Daylight Saving Time
begins. The DST switch point is
specified by the month, week of the
month and weekday. By default, DST
starts at 2:00 AM on the second
Sunday in March of each year. DST Start Hour 1-6 2 The hour when Daylight Saving Time
begins.
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 69
Parameter Options Default Description
DST end month DST end week DST end weekday
Month-week­weekday
Week = 1
st
, 2nd, 3rd,
4
th
or Last (last week
of the month)
First Sunday in November
The date when Daylight Saving Time
ends. The DST switch point is
specified by the month, week of the
month and weekday. By default, DST
ends at 2:00 AM on the first Sunday
in November of each year. DST End Hour 1-6 2 The hour when Daylight Saving Time
ends. Time
synchronization input
None DI1 DI2
None The external port receiving the time
synchronization pulses
Daylight Saving Time
When the daylight saving time is enabled, the meter automatically advances the device clock one hour (by default at 02.00 AM) when daylight saving time begins and puts the clock back one hour (by default at 02.00 AM) when it ends. The default daylight saving time change points are preset for the U.S.A.
The daylight saving time option is disabled in the PM172 by default. If the daylight saving time option is disabled, you need to manually adjust the device clock for daylight saving time.
Time Synchronization Pulses
External time synchronization pulses can be delivered through one of the digital inputs. If a digital input is selected as the time synchronization source, the edge of an external pulse adjusts the device clock at the nearest whole minute. The time accuracy could be affected by the debounce time of the digital input, and by the operation delay of the external relay.
Using Digital Inputs
The meter is provided with two digital inputs that can trigger the alarm/control setpoints to give an alarm on input status change, or can be linked to the energy/TOU registers to count pulses from external watt meters, or gas and water meters.
To configure them in your device, select the device site from the list box on the PAS toolbar, select General Setup from the Meter Setup menu, and then click on the Digital Inputs tab.
The available options are shown in the following table.
Parameter Options Default Description
Pulse input mode
PULSE MODE, KYZ MODE
PULSE MODE
In pulse mode, either leading, or
trailing edge of the input pulse is
recognized as an event. In KYZ
mode, both leading and trailing
edges of the input pulse are
recognized as separate events.
Pulse polarity NORMAL (N.O.),
INVERTING (N.C.)
NORMAL For the normal polarity, the open
to closed transition is considered a
pulse. For the inverting polarity,
the closed to open transition is
considered a pulse.
It has no meaning in KYZ mode
where both transitions are used.
Debounce time 1-1000 ms 10 ms The amount of time while the state
of the digital input should not
change to be recognized as a new
state. Too low debounce time could
produce multiple events on the
input change.
Chapter 4 PAS Application Software General Meter Setup
70 Series PM172 Powermeters
The debounce time is used the same for both digital inputs. If you change the debounce time for one digital input, the same debounce time is automatically assigned to the other.
Using Relay Outputs
The PM172 is equipped with two relays. Each relay can be operated either locally from the alarm/control setpoints in response to an external event, or by a remote command sent through communications, and can also be linked to an internal pulse source to produce energy pulses.
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 71
The available relay options are shown in the following table:
Parameter Options Default Description
Unlatched mode: the relay goes into its active state when the control setpoint is in active (operated) state, and returns into its non-active state when the setpoint is released.
Operation mode
UNLATHCED LATCHED PULSE KYZ
UNLATCHED
Latched mode: the relay goes into its active state when the control setpoint goes into active state and remains in the active state until it is returned into its non-active state by a remote command.
Pulse mode: the relay goes into its active state for the specified time, goes into non-active state for the specified time and remains in the non-active state.
KYZ mode: the relay generates transition pulses. The relay changes its output state upon each command and remains in this state until the next command.
Polarity NORMAL
(N.O.) INVERTING
(N.C.)
NORMAL With normal polarity, the relay is
normally de-energized in its non-active state and is energized in its active (operated) state.
With inverting polarity, the relay is normally energized in its non-active state and is de-energized in its active (operated) state. It is called failsafe relay operation.
Retentive mode
NO YES
NO Applicable for latched relays.
In non-retentive mode, the relay always returns to its non-active state upon power up.
In retentive mode, the relay status is restored to what it was prior to loss of power.
Pulse width 20-1000 ms 100 ms The actual pulse width is a multiple of
the 1-cycle time rounded to the nearest bigger value.
The pause time between pulses is equal to the pulse width.
Pulse source
NONE kWh IMP kWh EXP kvarh IMP kvarh EXP kvarh TOT kVAh
NONE Links a pulse relay to the internal
energy pulse source. The relay must be set into either pulse, or KYZ mode.
Pulse rate, kWh/Pulse
0.1-1000.0
1.0 kWh/Pulse Defines the pulse weight in kWh units per pulse
Generating Energy Pulses through Relay Outputs
To generate energy pulses through a relay output:
1. Set a relay to either pulse, or KYZ mode, and then select a polarity (active pulse edge) for energy pulses and a pulse width.
2. Select a source accumulator (type of energy) and the pulse rate for your output.
3. Store your new setup to the device.
Chapter 4 PAS Application Software General Meter Setup
72 Series PM172 Powermeters
Programming Analog Inputs
The PM172 can be provided with two optional analog inputs with options for 0-1mA, ±1mA, 0-20mA or 4-20mA input currents, depending on the order. Inputs with 0-1mA and ±1mA options can accept ×200% overload currents, i.e., can actually accommodate currents in the range of 0-2 mA and ±2mA.
The meter automatically converts the analog input readings received from the analog-to-digital converter to the user-defined engineering scale and shows the input values in true engineering units, for example, in volts, amps, or degrees, with the desired resolution.
To configure the Analog Inputs in your device, select General Setup from the Meter Setup menu, and then click on the Analog Inputs tab. If you are programming your device online, analog inputs are designated as not available if they are not present in the device.
The available options are described in the following table.
Option Range Description
AI type
0-1mA ±1mA 0-20mA 4-20mA
The analog input type. When connected to the meter, shows the actual type received from the device. When working off-line, select the analog input option corresponding to your meter.
Zero scale
-999,999 to 999,999
Defines the low engineering scale (in primary units) for the analog input corresponding to a lowest (zero) input current (0 or 4 mA)
Full scale
-999,999 to 999,999
Defines the high engineering scale (in primary units) for the analog input corresponding to a highest input current (1 or 20 mA)
Dec. Places
0-3
The number of decimal digits in a fractional part of the scaled engineering value
Value label
An arbitrary name you can give the analog input value
Always save your analog inputs setup to the site database in order to keep the labels you give the analog inputs. They are not stored in your device.
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 73
Scaling Non-directional Analog Inputs
For non-directional analog inputs with the 0-1mA, 0-20mA and 4-20mA current options, provide both zero and full engineering scales. Each of the scales operates independently.
Scaling ±1mA Analog Inputs
For directional ±1mA analog inputs, you should provide only the engineering scale for the +1 mA input current. The engineering scale for the 0 mA input current is always equal to zero. The device does not allow you to access this setting. Whenever the direction of the input current is changed to negative, the device automatically uses your full engineering scale settings for +1 mA with a negative sign.
Scaling Analog Inputs for 0-2 mA and ±2 mA
The input scales for 0-1 mA and ±1 mA analog inputs are always programmed for 0 mA and +1 mA regardless of the desired input range. If you want to use the entire input range of 2 mA or ±2 mA, set the analog input scales in your device as follows:
0-2 mA: set the 1 mA scale to 1/2 of the required full scale output for uni-directional parameters, and set the 0 mA scale to the negative full scale and the 1 mA scale to zero for bi-directional parameters.
±2 mA: set the 1 mA scale to 1/2 of the required full-scale output for both uni-directional and bi-directional parameters.
For example, to convert voltage readings from the analog transducer that transmits them in the range of 0 to 2 mA to the range 0 to 120V, set the full range for the +1 mA analog input to 60V; then the 2 mA reading is scaled to 120V.
Programming Analog Outputs
The meter can be ordered with two optional analog outputs with options for 0-1mA, ±1mA, 0-20mA or 4-20mA output currents.
The 0-1mA and ±1mA current outputs provide a 100% overload, and actually output currents up to 2 mA and ±2mA whenever the output value exceeds the engineering scale set for the 1 mA or ±1mA.
To configure the Analog Outputs in your device, select General Setup from the Meter Setup menu, and then click on the Analog Outputs tab. If you are programming your device online, analog outputs are designated as not available if they are not present in the device.
The available analog output options are described in the following table.
Option Range Description
AO type
0-1mA ±1mA 0-20mA 4-20mA
The analog output type. When connected to the meter, shows the actual AO type read from the device. When working off-line, select the analog output option corresponding to your meter.
Output parameter
See Appendix B
Selects the measured parameter to be transmitted through the analog output channel.
Zero scale
Defines the low engineering scale (in primary units) for the analog output corresponding to a lowest (zero) output current (0 or 4 mA)
Full scale
Defines the high engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA)
Chapter 4 PAS Application Software General Meter Setup
74 Series PM172 Powermeters
When you select an output parameter for the analog output channel, the default engineering scales are set automatically. They represent the maximum available scales. If the parameter actually covers a lower range, you can change the scales to provide a better resolution on the analog outputs.
Scaling Non-directional Analog Outputs
When programming scales for non-directional analog outputs with a 0-1mA, 0-20mA or 4-20mA current option, you can change both zero and full engineering scales for any parameter. The engineering scale need not be symmetrical.
Scaling Directional Power Factor
The engineering scale for the signed power factor emulates analog power factor meters. The power factor scale is -0 to +0 and is symmetrical with regard to
±1.000 (-1.000 +1.000). Negative power factor is scaled as
-1.000 minus measured value, and non-negative power factor is scaled as
+1.000 minus measured value. To define the entire power factor range from
-0 to +0, the default scales are specified as -0.000 to 0.000.
Scaling ±1mA Analog Outputs
Programming engineering scales for directional ±1mA analog outputs depends on whether the output parameter represents unsigned (as volts and amps) or signed (as powers and power factor) values.
If the output value is unsigned, you can change both zero and full engineering scales.
If the parameter represents a signed (directional) value, you should provide only the engineering scale for the +1 mA output current. The engineering scale for the 0 mA output current is always equal to zero for all values except the signed power factor, for which it is set to 1.000 (see “Scaling Directional Power Factor” above). The device does not allow you access to this setting if the parameter is directional. Whenever the sign of the output parameter is changed to negative, the device automatically uses your full engineering scale settings for +1 mA with a negative sign.
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 75
Scaling Analog Outputs for 0-2 mA and ±2 mA
The output scales for 0-1 mA and ±1 mA analog outputs are programmed for 0 mA and +1 mA regardless of the desired output current range. To use the entire output range of 2 mA or ±2 mA, set the analog output scales in your device as follows:
0-2 mA: set the 1 mA scale to 1/2 of the required full scale output for uni­directional parameters, and set the 0 mA scale to the negative full scale and the 1 mA scale to zero for bi-directional parameters.
±2 mA: set the 1 mA scale to 1/2 of the required full-scale output for both uni-directional and bi-directional parameters.
For example, to provide the 0 to 2 mA output current range for volts measured by the meter in the range of 0 to 120V, set the 1 mA scale to 60V; then the 120V reading will be scaled to 2 mA.
Programming the Analog Expander
Your meter can support up to two analog expanders that are connected through a serial RS-422 interface to the meter port COM2. Each expander has its own address 0 or 1 on the serial interface and provides 8 analog channels with options for 0-1mA, ±1mA, 0-20mA or 4-20mA output currents.
To configure the Analog Expander outputs in your device, select General Setup from the Meter Setup menu, and then click on the Analog Expander tab.
The expanded analog outputs are enumerated in the following manner: analog output channels 1 through 8 are associated with the analog expander with address 0, while channels 9 through 16 are associated with the analog expander with address 1.
The available analog expander outputs options are described in the following table.
Chapter 4 PAS Application Software General Meter Setup
76 Series PM172 Powermeters
Option Range Description
Output parameter
See Appendix B
Selects the measured parameter to be transmitted through the analog output channel.
Zero scale
Defines the low engineering scale (in primary units) for the analog output corresponding to a lowest (zero) output current (0 or 4 mA)
Full scale
Defines the high engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA)
Before entering the setup dialog, ensure that you selected the correct analog current option for your expander on the Instrument Setup tab in the Tools/Configuration dialog. For scaling output parameters, see “Programming Analog Outputs” above.
Ì Analog expander outputs are not operational until you globally enable the analog
expander option in your meter through the Device Options menu.
Using Counters
The meter provides four six-digit counters that count different events.
To configure the device counters, select General Setup from the Meter Setup menu, and then click on the Pulse/Event Counters tab.
Each counter is independently linked to any digital input and count input pulses with a programmable scale factor. Each counter can also be incremented in response to any internal or external event, checked and cleared through the Control Setpoints.
The following table lists available options.
Option Range Default Description
Pulse Input None,
DI1-DI2
None Links a digital input to the counter
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 77
Option Range Default Description
Multiplier 1-9999 1 The value added to the counter
when a pulse is detected on the pulse source input
Counter Value Displays the present counter
contents
You can preset a counter to a desired value or clear it through this dialog without affecting the counter setup. Check the Online button on the PAS toolbar before entering the setup dialog, type in the desired value into the Counter Value box, and then click Send.
Using Periodic Timers
The PM172E and PM172EH provide two programmable interval timers that can be used for periodic recording and triggering operations on a time basis through the Control Setpoints. When a pre-programmed timer interval expires, the timer generates an internal event that can trigger any setpoint (see “Using Alarm/Control Setpoints”).
To configure the device timers, select General Setup from the Meter Setup menu, and then click on the Periodic Timers tab.
To run a periodic timer, specify a non-zero time period for the timer. The time period can be set from 1 to 9999 seconds.
To stop a timer, set the time period to zero.
Using Control Setpoints
The PM172 has an embedded logical controller that runs different actions in response to user-defined internal and external events. Unlike a PLC, the meter uses a simplified programming technique based on setpoints that allows the user to define a logical expression based on measured analog and digital values that produce a required action.
Chapter 4 PAS Application Software General Meter Setup
78 Series PM172 Powermeters
The meter provides 16 control setpoints with programmable operate and release delays. Each setpoint evaluates a logical expression with up to four arguments using OR/AND logic. Whenever an expression is evaluated as “true”, the setpoint performs up to four concurrent actions that can send a command to the output relays, increment or decrement a counter, or trigger a recorder.
The logical controller provides very fast response to events. The scan time for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400 Hz).
To program the setpoints, select General Setup from the Meter Setup menu, and then click on the Control/Alarm Setpoints tab.
The available setpoint options are described in the following table.
Option Range Description
Triggers
OR/AND
OR, AND
The logical operator for the trigger
Trigger parameter
See Appendix C
The trigger parameter that is used as an argument in the logical expression
Operate limit
The threshold (in primary units) at which the conditional expression would be evaluated to true. Not applicable for digital triggers.
Release limit
The threshold (in primary units) at which the conditional expression would be evaluated to false. Defines the hysteresis for analog triggers. Not applicable for digital triggers.
Actions
Action
See Appendix C
The action performed when the setpoint expression is evaluated to true (the setpoint is in operated state)
Delays
Operate delay
0.1-999.9 sec
The time delay before operation when the operate conditions are fulfilled
Release delay
0.1-999.9 sec
The time delay before release when the release conditions are fulfilled
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 79
Setpoint #1 is factory preset to provide standard periodic data logs on a 15­minute time basis. It is linked to the device clock and runs data logs #1 and #2 at 15-minute boundaries of an hour.
Using Logical Expressions
Logical operators OR/AND are treated in a simplified manner. They have no specific priority or precedence rules.
Any trigger condition bound to the logical expression by the OR operator and evaluated as “true” will override any preceding condition evaluated as “false”. Similarly, any trigger condition evaluated as “false” and bound by the AND operator will override any condition evaluated before it as “true”.
To avoid confusion, it is recommended not to alternate different logical operators in one expression. Instead, bring all conditions that use the same logical operator together at one side of the expression, and the others - at the opposite side.
To explicitly override all other conditions with the critical trigger, put it at the end of the expression using the OR operator if you want the setpoint to be operated anyway when the trigger condition is asserted, and with the AND operator, if the setpoint should not be operated while the critical trigger is not asserted.
Using Numeric Triggers
For numeric (analog) triggers, a setpoint allows you to specify two thresholds for each trigger to provide hysteresis (dead band) for setpoint operations. The Operate Limit defines the operating threshold, and the second Release Limit defines the release threshold for the trigger. The trigger thresholds are specified in primary units.
If you do not want to use hysteresis for the trigger, set the Release Limit to the same as the Operate Limit.
Using Binary Triggers
Binary (digital) triggers, like digital inputs, relays, or internal static and pulsed events, are tested for ON (closed/set) or OFF (open/cleared) status.
The binary events are divided into two types: static events and pulsed events. Static events are level-sensitive events. A static event is asserted all the time while the corresponding condition exists. Examples are digital inputs, relays and event flags.
Pulsed events are edge-sensitive events with auto-reset. A pulsed event is generated for a trigger only once when a positive transition edge is detected on the trigger input. The examples of pulsed events are pulse inputs (transition pulses on the digital inputs), internal pulsed events (energy pulses and time interval pulses), and events generated by the interval timers. The logical controller automatically clears pulsed events at the end of each scan, so that triggers that used pulsed events are prevented from being triggered by the same event once again.
Using Event Flags
The PM172EH provides 8 common binary flags, called event flags, which can be individually set, cleared and tested through setpoints and via communications.
Event flags can be used in different applications, for example, to transfer events between setpoints in order to expand a logical expression or a list of actions that have to be done for a specific event, or to externally trigger setpoint actions from the SCADA system or from a PLC through communications.
Using Interval Timers
The PM172E and PM172EH provide two interval timers that are commonly used for periodic recording of interval data at the time of the fault or in the presence of other events detected by a setpoint. The timers can be
Chapter 4 PAS Application Software General Meter Setup
80 Series PM172 Powermeters
programmed to generate periodic events at user-defined intervals (see “Using Periodic Timers”).
Interval timers are not synchronized with the clock. When you run a timer, it generates a pulsed event that can trigger a setpoint if you have put the timer into a list of the setpoint triggers. When the setpoint event is asserted, the timer is restarted, and then generates the next event when the timer interval expires.
If you want to record interval data at predefined intervals without linking to other events, just select a timer as a setpoint trigger and specify a data log file you want to use for recording, in the setpoint actions list. If you want the periodic data to be recorded in presence of a specific event, select triggers that will identify your event, and then add the timer at the end of the trigger list using the AND operator.
Using Time Triggers
If you want the setpoint actions to be synchronized with the clock, for example, to provide synchronous recording interval data each 15 minutes or each hour, or to output time pulses through relay contacts, use the time triggers that generate static events synchronized to the device clock.
You can exercise the default setting for Setpoint #1 in your device as an example of using time triggers. The setpoint is pre-programmed for data profiling at 15-minute intervals using data logs #1 and #2.
Using the Voltage Disturbance Trigger
The PM172EH provides the voltage disturbance trigger (found under the VOLT DISTURB name) that detects all types of the voltage waveshape faults on any phase caused by fast transient voltages. You can use it for recording disturbances.
The operate threshold for the voltage disturbance trigger defines the maximum allowable voltage deviation from the steady-state level above which the device will declare a waveshape fault. By default, it is specified as a percent of the nominal device voltage. If you wish to use volts units instead, you can select the desired voltage disturbance units from the Preferences tab in the Tools/Options/Preferences dialog.
Ì
The voltage waveforms in 4LN3, 4LL3, 3LN3, 3LL3, 3BLN3 and 3BLL3
wiring modes represent line-to-neutral voltages; otherwise, they will be line­to-line voltages. Take it into account when specifying the nominal device voltage that is used as a reference for the disturbance trigger.
The trigger does not respond to slow voltage variations whenever the voltage rise above or drop below the specified threshold takes longer than 1 cycle time.
Delaying Setpoint Operations
Two optional delays can be added to each setpoint to extend monitoring setpoint triggers for a longer time before making a decision on whether the expected event occurred or not. When a delay is specified, the logical controller will change the setpoint status only if all conditions are asserted for a period at least as long as the delay time.
Note that you cannot use delays with pulsed events since they are cleared immediately and will no longer exist on the next setpoint scan.
Using Setpoint Events and Actions
When a setpoint status changes, i.e., a setpoint event is either asserted or de-asserted, the following happens in your device:
1. The new setpoint status is logged to the setpoint status register that can be monitored through communications from the SCADA system or from a programmable
Chapter 4 PAS Application Software General Meter Setup
Series PM172 Powermeters 81
controller in order to give an indication on the expected event.
2. The operated setpoint status is latched to the setpoint alarm latch register accessible through communications. The register holds the last setpoint alarm status until it is explicitly cleared through communications.
3. Up to four programmable actions can be performed in sequence on setpoint status transition when a setpoint event is asserted.
Generally, setpoint actions are performed independently for each setpoint and can be repeated a number of times for the same target. The exceptions are relay operations, data logging and waveform logging that are shared for each separate target between all setpoints using an OR scheme.
A relay output is operated when one of the setpoints linked to the relay is activated and will stay in the operated state until all of these setpoints are released (except for latched relays that require a separate release command to be deactivated).
Data logging and waveform logging directed to the same file are done once for the first setpoint among those that specify the same action, guaranteeing that there will not be repeated records related to the same time.
Recording Setpoint Events
Time-tagged setpoint events can be recorded to the device Event Log if you put a corresponding action into the setpoint action list. The Event Recorder will log any setpoint transition event: both when the setpoint is operated, and when it is released. The Event Recorder will put into a log file a separate record for each active trigger caused a setpoint status transition, and a separate record for each action done on the setpoint activation (except for data logging actions that are not recorded to the Event Log).
Chapter 4 PAS Application Software Configuring Summary Energy and TOU Registers
82 Series PM172 Powermeters
Configuring Summary Energy and TOU Registers
The PM172E and PM172EH provide 8 total (summary) energy and 8 concurrent tariff energy and maximum demand registers that can be linked to any internal energy source or to any external pulse source that delivers pulses through the device digital inputs.
The meter tariff structure supports 8 different tariffs using an arbitrary tariff schedule. A total of 4 types of days and 4 seasons are supported with up to eight tariff changes per day.
The meter can provide automatic daily profile recording for total and tariff energy and maximum demand registers.
By default, the billing registers in your meter and the tariff system are not operational. To activate the summary/tariff registers or to change the profile for the first billing register:
1. Link the billing registers to the respective energy sources, and then configure the options for these registers like whether the only totalization or both total and tariff registers would be used, and whether daily profiling should be enabled for the energy usage and maximum demand registers.
2. Configure the daily tariff schedule using the TOU daily profiles for all types of days and seasons.
3. Configure the season tariff schedule using the TOU calendar.
Setting up Total and Tariff Registers
To configure the device total (summary) and TOU registers, select Energy/TOU from the Meter Setup menu.
Chapter 4 PAS Application Software Configuring Summary Energy and TOU Registers
Series PM172 Powermeters 83
The available options are shown in the following table:
Parameter Options Default Description
Summary/TOU Registers
TOU Unchecked
Checked
Unchecked Links tariff registers to the selected
energy source
Use Profl Unchecked
Checked
Unchecked Enables automatic daily profiling for
energy usage registers (both total and tariff registers if TOU is enabled)
Dmd Profl Unchecked
Checked
Unchecked Enables automatic daily profiling for
maximum demand registers (both total and tariff registers if TOU is enabled)
Sum Profl Unchecked
Checked
Unchecked Enables daily profiling for summary
registers (total of all tariffs)
Units kWh, kvarh, kVAh,
m3, CF (cubic foot), CCF (hundred cubic feet)
None The register measurement units. When
a register is linked to an internal energy source, it is set automatically. When an external pulse source is used, the user can select a measurement unit for the register.
Register Source List
Source Input
None kWh Import kWh Export kvarh Import kvarh Export kVAh,
DI1-DI2
None Links an energy source to the register
Multiplier 0.001 to 100.000 1.000 The multiplication factor for the energy
source.
Target Reg#1- Reg#8 None Defines the target billing register for the
energy source. It is set automatically.
Configuring the Daily Tariff Schedule
To configure your daily tariff schedule, select Energy/TOU from the Meter Setup menu, and then click on the TOU Daily Profiles tab.
The daily profile setup allows you to specify the daily tariff change points with a 15-minute resolution for 4 seasons using 4 different daily schedules for each season.
To configure your daily profiles:
1. Select the desired season and day type.
2. Select the start time for each tariff change point and the corresponding active tariff number.
3. Repeat the setup for all active profiles.
The first tariff change point is fixed at 00:00 hours, and the last tariff change you specified will be in use until 00:00 hours on the next day.
The energy daily profile log will be automatically configured for the number of active tariffs you defined in the meter TOU daily profile.
Chapter 4 PAS Application Software Configuring Summary Energy and TOU Registers
84 Series PM172 Powermeters
Configuring the Season Tariff Schedule
To configure your season tariff schedule, select Energy/TOU from the Meter Setup menu, and then click on the TOU Calendar tab.
The meter’s TOU calendar allows you to configure any tariff schedule based on any possible utility regulation. The calendar itself has 32 entries that allow you to specify profiles for working days and holidays through all seasons in any order that is convenient for you, based on simple intuitive rules. There
Chapter 4 PAS Application Software Configuring Summary Energy and TOU Registers
Series PM172 Powermeters 85
are no limitations on how to define your schedule. The meter is able to automatically recognize your settings and to select a proper daily tariff schedule for any day within a year.
The above picture gives you an example of a single-season tariff schedule configured for weekends and the designated U.S.A. holidays.
To configure your season tariff schedule:
1. In the “Season” box, select the season, and in the “Day Type” box, select a day type for this calendar entry.
2. Select the time interval when this daily tariff schedule is effective, based on the start and the end weekdays and, for a multi-season schedule, on the start and the end month for the selected season. It does not matter which order of weekdays or months you select: the meter can recognize the correct order by itself.
3. For exception days like designated holidays, select a specific day either by specifying a day and month, or by selecting a month, a week and a weekday within the month.
Chapter 4 PAS Application Software Configuring Recorders
86 Series PM172 Powermeters
Configuring Recorders
The PM172E and PM72EH are provided with a 1-Megabyte onboard non­volatile memory for data, event and waveform recording.
Before using recorders, the device memory should be partitioned between log files. The device memory is fully configurable. You can define how much memory to allocate for each log file. If you want to change the factory settings, follow the guidelines in the section below.
Configuring Device Memory
The device memory can be partitioned for a total of 11 log files:
Event Log
8 Data Logs
2 Waveform Logs
To view the present device memory settings, select Memory/Log from the Meter Setup menu, and then click on the Log Memory tab.
The following table lists available file options.
Option Range Description
Type
WRAP AROUND NON-WRAP DAYLY PRF
Defines the file behavior when it is filled up. WRAP AROUND: recording continues over the oldest records. NON-WRAP: recording is stopped until the file is cleared. DAILY PRF: daily TOU profile data log (only for Data Log #8).
Size
The memory size allocated to the file. Set automatically depending on the size of the records and the number of records in the file.
Sections/Channels
0-14
The numbers of sections in a multi-section TOU profile data log file, or the number of recording channels in a waveform log file
Num. of Records
0-65535
Allocates the file memory for predefined number of records
Record size
The size of the file record for a single channel or a section. Set automatically depending on the file and on the number of parameters in the data record
Parameters
0-16
The number of parameters in a single data record
Memory is allocated for each file statically when you set up your files and will not change unless you re-organize the files. The meter automatically
Chapter 4 PAS Application Software Configuring Recorders
Series PM172 Powermeters 87
performs de-fragmentation of the memory each time you re-organize your files. This helps keep all free memory in one continuous block and thus prevents possible leakage of memory caused by fragmentation.
To change the file properties or to allocate the memory for a new file, double click on the file partition you want to change, select desired parameters for your log, and then click OK. For your reference, the record size and the number of records available for your file are reported in the dialog box.
To delete an existing file partition, click on Delete and then click OK.
The following table shows how to calculate a file size for different log files.
File Record Size, Bytes File Size, Bytes
Event Log 16 Record size x Number of records Data Log 8 + 4 x Number of parameters Record size x Number of records TOU Profile Data Log
#8
8 + 4 x (Number of season tariffs (+ 1 if the TOU summary register is also ordered))
Record size x Number of TOU registers x Number of records (x 2 if the maximum demand profile is also ordered)
Waveform Log 1040 (per channel) Record size x 6 x Number of series
(events) x Number of records per series
For more information on configuring specific files, see “Configuring Data Log Files” and “Configuring Waveform Files” below.
The memory is pre-configured for common data trending and fault recording applications as shown in the following table.
No. File Type Size,
Bytes
Channels Number of
Records
Number of
Events
Description
1 Event log Wrap around 16000 1000 1000 2 Data log #1 Wrap around 103680 1440 1440 Configured for
data trending
3 Data log #2 Wrap around 103680 1440 1440 Configured for
data trending 18 Waveform log #1 Wrap around 249600 6 40 40 19 Waveform log #2 Wrap around 124800 6 20 20
Configuring the Event Recorder
To configure the Event Log file:
1. Double click on the Event Log file partition with the left mouse button.
2. Select a file type for your file.
3. Select the maximum number of records you want to be recorded in the file.
Chapter 4 PAS Application Software Configuring Recorders
88 Series PM172 Powermeters
4. Click OK, and then send your new setup to the meter or save to the device database.
By default, the Event Recorder stores all events related to configuration changes, reset, and device diagnostics. In addition, it records events related to setpoint operations. Each setpoint should be individually enabled for recording to the Event Log.
To log setpoint operations, add the “Event log” action to the setpoint actions list. When a setpoint event happens, the Event Recorder logs all setpoint conditions that caused the event and all setpoint actions performed in response to the event. Logging actions themselves will not be recorded to the Event Log.
Configuring the Data Recorder
The Data Recorder is programmable to record up to 16 data parameters per record in each of 8 data log files. The list of parameters to be recorded to a data log is configured individually for each file.
Conventional Data Log Files
To create a new data log file or re-configure an existing file:
1. Double click on the file partition with the left mouse button.
2. Select a file type for your file.
3. Select the number of parameters you want to be recorded in the file records.
4. Select the maximum number of records you want to be recorded in the file.
5. Click OK, and then send your new setup to the meter, or save to the device database.
6. Highlight the data log file row with the left mouse button, and then click on the “Setup Recorder” button, or click on the “Data Recorder” tab and select the log number corresponding to your file.
7. Configure the list of parameters to be recorded in your data log file. You are not allowed to select more parameters than you defined when configuring your file. Refer to Appendix D for a list of available parameters.
For your convenience, PAS will follow your selection and help you to configure a series of the neighboring parameters: when you open the “Group” box for the next parameter, PAS highlights the same group as in your previous selection; if you select this group again, PAS will
Chapter 4 PAS Application Software Configuring Recorders
Series PM172 Powermeters 89
automatically update the “Parameter” box with the following parameter in the group.
8. Add the name for your data log file in the “Name” box. It will appear in the data log reports.
9. Save your new setup to the device database, and send it to the meter.
Factory Preset Periodic Data Logs
Data logs #1 and #2 are factory preset for periodic recording of the standard power quantities as shown in the following table.
No. Parameter No. Parameter
Data Log #1
1 V1/V12 9 Total kVA 2 V2/V23 10 Total PF 3 V3/V31 11 V1/V12 THD 4 I1 12 V2/V23 THD 5 I2 13 V3/V31 THD 6 I3 14 I1 THD 7 Total kW 15 I2 THD 8 Total kvar 16 I3 THD
Data Log #2
1 V1/V12 Demand 9 KVA Sliding Demand 2 V2/V23 Demand 10 kWh Import 3 V3/V31 Demand 11 kWh Export 4 I1 Demand 12 kvarh Import 5 I2 Demand 13 kvarh Export 6 I3 Demand 14 kVAh 7 kW Import Sliding Demand 15 In 8 kvar Import Sliding Demand 16 Frequency
TOU Profile Data Log Files
Data Log #8 is configurable to store TOU daily profile log records on a daily basis.
A TOU profile log file is organized as a multi-section file that has a separate section for each TOU energy and maximum demand register. The number of sections is taken automatically from the Summary/TOU Registers setup (see “Configuring Summary and TOU Registers”). I f you selected to profile TO U
Chapter 4 PAS Application Software Configuring Recorders
90 Series PM172 Powermeters
maximum demands along with energy registers, then the number of sections in the file will be twice the number of the allocated TOU registers.
To configure a TOU daily profile log file:
1. Configure your TOU registers and TOU schedule in the meter before allocating memory for the profile log file (see “Configuring Summary and TOU Registers”) .
2. Double click on the DATA LOG #8 partition with the left mouse button.
3. Select the TOU Daily profile file type for your file.
4. Select the number of season tariffs in your TOU schedule. Add one additional parameter if you selected to record the Summary (TOU total) registers as well.
5. Select the maximum number of records you want to be recorded in the file assuming that a new record will be added once a day.
6. Click OK and send your setup to the meter or save to the database.
Configuring the Waveform Recorder
Waveform log files are organized as multi-section files that store data for each recording channel in a separate section. A waveform log file stores 6 channels simultaneously: three voltage and three current channels.
A single waveform record for a channel contains 512 points of the sampled input signal. If a waveform log is configured to record more samples per event than a single record can hold, the waveform recorder stores as many records per event as required to record the entire event. All waveform records related to the event are merged in a series and have the same series number, so that they can be plotted together.
The PM172EH supports two waveform files that record waveforms at two fixed sampling rates:
Waveform Log #1 – at 32 samples/cycle
Waveform Log #2 – at 128 samples/cycle
To configure a waveform log file:
1. Double click on a waveform log partition with the left mouse button.
2. Select a file type for your file.
3. Select the maximum number of records you want to be recorded in the file.
The number of records in the waveform log file needed to store one waveform event (series) is defined as follows:
Chapter 4 PAS Application Software Configuring Recorders
Series PM172 Powermeters 91
Number of Records per Series = Sampling Rate (Samples per Cycle) x Number of Cycles per Event / 512
The total number of records you must allocate to store the required number of events (series) is defined as follows:
Number of Records = Number of Records per Series x Number of Series
For example, if you want to record a 64-cycle waveform sampled at a rate of 32 samples per cycle, the number of records required for one waveform series would be:
Number of Records per Series = (32 x 64)/512 = 4.
If you want to allocate space sufficient to store 20 waveform events (series), you should set up the waveform log file for 4 x 20 = 80 records.
4. Click OK, and send your setup to the meter or save to the database.
5. Click “Setup Recorder”, or click on the “Waveform Recorder” tab.
Chapter 4 PAS Application Software Configuring Recorders
92 Series PM172 Powermeters
The following table lists available waveform options.
Option Format/Range Description
Samples per Cycle
32, for Waveform Log #1 128, for Waveform Log #2
Fixed for the file
Cycles per Series
16-2560 (32 samples/cycle), 4-640 (128 samples/cycle)
Defines the total duration of the waveform per event/series
Before Cycles
1-20
Defines the number of cycles to be recorded prior to event
Num. of Channels
6
Fixed. Shows the number of the simultaneously recorded channels
6. Select the number of cycles to be recorded prior to the event, and a total number of cycles in the waveform.
7. Add the name for your waveform log file in the “Name” box. It will appear in the waveform reports.
8. Save you waveform setup to the device database, and send it to the meter.
Chapter 4 PAS Application Software Configuring Communication Protocols
Series PM172 Powermeters 93
Configuring Communication Protocols
This section describes how to customize protocol options for use with your application software.
Configuring Modbus
Modbus Point Mapping
The PM172 provides 120 user assignable registers in the address range of 0 to 119. You can re-map any register available in the meter to any assignable register so that Modbus registers that reside at different locations may be simply accessed using a single request by re-mapping them to adjacent addresses.
Initially these registers are reserved and none of them points to an actual data register. To build your own Modbus register map:
1. Select Protocol Setup from the Meter Setup menu and click on the Modbus Registers tab.
2. Click on the Default button to cause the assignable registers to reference the actual default meter register 6656 (0 through 119 are not allowable register addresses for re-mapping).
3. Type in the actual addresses you want to read from or write to via the assignable registers. Refer to the PM172 Modbus Reference Guide for a list of the available registers. Notice that 32-bit Modbus registers should always start at an even register address.
4. Click Send to download your setup to the meter.
Chapter 4 PAS Application Software Configuring Communication Protocols
94 Series PM172 Powermeters
Configuring DNP3
DNP Options can be changed both via DNP3 and Modbus. Refer to the PM172 DNP3 Reference guide for information on the protocol implementation and a list of the available data points.
DNP Options
To view or change the factory-set DNP options, select Protocol Setup from the Meter Setup menu and click on the DNP Options tab.
The following table describes available DNP options. Refer to the DNP3 Data Object Library document available from the DNP User’s Group on the DNP3 object types.
Parameter Options Default Description
Binary Inputs (BI)
Number of BI to Generate events
0-64 3 0 The total number of BI change event
points for monitoring
Binary Input Object
Single-bit With Status
Single-bit The default BI object variation for
requests with qualifier code 06 when no specific variation is requested
Binary Input Change Event Object
Without Time With Time
With Time The default BI change event object
variation for requests with qualifier code 06 when no specific variation is requested
Analog Inputs (AI)
Number of AI to Generate events
0-64 3 32 The total number of AI change event
points for monitoring
Analog Input Object
32-bit 32-bit –Flag 16-bit 16-bit –Flag
16-bit -Flag The default AI object variation for
requests with qualifier code 06 when no specific variation is requested
Chapter 4 PAS Application Software Configuring Communication Protocols
Series PM172 Powermeters 95
Parameter Options Default Description
Analog Input Change Event Object
32-bit -Time 32-bit +Time 16-bit -Time 16-bit +Time
16-bit +Time The default AI change event object
variation for requests with qualifier code 06 when no specific variation is requested
Binary Counters (BC)
Number of BC to Generate events
0-64
3
0 The total number of BC change event
points for monitoring
Binary Counter Object
32-bit +Flag 32-bit –Flag 16-bit +Flag 16-bit –Flag
32-bit -Flag The default BC object variation for
requests with qualifier code 06 when no specific variation is requested
Binary Counter Change Event Object
32-bit -Time 32-bit +Time 16-bit -Time 16-bit +Time
32-bit +Time The default BC change event object
variation for requests with qualifier code 06 when no specific variation is requested
Frozen Binary Counter Object
32-bit +Flag 32-bit –Flag 32-bit +Time 16-bit +Flag 16-bit –Flag 16-bit +Time
32-bit -Flag The default frozen BC object variation
for requests with qualifier code 06 when no specific variation is requested
DNP General Options
16-bit AI Scaling
Disabled Enabled
Enabled Allows scaling 16-bit analog input
objects (see description below)
16-bit BC Scaling
x1, x10, x100, x1000
x1 Allows scaling 16-bit binary counter
objects (see description below)
Re-mapping Event Points
Disabled Enabled
Disabled Allows re-mapping event points starting
with point 0.
SBO Timeout 1
2-30 sec
10 Defines the Select Before Operate
(SBO) timeout when using the Control­Relay-Output-Block object
Time Sync Period
2
0-86400 sec
86400 Defines the time interval between
periodic time synchronization requests
Multi Fragment Interval
5-500 ms
50 Defines the time interval between
segments of the response message when it is fragmented
1
The Select Before Operate command causes the device to start a timer. The following Operate command must be sent before the specified timeout value expires.
2
The device requests time synchronization by bit 4 in the first octet of the internal indication word being set to 1 when the time interval specified by the Time Sync Period elapses. The master should synchronize the time in the device by sending the Time and Date object to clear this bit. The device does not send time synchronization requests if the Time Sync Period is set to 0.
3
The total number of AI, BI and BC change event points may not exceed 64. When
you change the number of the change event points in the device, all event setpoints are set to defaults (see Configuring DNP Event Classes below).
Scaling 16-bit AI objects
Scaling 16-bit AI objects allows accommodating native 32-bit analog input readings to 16-bit object format; otherwise it may cause an over-range error if the full-range value exceeds a 16-bit point limit.
Scaling is enabled by default. It is not applied to points that are read using 32-bit AI objects.
Refer to the PM172 DNP3 Reference Guide for information on the data point scales and on a reverse conversion that should be applied to the received scaled values.
Scaling 16-bit Binary Counters
Scaling 16-bit Binary Counters allows changing a counter unit in powers of 10 to accommodate a 32-bit counter value to 16-bit BC object format.
Chapter 4 PAS Application Software Configuring Communication Protocols
96 Series PM172 Powermeters
If the scaling unit is greater than 1, the counter value is reported being divided by the selected scaling unit from 10 to 1000. To get the actual value, multiply the counter reading by the scaling unit.
Configuring DNP Class 0
The most common method of getting static object information from the meter via DNP is to issue a read Class 0 request.
The PM172 allows you to configure the Class 0 response by assigning ranges of points to be polled via Class 0 requests.
To view or change the factory-set DNP Class 0 assignments, select Protocol Setup from the Meter Setup menu and click on the DNP Class 0 Points tab.
The factory-set Class 0 point ranges are shown in the picture below. To change the factory settings and build your own Class 0 response message:
1. Select the object and variation type for a point range.
2. Specify the start point index and the number of points in the range. Refer to the PM172 DNP3 Reference Guide for available data points.
3. Repeat these steps for all point ranges you want to be included into the Class 0 response.
4. Click Send to download your setup to the meter.
Configuring DNP Event Classes
The PM172 can generate object change events for any static analog input, binary input and binary counter point when a corresponding point either exceeds a predefined threshold, or the point status changes. A total of 64 change event points are available for monitoring.
Object change events are normally polled via DNP Class 1, Class 2 or Class 3 requests. You can link any change event point to any event class upon the event priority. Refer to the PM172 DNP3 Reference Guide for more information on polling event classes via DNP.
A change event point index is normally the same as for the corresponding static object point. If you wish to use independent numeration for event
Chapter 4 PAS Application Software Configuring Communication Protocols
Series PM172 Powermeters 97
points, enable re-mapping event point indices via DNP Options setup (see above) so they would start with index 0.
You should define a separate event setpoint for each static object point you wish to be monitored for change events. To view or change the factory-set DNP event setpoints, select Protocol Setup from the Meter Setup menu and click on the DNP Event Setpoints tab.
The number of event setpoints for each static object type is specified via the DNP Options setup (see above). Notice that the device clears all event buffers and links the default set of static points to each event object type every time you change the number of points for any of the objects.
To define setpoints for selected static points:
1. Check the “Ext” box if you wish to use the extended point list.
2. Select a parameter group and then a desired parameter for each event point.
3. For AI and BC points, select a relation and an operating threshold or a deadband to be used for detecting events. All thresholds are specified in primary units. The following relations are available:
Delta – a new event is generated when the absolute
value of the difference between the last reported point value and its current value exceeds the specified deadband value;
More than (over) - a new event is generated when the
point value rises over the specified threshold, and then when it returns below the threshold minus a predefined return hysteresis – applicable for AI objects;
Less than (under) - a new event is generated when
the point value drops below the specified threshold, and then when it returns above the threshold plus a predefined return hysteresis – applicable for AI objects.
Chapter 4 PAS Application Software Configuring Communication Protocols
98 Series PM172 Powermeters
A hysteresis for the return threshold is 0.05 Hz for frequency and 2% of the operating threshold for all other points.
4. Check the “Ev On” box for the points you wish to be included into event poll reports.
5. In the “Ev Class” box, select the event poll class for the change event points.
6. Repeat these steps for all points you want to be monitored for events.
Click Send to download your setup to the meter.
Chapter 4 PAS Application Software Remote Device Control
Series PM172 Powermeters 99
Remote Device Control
This section describes online operations on the meter you can perform through PAS. To access device control options you should have your device online.
Remote Relay Control
PAS allows you to send a command to any relay in your device or release a latched relay, except of the relays that are linked to an internal pulse source. These relays cannot be operated outside of the device.
To enter the Remote Relay Control dialog, check the On-line button on the PAS toolbar, select Device Control from the Monitor menu, and then click on the Remote Relay Control tab.
To send a remote command to the relay:
1. From the “Relay Command” box for the relay, select the desired command:
OPERATE – to operate a relay RELEASE - to remove your remote command, or to release a latched
relay
2. Click on Send.
Event Flags
The PM172EH provides 8 common event flags that are intended for use as temporary event storage and can be tested and operated from the control setpoints. You can transfer an event to the setpoint and trigger its operation remotely by changing the event status through PAS.
To enter the Event Flags dialog, check the On-line button on the PAS toolbar, select Device Control from the Monitor menu, and then click on the Event Flags tab.
To change the status of an event flag:
1. From the “Status” box, select the desired flag status.
Chapter 4 PAS Application Software Remote Device Control
100 Series PM172 Powermeters
2. Click on Send.
Device Diagnostics
Device diagnostic messages may appear as a result of the PM172 built-in diagnostic tests performed during a start-up and device operation.
To enter the Device Diagnostics dialog, check the On-line button on the PAS toolbar, select Device Control from the Monitor menu, and then click on the Device Diagnostics tab.
All diagnostic events are recorded to the Event log and can be inspected via PAS (see Viewing the Device Event Log
). The diagnostics status is also recorded to a non-volatile register, which is not affected by loss of power and may be read and cleared via communications or via PAS.
Loading...