
LIMITED WARRANTY
The manufacturer offers the customer an 24-month functional warranty on
the instrument for faulty workmanship or parts from date of dispatch from
the distributor. In all cases, this warranty is valid for 36 months from the
date of production. This warranty is on a return to factory basis.
The manufacturer does not accept liability for any damage caused by
instrument malfunction. The manufacturer accepts no responsibility for
the suitability of the instrument to the application for which it was
purchased.
Failure to install, set up or operate the instrument according to the
instructions herein will void the warranty.
Your instrument may be opened only by a duly authorized representative
of the manufacturer. The unit should only be opened in a fully anti-static
environment. Failure to do so may damage the electronic components
and will void the warranty.
NOTE
The greatest care has been taken to manufacture and calibrate your
instrument. However, these instructions do not cover all possible
contingencies that may arise during installation, operation or
maintenance, and all details and variations of this equipment are not
covered by these instructions.
For additional information regarding installation, operation or maintenance
of this instrument, contact the manufacturer or your local representative or
distributor.
IMPORTANT
Please read the instructions this manual before performing
installation, and take note of the following precautions:
Ensure that all incoming AC power and other power sources are
turned OFF before performing any work on the instrument. Failure
to do so may result in serious or even fatal injury
and/or equipment
damage.
Before connecting the instrument to the power source, check the
labels on the side of the instrument to ensure that your instrument is
equipped with the appropriate power supply voltage, input voltages,
currents and communication protocol for your application.
Under no circumstances should the instrument be connected
to a power source if it is damaged.

ii
To prevent potential fire or shock hazard, do not expose the
instrument to rain or moisture.
The secondary of an external current transformer must never be
allowed to be open circuit when the primary is energized. An open
circuit can cause high voltages, possibly resulting in equipment
damage, fire and even serious or fatal injury
. Ensure that the current
transformer wiring is made through shorting switches and is secured
using an external strain relief to reduce mechanical strain on the
screw terminals, if necessary.
Setup procedures must be performed only by qualified personnel
familiar with the instrument and its associated electrical equipment.
DO NOT open the instrument under any circumstances.
Modbus is a trademark of Modicon, Inc.
Read this manual thoroughly before connecting the meter to the
current carrying circuits. During operation of the meter,
hazardous voltages are present on input terminals. Failure to
observe precautions can result in serious or even fatal injury or
damage to equipment.
BG0306 Rev. A1

Table of Contents
Quick Start......................................................................... iv
Chapter 1 Introduction ....................................................1
1.1 About This Manual ..............................................................1
1.2 About The PM130 ................................................................1
Chapter 2 Installation ...................................................... 6
2.1 Mechanical Installation .......................................................6
2.2 Electrical Installation...........................................................8
Chapter 3 Using The Menus ...........................................17
Chapter 4 Setup Menus................................................... 19
4.1 Basic Setup Menu ...............................................................19
4.2 Communications Port Setup Menu....................................21
4.3 Pulsing Output Setup Menu (PM130E) .............................. 22
4.4 Alarm/Event Setpoints Setup Menu...................................23
4.5 Relay Operation Control Menu...........................................27
4.6 Display Setup Menu ............................................................28
4.7 User Selectable Options Menu...........................................29
4.8 Access Control Menu.......................................................... 30
4.9 Reset/Synchronization Menu .............................................31
Chapter 5 Data Display.................................................... 32
5.1 Navigating in the Display Mode .........................................32
5.2 Data Display Formats.......................................................... 34
5.3 Self-Test Diagnostics Display ............................................39
Chapter 6 Viewing Status Information........................... 41
6.1 The Status Information Menu ............................................. 41
6.2 Status Display Formats.......................................................42
Appendix: Technical Specifications ...............................43

SETUP (see Chapter 4 for full instructions)
All setups can be performed directly on the front panel or via
communications using PComTest communication software, except for
Communications and Display setups which must be performed directly on
the instrument panel.
Performing Basic and Communications Setup
Press .
Press to activate middle window.
Press ▲▼ to scroll to desired option.
Press to activate lower window.
Press ▲▼ to scroll to desired value.
Press to save selected value.
Basic and Communications Setup Options (∗ default setting)
Code Parameter Options Description
ConF
Wiring mode 3OP2 3-wire open delta using 2 CTs
4Ln3∗
4-wire Wye using 3 PTs
3dir2 3-wire direct connection using 2 CTs
4LL3 4-wire Wye using 3 PTs
3OP3 3-wire open delta using 3 CTs
3Ln3 4-wire Wye using 2 PTs
3LL3 4-wire Wye using 2 PTs
Pt
PT ratio
1.0∗ - 6,500.0
The potential transformer ratio
Ct
CT primary current 1-50,000A
(5*)
The primary rating of the current
transformer
d.P
Power demand
period
1, 2, 5, 10,
15*, 20, 30,
60, E
The length of the period for power
demand calculations, in minutes.
E = external synchronization
n.dp
Number of power
demand periods
1-15
(1*)
The number of demand periods to be
averaged for sliding window demands
1 = block interval demand calculation
A.dP
Ampere/Volt
demand period
0-1800
(900*)
The length of the period for
volt/ampere demand calculations, in
seconds 0 = measuring peak current
buF
Averaging buffer
size
8∗,16,32
The number of cycles for RMS sliding
averaging
rSt
Reset
enable/disable
diS∗, En
Protects all reset functions, both via
the front panel or communications
Freq
Nominal frequency 50, 60 Hz The nominal power utility frequency
Prot
Communications
protocol
ASCII∗, rtu,
dnP3
ASCII, Modbus RTU or DNP3.0
protocol
rS
Interface standard 485 RS-485 interface (not changeable)
Addr
Address
ASCII: 0∗-99, Modbus: 1∗-247, DNP3.0: 0∗-255
bAud
Baud rate 110, 300, 600, 1200, 2400, 4800, 9600*, 19200 bps
dAtA
Data format 7E , 8E (7/8 bits, even parity), 8n* (8 bits, no parity)
E
E
SELECT
CH
ENTER
SELECT
SELECT
ENTER
bASc
4L-n
ConF
Port
ASCII
Prot
men

Chapter 1 Introduction 1
Chapter 1 Introduction
1.
1.1 About This Manual
This manual is intended for the user of the PM130 Powermeter.
The PM130 is a microprocessor-based instrument used for measurement, monitoring, and management of electrical parameters.
This chapter gives an overview of this manual and an introduction
to the PM130.
Chapter 2, Installation, provides instructions for mechanical and
electrical installation.
Chapter 3, Using the Menus, presents the structure of menus for
setup and status viewing.
Chapter 4, Setup Menus, provides instructions for performing
parameter setup via the front panel.
Chapter 5, Data Display, guides you through the display pages.
Chapter 6, Viewing Status Information, tells you how to access
additional status information on the instrument. This information
may be useful during installation.
Technical Specifications for the PM130 are found in the Appendix.
1.2 About The PM130
The PM130 is a compact panel mounted 3-phase AC Powermeter,
specially designed to meet the requirements of users ranging from
electrical panel builders to substation operators. The PM130 is
available in three models: the PM130 for basic voltage, current
and frequency measurements; the PM130P which adds power and
power factor measurements; and the PM130E which adds power
demands and energy measurements. All models are suitable for
mounting on both 4-inch round and 92x92mm square cut-outs.
Features
Display: The front panel features bright LED displays (three
windows, up to 38 pages) with adjustable display update time, and
a LED bar graph showing percentage load with respect to userdefinable nominal (100%) load current. In the common
measurements group (see Chapter 5), Display Auto Scroll is
available with a programmable scroll interval of 2 to 15 seconds.

Chapter 1 Introduction
2
Automatic return to the main screen is available after 30 seconds
of uninterrupted use.
Setup is menu driven, with optional password protection.
Communications are available using an RS-485 standard, with
ASCII/Modbus or ASCII/DNP3.0 protocols. 120 user assignable
registers are available. Transmitter and receiver status are
displayed on the status information page (see Chapter 6).
One multi-purpose relay (optional) is provided for energy pulsing
(KYZ) or alarm and remote control. Up to 16 setpoints can be
assigned to the relay.
Four time operation counters are provided which are operated
and released by user-defined triggers. These are for counting total
generator time or transformer or power line time overload.
External synchronization of the power demand interval is
provided through communications in the PM130E.
Three user-selectable options are provided:
Power calculation mode (P.cAL):
Mode 1: Reactive power calculation (rEAc)
Active power P and reactive power Q are measured
directly and apparent power S = √ P
2
+ Q2
Mode 2: Non-active power calculation (nAct)
Active power is measured directly, and apparent
power S = V × I (V, I - rms voltage and currents)
and non-active power N = √ S
2 - P2
Mode 1 is recommended for electrical networks with low
harmonic distortion (voltage THD < 5%, current THD < 10%);
Mode 2 is recommended for all other cases. (
The PM130 does
not measure harmonics; contact your distributor for information on
instruments that provide harmonic measurement).
Energy rollover value (roll – PM130E only)
This option specifies the point at which the energy value rolls
over to zero. For example, if the roll value is 10.E4, then the
energy counter has 4 digits, i.e., energy is displayed up to 9999
kWh (kvarh, kVAh) with resolution 1 kW-hour.
Roll value Maximum Energy Resolution
10.E4 9999 kWh (kvarh, kVAh) 1 kWh (kvarh, kVAh)
10.E5 99999 kWh (kvarh, kVAh) 1 kWh (kvarh, kVAh)
10.E6 999.99 MWh (kvarh, kVAh) 10 kWh (kvarh, kVAh)
10.E7 9999.9 MWh (kvarh, kVAh) 100 kWh (kvarh, kVAh)
10.E8 99999. MWh (Mvarh, MVAh) 1 MWh (Mvarh, MVAh)

Chapter 1 Introduction 3
The roll value may be changed in accordance with the average
load of the power line. For example, if average power equals 400
kW and the counter must reset every 3 months (2160 hours),
then energy during this period equals 864000 (6 digits) and the
roll = 10.E6.
Phase energy calculations mode (Ph.En)
This option is used to enable or disable phase energy calculations.
Measured Parameters
Note: Real-time values are measured over 1 cycle of fundamental frequency;
Average values are of 8, 16 or 32 real-time values
available in the PM130P/PM130E
Output
Parameter Display Comm. Pulse Alarm
Average Values: Amps, Volts,
Frequency
$ = setup via PC
# = setup via panel
Average RMS Voltage per phase
#$
Average RMS Current per phase
#$
Average Frequency
#$
Average Neutral Current
#$
Voltage & Current unbalance
Amps & Volt Demand Parameters
Ampere Demand per phase
#$
Volt Demand per phase
#$
Ampere Maximum Demand per phase
Voltage Max. Demand per phase
Average Power values
Average Active Power per phase
Average Reactive Power per phase
Average Apparent Power per phase
Average Total Active Power
#$
Average Total Reactive Power
#$
Average Total Apparent Power
#$
Average Power Factor per phase
Average Total Power Factor
#$
Power Demand Parameters
Active Power Accumulated Demand
#$
Apparent Power Accumulated Demand
#$
Active Power Demand
#$
Active Power Sliding Demand
#$
Apparent Power Demand
#$
Apparent Power Sliding Demand
#$
Active Power Predicted Demand
#$
Apparent Power Predicted Demand
#$
P
P E
P E
E
P E
P E

Chapter 1 Introduction
4
available in the PM130P/PM130E
Output
Parameter Display Comm. Pulse Alarm
Active Power Maximum Demand
Apparent Power Maximum Demand
Energy Per Phase
Active Energy Import per phase
Reactive Energy Import per phase
Apparent Energy per phase
Total Energy
Total Active Energy Import
#$
Total Active Energy Export
#$
Total Reactive Energy Import
#$
Total Reactive Energy Export
#$
Total Reactive Energy net
Total Reactive Energy Absolute
#$
Total Apparent Energy
#$
Min/Max Log
Min/Max Volts
Min/Max A, Neutral current
Min/Max frequency
Min/Max kW, kvar, kVA, PF
Real-time Amps, Volts, Frequency
RT RMS Voltage per phase
#$
RT RMS Current per phase
#$
RT Frequency
#$
RT Neutral Current
RT Voltage & Current unbalance
#$
Real-time Power Values
RT Active Power per phase
RT Reactive Power per phase
RT Apparent Power per phase
RT Total Active Power
RT Total Reactive Power
RT Total Apparent Power
RT Power Factor per phase
RT Total Power Factor
Phase Rotation
#$
Counters
Remote Relay Control
Alarm Trigger Status
Self-Diagnostic Tests
E
E
P E
P E
P E
P
E
P
E
P E

Chapter 2 Installation
8
2.2 Electrical Installation
) Before installation ensure that all incoming power
sources are shut OFF. Failure to observe this practice can
result in serious or even fatal injury and damage to
equipment.
Connections to the PM130 are made via terminals (voltage input,
power supply, communication and optional relay output) and CT
cores located on the rear of the instrument as shown in Figure 2-3.
Note: If your PM130 was not ordered with the optional relay, it will
not have the relay connector.
Figure 2-3 PM130 Connections - Rear View
2.2.1 Power Supply Connection
The power supply can be dedicated-fused, or from a monitored
voltage if it is within the instrument’s power supply range.
Connection to the AC power supply is: Line to terminal L; Neutral
to terminal N.

Chapter 2 Installation 11
2.2.4 Voltage Inputs
690V Inputs (Standard):
690V inputs are usually used with direct connection. Use any of the
seven wiring configurations shown in Figures 2-5 through 2-11.
120V Inputs (Option U):
120V inputs usually implies use of a potential transformer (PT).
The PT requires use of any of the four wiring configurations shown
in Figures 2-7 through 2-10.
Wiring Configurations 'Wiring Mode' Definition
(See parameter setup instructions in Section 4.1)
3-wire direct connection using 2
CTs (2-element)
3dir2 (Figure 2-5)
4-wire WYE direct connection
using 3 CTs (3-element)
4Ln3 or 4LL3 (Figure 2-6)
4-wire WYE connection using 3
PTs, 3 CTs (3-element)
4Ln3 or 4LL3 (Figure 2-7)
3-wire open delta connection
using 2 PTs, 2 CTs (2-element)
3OP2 (Figure 2-8)
3-wire open delta connection
using 2 PTs, 3 CTs
(2½ -element)
3OP3 (Figure 2-9)
4-wire WYE connection using 2
PTs, 3 CTs (2½-element)
3Ln3 or 3LL3 (Figure 2-10)
4-wire delta direct connection
using 3 CTs (3-element)
4Ln3 or 4LL3 (Figure 2-11)

Chapter 3 Using the Menus 17
Chapter 3 Using The Menus
3.
Press to enter the setup mode. The primary menus will
appear:
Press again to activate the window of the desired primary
menu. Press
.
Select CHG to initialize or modify the instrument setup, or to clear
the accumulated values stored in the instrument. Entry to this
menu can be protected by a password.
Select StA to view extended status information which may be
useful during installation and in certain applications.
Select OPS for viewing (not editing) the instrument setup options.
After selecting either OPS or CHG, the list of setup menus is
displayed in the upper window. Figure 3-1 presents a complete
menu list. Depending on the model of your instrument, some
menus may not appear.
Password
The Setup Change Menu can be secured by a user-defined
password comprised of 4 digits. The instrument is shipped with
password protection disabled. To enable password protection, go
to the Access Control Menu (see Section 4.13).
The Password Menu appears if password protection is enabled.
To enter a password:
Set the first digit using the up and down arrow keys.
Press to advance to the next digit. As you
advance, the previous digit will become invisible.
Set the other password digits in the same manner.
Press to continue setup. If your password is incorrect,
you will return to the Primary Selection Menu.
SELECT
SELECT
ENTER
SELECT
StA
ENTER
StA
CHG
OPS
- Status Information Menu (see Chapter 6)
- Setup Options Menu
- Setup Change Menu (see Chapter 4)
PASS
0000
SELECT
ENTER

Chapter 4 Setup Menus 19
Chapter 4 Setup Menus
4. CHAPTER 3 SETUP MENUS
NOTE: Instrument setup can be performed directly on the front
panel using the setup menus or via communications using
PComTest communication software. PComTest is supplied with your
instrument and provides full setup capabilities for your instrument.
For information on using PComTest, refer to the user documentation
supplied with your instrument.
4.1 Basic Setup Menu
This menu contains the basic configuration options which define
the general operating characteristics of your instrument, such as
wiring mode, input scales, the size of the RMS averaging buffer,
etc. Table 4-1 lists the basic setup options, their code names and
applicable ranges.
Activate the middle window to scroll through the list of available
options, and then activate the lower window to set the option
value.
To select and view a setup option:
Press to activate the middle window
Use the up/down arrow keys to scroll to the desired option.
The current value for this option appears in the lower
window.
To change the value of the selected option:
Press to make the lower window active.
Press the up/down arrow keys to scroll to the desired
value.
Press to store the selected value, or press
to quit the setup menu.
Table 4-1 Basic Setup Options (∗ default setting)
Code Parameter Options Description
ConF
Wiring mode 3OP2 3-wire open delta using 2 CTs
(2 element)
4Ln3∗
4-wire Wye using 3 PTs (3 element),
line to neutral voltage readings
3dir2 3-wire direct connection using 2 CTs
(2 element)
4LL3 4-wire Wye using 3 PTs (3 element),
line to line voltage readings
SELECT
SELECT
bASc
4L-n
ConF
ENTER
ESC
SELECT
CH

Chapter 4 Setup Menus
20
Code Parameter Options Description
ConF
Wiring mode 3OP3 3-wire open delta using 3 CTs
(2½ element)
3Ln3 4-wire Wye using 2 PTs (2½
element), line to neutral voltage
readings
3LL3
4-wire Wye using 2 PTs (2½
element), line to line voltage
readings
Pt
PT ratio
1.0∗ -
6,500.0
The potential transformer ratio
Ct
CT primary
current
1-50,000
(5*)
The primary rating of the current
transformer, in A
d.P
Power demand
period
(PM130E)
1, 2, 5,
10, 15*,
20, 30,
60, E
The length of the period for power
demand calculations, in minutes.
E = external synchronization
n.dp
Number of
power demand
periods
1-15
(1*)
The number of demand periods to
be averaged for sliding window
demands
(PM130E)
1 = block interval demand calculation
A.dP
Ampere/Volt
demand period
0-1800
(900*)
The length of the period for
volt/ampere demand calculations, in
seconds
0 = measuring peak current
buF
Averaging
buffer size
8∗,16,32
The number of measurements for
RMS sliding averaging
rSt
Reset
enable/disable
diS∗, En
Protects all reset functions, both via
the front panel or communications.
Freq
Nominal
frequency
50, 60 Hz
The nominal power utility frequency
Synchronization of the power demand interval can be made through
communications (see the PM130 Communications Reference Guides) or via
the front panel (see Section 4.9). If the power demand period is set to E, an
external synchronization pulse denoting the start of the next demand interval
can be simulated by using the synchronization command sent via
communications.
60 Hz default for North America; elsewhere, default is 50Hz.
NOTES
1) The maximum value for CT PRIMARY CURRENT × PT RATIO is
10,000,000. If this product is greater, power related values will be zeroed.
2) Always specify WIRING MODE, PT RATIO and CT PRIMARY
CURRENT prior to setting up alarm setpoints, otherwise the
alarm/event setpoints which use these parameters will automatically be
disabled.

Chapter 4 Setup Menus 21
4.2 Communications Port Setup Menu
This menu allows you to access the communications port options
that the PM130 uses to communicate with a master computer.
Table 4-2 lists the communications options, their code names and
applicable choices.
Activate the middle window to scroll through the list of available
options, and then activate the lower window to set the option
value.
To select and view a setup option:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired option.
The option setting will appear in the lower window.
To change the selected option:
Press to activate the lower window.
Press the up/down arrow keys to scroll to the desired
value.
Press to store the selected value or press
to quit the setup menu.
Table 4-2 Communications Options (∗ default setting)
Code Parameter Options Description
Prot
Communications
protocol
ASCII∗
rtu
dnP3
ASCII protocol
Modbus RTU protocol
DNP3.0 protocol
rS
Interface standard
485
RS-485 (not changeable)
0∗-99 ASCII
Powermeter address
Addr
Address
1∗-247 Modbus
0∗-255 DNP3.0
bAud
Baud rate
110
110 baud
300
300 baud
600
600 baud
1200
1200 baud
2400
2400 baud
4800
4800 baud
9600∗
9600 baud
19.20
19,200 baud
dAtA
Data format
7E
7 bits, even parity
8n∗
8 bits, no parity
8E
8 bits, even parity
SELECT
Port
ASCII
Prot
SELECT
CH

Chapter 4 Setup Menus
22
4.3 Pulsing Output Setup Menu (PM130E)
This menu allows you to program a relay (optional) provided by
your PM130E instrument to output energy pulses. Available
pulsing parameters are listed in Table 4-3.
To change the pulse relay setup:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired
output parameter. Selecting nonE disables pulsing
through this relay.
Press to activate the lower window.
Use the up/down arrow keys to set the amount of
unit-hours per pulse. The available range is 1-9999.
Press to store the new setup, or press
to quit the setup without changes.
To quit the pulsing setup menu:
From the upper window, press or .
Table 4-3 Pulsing Output Parameters
Code Parameter Units
nonE Output disabled
Ac.Ei
Active energy import kWh import (positive)
Ac.EE
Active energy export kWh export (negative)
rE.Ei
Reactive energy import kvarh import (inductive)
rE.EE
Reactive energy export kvarh export (capacitive)
rE.Et
Reactive energy total kvarh total (absolute)
AP.Et
Apparent energy total kVAh total
NOTES
1. If your instrument is not equipped with the optional relay, then this
setup parameter will not appear on the display.
2. You will not be able to store your setup in the instrument if you
assigned a parameter to relay output with a zero number of unithours per pulse.
3. If a relay you allocated for pulsing has been manually operated or
released, it reverts automatically to normal operation.
4. If a relay you allocated for pulsing has been engaged by an
alarm/event setpoint, the setpoint is automatically disabled.
SELECT
SELECT
ENTER
ESC
ESC
ENTER
rEL
1
Ac.Ei
SELECT
CH

Chapter 4 Setup Menus 23
4.4 Alarm/Event Setpoints Setup Menu
Your instrument provides 16 alarm/event setpoints that can
monitor a wide variety of events; in turn, these events can be
programmed to trigger specific actions. This menu is used to
specify the events to be monitored by the setpoints, and actions to
be triggered by those events.
To program a setpoint (all 16 can be assigned to the relay) you
need to define up to six setup parameters: the setpoint trigger
parameter, operate and release limits, optional operate and
release delays, and the setpoint action. Tables 4-4, 4-5 and 4-6 list
the setpoint setup parameters, available triggers and setpoint
actions.
Example:
Trigger
parameter
Setpoint 1 is set to monitor the real-time
high current on phase 1 (the trigger
parameter).
Operate limit }
}
}
}
Release limit }
The operate (On) and release (OFF)
limits which determine setpoint
operation are defined as 1200A and
1100A respectively.
Operate delay }
}
}
Release delay
}
The delays before operation (On d)
and release (OFFd) are set at 5
seconds and 10 seconds respectively.
Setpoint action
The action to be triggered is relay
operation.
To select a setpoint:
Scroll to the desired setpoint using the up/down arrow keys.
To view the setup options for the setpoint:
Press to activate the middle window.
SP 1
RHi.C1
triG
SP 1
5
On d
SP 1
10
OFFd
SP 1
1200
On
SP 1
rEL

Chapter 4 Setup Menus
24
Use the up/down arrow keys to scroll to the desired setup
option. The value associated with this option is displayed in the
lower window.
To change the selected setup option:
Press to activate the lower window.
Use the up/down arrow keys to scroll to the desired value.
Press to store the new value.
Press to leave the value unchanged.
To store your new setup for the setpoint:
From the middle window, press .
To quit the setpoint setup without changes:
From the middle window, press .
To quit the setpoints setup menu:
From the upper window, press or .
NOTES
1. If your instrument is not equipped with the optional relay, then these
setup parameters will not appear on the display.
2. When you enter the setpoints setup menu at the protected level,
monitoring setpoints is temporarily suspended until you return to the
main setup menu.
3. Each time you select a new trigger parameter, the operate and
release limits are set by default to zero.
4. You will not be able to store your setpoint setup to the instrument if a
setpoint action is directed to a relay allocated for pulsing.
5. The setpoint action directed to a relay output can be overridden using
commands sent via communications. A relay can be manually
operated or released. When the relay reverts to normal operation, it
is automatically returned under setpoint control.
Table 4-4 Setpoint Setup Options (middle window)
Code Option Description
triG
Trigger
parameter
The measurement parameter or signal to be
monitored by the setpoint.
On
Operate limit The threshold at which the setpoint becomes
operative.
OFF
Release limit The threshold at which the setpoint is released
(becomes inoperative).
On d
Operate delay Time delay (0.1 sec.resolution) before
operation.
OFF d
Release delay Time delay (0.1 sec. resolution) before release.
Act
Setpoint action The action performed when the setpoint is
operative.
SELECT
ENTER
ENTER
ENTER
ESC
ESC
ESC

Chapter 4 Setup Menus 25
Table 4-5 Setpoint Triggers
(lower window, when middle window is triG)
Code Parameter Unit Range
nonE Setpoint disabled
Phase Reversal
POS.ro.
Positive phase rotation reversal
NEG.ro.
Negative phase rotation reversal
Real-time Values on any Phase
r. Hi. U
High voltage V 0 to Vmax
r. Lo. U
Low voltage V 0 to Vmax
r. Hi. C
High current A 0 to Imax
r. Lo. C
Low current A 0 to Imax
Real-time Auxiliary Measurements
r. Hi.Fr
High frequency Hz 0 to 100.00
r. Lo.Fr
Low frequency Hz 0 to 100.00
r. U.Unb
Voltage unbalance % 0 to 300
r. C.Unb
Current unbalance % 0 to 300
Average Values per Phase
A. Hi.C1
High current L1 A 0 to Imax
A. Hi.C2
High current L2 A 0 to Imax
A. Hi.C3
High current L3 A 0 to Imax
A. Lo.C1
Low current L1 A 0 to Imax
A. Lo.C2
Low current L2 A 0 to Imax
A. Lo.C3
Low current L3 A 0 to Imax
Average Values on any Phase
A. Hi. U
High voltage V 0 to Vmax
A. Lo. U
Low voltage V 0 to Vmax
A. Hi. C
High current A 0 to Imax
A. Lo. C
Low current A 0 to Imax
Average Total Values
A. Hi.P.i
High total kW import (positive) kW 0 to Pmax
A. Hi.P.E
High total kW export (negative) kW 0 to Pmax
A. Hi.q.i
High total kvar import (positive) kvar 0 to Pmax
A. Hi.q.E
High total kvar export (negative) kvar 0 to Pmax
A. Hi. S
High total kVA kVA 0 to Pmax
A. PF.LG
Low total PF Lag 0 to 1.000
A. PF.Ld
Low total PF Lead 0 to 1.000
Average Auxiliary Measurements
Ar neU.C
High neutral current A 0 to Imax
Ar Hi.Fr
High frequency Hz 0 to 100.00
Ar Lo.Fr
Low frequency Hz 0 to 100.00
Present Demands
Hi d.U1
High volt demand L1 V 0 to Vmax
Hi d.U2
High volt demand L2 V 0 to Vmax
Hi d.U3
High volt demand L3 V 0 to Vmax
Hi d.C1
High ampere demand L1 A 0 to Imax
Hi d.C2
High ampere demand L2 A 0 to Imax
Hi d.C3
High ampere demand L3 A 0 to Imax
P
E
P
E
P
E
P
E
P
E
P
E

Chapter 4 Setup Menus
26
Code Parameter Unit Range
Hi d.P
High block interval kW demand kW 0 to Pmax
Hi d.S
High block interval kVA demand kVA 0 to Pmax
Hi Sd.P
High sliding window kW demand kW 0 to Pmax
Hi Sd.S
High sliding window kVA demand kVA 0 to Pmax
Hi Ad.P
High accumulated kW demand kW 0 to Pmax
Hi Ad.S
High accumulated kVA demand kVA 0 to Pmax
Hi Pd.P
High predicted sliding window kW
demand
kW 0 to Pmax
Hi Pd.S
High predicted sliding window kVA
demand
kVA 0 to Pmax
The parameter limits are as follows:
Vmax (690 V input option) = 828 V @ PT Ratio = 1
Vmax (690 V input option) = 144 × PT Ratio [V] @ PT Ratio > 1
Vmax (120 V input option) = 144 × PT Ratio [V]
Imax (50% over-range) = 1.5 × CT primary current [A]
Pmax = (Imax × Vmax × 3)/1000 [kW] @ wiring mode 4Ln3 or 3Ln3
Pmax = (Imax × Vmax × 2)/1000 [kW] @ wiring mode 4LL3, 3OP2, 3dir2,
3OP3 or 3LL3
The setpoint is operated when the actual phase sequence does not match
the indicated normal phase rotation.
The actual frequency range is 45.00 - 65.00 Hz.
For 4LN3 or 3LN3 wiring modes, voltages will be line-to-neutral; for any
other wiring mode, they will be line-to-line.
Table 4-6 Setpoint Actions
(lower window, when middle window is Act)
Code Action
nonE No action
rEL Operate relay
In.Cn.1 Increment counter #1
In.Cn.2 Increment counter #2
In.Cn.3 Increment counter #3
In.Cn.4 Increment counter #4
ti.Cn.1 Count operating time using counter #1
ti.Cn.1 Count operating time using counter #2
ti.Cn.1 Count operating time using counter #3
ti.Cn.1 Count operating time using counter #4
When a setpoint is operated, its status is always stored to the alarm status
register even if no action is assigned to the setpoint. The alarm status can
be inspected and cleared from the front panel through the Status
Information Menu (see Section 6.2) or via communications.
This action converts a common event counter to the time counter which
measures time at 0.1 hour resolution while the setpoint is in the operated
state. Each time counter has a non-volatile shadow counter which counts
time at 1 second resolution before the corresponding time counter is
incremented. Time counters can be inspected via the Status Information
Menu. They are labeled by
an hour mark in the middle window.
E
E
E
E
E
E
E
E
available in the PM130E
E
available in the PM130P
P

Chapter 4 Setup Menus 27
4.5 Relay Operation Control Menu
This menu allows you to set the relay operation mode: non-failsafe
or failsafe. Failsafe relay operation is the opposite of normal
operation where relay contacts are closed when a relay is
operated (activated), and are open when a relay is released (deactivated). In failsafe mode, an alarm is activated by a nonenergized relay which will open in all cases when an alarm
condition is present or an alarm setpoint is not operational either
due to a loss of control power or due to corruption of the setpoint
setup configuration. A failsafe relay is closed only if it is under
setpoint control and no alarm conditions exist, or if it is manually
operated via communications.
To change the relay operation mode:
Press to activate the lower window.
Use the up/down arrow keys to set the desired
option. Select nor for normal (non-failsafe) relay
operation, or select FSAFE for failsafe relay
operation.
Press to store your new setting or press to
leave your previous setting unchanged.
To quit the setup menu:
From the middle window, press or .
NOTES
1. You will not be able to change the relay operation mode if a relay has
been allocated for pulsing.
2. When a failsafe relay is allocated for pulsing, it automatically reverts
to normal operation.
SELECT
CH
ENTER
ENTER
rELo
nor
rEL
ESC
ESC
SELECT
ENTER
ENTER

Chapter 4 Setup Menus
28
4.6 Display Setup Menu
This menu allows you to view and change display properties.
Table 4-7 lists available options with their code names and
applicable ranges.
Table 4-7 Display Options (∗ default setting)
Display Code Parameter Options Description
UPdt
Update
time
0.1 – 10.0 s
(0.5)*
defines interval
between display
updates
ScrL
Auto scroll
interval
nonE*
2-15 s
disables/enables auto
scroll on common
measurements
display; defines auto scroll interval
rEtn
Auto return
to the main
screen
diS*, En
Disables/enables
auto return to the
main screen after 30
seconds of
uninterrupted use
bAr
Nominal
load
current for
LED bar
graph
0-50000A
(0*)
defines the nominal
load (100%) level for
the bar graph display
(0 = CT primary
current)
Ph.P
Phase
powers
display
mode
diS*, En
disables/enables
display of phase
powers in common
measurements
To select a display option:
Press to activate the middle window, and then use the
up/down arrow keys to scroll to the desired option.
To change the display option:
Press to activate the lower window.
Use the up/down arrow keys to set the desired option.
Press to store your new setting or press to leave
your previous setting unchanged.
To quit the display setup menu:
From the middle window, press or .
SELECT
CH
ENTER
ENTER
SELECT
SELECT
ESC
ESC
ENTER
ENTER
available in the PM130E
E
available in the PM130P
P
diSP
5
ScrL
E
P
diSP
5000
bAr
diSP
5
rEtn
diSP
diS
Ph.P
diSP
0.5
UPdt

Chapter 4 Setup Menus 29
4.7 User Selectable Options Menu
This menu allows you to change options which relate to the
instrument features and functionality. Table 4-8 lists all available
options with their code names and applicable ranges.
To select an option:
Press to activate the middle window, and
then use the up/down arrow keys to scroll to the
desired option.
To change the selected option:
Press to activate the lower window.
Use the up/down arrow keys to set the desired value.
Press to store your new setting or to
leave the previous setting unchanged.
To quit the display setup menu:
From the middle window, press or .
Table 4-8 User Selectable Options (∗ default setting)
Code Parameter Options Description
P.cAL
Power calculation
mode
rEAc*
nAct
Using reactive power
Using non-active power
roLL
Energy roll value
10.E4
10.E5
10.E6
10.E7
10.E8*
10,000
100,000
1,000,000
10,000,000
100,000,000
Ph.En
Phase energy
measurements
diS*, En Enables/disables
measurements of energies
per phase
SELECT
SELECT
OPtS
rEAc
P.cAL
ENTER
ESC
ESC
ENTER
SELECT
CH
ENTER ENTER
E P
E
E
available in the PM130E
available in the PM130P
E
P

Chapter 4 Setup Menus
30
4.8 Access Control Menu
This menu can be only accessed via the Setup Change Menu
(CHG). It is used in order to:
• change the user password
• enable or disable password check
To view an option setting:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired option (PASS
or CtrL).
Password Setting Password Protection Control
To change the password:
Press to activate the lower window.
Use the up/down arrow keys to modify the password. The password
can be up to four digits long.
Press to store your new password, or to leave the
password unchanged.
To enable/disable password checking:
Press to activate the middle window, and then use the
up/down arrow keys to move to the CtrL entry.
Press to activate the lower window.
Use the up/down arrow keys to change the password checking
status: select OFF to disable password protection, or select On to
enable password protection.
Press to store your new option, or to leave the
option unchanged.
To quit the setup menu:
From the middle window, press or .
Store your password in a safe place. If you do not provide the
correct password, you will need to contact your local
distributor for the super-user password to override password
protection.
SELECT
CH
ENTER ENTER
SELECT
SELECT
SELECT
SELECT
AccS
8780
PASS
AccS
OFF
CtrL
ENTER
ESC
SELECT
ESC
ESC
ENTER

Chapter 4 Setup Menus 31
4.9 Reset/Synchronization Menu
This menu allows you to reset to zero the accumulators and
Min/Max registers in your instrument, and also to synchronize the
power demand interval in the PM130E. The menu can be only
accessed via the Setup Change Menu (CHG). If the reset is
disabled from the Basic Setup Menu (see Section 4.1), you will not
be able to enter this menu.
The menu uses the following labels:
EnrG Resets total accumulated energies
dnd Resets all total maximum demands
P.dnd Resets total power maximum demands
A.dnd Resets volt/ampere maximum demands
Cnt Resets all event/time counters
Cnt.1 Resets counter # 1
Cnt.2 Resets counter # 2
Cnt.3 Resets counter # 3
Cnt.4 Resets counter # 4
Lo.Hi Resets Min/Max registers (does not affect maximum demands)
d.Snc Provides synchronization of the power demand interval (see
Notes below)
To reset the desired locations:
Press to activate the middle window; use the up/
down arrow keys to scroll to the desired data location entry.
Press to activate the lower window.
Press and hold for about 5 seconds until
the do label is replaced with done; release the key.
You will return to the middle window.
Press to quit the menu.
NOTES:
If you select the d.Snc entry, take into consideration the following:
1) If the power demand period is specified in minutes (see Section 4.1,
Basic Setup Options), this action provides synchronization of the
instrument’s internal timer. If the time expired from the beginning of the
current demand interval is more than 30 seconds, the new demand
interval starts immediately, otherwise synchronization is delayed until
the next demand interval.
2) The synchronization is made exactly 5 seconds after you first press
and hold .
If the CHG is not secured by a password, fast reset of the Min/Max
registers, maximum demands and energies can be done from the data
display mode (see Section 5.1) and counters from the status information
menu (see Section 6.1) without entering the reset menu.
SELECT
CH
ENTER
ENTER
SELECT
SELECT
ENTER
rSt
do
EnrG
E
E
E
E
available in the PM130E
E
ESC
ENTER

Chapter 5 Data Display
32
Chapter 5 Data Display
5.
5.1 Navigating in the Display Mode
The front panel has a simple interface that allows you to display
numerous measurement parameters in up to 38 display pages. For
easier reading, the parameters are divided into three groups, each
accessible by a designated key. These are:
Common measurements
- no selection key
Min/Max measurements
- selected by the key
Energy measurements
- selected by the key
The up/down arrow keys are used as follows in the Display Mode:
Scrolls through the pages downward (forward)
Scrolls through the pages upward (backward)
Returns to the first page within current measurement group
For each display page, up to three parameters can be displayed.
The Load bar graph displays the amount, in percent, of the current
load with respect to user-defined nominal load current. The highest
current measured by the PM130 is divided by the nominal load
current as defined in the Display Setup Menu (see Section 4.6)
and expressed as a percent by the LEDs (40% to 110%) which are
lit. For example, if all LEDs up to and including 90% are lit, this
means that the load is 90%-100% of the nominal load current. If
the nominal load current is set to 0, the CT primary current setup is
used.
MAX/MIN
ENERG
small LEDs -
indicate measured
parameter
Load bar graph -
indicates %
nominal load
current
round LEDs -
indicate
measurement
group

Chapter 5 Data Display 33
In the Display Mode, the front panel display is updated
approximately twice per second; you can adjust the display update
rate via the Display Setup Menu (see Section 4.6).
Tables 5-1 and 5-2 list all displayed parameters and their LED
indicators.
NOTES
1. The common measurements group does not have a designated
indicator LED. If no indicator LED is lit up below the display, this means
that the common measurement parameters are being displayed at this
time. To return to the common measurements from another group, just
press the same key that you used to display this group (the key pointed
to by an illuminated LED).
2. When you move to another measurement group, the instrument stores
your last location; when you return to the previous group, the
instrument restores the last page. At power up, the instrument always
returns to the common measurements group and shows you the last
page that was displayed prior to loss of power.
Selecting a Display Page
Press the up/down arrow keys to scroll through display pages.
Selecting Common Measurements
Press the key pointed to by the illuminated round LED below the
front panel display. If no LED is lit up, this means that the front
panel displays the common measurements parameters.
When Display Auto Scroll is in effect (see Section 4.6), the
display will scroll automatically within 30 seconds after any of
the following:
• power up
• returning to the common measurements display
• pressing either arrow key
Press either arrow key to pause scrolling at the current page.
Selecting Min/Max Measurements
Press the key. Use the up/down arrow keys to scroll
through Min/Max measurements.
Selecting Energy Measurements
Press the key. Use the up/down arrow keys to scroll
through the different energy readings.
Auto Return to the Main Screen
If display Auto Return option is enabled (see Section 4.6), the
display will automatically return to the main screen from any other
measurement screen after 30 seconds of uninterrupted use.
MAX/MIN
ENERG

Chapter 5 Data Display
34
Fast Reset of Accumulated Data
When changing data via the front panel is not secured by a
password, you can reset the Min/Max registers, maximum
demands and energies from the display mode without entering the
reset menu.
Select the display page of the data you want to reset. To reset:
• Min/Max log registers: select a Min/Max page from the
Min/Max measurements display (where a Max or Min round
LED is illuminated).
• Ampere and volt maximum demands: select the ampere or
volt maximum demand page from the Min/Max
measurements display (where a MAX DMD LED is
illuminated, and volts or amps LEDs at the right are lit).
• Power maximum demands: select the power maximum
demand page from the Min/Max measurements display
(where a MAX DMD LED is illuminated, and kVA/MVA and
kW/MW LEDs at the right are lit).
• Total and phase energies: select the energy measurements
display.
While holding the key, press and hold for
about 5 seconds. The displayed data is reset to zero.
5.2 Data Display Formats
The display windows are labeled in the table as follows: 1 = upper
window, 2 = middle window, 3 = lower window.
Table 5-1 Displayed Parameters for the PM130
Page Window Indicato
Unit
Common Measurements
1 1
V1/V1-2
Voltage L12 4 V/kV
1 2
V2/V2-3
Voltage L23 4 V/kV
1 3
V3/V3-1 L. Voltage L31
4 V/kV
2 1
V1/V1-2
Voltage L1 4 V/kV
2 2
V2/V2-3
Voltage L2 4 V/kV
2 3
V3/V3-1 P. Voltage L3
4 V/kV
3 1
A1
Current L1 4 A/kA
3 2
A2
Current L2 4 A/kA
3 3
A3
Current L3 4 A/kA
4 1
A Neut
Neutral current 4 A/kA
4 2
Hz
Frequency 4 Hz
4 3
Phase
Rot.
Phase rotation sequence
(POS/NEG/ERR)
4
SELECT
ENTER

Chapter 5 Data Display 35
Page Window Indicato
Unit
Min/Max Measurements
MIN
1 1
V1/V1-2
Min. real-time voltage
L1/L12
4 V/kV
1 2
V2/V2-3
Min. real-time voltage
L2/L23
4 V/kV
1 3
V3/V3-1
Min. real-time voltage
L3/L31
4 V/kV
MAX
2 1
V1/V1-2
Max. real-time voltage L1/L12 4 V/kV
2 2
V2/V2-3
Max. real-time voltage L2/L23 4 V/kV
2 3
V3/V3-1
Max. real-time voltage L3/L31 4 V/kV
MAX DMD
3 1
A1
Max. ampere demand L1 4 A/kA
3 2
A2
Max. ampere demand L2 4 A/kA
3 3
A3
Max. ampere demand L3 4 A/kA
Displayed readings for all electrical quantities except Min/Max log are sliding
average values.
Voltage and current readings with a decimal point are displayed in kV and
kA. When the value width exceeds the window resolution, the right-most
digits are truncated.
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-
neutral; for any other wiring mode, they will be line-to-line voltages.
Displayed only in the 4LN3 or 3LN3 wiring mode.
' L' and ' P' indicators appear only in the case of 4LN3 or 3LN3 wiring
modes where both line-to-line and line-to-neutral voltages are present.

Chapter 5 Data Display 37
Page Window Indicator
LED
Parameter
Digits Unit
Min/Max Measurements
MIN
1 1
V1/V1-2
Min. real-time voltage
L1/L12
4 V/kV
1 2
V2/V2-3
Min. real-time voltage
L2/L23
4 V/kV
1 3
V3/V3-1
Min. real-time voltage
L3/L31
4 V/kV
2 1
A1
Min. real-time current L1 4 A/kA
2 2
A2
Min. real-time current L2 4 A/kA
2 3
A3
Min. real-time current L3 4 A/kA
3 1
kVA
Min. real-time total kVA 4 kVA/MVA
3 2
PF
Min. real-time total power
factor
4
3 3
kW
Min. real-time total kW 4 kW/MW
4 1
A NEUT
Min. real-time neutral
current
4 A/kA
4 2
Hz
Min. real-time frequency 4 Hz
4 3
kvar
Min. real-time total kvar 4 kvar/Mvar
MAX
5 1
V1/V1-2
Max. real-time voltage
L1/L12
4 V/kV
5 2
V2/V2-3
Max. real-time voltage
L2/L23
4 V/kV
5 3
V3/V3-1
Max. real-time voltage
L3/L31
4 V/kV
6 1
A1
Max. real-time current L1 4 A/kA
6 2
A2
Max. real-time current L2 4 A/kA
6 3
A3
Max. real-time current L3 4 A/kA
7 1
kVA
Max. real-time total kVA 4 kVA/MVA
7 2
PF
Max. real-time total power
factor
4
7 3
kW
Max. real-time total kW 4 kW/MW
8 1
A NEUT
Max. real-time neutral
current
4 A/kA
8 2
Hz
Max. real-time frequency 4 Hz
8 3
kvar
Max. real-time total kvar 4 kvar/Mvar
MAX DMD
9 1
V1
Max. volt demand L1/L12 4 V/kV
9 2
V2
Max. volt demand L2/L23 4 V/kV
9 3
V3
Max. volt demand L3/L31 4 V/kV

Chapter 5 Data Display 39
Page Window Indicator
LED
Parameter
Digits Unit
11 1
MVAh AP.En.
Label
11 2
L2
Label
11 3 MVAh L2 5 MVAh
12 1
MWh Ac.En.
Label
12 2
IP.L3
Label
12 3 MWh import L3 5 MWh
13 1
Mvarh rE.En.
Label
13 2
IP.L3
Label
13 3 Mvarh import L3 5 Mvarh
14 1
MVAh AP.En.
Label
14 2
L3
Label
14 3 MVAh L3 5 MVAh
Display readings for all electrical quantities except Min/Max log and
energies are sliding average values.
Voltage and current readings with a decimal point are displayed in kV and
kA. Power readings with a decimal point are displayed in MW, Mvar, and
MVA. When the value width is over the window resolution, the right most
digits are truncated.
By default, the maximum range for energy readings is 99,999,999
MWh/Mvarh/MVAh. Beyond this value, the reading will roll over to zero.
When the energy reading exceeds the window resolution, the right-most
digits are truncated. To avoid truncation, you can change the energy roll
value to lower limit via the User Selectable Options menu (see Section
4.7). Negative (exported) energy readings are displayed without a sign.
Per phase power and power factor readings are displayed only in
4LN3/4LL3 and 3LN3/3LL3 wiring modes (see Section 4.1) if the phase
powers display is enabled in the Display Setup menu (see Section 4.6).
Phase energy readings are displayed only in 4LN3/4LL3 and 3LN3/3LL3
wiring modes if they are enabled in the User Selectable Options menu (see
Section 4.7).
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-
to-neutral; for any other wiring mode, they will be line-to-line voltages.
Displayed only in the 4LN3 or 3LN3 wiring mode.
5.3 Self-Test Diagnostics Display
The PM130 periodically performs self-test diagnostics during
operation. If the instrument fails the test, it discards the last
measurement results, and an error code is displayed for one
second on all LEDs. Error codes are listed in Table 5-3. Code ‘8’
indicates normal operation.
available in the PM130E
E

Chapter 6 Viewing Status Information 41
Chapter 6 Viewing Status
Information
6.
Through the Status Information Menu (STA), it is possible to view the
status of various instrument features.
6.1 The Status Information Menu
To enter the Status Information Menu:
From the display mode, press to enter the Primary
Selection Menu.
Press to activate the StA window.
Press .
To select a display page:
Press the up/down arrow keys to scroll through the display
pages.
To quit the menu and return to the display mode:
Press or .
Front Panel Display
When you are in the Status Information Menu, the front panel
display is updated approximately four times per second and shows
you a wide variety of status information that you can review by
scrolling through display pages.
The status parameters are designated by the abbreviated labels in
the upper and/or middle window. The upper window flashes,
indicating that you are in the menu display.
Viewing and Clearing Alarms
Whenever a setpoint signals an alarm, it is latched to non-volatile
memory and remains when the alarm condition disappears.
Alarms which have occurred can be inspected and cleared all
together through the Status Information Menu. When a number of
alarms are present, use the up and down keys to scroll through all
alarms.
To clear alarms:
From the Status Information Menu, select either display page
where an alarm is displayed.
SELECT
StA
ENTER
SELECT
SELECT
ENTER
ENTERESC

Chapter 6 Viewing Status Information
42
While holding the key, press and hold for
about 5 seconds until the alarm trigger code displayed in the
lower window changes to "none".
Fast Reset of Counters
When changing data via the front panel is not secured by a
password, you can reset the counters from the Status Information
Menu display without entering the reset menu:
Select the page where the counter you want to reset is displayed.
While holding the key, press and hold for
about 5 seconds. The displayed data is reset to zero.
6.2 Status Display Formats
Table 6-1 lists all the displays available from the Status
Information Menu. The display windows are labeled in the table as
follows: 1 = upper window, 2 = middle window, 3 = lower window.
Table 6-1 Status Information
Page Window Parameter Digits Unit
1 1
PHAS
Label
1 2
rOt
Label
1 3 Phase rotation sequence
(POS/NEG/ERR)
4
2 1
rEL
Label
2 3 Relay status 1
3 1
Cnt.1
Label
3 3 Counter #1 5
4 1
Cnt.2
Label
4 3 Counter #2 5
5 1
Cnt.3
Label
5 3 Counter #3 5
6 1
Cnt.4
Label
6 3 Counter #4 5
7 1
Port
Label
7 2
rd. Receiver status (flashing r
while receiving data)
1
7 3
td. Transmitter status (flashing t
while transmitting data)
1
8 1
Alar
Label
8 2
SP. Alarm setpoint number
4
8 3 Alarm trigger code (see Table 4-5) 5
P E
SELECT
ENTER
SELECT
ENTER
available in the PM130P
P
available in the PM130E
E

Appendix: Technical Specifications 43
Appendix: Technical Specifications
7. ions
Input and Output Ratings
3 voltage
inputs
690 V:
(standard)
DIRECT INPUT - Nominal: 690V line-to-line
voltage, 790V maximum; 400V line-to-neutral,
460V maximum - Burden: <0.5 VA
INPUT USING PT - Burden: <0.15 VA
120 V:
(optional)
INPUT USING PT - Nominal: 120V line-to-line
voltage, 144V maximum - Burden: <0.1 VA
3 current
inputs
5A:
(standard)
(galvanically
INPUT VIA CT with 5A secondary output
Burden: 2.5 to 4 mm
2
(13-11 AWG) wire from CT
Overload withstand: 15A RMS continuous, 250A
RMS for 1 second
isolated)
1A:
(optional)
INPUT VIA CT with 1A secondary output
Burden: 2.5 to 4 mm
2
(13-11 AWG) wire from CT
Overload withstand: 3A RMS continuous, 50A
RMS for 1 second
Voltage input terminals
UL recognized E129258
Maximum wire section: 4 mm
2
(10 AWG)
Optically isolated
communication port
EIA RS-485 standard
Maximum wire section: 2.5 mm
2
(12 AWG)
Relay output
Relay rated at 3A, 250 V AC / 3A, 30 V DC /
0.5A, 110 V DC
Maximum wire section: 1.5 mm
2
(14 AWG)
2 contacts (SPST Form A)
Display
3 windows high-brightness 7-segment digit LEDs
3 color LED bar graph 40-110%
Power Supply
Galvanically isolated
power supply (factory
set) 120 or 230 V AC
Maximum wire section: 1.5 mm
2
(14 AWG)
88-138V AC or 176-265V AC; 50/60 Hz;
Burden: 5 VA
Environmental Conditions
Operating temperature
-20°C to +60°C (-4°F to +140°F)
Storage temperature
-25°C to +80°C (-13°F to +176°F)
Humidity
0 to 95% non-condensing

Appendix: Technical Specifications
44
Construction
Instrument
body
Case enclosure: flame resistant ABS & Polycarbonate
blend
Dimensions: 114.3
x 114.3 x 109 mm ( 4.5 x 4.5 x 4.29 “)
Mounting: 4-inch round or 92x92mm square cut-out
Instrument
weight
0.70 kg (1.54 lb.)
Standards Compliance
UL File # E129258
CE-EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
CE-LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC
Harmonized standards to which conformity is declared:
EN55011:1991; EN50082-1:1992; EN61010-1:1993; A2/1995
EN50081-2:1994 EMC Generic Emission Standard - Industrial
Environment
EN50082-2:1995 EMC Generic Immunity Standard - Industrial
Environment
EN55022: 1994 Class A
EN61000-4-2: 1995 Electrostatic Discharge
EN61000-4-4: 1995 Electrical Fast Transient
EN61000-4-8: 1993 Power Frequency Magnetic Field
ENV50140: 1993 Radio Frequency Electromagnetic Field, Amplitude
Modulated
ENV50204: 1995 (200Hz) Radio Frequency Electromagnetic Field, Pulse
Modulated
ENV50141: 1993 Radio Frequency Common Mode, Amplitude Modulated
ANSI C37.90.1: 1989 Surge Withstand Capability
ANSI C62.41 - 1991 Standard Surge

Appendix: Technical Specifications 45
Measurement Specifications
Accuracy, % Range Display resolution (%Rdg)
Parameter Full scale Rdg FS Conditions
@
range
Voltage
120V
×PT
@ 120V
400V×PT
@ 690V
208V
×PT
@ 120V
690V
×PT
@ 690V
0.3 10% to 120% FS 0 to 999,000 V
1 V @ 1V to 9,999 V
≤0.1%
@
10,000 V to 999,000 V
Starting voltage 1.5% FS
Line current
CT PRIMARY CURRENT 0.3 2% to 150% FS 0 to 60,000 A
1 A @ 1A to 9,999 A
≤0.1%
@
10,000 A to 60,000 A
Starting current 0.75% FS
Active power
0.36
×PT×CT @ 120V input
1.2
×PT×CT @ 690V input
0.5
|PF| ≥ 0.5
-2,000,000 to
+2,000,000 kW
1 kW @ 1kW to 9,999 kW
≤0.1%
@
10 MW to 2,000 MW
Reactive power
0. 36
×PT×CT @ 120V input
1.2
×PT×CT @ 690V input
0.5
|PF| ≤ 0.9
-2,000,000 to
+2,000,000 kvar
1 kvar @ 1kvar to 9,999 kvar
≤0.1%
@
10 Mvar to 2,000 Mvar
Apparent power
0. 36
×PT×CT @ 120V input
1.2
×PT×CT @ 690V input
0.5
|PF| ≥ 0.5
0 to
2,000,000 kVA
1 kVA @ 1kVA to 9,999 kVA
≤0.1%
@
10 MVA to 2,000 MVA
Power factor
1 1
|PF| ≥ 0.5,
U ≥ 10% FSU
I ≥ 10% FSI
-0.999 to +1.000 0.001
Frequency
0.1 45.00 to 65.00 Hz 0.01 Hz
For Ln reading
and for
3OP2/3OP3
wiring
modes
For LL
reading except
3OP2/3OP3
wiring modes

Appendix: Technical Specifications
46
Accuracy, % Range Display resolution (%Rdg)
Parameter Full scale Rdg FS Conditions
@
range
Neutral
(unbalanced)
current
CT PRIMARY CURRENT 0.6 2% to 150% FS 0 to 60,000 A
1 A @ 1A to 9,999 A
≤0.1%
@
10,000 A to 60,000 A
Ampere demand same as for current
kW demand (block & sliding) same as for kW
kVA demand (block & sliding ) same as for kVA
Active energy
Import & Export
according to power accuracy
0 to 99,999 MWh
1 kWh @ 1 to 99,999 kWh
10 kWh
@
100.00 to 999.99
MWh
100 kWh
@
1000.0 to 9999.9
MWh
1MWh @ 10.0 to 99.99 GWh
Reactive energy
Import & Export
according to power accuracy
0 to 99,999 Mvarh
1 kvarh @ 1 to 99,999 kvarh
10 kvarh
@
100.00 to 999.99
Mvarh
100 kvarh
@
1000.0 to 9999.9
Mvarh
1Mvarh @ 10.000 to 99.999
Gvarh
Apparent energy
according to power accuracy
0 to 99,999 MVAh
1 kVAh @ 1 to 99,999 kVAh
10 kVAh
@
100.00 to 999.99
MVAh
100 kVAh
@
1000.0 to 9999.9
MVAh
1MVAh @ 10.000 to 99.999
GVAh

Appendix: Technical Specifications 47
Key:
PT = external potential transformer ratio CT, CT Primary Current = primary current rating of external current transformer
FSU = voltage full scale
FSI = current full scale
@ 10% to 120% of voltage FS and 2% to 150% of current FS
Higher resolution is achievable via communications
Where the current is > 10% FS, the energy accuracy is better than 1.5% Rdg.
Additional Notes
1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not include
inaccuracies introduced by the user's potential and current transformers.
2. Specifications assume a reference temperature of 20 - 26
°C.
3. Specifications for kvar, kVA and PF assume voltage and current waveforms with THD
≤ 5%
4. Ordinary measurement error is considerably less than the specified accuracy which indicates maximum error.

Index
accuracy, 47
active energy, 46
active power, 45
ampere demand, v, 20, 25, 35,
38
analog outputs, 20
basic setup, 19
burden, 43
communications, 47
CT, v, 9, 20, 32, 43, 45, 46, 47
CT PRIMARY CURRENT, 20,
45, 46, 47
current inputs, 43
current transformers, 47
demand, v, 20, 25, 26, 34, 35,
37, 38, 46
demand period, v, 20
display, 1, 27, 28, 29, 31, 32, 33,
34, 41, 42
display mode, 31, 34, 41, 42
energy, 1, 22, 29, 33, 34, 39, 46,
47
external synchronization, v, 20
frequency, 45
inputs, 43
Load bar graph, 32
measurement, 47
menu, 17, 19, 21, 22, 23, 24, 27,
28, 29, 30, 31, 39, 41
Modbus, ii, v, 16, 21
mounting, 1, 6
open delta, v, 11, 19, 20
overload withstand, 43
password, 17, 30, 31, 34, 42
PComTest, v, 19
power, i, v, 1, 8, 20, 27, 29, 33,
34, 36, 37, 38, 39, 40, 45, 46
power demand, v, 20
power factor, 45
power source, i, 8
power supply, 43
PT, v, 11, 20, 43, 45, 47
PT RATIO, 20
pulsing, 22, 24, 27
reactive energy, 46
reactive power, 29, 45
relays, 22
reset, v, 20, 31, 34, 40, 41, 42
self tests, 39
setpoints, 20, 23, 24
setup mode, 17
standards, 43
status, 1, 17, 26, 30, 41, 42
technical specifications, 43
terminals, ii, 8, 43
voltage inputs, 43
wiring configuration, 11
Wye, v, 19, 20
48