Satec EM132, EM133, EM133-SE Installation And Operation Manual

BG0491 REV. A12
EM13x Series
SMART MULTIFUNCTION METER
Installation and Operation Manual
2 EM13x Series SMART MULTIFUNCTION METER
LIMITED WARRANTY
The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts from date of dispatch from the distributor. In all cases, this warranty is valid for 36 months from the date of production. This warranty is on a return to factory basis.
The manufacturer does not accept liability for any damage caused by instrument malfunction. The manufacturer accepts no responsibility for the suitability of the instrument to the application for which it was purchased.
Failure to install, set up or operate the instrument according to the instructions herein will void the warranty.
Only a duly authorized representative of the manufacturer may open your instrument. The unit should only be opened in a fully anti-static environment. Failure to do so may damage the electronic components and will void the warranty.
The greatest care has been taken to manufacture and calibrate your instrument. However, these instructions do not cover all possible contingencies that may arise during installation, operation or maintenance, and all details and variations of this equipment are not covered by these instructions.
If the equipment is used in a manner not specified by SATEC LTD, the protection provided by the equipment may be impaired.
For additional information regarding installation, operation or maintenance of this instrument, contact the manufacturer or your local representative or distributor.
All trademarks are property of their respective owners.
Copyright 2007-2017 SATEC LTD.
EM13x Series SMART MULTIFUNCTION METER 3
WARNING
Read the instructions in this manual before performing installation and take note of the following precautions:
1. Ensure that all incoming AC power and other power sources are turned OFF before performing
any work on the instrument. Protect the measurement AC Inputs voltage (V1, V2, V3) with 2A external overcurrent protection device and the power supply source inputs with 5A external overcurrent protection device, located close to the equipment.
2. Before connecting the instrument to the power source, check the labels on the back of the
instrument to ensure that your instrument is equipped with the appropriate power supply voltage, input voltages and currents. Failure to do so may result in serious or even fatal injury and/or equipment damage.
3. Under no circumstances should the instrument be connected to a power source if it is damaged.
4. To prevent potential fire or shock hazard, do not expose the instrument to rain or moisture.
5. The secondary of an external current transformer must never be allowed to be open circuit
when the primary is energized. An open circuit can cause high voltages, possibly resulting in equipment damage, fire and even serious or fatal injury. Ensure that the current transformer wiring is secured using an external strain relief to reduce mechanical strain on the screw terminals, if necessary.
6. Only qualified personnel familiar with the instrument and its associated electrical equipment
must perform setup procedures.
7. Do not open the instrument under any circumstances when it is connected to a power source.
8. Do not use the instrument for primary protection functions where failure of the device can cause
fire, injury or death. The instrument can only be used for secondary protection if needed.
Read this manual thoroughly before connecting the device to the current carrying circuits. During operation of the device, hazardous voltages are present on input terminals. Failure to observe precautions can result in serious or even fatal injury or damage to equipment.
This equipment does not require cleaning for proper operation
4 EM13x Series SMART MULTIFUNCTION METER
Quick Start Guide
This section can be used by a licensed electrician to install and perform basic EM13X setup. For more detailed EM13X Series setup and use instructions, see the following chapters in this manual.
This quick start guide will assist you to have the unit running for the first time.
During the operation of the meter, hazardous voltages are present in the input terminals. Failure to observe precautions can result in serious or even fatal injury or damage to equipment.
For complete and accurate in-depth instructions, refer to the following chapters in this manual.
Installing the EM13X SERIES
Mounting the EM13X SERIES Unit
To mount the EM13X SERIES on Din rail:
Hang the EM13X Series unit on the DIN Rail by positioning the upper side
first then lower side.
Push up the DIN rail brackets to lock the EM13X Series on the rail.
Mounting the EM13X Series on DIN-Rail
EM13x Series SMART MULTIFUNCTION METER 5
To mount the EM13X Series on flat surface:
Locate the EM13X Series on the surface to Push up the DIN rail brackets to lock the EM13X Series on the rail.
Connecting the EM13X Series Unit
Ensure that all incoming power sources are OFF. Check that you have the appropriate power supply. For direct connection, connect to CT wires through the meter CT
terminals. Observe the arrow that indicates the current direction.
In case of a retrofit application or high current external SATEC CT (or
Split Core) where each external CT ends with two wires:
Connect the wire to the meter current termination
screws.
Connect the measured voltage inputs Connect COM1 – RS-485 communication port In case of EM132/133 model with Aux. Power supply connect the Power
Supply inputs using 1.5 mm2/14AWG-dedicated wires.
Common Wiring Mode: EM13x and EM13x-SE 4LL3 or 4Ln3
EM13x-SE: Self Energized Meter model
6 EM13x Series SMART MULTIFUNCTION METER
CT wiring
To connect an Option module:
Assemble the module on the meter. Power the EM13X Series unit on.
Assembly a small module
EM13x Series SMART MULTIFUNCTION METER 7
Assembling the 12DI/4RO module
To operate the EM13X Series:
Perform device diagnostics. Configure the device through the EM13X Series unit front panel display
Configuring the EM13X Series remotely
Install the PAS application software on your PC. Configure the PAS database for your meter. Configure the PAS communications settings. Upgrade the meter firmware if a new version is available. Set up the meter using the PAS application software. Configure your security settings through the meter security setup. Configure your communication protocol settings. Configure Billing/TOU registers.
At this stage, the EM13X Series should be ready for operation.
Chapter 1 General Information Features
8 EM13x Series SMART MULTIFUNCTION METER
Table of Contents
Chapter 1 General Information .......................................................................... 11
1.1 Features .......................................................................................................................13
1.2 Available Options .......................................................................................................14
Digital I/O ............................................................................................................ 15
Analog Output ...................................................................................................... 15
Additional Communication Port– COM2 .................................................................... 15
1.3 Customized Options ..................................................................................................16
Device Resolution .................................................................................................. 16
Display Options ..................................................................................................... 16
1.4 Measured Parameters ..............................................................................................17
1.5 Labelling ......................................................................................................................19
Chapter 2 Installation .......................................................................................... 20
2.1 Site Requirements .....................................................................................................20
2.2 Package Contents ......................................................................................................20
2.3 Mechanical Installation .............................................................................................20
Wall Mounting ....................................................................................................... 22
DIN Rail Mounting ................................................................................................. 23
Add-On Module Mounting ....................................................................................... 24
2.4 Electrical Installation .................................................................................................25
Connecting the wires ............................................................................................. 25
Typical Installation ................................................................................................ 26
Terminals ............................................................................................................. 31
Power Source Connection ....................................................................................... 32
Voltage Input connection ....................................................................................... 34
Current Input Connection ....................................................................................... 35
Wiring Diagrams ................................................................................................... 36
2.5 Battery Replacement ................................................................................................43
2.6 I/O Connections ........................................................................................................44
2DI/1RO Standard ................................................................................................ 44
4DI/2RO Module ................................................................................................... 45
8 DI module ......................................................................................................... 46
12DI/4RO Module ................................................................................................. 46
4AO Module - Analog Outputs ................................................................................. 47
2.7 Communications Connections .................................................................................49
RS-485 Connection ............................................................................................... 50
ETH module – COM2 Ethernet Connection................................................................ 51
PRO module – COM2 PROFIBUS Connection ............................................................. 52
CANopen module – COM2 CANopen Connection ....................................................... 53
RS-232/422-485 module – COM2 Connection .......................................................... 53
Connecting a GSM/GPRS/3G module ....................................................................... 54
Connecting an RF module ...................................................................................... 55
Chapter 3 Using Front Display ............................................................................ 56
Energy Pulse LED .................................................................................................. 56
COMPort Activity LEDs ........................................................................................... 56
VOLTAGES LEDs ................................................................................................... 56
Navigation Buttons ................................................................................................ 56
3.1 Display Operations ....................................................................................................57
Navigation Buttons ................................................................................................ 57
Chapter 1 General Information Features
EM13x Series SMART MULTIFUNCTION METER 9
Navigating in Data Display Mode ............................................................................. 58
Display Features ................................................................................................... 58
Measurement Units ............................................................................................... 59
3.2 Data Displays ..............................................................................................................59
TEST Mode Data Display ........................................................................................ 59
Billing Period Energy Data Displays ......................................................................... 59
TOU/Maximum Demand Power Data Display ............................................................ 61
Instrumentation Measurement Maximum Demand Data Display ................................. 63
Instrumentation Measurement ................................................................................ 64
Status Inputs and Outputs ..................................................................................... 66
Device Info Display ............................................................................................... 67
3.3 Programming Mode ..................................................................................................69
Navigation Buttons ................................................................................................ 69
Entering Numeric Values ........................................................................................ 69
Password Security ................................................................................................. 69
Setup Menus and Access Rights .............................................................................. 69
Viewing and Changing Setup Options ...................................................................... 71
Chapter 4 Using PAS Software ........................................................................... 72
4.1 Installing PAS .............................................................................................................72
4.2 Creating a New Site for your Meter ........................................................................72
Chapter 5 Configuring the EM13X Series .......................................................... 74
5.1 Configuring Communications ..................................................................................74
Setting Up Serial Communication Ports .................................................................... 74
Setting up the Ethernet .......................................................................................... 76
Setting up GPRS Network ...................................................................................... 77
Setting Up eXpertPower Client ................................................................................ 78
Setting Up TCP Notification Client ............................................................................ 79
5.2 General Meter Setup .................................................................................................80
Basic Meter Setup ................................................................................................. 80
Device Options ..................................................................................................... 83
Configuring Digital Inputs ....................................................................................... 84
Configuring Relay Outputs ...................................................................................... 86
Configuring Analog Outputs .................................................................................... 89
Configuring Counters ............................................................................................. 91
Configuring Alarm/Control Setpoints........................................................................ 93
Configuring the Display .......................................................................................... 96
Local Time Settings ............................................................................................... 98
5.3 Configuring Meter Security ................................................................................... 100
5.4 Configuring Billing/TOU ........................................................................................ 102
Configuring Billing/Tariff Registers ......................................................................... 102
Configuring the Daily Tariff Schedule ..................................................................... 104
Configuring the Season Tariff Schedule .................................................................. 105
5.5 Configuring Recorders ........................................................................................... 106
Configuring Meter Memory ................................................................................... 106
Configuring the Event Recorder ............................................................................ 108
Configuring the Data Recorder .............................................................................. 108
5.6 Configuring Communication Protocols ............................................................... 111
Configuring Modbus ............................................................................................. 111
Configuring DNP3 ................................................................................................ 112
Chapter 6 Device Control and Upgrading ....................................................... 115
6.1 Resetting Accumulators, Maximum Values and Files ...................................... 115
6.2 Updating the Meter Clock ...................................................................................... 117
Chapter 1 General Information Features
10 EM13x Series SMART MULTIFUNCTION METER
6.3 Viewing and Clearing Device Diagnostics .......................................................... 118
6.4 Viewing Communication Status and Statistics.................................................. 118
6.5 Remote Relay Control ............................................................................................ 119
6.6 Upgrading Device Firmware ................................................................................. 120
Chapter 7 Monitoring Meters ........................................................................... 122
7.1 Viewing Real-time Data ......................................................................................... 122
7.2 Viewing Real-time Min/Max Log ......................................................................... 125
7.3 Viewing Real-time Waveforms ............................................................................ 125
7.4 Viewing Real-time Harmonic Spectrum ............................................................. 127
Chapter 8 Retrieving and Storing Files ........................................................... 131
8.1 Uploading Files on Demand .................................................................................. 131
8.2 Using the Upload Scheduler.................................................................................. 132
8.3 Viewing Files On-line .............................................................................................. 134
8.4 Exporting Files ......................................................................................................... 134
Exporting Files in COMTRADE and PQDIF Formats ................................................... 134
Exporting Files in Excel Format ............................................................................. 135
8.5 Archiving Files ......................................................................................................... 136
Chapter 9 Viewing Files .................................................................................... 137
9.1 Operations with Files ............................................................................................. 137
9.2 Viewing Options ...................................................................................................... 137
Customizing Views .............................................................................................. 137
Working with Tables ............................................................................................ 138
Working with Graphic Windows ............................................................................. 138
9.3 Viewing the Event Log ........................................................................................... 140
9.4 Viewing the Data Log ............................................................................................. 141
Appendix A Technical Specifications .............................................................. 143
Appendix B Standards Compliance ................................................................. 149
Appendix C Analog Output Parameters ......................................................... 152
Appendix D Setpoint Triggers and Actions .................................................... 154
Appendix E Parameters for Data Monitoring and Logging .......................... 157
Appendix F Billing/TOU Profile Log File ......................................................... 166
Appendix G Data Scales .................................................................................... 168
Appendix H Device Diagnostic Codes ............................................................. 169
Chapter 1 General Information Features
EM13x Series SMART MULTIFUNCTION METER 11
Chapter 1 General Information
The EM13X Series is a compact, multi-function, three-phase AC Powermeter specially designed to meet the requirements of users ranging from electrical panel builders to substation operators.
The EM13X Series measuring and power supply inputs comply with Measuring Category III
The EM13X Series offers standard voltage, current, power and frequency measurements, amp-demand, energy measurements and data logging, harmonic analysis and control capabilities.
The EM13X Series consists of three different models series:
EM132/EM133 with AC/DC Auxiliary Power Supply (40-318V AC/DC)
EM132/EM133-5, internal CT, transformer operated
configuration with current inputs: In = 5A, Imax = 10A
EM132/EM133-1, internal CT, transformer operated
configuration with current inputs: In = 1A, Imax = 2A
EM132/EM133-RS5, external CT, transformer operated
configuration with current inputs (secondary current): In =
2.mA, Imax = 5mA
EM132/EM133-50, internal CT, direct connection
configuration with current inputs: In = 50A, Imax = 63A
EM132/EM133-HACS, external CT, direct connection
configuration with current inputs (secondary current): In = 20mA, Imax = 40mA
EM133-SE – self energized device with 3 Phase Power Supply,
operating from any combination of the measured phases
EM133-SE-5, internal CT, transformer operated configuration
with current inputs: In = 5A, Imax = 10A
EM133-SE-1, internal CT, transformer operated configuration
with current inputs: In = 1A, Imax = 2A
EM133-SE-RS5, external CT, transformer operated
configuration with current inputs (secondary current): In =
2.mA, Imax = 5mA
EM133-SE-50, internal CT, direct connection configuration
with current inputs: In = 50A, Imax = 63A
Chapter 1 General Information Features
12 EM13x Series SMART MULTIFUNCTION METER
EM133-SE-HACS, external CT, direct connection
configuration with current inputs (secondary current): In = 20mA, Imax = 40mA
EM132/EM133-21DC with DC Auxiliary Power Supply (9-36 VDC)
EM132/EM133-21DC-5, internal CT, transformer operated
configuration with current inputs: In = 5A, Imax = 10A
EM132/EM133-21DC-1, internal CT, transformer operated
configuration with current inputs: In = 1A, Imax = 2A
EM132/EM133-21DC-RS5, external CT, transformer operated
configuration with current inputs (secondary current): In =
2.mA, Imax = 5mA
EM132/EM133-21DC-50, internal CT, direct connection
configuration with current inputs: In = 50A, Imax = 63A
EM132/EM133-21DC-HACS, external CT, direct connection
configuration with current inputs (secondary current): In = 20mA, Imax = 40mA
All models series include the following units:
2 lines of 16 characters LCD display. A standard RS-485 communication port, Infra-Red Communication
port and an additional optional Ethernet, Profibus or RS-232/RS­422/RS-485 or RF Modem port. These ports allow local and remote automatic meter readings and setup through the supplemental communication or user data acquisition software
Different communication options for remote communications with the
meter. These options enable LAN and Internet communication with the unit.
Two digital inputs with 10-ms scan time and one relay output with 1-
cycle update time
The EM13X Series is suitable for mounting on both standard DIN-Rail and wall-mount.
Chapter 1 General Information Features
EM13x Series SMART MULTIFUNCTION METER 13
1.1 Features
Multifunctional 3-phase Power Meter
3 voltage inputs and 3 current transformer-isolated AC inputs for
direct connection to power line or via potential and current transformers
True RMS, volts, amps, power, power factor, neutral current, voltage
and current unbalance, frequency
Ampere/Volt demand meter 25/50/60/400
1
Hz measurement capabilities
Billing/TOU Energy Meter
IEC 62053-22 Class 0.5S /ANSI C12.20 Acc. Class 0.5, four-quadrant
active and reactive energy polyphase static meter
Three-phase total and per phase energy measurements; active,
reactive and apparent energy counters
Time-of-Use, 4 totalization and tariff energy/demand registers x 8
tariffs, 4 seasons x 4 types of days, 8 tariff changes per day,
One–time easy programmable tariff calendar schedule Automatic daily energy and maximum demand profile log for total
and tariff registers
Voltage and current THD, current TDD and K-Factor, up to 40th
order harmonic
Voltage and current harmonic spectrum and angles
Real-time Waveform Capture
Real-time “scope mode” waveform monitoring capability Simultaneous 6-channel one-cycle waveform capture at a rate of 64
samples per cycle
Programmable Logical Controller
Embedded programmable controller 16 control setpoints; programmable thresholds and delays Relay output control 1-cycle response time Non-volatile memory for long-term event and data recording Event recorder for logging internal diagnostic events and setup
changes
Two data recorders; programmable data logs on a periodic basis;
automatic daily energy and maximum demand profile log
Digital I/O
2 digital inputs (standard) and four to twelve digital inputs (optional)
with 1/2 cycle scan time; automatic recording of last five digital input
1
25Hz and 400Hz options are available only with internal CT.
Chapter 1 General Information Available Options
14 EM13x Series SMART MULTIFUNCTION METER
change events with timestamps (see the EM13X Series MODBUS Reference Guide)
1 relay output (standard) and two to four relay outputs (optional)
with 1-cycle update time; unlatched, latched, pulse and KYZ operation; energy pulses
Display
Easy to read 2x16 characters LCD display, adjustable update time Auto-scroll option with adjustable page exposition time; auto-return
to a default page
Programmable display auto-scroll sequence
Communications
Standard 2-wire RS-485 communication port; MODBUS RTU, DNP3,
SATEC ASCII and IEC 60870-5-101 communication protocols
Optional second communication port; MODBUS RTU, MODBUS/TCP,
DNP3, DNP3/TCP, SATEC ASCII, PROFIBUS DP, CANopen and IEC 60870-5-104 (over TCP) communication protocols
eXpertPower client for communicating with the SATEC proprietary
eXpertPower Internet services (with the Ethernet/GPRS module)
TCP notification client for communicating with a remote
MODBUS/TCP server on events or periodically on a time basis (with the Ethernet/GPRS module)
Meter Security
Password security for protecting meter setups and accumulated data
from unauthorized changes
Upgradeable Firmware
Easy upgrading device firmware through a serial or Ethernet port.
Software Support
PAS™ – meter configuration and data acquisition SATEC Software
tool
eXpertPower™ – SATEC proprietary Internet services
1.2 Available Options
The EM13X Series can be provided with an optional expansion module from the following list:
Digital I/O Analog outputs Ethernet communication port PROFIBUS DP communication port CANopen communication port RS-232/RS-422/RS-485 communication port Cellular communication port based on ENFORA GPRS or TELIT 3G or
4G engine
RF communication port
Chapter 1 General Information Available Options
EM13x Series SMART MULTIFUNCTION METER 15
Digital I/O
The EM13X Series digital I/O expansion module provides:
4DI/2RO Module
4dry contact digital inputs (DI) for monitoring external contacts and
receiving pulses from energy, water, and gas meters; Programmable de-bounce time; 1-ms scan time.
2 electro-mechanical or solid-state relay outputs (RO) for alarms and
controls, and for output energy pulses; unlatched, latched and pulse operations, failsafe operation for alarm notifications; programmable pulse width; direct remote relay control through communications; 1­cycle update time.
8DI module
8 dry contact digital inputs (DI) for monitoring external contacts and
receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time.
12DI/4RO Module
12 dry contact digital inputs (DI) for monitoring external contacts
and receiving pulses from energy, water, and gas meters; Programmable de-bounce time; 1-ms scan time.
4 electro-mechanical relay outputs (RO) for alarms and controls, and
for output energy pulses; unlatched, latched and pulse operations, failsafe operation for alarm notifications; programmable pulse width; direct remote relay control through communications; 1-cycle update time.
Analog Output
The EM13X Series analog output (AO) expansion module provides:
4 optically isolated analog outputs with an internal power supply; Options for 0-20mA, 4-20mA, 0-1mA, and  1mA output; 1-cycle
update time.
Additional Communication Port– COM2
A second COM2 communication port can be ordered as an expansion module. COM2 options available:
Ethernet 10/100BaseT port; MODBUS/TCP, DNP3/TCP or IEC 60870-
5-104 communications protocols
PROFIBUS DP port CANopen port RS-232/RS-422/RS-485 port; MODBUS RTU, DNP3 or IEC 60870-5-
101, and SATEC ASCII communication protocols;
GPRS or 3G/4G cellular communications port; MODBUS/TCP protocol RF communication; MODBUS RTU protocol
Chapter 1 General Information Customized Options
16 EM13x Series SMART MULTIFUNCTION METER
1.3 Customized Options
Presentation of data on the front display and via communications can be customized to best suit the user application.
Device Resolution
A low or high-resolution option can be selected for the presentation of voltage, current, and power for use in high and low power applications.
Display Options
Different display options are available for customization to be used in dark or non-safe locations, or in places that are hardly accessible for observation.
Chapter 1 General Information Measured Parameters
EM13x Series SMART MULTIFUNCTION METER 17
1.4 Measured Parameters
Table 1: Measured and Displayed Parameters
Parameter
Display
Comm.
Analog
Pulse
Alarm
1-cycle Real-time Measurements
RMS Voltage per phase
 
RMS Current per phase
 
kW per phase
 kvar per phase
 kVA per phase
 Power Factor per phase
 Total kW
 
Total kvar
 
Total kVA
 
Frequency
 
Neutral Current
 
Total Power Factor
 
Voltage & Current unbalance
1-sec Average Measurements
RMS Voltage per phase
RMS Current per phase
kW per phase
 kvar per phase
 kVA per phase
 Power Factor per phase
 Total kW
Total kvar
Total kVA
Total Power Factor
Frequency
Neutral Current
Voltage & Current unbalance
Amps & Volt Demands
Ampere & Volt Demand per phase
 Ampere Maximum Demand per phase
 Voltage Maximum Demand per phase
 Power Demands
kW Accumulated Demand Import & Export
 
kvar Accumulated Demand Import & Export
 
kVA Accumulated Demand
 
kW Demand Import & Export
 kvar Demand Import & Export
kVA Demand
 kW Sliding Demand Import & Export
 kvar Sliding Demand Import & Export
 kVA Sliding Demand
 kW Predicted Demand Import & Export
 kvar Predicted Demand Import & Export
 kVA Predicted Demand
 kW Maximum Demand Import
kW Maximum Demand Export
Chapter 1 General Information
18 EM13x Series SMART MULTIFUNCTION METER
Parameter
Display
Comm.
Analog
Pulse
Alarm
kvar Maximum Demand Import
kvar Maximum Demand Export
kVA Maximum Demand
Total Energy
Total kWh Import & Export
 
Total kvarh Import & Export
 
Total kvarh Net
Total kVAh
 
Energy per Phase
kWh Import per phase
kvarh Import per phase
kVAh per phase
TOU Registers
4 TOU energy registers (kWh and kvarh import & export, kVAh, 4 pulse sources)
4 TOU maximum demand registers
8 tariffs, 4 seasons x 4 types of day
Harmonic MeasurementsEH
Voltage THD per phase
Current THD per phase
Current TDD per phase
K-factor per phase
Voltage harmonics per phase up to order 40
Current harmonics per phase up to order 40
Voltage harmonic angles up to order 40
Current harmonic angles up to order 40
Fundamental Component
Voltage and Current per phase
kW, PF per phase
kvar, KVA per phase
Total kW, PF
Total kvar, KVA
Min/Max Logging
Min/Max A, V, total kW, kvar, kVA, PF
Min/Max Frequency, Neutral current
Phase Rotation
 Voltage and Current Phase Angles
Day and Time
Pulse Counters
 Digital Inputs (optional)
 Relay Outputs (optional)
 Remote Relay Control (optional)
Alarm Triggers/Setpoints
 Self-diagnostics
Chapter 1 General Information Labelling
EM13x Series SMART MULTIFUNCTION METER 19
1.5 Labelling
Figure 1-1 EM133 label – UL marking
Figure 1-2 EM133 label – NMI marking
Figure 1-3 EM133 label – CE MID marking
Chapter 2 Installation Site Requirements
20 EM13x Series SMART MULTIFUNCTION METER
Chapter 2 Installation
This chapter discusses the following types of physical installations for the EM13X Series SMART MULTIFUNCTION METER:
Mechanical Installation Electrical Installation I/O Connections COM Port Connections.
2.1 Site Requirements
Environmental conditions: as specified in Technical Specifications in
Appendix A
Electrical requirements: as specified in Technical Specifications in
Appendix A
See Technical Specifications in Appendix A for more details
2.2 Package Contents
The EM13X Series SMART MULTIFUNCTION METER package contains the following items:
EM13X Series SMART MULTIFUNCTION METER unit Technical Documentation CD EM13X Series Quick Start guide
2.3 Mechanical Installation
Refer to the figures provided in this section to properly perform the mechanical installation.
Chapter 2 Installation Mechanical Installation
EM13x Series SMART MULTIFUNCTION METER 21
Figure 2-1 Dimensions
Chapter 2 Installation Mechanical Installation
22 EM13x Series SMART MULTIFUNCTION METER
Wall Mounting
To mount the meter on the wall:
Position the meter on the wall according to hole locations as shown in figure 2-2
Affix the meter using washers and nuts.
Figure 2-2. Surface Mounting
Chapter 2 Installation Mechanical Installation
EM13x Series SMART MULTIFUNCTION METER 23
DIN Rail Mounting
The EM13X Series can be mounted on a standard 35-mm DIN rail as shown in figure 2-3
Figure 2-3. EM13X Series DIN Rail Mounting
Chapter 2 Installation Mechanical Installation
24 EM13x Series SMART MULTIFUNCTION METER
Add-On Module Mounting
Before Add-On Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
Turn off the EM13X Series auxiliary power supply or voltage supply inputs (SE model).
Remove the module connector cover from the EM13X Series to access the module connector as shown in figure 2-4below
Figure 2-4. EM13X Series module connector location
Figure 2-5. EM13X Series module assembly
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 25
2.4 Electrical Installation
The equipment installation shall conform to the following instructions:
a) a switch or circuit-breaker shall be included in the building installation as close as possible to the equipment supply voltage;
b) It shall be in close proximity to the equipment and within easy reach of the OPERATOR;
c) It shall be marked as the disconnecting device for the equipment.
d) Before installing, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
e) The current sensors may not be installed in a panel where they exceed 75% of the wiring space of any cross-sectional area within the panel.
Connecting the wires
All conductors must be stranded copper. All conductors and insulation systems and crimped devices must be appropriate for the application. SATEC requires using crimped ferrules on stranded wire.
Table 3 below summarizes the different conductors’ sizes to be used in the EM133 external connections.
Table 2: Wiring Configurations
Terminals
Conductor size
Torque
[Nm]
Notes EM133 model
Minimum
AWG (mm²)
Maximum
AWG (mm²)
Aux. Power Supply Inputs
L/+, N/-
N/A in EM133­SE models
22 (0.5)
12 (4.0)
0.5-0.7
Use 600V insulated conductors Required crimped ferrule: Panduit (22AWG) F75-10-M Panduit (12AWG) F81-15-M
Voltages Inputs V1, V2, V3, Vn
N/A in EM133­SE-100A
22 (0.5)
12 (4.0)
0.5-0.7
Use 600V insulated conductors Required crimped ferrule: Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M
Current Inputs I1, I2, I3, N
EM133/SE­1A, 5A, HACS
22 (0.5)
10 (6.0)
1.8-2
Use 600V insulated conductors Required crimped ferrule: Panduit (22AWG) F75-10-M
Panduit (10AWG) F82-15-M
Current Inputs I1, I2, I3, N
EM133/SE­100A
6 (16)
4 (25)
2-2.7
Use 600V insulated conductors Required crimped ferrule: Panduit (6AWG) F84-15-M
Panduit (4AWG) F85-15-M
COM1, I/O connections
All Models
22 (0.5)
12 (4.0)
0.5-0.7
Use 600V insulated conductors Required crimped ferrule: Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M
Chapter 2 Installation Electrical Installation
26 EM13x Series SMART MULTIFUNCTION METER
Typical Installation
Figure 2-6a Typical Installation Diagram with Auxiliary Power Supply
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 27
Figure 2-6b Typical Installation Diagram with Self Energized Power Supply – direct connection with HACS
*
*
1. SATEC RF chokes to be installed between CBR and Meter
Voltage Inputs in residential area or other places require ANCI C12.20 compliance. Otherwise it may be bypassed.
2. AC0242 shall be routed with the voltage lines (bundled),
separately from communication & I/O lines
Chapter 2 Installation Electrical Installation
28 EM13x Series SMART MULTIFUNCTION METER
Figure 2-6c Typical Installation Diagram with Self Energized Power Supply – direct connection
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 29
Figure 2-6d Typical Installation Diagram with Self Energized Power Supply – Transformer Operated
(indirect connection)
*
*
1. SATEC RF chokes to be installed between CBR and Meter
Voltage Inputs in residential area or other places require ANCI C12.20 compliance. Otherwise it may be bypassed.
2. AC0242 shall be routed with the voltage lines (bundled),
separately from communication & I/O lines
Chapter 2 Installation Electrical Installation
30 EM13x Series SMART MULTIFUNCTION METER
Figure 2-6e Typical Installation Diagram with 12/24 VDC Auxiliary Power Supply
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 31
Terminals
The EM132/133/133-SE terminals are constructed as a built-in part of the meter equipment. The terminals are divided in two different terminal categories:
1) High power terminal, dedicated to current terminals only, with a
torque rating of 2.0-2.3Nm
2) Low power terminal, dedicated to voltage, Digital Inputs, COM1
and Relay output terminals only with a torque rating of 0.5-0.7Nm
Figure 2-7a Terminals View EM133 Model
Chapter 2 Installation Electrical Installation
32 EM13x Series SMART MULTIFUNCTION METER
Figure 2-7b Terminals View EM133-SE Model
Power Source Connection
The equipment installation shall conform to the following instructions:
a) a switch or circuit-breaker shall be included in the building installation as close as possible to the equipment supply voltage;
b) It shall be in close proximity to the equipment and within easy reach of the OPERATOR;
c) It shall be marked as the disconnecting device for the equipment.
d) Before installing, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
e) The current sensors may not be installed in a panel where they exceed 75% of the wiring space of any cross-sectional area within the panel.
The power source can be a dedicated fuse or a monitored voltage if it is within the instrument power supply range.
To connect an AC Auxiliary Power Supply (EM133 model only):
Connect the Line wire to terminal (9).
Connect the Neutral wire to terminal (10)
To connect to a DC Auxiliary Power Supply (EM133 and EM133-21DC models only):
Connect the positive wire to terminal (9)
Connect the negative wire to terminal (10)
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 33
Figure 2-8 EM13X Series Auxiliary Power Supply connection
Chapter 2 Installation Electrical Installation
34 EM13x Series SMART MULTIFUNCTION METER
Voltage Input connection
The equipment installation shall conform to the following instructions:
a) a switch or circuit-breaker shall be included in the building installation as close as possible to the equipment supply voltage;
b) It shall be in close proximity to the equipment and within easy reach of the OPERATOR;
c) It shall be marked as the disconnecting device for the equipment.
d) Before installing, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
e) The current sensors may not be installed in a panel where they exceed 75% of the wiring space of any cross-sectional area within the panel.
EM13x Series (with Aux. Power Supply) 690V Inputs (Standard)
Figure 2-9EM13X Series (with Aux. Power Supply) measured Voltage connections
690V inputs are usually used with direct connection. Use any of the seven wiring configurations shown in Figures 2-8 through 2-15.
EM13X-SE model Voltage connections
Figure 2-10 EM13X-SE model measured Voltage connections
EM133-SE model with measuring nominal current 1A or 5A or 2.5mA (using RS5), indirect connection – nominal voltage input is 120(207) to 277 (480) VAC.
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 35
EM133-SE model with measuring nominal current 50A or 20mA (using HACS), direct connection – nominal voltage input is up to 230(400) VAC.
Current Input Connection
The EM13X Series consists of five different models according to the current inputs measurement:
1A nominal current (2A maximum) using internal CT – transformer operated Connection
5A nominal current (10A maximum) using internal CT – transformer operated Connection
50A nominal current (63A maximum) using internal CT – Direct Connection, in EM133-SE model Current Inputs and Voltage Inputs are internally connected together
20mA nominal current (40mA maximum) using HACS (external CT provided by SATEC) – Transformer Connection
2.5mA nominal current (5mA maximum) using RS5 (external CT provided by SATEC) – Transformer Connection
Figure 2-11 EM13X Series measured Current connections
Chapter 2 Installation Electrical Installation
36 EM13x Series SMART MULTIFUNCTION METER
Wiring Diagrams
For AC input ratings, see Technical Specifications in Appendix A for more details.
Table 3 presents the available wiring configurations in the meter.
Table 3: Wiring Configurations
Wiring Configuration
Setup Code
Figure
3-wire 2-element Delta direct connection using 2 CTs
3dir2
2-12
4-wire 3-element Wye direct connection using 3 CTs
4Ln3 or 4LL3
2-13
4-wire 3-element Wye connection using 3 PTs, 3 CTs
4Ln3 or 4LL3
2-14
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs
3OP2
2-15
4-wire 2½-element Wye connection using 2 PTs, 3 CTs
3Ln3 or 3LL3
2-16
3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs
3OP3
2-17 4-wire 3-element Delta direct connection using 3 CTs
4Ln3 or 4LL3
2-18
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs
3bLn3 or 3bLL3
2-19
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 37
Figure 2-12 3-Wire 2-Element Delta Direct Connection Using 2 CTs (Wiring Mode = 3dir2)
Chapter 2 Installation Electrical Installation
38 EM13x Series SMART MULTIFUNCTION METER
Figure 2-13 4-Wire Wye 3-Element Direct Connection Using 3 CTs (Wiring Mode = 4LL3 or 4Ln3)
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 39
Figure 2-14 4-Wire Wye 3-Element Connection Using 3 PTs, 3 CTs (Wiring Mode = 4LL3 or 4Ln3)
Figure 2-15a 3-Wire 2-Element Open Delta Connection Using 2 PTs, 2 CTs (Wiring Mode = 3OP2)
Chapter 2 Installation Electrical Installation
40 EM13x Series SMART MULTIFUNCTION METER
Figure 2-15b 3-Wire 2-Element Open Delta Connection Using 3 PTs, 2 CTs (Wiring Mode = 3OP2)
This configuration provides accurate power measurements only if the voltages are balanced.
Figure 2-16 4-Wire Wye 2½-Element Connection Using 2 PTs, 3 CTs (Wiring Mode = 3LL3 or 3Ln3)
Chapter 2 Installation Electrical Installation
EM13x Series SMART MULTIFUNCTION METER 41
Figure 2-17 3-Wire 2½-Element Open Delta Connection Using 2 PTs, 3 CTs (Wiring Mode = 3OP3)
Figure 2-18 4-Wire 3-Element Delta Direct Connection Using 3 CTs (Wiring Mode = 4LL3 or 4Ln3)
Chapter 2 Installation Electrical Installation
42 EM13x Series SMART MULTIFUNCTION METER
Figure 2-19 3-Wire 2½-Element Broken Delta Connection Using 2 PTs, 3 CTs (Wiring Mode = 3bLn3 or
3bLL3)
Chapter 2 Installation Battery Replacement
EM13x Series SMART MULTIFUNCTION METER 43
2.5 Battery Replacement
WARNING!
Only qualified personnel familiar with the instrument and its associated electrical equipment must perform the RTC battery backup replacement.
The battery replacement must be performed while equipment power supply is "ON"
To replace the CR2032 RTC battery:
1) Remove the EM13X Series cover
2) Remove the old battery by lifting up the battery holder retractable tab.
3) Place the new CR2032 battery into the battery holder while holding up the battery holder retractable tab in such a way that the (+) battery pole
is toward the battery holder, as shown in Figure 2-7.
Figure 2-7 EM13X Series Battery Replacement
Chapter 2 Installation I/O Connections
44 EM13x Series SMART MULTIFUNCTION METER
2.6 I/O Connections
Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
For I/O ratings, see Technical Specifications in Appendix A.
2DI/1RO Standard
Relay Output
The EM13X Series basic provides one dry contact relay (SSR FORM A) for energy pulsing, alarms or remote control
Figure 2-8 EM13X Series Relay output connection
Digital Inputs
Two optically isolated status inputs are provided for status monitoring, pulse counting, external power demand period, and time synchronization.
Figure 2-9 EM13X Series Digital Input connections
Chapter 2 Installation I/O Connections
EM13x Series SMART MULTIFUNCTION METER 45
4DI/2RO Module
Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
Figure 2-10 4DI/2RO Module Assembly
Relay Outputs
There are two relay outputs provided for energy pulsing, alarms, or remote control.
Figure 2-11 Relay Output Connection
Digital Inputs
Four optically isolated status inputs are provided for status monitoring, pulse counting, external power demand period, and time synchronization.
Figure 2-12 4 DI/2DO - Digital Input Connection
Chapter 2 Installation I/O Connections
46 EM13x Series SMART MULTIFUNCTION METER
8 DI module
Eight optically isolated status inputs are provided for status monitoring, pulse counting, external power demand period, and time synchronization
Figure 2-13 8 DI - Digital Input Connection
12DI/4RO Module
The 12DI/4RO module can be equipped with optional communication port COM2 – ETHERNET or RS-422/485.
Figure 2-14 12DI/4RO Module
Relay Outputs
There are four electro-mechanic relay outputs provided for energy pulsing, alarms, or remote control.
Chapter 2 Installation I/O Connections
EM13x Series SMART MULTIFUNCTION METER 47
Figure 2-15 Relay Output Connection
Digital Inputs
12 optically isolated status inputs are provided for status monitoring, pulse counting, external power demand period, and time synchronization.
Figure 2-16 12 Digital Input Connection
4AO Module - Analog Outputs
The 4AO module has four optically isolated analog outputs with an internal power supply and current output options of 0-20 mA and 4-20 mA (current loop load of up to 500 Ohm), 0-1 mA and ±1 mA (2mA 100% overload, current loop load of up to 5 kOhm).
Chapter 2 Installation I/O Connections
48 EM13x Series SMART MULTIFUNCTION METER
Figure 2-17 4AO Module Assembly
Figure 2-18 Analog Output Connection
It is recommended to connect unused Analog output channels to Common terminal.
The 4AO module TERMINAL is for use only with equipment which has no live parts which are ACCESSIBLE
The RATING of the insulation of the external equipment for use with the 4AO module, shall comply according to Installation Category III for insulation to be suitable for SINGLE FAULT CONDITION
The external equipment TERMINAL connection type is normally terminal block for wire size 14 AWG (up to 1.5 mm2)
The type of equipment that might be connected to the TERMINAL is:
Programmable Logic Controller for automation – PLC
Digital or Analog meter
Chapter 2 Installation Communications Connections
EM13x Series SMART MULTIFUNCTION METER 49
2.7 Communications Connections
Before installing the Communication Module, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
Several communication options are available for the EM13X Series:
COM1 (standard): RS-485 COM2 (optional module):
Ethernet 10/100BaseT
PROFIBUS DP
CANopen
RS-232 or RS-422/485
GPRS/3G/4G
RF
COM3 (standard): IR
A full description of the communication protocols is found in the EM13X Series protocol guides that come with your meter.
Chapter 2 Installation Communications Connections
50 EM13x Series SMART MULTIFUNCTION METER
RS-485 Connection
Figure 2-19 COM1 RS-485 2-Wire Connection
Communication cable Specification: Shielded, #22AWG.
Note: pay attention to GND connection (SH->GND).
RS-485 COM1
Chapter 2 Installation Communications Connections
EM13x Series SMART MULTIFUNCTION METER 51
ETH module – COM2 Ethernet Connection
Figure 2-20 COM2 Ethernet Connection
The ETH module TERMINAL is for use only with equipment which has no live parts which are ACCESSIBLE
The RATING of the insulation of the external equipment for use with the ETH module, shall comply according to Installation Category III for insulation to be suitable for SINGLE FAULT CONDITION
The external equipment TERMINAL connection type is RJ-45
The type of equipment that might be connected to the TERMINAL is:
Personal Computer – PC or LAPTOP
10/100Base-T LAN HUB and/or Switch
Chapter 2 Installation Communications Connections
52 EM13x Series SMART MULTIFUNCTION METER
PRO module – COM2 PROFIBUS Connection
Figure 2-21 COM2 PROFIBUS Connection
The PRO module TERMINAL is for use only with equipment which has no live parts which are ACCESSIBLE
The RATING of the insulation of the external equipment for use with the PRO module, shall comply according to Installation Category III for insulation to be suitable for SINGLE FAULT CONDITION
The external equipment TERMINAL connection type is DB9
The type of equipment that might be connected to the TERMINAL is:
Programmable Logic Controller for automation – PLC
Chapter 2 Installation Communications Connections
EM13x Series SMART MULTIFUNCTION METER 53
CANopen module – COM2 CANopen Connection
RS-232/422-485 module – COM2 Connection
Figure 2-22 COM2 RS-232 connection
Chapter 2 Installation Communications Connections
54 EM13x Series SMART MULTIFUNCTION METER
Figure 2-23 COM2 RS-422/485 connection
The RS-232/422-485 module TERMINALS are for use only with equipment which has no live parts which are ACCESSIBLE
The RATING of the insulation of the external equipment for use with The RS-232/422-485 module, shall comply according to Installation Category III for insulation to be suitable for SINGLE FAULT CONDITION
The external equipment TERMINAL connection type is normally terminal block for wire size 14 AWG (up to 1.5 mm²) – RS­422/485 port and DB9 male-to-female cable more than 22 AWG (0.3mm²)
The type of equipment that might be connected to the TERMINAL is:
Personal Computer – PC or LAPTOP
Connecting a GSM/GPRS/3G module
A GSM/GPRS modem can be connected to the meter COM2 port to provide communications with the remote MODBUS/TCP server via a wireless GPRS network.
Figure 2-24 COM2 GPRS/3G module Connection
Chapter 2 Installation Communications Connections
EM13x Series SMART MULTIFUNCTION METER 55
The GSM/GPRS SIM must not have any incoming voice call. The customer must require from the Service Provider for DATA services only
The GPRS modem module can be equipped with two different antennas: internal Antenna for installation into plastic closet or no-metallic environment. For metallic installation use external antenna
See Setting Up GPRS in Chapter 5 for information on configuring GPRS communications in your meter.
Connecting an RF module
Figure 2-25 COM2 RF module Connection
The RF modem module can be equipped with two different antennas: internal Antenna for installation into plastic closet or no-metallic environment. For metallic installation use external antenna
Chapter 3 Using Front Display Communications Connections
56 EM13x Series SMART MULTIFUNCTION METER
Chapter 3 Using Front Display
This chapter provides EM13X Series SMART MULTIFUNCTION METER front panel information and operating procedures.
Figure 3-1: EM13X Series Unit
Energy Pulse LED
The EM13X Series has a red “Energy Pulse” LED. It flashes at a constant rate when a load is applied to the meter.
There are two modes of LED operation:
NORMAL mode: the LED pulses indicate imported Wh at a rate of
1,000 pulses per kWh
TEST mode: the LED pulses indicate either imported Wh, or
imported (inductive) varh at a rate of 10,000 pulses per kWh/kvarh
The energy test mode can be enabled through the Device Options setup. When in test mode, the energy and demand accumulators do not account for consumed energy.
COMPort Activity LEDs
The meter has two yellow LEDs “RX” and “TX”, which indicate activity on the COM1 communication port. The LEDs flash when the port is receiving or transmitting data.
VOLTAGES LEDs
The meter has three green LEDs “L1, "L2" and "L3”, which indicate
voltage measurement input presence. When LEDs are "ON", that means that the voltage measurement inputs exist in the meter
Navigation Buttons
The EM13X Series is provided with two push buttons that are normally used to navigate between different measurement displays.
The "UP" and "DOWN" function of buttons changes depending on what operating mode the display is in. In programming mode, the buttons access the device setup menus where the default factory-set device settings can be changed.
Chapter 3 Using Front Display Display Operations
EM13x Series SMART MULTIFUNCTION METER 57
3.1 Display Operations
The EM13X Series has a high-contrast graphical LCD display with backlight for local data read outs, meter setup and servicing.
The display operates in two modes:
Multi-page data display mode with Auto-Scroll feature allows you to
scroll through display screens and pages to view various billing, instrumentation and status data.
Programming mode allows you to enter menu-driven device setups
for inspecting and changing factory set meter parameters, or resetting maximum demands, counters and device diagnostics messages. The display is normally updated once per second except of the clock display where the update rate changes to twice per second.
Navigation Buttons
The EM13X Series is provided with two navigation buttons,
SELECT/ENTERbutton and SCROLL button.
You can perform three types of actions with each button:
Short press, or “press and release” Long press, or “press and hold for 1 to 2 seconds” Extended press, or ”press and hold for 5 seconds or longer ”
The function of each button changes depending on what operating mode the display is in.
The SCROLL button operates once it is briefly pressed. It has two functions:
In data display mode, it scrolls through the display pages. In programming mode, it scrolls through the menu items and allows
changing a selected digit when entering numbers.
The SELECT/ENTER button normally operates once it’s released. The button function changes depending on the time the button is pressed:
In data display mode, when pressed briefly and released, it scrolls
through the display views; a long press for more than 5 seconds switches to programming mode.
In programming mode, when pressed briefly and released, it moves
from one menu item to another; a long press for one second selects a highlighted menu item allowing to enter a submenu or to store a changed item.
In data display mode, when the SCROLL and SELECT/ENTER buttons are briefly pressed together and then released, the current display returns to the start page; in some pages, an extended press for more
than 5 seconds is used as a “shortcut” for immediate entering a
specific programming menu.
Chapter 3 Using Front Display Display Operations
58 EM13x Series SMART MULTIFUNCTION METER
Navigating in Data Display Mode
The following table gives a summary of the button operations in data display mode.
Button
Press
Operations
SCROLL
Short press
Scroll through pages
SELECT/ENTER
Short press
Scroll through displays
SELECT/ENTER
Long press
Enter programmed parameter
SELECT/ENTER
Extended press
Enter programming mode
The EM13X Series provides 7 different multi-page data displays. See
Data Displays for the full displays list and enumeration.
Display Features
The EM13X Series display has a number of programmable features that can be disabled, enabled and adjusted via the meter Display Setup (see Display Setup in Chapter 5).
Backlight
A short press on any button while the display backlight is off switches the backlight on.
The backlight stays on as long as you selected in the display setup and then dims to conserve power. The backlight time is factory set to 1 minute and can be programmed from 1 to 10 minutes. You can temporarily set the backlight to continuous operation if you need to work in dark for more time.
Auto-Return
If the Auto-Return feature is enabled and no button is pressed for the programmable Auto-Return interval (1 to 30 minutes for data displays; fixed at 5 minutes for setup menus), the display automatically returns to the default page from any other data display or a setup menu.
If the Auto-Scroll feature is enabled, the display immediately enters the auto scroll sequence.
Auto-Scroll
If the Auto-Scroll feature is enabled, the data display automatically scrolls through all pages of all data displays that are included into the programmable auto-scroll sequence. The scroll interval is adjustable in the range of 2 to 30 seconds. The scroll sequence may include all or only selected displays.
The display automatically enters auto scrolling if no button is pressed for the Auto-Return interval when the Auto-Return feature is enabled or in 1 minute if this feature is disabled. In the last case, the scroll sequence is restored from the point where it was interrupted.
To stop auto scrolling, press briefly any button if the backlight is on; else press briefly any button twice since the first press only sets the backlight on and does not affect auto scrolling.
Auto-Scroll is not operational in TEST mode.
Chapter 3 Using Front Display Data Displays
EM13x Series SMART MULTIFUNCTION METER 59
Measurement Units
The following table shows the display resolution for common displayed quantities. All measured data is displayed in primary units.
Measured
Quantity
Voltage Connection
Units and Display Resolution
Energy
kWh, kvarh, kVAh with one decimal place. The number of digits is programmable (see Device Options
and Mode Control in Chapter 5).
Power
Direct
(PT = 1.0)
kW, kvar, kVA with three decimal places
Transformer
(PT>1.0)
MW, Mvar, MVA with three decimal places
Voltage
Direct
(PT = 1.0)
Volts with one decimal place
Transformer
(PT>1.0)
Kilovolts with three decimal places
Current
Amperes with two decimal places
3.2 Data Displays
The EM13X Series has 7 multi-page data displays listed in the following table.
Display Sequence
Display type
Display Contents
1
Billing/TOU reg.
Energy billing period data
2
TOU/Max. DEMAND
Max. DMD Power billing period data 3 Energy
Total and Phase Energy data
4
MAX. DEMAND
Engineering maximum demands
5
Measurement
Instrumentation data
6
Phase Rotation
Phase, I/O and Counter data
7
Diagnostics
Device diagnostics messages and Device service data
TEST Mode Data Display
The TEST data display is shown in TEST mode in place of the billing period data displays, "NORM" is replaced by "TEST". See Device
Options and Mode Control in Chapter 5 on how to enter the meter
TEST mode.
DISPLAY
Description
11:13:11 TEST 20/09/2011 T1 -
TEST mode display: test LED pulse rate in secondary Wh/imp, test kWh and kvarh energy registers readings in primary units with an extended 0.001 kWh resolution.
Billing Period Energy Data Displays
The EM13X Series provides billing period data displays for energy and general purpose volume data as m³, cf or Ccf calculated using Digital Input for water and/or gas meter application.
Only registers you selected in the billing/TOU register setup and tariff rates listed in the TOU daily profiles are included (see Configuring
Billing/Tariff Registers and Configuring the Daily Tariff Schedule in
Chapter 5).
Chapter 3 Using Front Display Data Displays
60 EM13x Series SMART MULTIFUNCTION METER
The following example demonstrates the present billing period displays for two configured billing registers (kWh imported and kvarh imported) and for three active tariff rates. The actual register contents in your installation may be different depending on your selection of register sources.
DISPLAY
Description
Reg 1 Imp 725 kWh
Total Import Active energy data. Billing period according to TOU predefined profile (Reg1 for TOU actve energy and Reg2 for TOU reactive energy are predefined TOU/Register factory setup, can be changed by user, see Configuring
Billing/Tariff Registers and Configuring the Daily Tariff Schedule in Chapter 5)
Reg 1/T1 Imp 517 kWh
Tariff 1 Import Active energy data.
Reg 1/T2 Imp 114 kWh
Tariff 2 Import Active energy data.
Reg 1/T3 Imp 94 kWh
Tariff 3 Import Active energy data.
Reg 2 Imp 221 kvarh
Total Import Reactive energy data.
Reg 2/T1 Imp 165 kvarh
Tariff 1 Import Reactive energy data.
Reg 2/T2 Imp 35 kvarh
Tariff 2 Import Reactive energy data.
Reg 2/T3 Imp 21 kvarh
Tariff 3 Import Reactive energy data.
Single Phase billing data2 Total Import Phase 1 active energy data
Tariff 1 Import Phase 1 active energy data.
2
Only from S/W V12.2.1
Chapter 3 Using Front Display Data Displays
EM13x Series SMART MULTIFUNCTION METER 61
Tariff 2 Import Phase 1 active energy data.
Tariff 3 Import Phase 1 active energy data.
Total Import Phase 2 active energy data
Tariff 1 Import Phase 2 active energy data.
Tariff 2 Import Phase 2 active energy data.
Tariff 3 Import Phase 2 active energy data.
Total Import Phase 3 active energy data
Tariff 1 Import Phase 3 active energy data.
Tariff 2 Import Phase 3 active energy data.
Tariff 3 Import Phase 3 active energy data.
TOU/Maximum Demand Power Data Display
The following example demonstrates the TOU/Maximum Demand displays for three configured registers (MAX kW imported, MAX kvar imported and MAX kVA imported) and for three active tariff rates. The actual register contents in your installation may be different depending on your selection of register sources.
DISPLAY
Description
Chapter 3 Using Front Display Data Displays
62 EM13x Series SMART MULTIFUNCTION METER
DISPLAY
Description
Reg 1 Imp MAX
0.008 kW
Total Import Max. DMD active power data (Reg1 for TOU/Max. DMD actve power, Reg2 for TOU/Max. DMD reactve power predefined TOU/Register factory setup, can be changed by user, see Configuring
Billing/Tariff Registers and Configuring the Daily Tariff Schedule in Chapter 5)
Reg 1/T1 Imp MAX
0.008 kW
Tariff 1 Import max. active power dmd data.
Reg 1/T2 Imp MAX
0.008 kW
Tariff 2 Import max. active power dmd data
Reg 1/T3 Imp MAX
0.002 kW
Tariff 3 Import max. active power dmd data
Reg 2 Imp MAX
0.003 kvar
Total Import Max. DMD reactive power data
Reg 2/T1 Imp MAX
0.003 kvar
Tariff 1 Import max. reactive power dmd data.
Reg 2/T2 Imp MAX
0.003 kvar
Tariff 2 Import max. reactive power dmd data.
Reg 2/T3 Imp MAX
0.001 kvar
Tariff 3 Import max. reactive power dmd data.
Reg 3 Imp MAX 0 kVA
Total Import Max. DMD apparent power data
Reg 3/T1 Imp MAX 0 kVA
Tariff 1 Import max. apparent power dmd data.
Reg 3/T2 Imp MAX 0 kVA
Tariff 2 Import max. apparent power dmd data.
Reg 3/T3 Imp MAX 0 kVA
Tariff 3 Import max. apparent power dmd data.
Chapter 3 Using Front Display Data Displays
EM13x Series SMART MULTIFUNCTION METER 63
Instrumentation Measurement Maximum Demand Data Display
Maximum demand displays show engineering maximum demands (not billing maximum demands) for import/export powers, voltages, and currents.
DISPLAY
Description
MAX. DMD P Imp 0.008 kW
Total Import Max. DMD active power data
MAX. DMD P Exp 0 kW
Total Export Max. DMD active power data
MAX. DMD Q Imp 0.003 kvar
Total Import Max. DMD reactive power data
MAX. DMD Q Exp 0 kvar
Total Export Max. DMD reactive power data
MAX. DMD S 0.008 kVA
Total Import Max. DMD apparent power data
MAX. DMD I1 0 A
Max. DMD Phase 1 current data
MAX. DMD I2 0 A
Max. DMD Phase 2 current data
MAX. DMD I3 0 A
Max. DMD Phase 3 current data
MAX. DMD In 0 A
Max. DMD neutral current data
MAX. DMD V1 0 V
Max. DMD Phase 1 voltage data
MAX. DMD V2 0 V
Max. DMD Phase 2 voltage data
Chapter 3 Using Front Display Data Displays
64 EM13x Series SMART MULTIFUNCTION METER
MAX. DMD V3 0 V
Max. DMD Phase 3 voltage data
Instrumentation Measurement
Instrumentation Measurements represent general instrumentation data you can use while installation and inspecting the meter. Use phase angles displays to check the order of phases when connecting wires to the meter terminals.
DISPLAY
Description
V1 0 V V2 0 V
V1 and V2 Phase-to-neutral voltages. Only displayed in 4-wire configurations with a neutral.
V3 0 V
V2 Phase-to-neutral voltage
V12 0 V V23 0 V
Phase-to-Phase voltages.
V31 0 V
Phase-to-Phase voltages.
I1 0 A I2 0 A
Phase currents.
I3 0 A In 0 A
Phase currents, neutral current is calculated.
P 0 kW Q 0 kvar
Total powers.
S 0 kVA PF 0
Total apparent power and total power factor
L1 P 0 kW L1 Q 0 kvar
Phase 1 active and reactive power
Chapter 3 Using Front Display Data Displays
EM13x Series SMART MULTIFUNCTION METER 65
DISPLAY
Description
L1 S 0 kVA L1 PF 0
Phase 1 apparent power and power factor
L2 P 0 kW L2 Q 0 kvar
Phase 2 active and reactive power
L2 S 0 kVA L2 PF 0
Phase 2 apparent power and power factor
L3 P 0 kW L3 Q 0 kvar
Phase 3 active and reactive power
L3 S 0 kVA L3 PF 0
Phase 3 apparent power and power factor
H1 P 0 kW H1 Q 0 kvar
First Harmonic Total powers.
H1 S 0 kVA H1 PF 0
First Harmonic Total apparent power and total power factor
H1/L1 0 kW H1/L1 0 kvar
First Harmonic Phase 1 active and reactive power
H1/L1 0 kVA H1/L1 0 PF
First Harmonic Phase 1 apparent power and power factor
H1/L2 0 kW H1/L2 0 kvar
First Harmonic Phase 2 active and reactive power
H1/L2 0 kVA H1/L2 0 PF
First Harmonic Phase 2 apparent power and power factor
H1/L3 0 kW H1/L3 0 kvar
First Harmonic Phase 3 active and reactive power
Chapter 3 Using Front Display Data Displays
66 EM13x Series SMART MULTIFUNCTION METER
DISPLAY
Description
H1/L3 0 kVA H1/L3 0 PF
First Harmonic Phase 3 apparent power and power factor
V1 THD 0 % I1 THD 0 %
Phase 1 voltage and current THD
V2 THD 0 % I2 THD 0 %
Phase 2 voltage and current THD
V3 THD 0 % I3 THD 0 %
Phase 3 voltage and current THD
I1 TDD 0 % I2 TDD 0 %
Total Demand current Distortion
I3 TDD 0 %
Total Demand current Distortion
V Unb 0 % I Unb 0 %
Voltage and Current unbalance
Freq 0 Hz
Frequency
V1 Ang 0° I1 Ang 0°
Voltage and Current Phase 1 angles (relative to V1 voltage)
V2 Ang 0° I2 Ang 0°
Voltage and Current Phase 2 angles (relative to V1 voltage)
V3 Ang 0° I3 Ang 0°
Voltage and Current Phase 3 angles (relative to V1 voltage)
Status Inputs and Outputs
DISPLAY
Description
Chapter 3 Using Front Display Data Displays
EM13x Series SMART MULTIFUNCTION METER 67
DISPLAY
Description
Phase Rotation: Error
Phase rotation order (Error, Positive, Negative)
DI: 123456 000000
Digital Inputs status
Relays: 123 000
Relays control status
Counter 1: 0
Status/Event Counter 1
Counter 2: 0
Status/Event Counter 2
Counter 3: 0
Status/Event Counter 3
Counter 4: 0
Status/Event Counter 4
Device Info Display
The device info display provides different service information that may be required for meter identification and inspection, like product and firmware information, communication settings, and so on, and shows device diagnostic messages recorded as a result of the meter self-test diagnostics during start-up and operation.
If there are diagnostic messages, Some of the diagnostics events are cleared automatically as the event source disappears. See Device
Diagnostic Codes in Appendix G for a full list of diagnostic messages
and their meanings. See Clearing Device Diagnostics for information on how to clear the device diagnostics from the display and via PAS.
The diagnostic icon can be disabled or enabled via the Display Setup menu.
DISPLAY
Description
Diagnostics: 8
Power Down message
Chapter 3 Using Front Display Data Displays
68 EM13x Series SMART MULTIFUNCTION METER
DISPLAY
Description
S/N: 12345744 S/W: V12.1.1
Meter identification info, serial number and device SW version
Boot: V1.1.1 Modem: N/A
Boot SW version and Modem setup
COM1: a221,b115.2 Modbus RTU
Communication port COM1 info
COM2: RF, a221 Modbus RTU
Communication port COM2 info
COM3: a1,b19.2 Modbus RTU
Communication port COM3 info
Chapter 3 Using Front Display Programming Mode
EM13x Series SMART MULTIFUNCTION METER 69
3.3 Programming Mode
To enter programming mode from the data display, press and hold the SELECT/ENTER button for more than 5 seconds.
Navigation Buttons
The following table gives a summary of the button operations in programming mode.
Button
Press
Operations
SCROLL
Short press
Scroll through a menu item list in a highlighted window or increment a highlighted digit in a numeric field
SELECT/ENTER
Short press (less than 1 second) = SELECT
Highlight a menu window or a digit in a numeric field
SELECT/ENTER
Long press (1 to 2 seconds) = ENTER
Store the changed item or perform an action indicated in a highlighted window
Entering Numeric Values
Whenever a numeric value is to be changed, use a short press on the SELECT/ENTER button to highlight a desired digit, and then use the SCROLL button to change the value of the highlighted digit. A highlighted digit appears in inversed color. If you missed a digit, just continue moving through the rest of digits until you reach the desired place.
Once the number is set to the desired value, press and hold the SELECT/ENTER button for 1-2 seconds to save your new setting.
To reject your changes and restore the previous value, use a short press on the SELECT/ENTER button to return to the higher-level window.
Password Security
The setup menus are secured by 8-digit user passwords. Every time you enter programming mode, you are prompted for a correct password. The meter is primarily shipped with all passwords preset to 9 at the factory.
It is recommended that you change the factory set passwords as fast as possible to protect your setups and accumulated data from unauthorized changes. See Configuring Meter Passwords in Chapter 5 on how to change passwords in your meter.
Enter the password as you enter numeric values. As you move to the next place, the digit entered is saved and then zeroed. If you missed a digit, you should re-type all preceding digits before you reach the missed place again.
Once the password is set to the desired value, press and hold the SELECT/ENTER button for more than 1 second. If the password you entered is correct, you move to the main device menu, otherwise you return back to the data display.
Setup Menus and Access Rights
The EM13X Series setup is menu-driven. The meter provides 11 menus that allow local accessing a limited number of meter setups and control
Basic PT Ratio
100.0
Basic PT Ratio
100.0
SHORT PRESS
Basic PT Ratio
150.0
LONG PRESS
Enter Password 00000000
SHORT PRESS
LONG PRESS
Enter Password 00000009
Chapter 3 Using Front Display Programming Mode
70 EM13x Series SMART MULTIFUNCTION METER
functions listed in the following table. Access to particular menus is granted depending on the security level of the password you entered.
Menu
Label
Menu Function
Security Level
View
Change
Reset
Reset of billing and engineering maximum demands, device diagnostics, meter and failure counters
Low
See Table below
RTC
RTC clock setup
Low
Low
Basic
Basic device setup
Low
High
Options
Device options setup
Low
High
COM1
COM1 serial port setup
Low
Medium
COM2
COM2 serial port setup
Low
Medium
COM3
COM3 serial port setup
Low
Medium
Local
Local settings
Low
Medium
Disp
Display setup
Low
Low
Access
Meter passwords setup
High
High
Loader
Launches flash download via a local serial port
Medium
Medium
Access to the RESET menu entries is allowed depending on your security level.
If your security level does not allow access to a menu, it will not be listed in the main menu list, and you will not be able to highlight menu items that you are not allowed to change, but you can still view their present settings.
Chapter 3 Using Front Display Programming Mode
EM13x Series SMART MULTIFUNCTION METER 71
Viewing and Changing Setup Options
Once you entered a correct password you are moved to the main meter menu.
The main menu has two windows: the left window displays a submenu list, while the right window is an assisting Exit window that allows easy returning back to the data display. A currently active menu item is highlighted by flashing.
To select a desired menu entry from the menu list:
If the left window is not highlighted yet, highlight it by briefly pressing the SELECT/ENTER button.
Use the SCROLL button to scroll through the menu list until the desired menu entry appears
Press the SELECT/ENTER button for more than 1 second to enter the selected submenu.
Once you entered a submenu, the left window is still showing the menu name, while the upper-right window represent a submenu options list, and the lower-right window indicates the present option value.
To select an option you want to view or change:
Use the SCROLL button to scroll through the option list until the
desired option’s name appears in the window.
To change the selected option’s value:
Press the SELECT/ENTER button briefly to highlight the lower-right window.
If an option is represented by a list of values, use the SCROLL button to scroll through the list until a desired value appears in the window. It an option is represented by a numeric value, use the SCROLL button to adjust each digit to the desired value, and use a short press on the SELECT/ENTER button to move through digits.
Once the desired value is selected, press the SELECT/ENTER button for more than 1 second to save your new setting. You return to the upper­right window and can continue scrolling through the rest of options or can return to the main menu
If you wish to leave the option value unchanged, use a short press on the SELECT/ENTER button to return to the upper-right window.
To exit the submenu and return to the main menu:
If the upper-right window is not highlighted yet, highlight it by briefly
pressing the SELECT/ENTER button.
Press the SELECT/ENTER button for more than 1 second. You will return
to the main menu.
To exit the main menu and return to the data display:
Press briefly the SELECT/ENTER button to highlight the right-upper Exit
window.
Press the SELECT/ENTER button for more than 1 second. You will return
back to the data display.
Enter Password 00000000
SHORT PRESS
LONG PRESS
Enter Password 00000009
Reset Exit
Disp Exit
SCROLL until
Disp menu
LONG PRESS
Disp Autoscroll 5
SHORT PRESS
Disp Autoscroll 5
LONG PRESS
SCROLL
Disp Autoscroll Disabled
Disp Autoscroll Disabled
LONG PRESS
Disp Exit
SHORT PRESS
Disp Exit
LONG PRESS
10:57:00 NORM 22/09/2011 T1 -
Chapter 4 Using PAS Software Installing PAS
72 EM13x Series SMART MULTIFUNCTION METER
Chapter 4 Using PAS Software
The support PAS software is a configuration and data acquisition tool that allows you to configure all of the EM13X Series features, monitor your meters on-line, retrieve recorded files and view reports. PAS can communicate with your EM13X Series via a serial port and via the Ethernet.
This chapter gives information on how to install and run PAS on your computer, and how to prepare information for your meter using PAS.
4.1 Installing PAS
You need PAS V1.4 Build 5 or higher to take an advantage of the meter data logging options.
To install PAS on your PC:
Insert the installation CD supplied with your meter into CD drive.
Open My Computer on your Desktop.
Click on your CD drive icon, select the PAS directory, and then double click on Setup (shown as an Application type file).
Follow InstallShield® Wizard instructions on the screen.
PAS is installed by default to the C:\Pas folder.
When installation is complete, the PAS icon appears on your Desktop. Double click on the PAS icon to run PAS.
For general information on how to work with PAS, see the “PAS Getting Started” guide supplied on the installation CD.
4.2 Creating a New Site for your Meter
PAS keeps all communication and configuration data for your meter in a configuration database called a site database. During configuration, store all setup data to the site database so that PAS recognizes device properties regardless of whether the meter is online or offline.
To communicate with the meters, create a separate site database for each device.
To create a new database for your meter:
Select Configuration from the Tools menu.
P
Chapter 4 Using PAS Software Creating a New Site for your Meter
EM13x Series SMART MULTIFUNCTION METER 73
Figure 4-1: Configuration Dialog Box – Instrument Setup Tab
Click the Sites button on the right-hand-side.
From the Look in box, select the directory where a new database will be stored. By default, it is the Sites directory.
Type a site name for your device in the File name box, click New, and then click OK.
On the Instrument Setup tab, select EM13X Series in the Model box. PAS automatically selects the appropriate instrument options for your meter.
Select a correct CT secondary current (5A or 1A) for your meter.
If you wish to add any comments for your meter, type the comments in the Comment box.
For more device configuration details using PAS Software refer to PM130 PLUS Installation and Operation Manual BG0425 REV.12
Chapter 5 Configuring the EM13X Series Configuring Communications
74 EM13x Series SMART MULTIFUNCTION METER
Chapter 5 Configuring the EM13X
Series
This chapter describes how to configure the EM13X Series for your particular environment and application from the front display and via PAS. To access your meter configuration options via PAS, you should create a site database for your device as shown in Chapter 4.
5.1 Configuring Communications
Setting Up Serial Communication Ports
Using the Front Display
Select COM1 through COM3 from the main menu. See Viewing and
Changing Setup Options in Chapter 3 for information on navigating in
menus.
See the table below for available communication options.
Using PAS
Select Communications Setup from the Meter Setup menu, and then click on the Serial Ports Setup tab. In the Port box, select the desired device port.
Figure 5-1: Communication Setup Dialog Box – Serial Ports Setup Tab
COM1 Protocol Modbus RTU
Chapter 5 Configuring the EM13X Series Configuring Communications
EM13x Series SMART MULTIFUNCTION METER 75
To change the port settings in your device, select desired port parameters, and then click Send.
The following table lists available port options.
Table 4: COMPort Options
Display Label
Parameter
Options
Default
Description
Protocol
Communication protocol
MODBUS RTU, MODBUS ASCII, DNP3, SATEC ASCII, IEC 60870-5
MODBUS RTU (COM 1-3)
The communications protocol for the port
Interface
Port interface
RS485, RS232, IR, GPRS, ETHERNET, PROFIBUS, CANopen
RS485 (COM1) RS232 (COM2) IR (COM3)
Not changeable; automatically detected by the meter
Address
Device address
MODBUS: 1-247 DNP3: 0-65532 IEC 60870-5: 1-4095
1
Device network address
Baud Rate
Baud rate
COM1: 300-115.2 kbps, COM2: 300-115.2 kbps COM3: 9600-38400 kbps
19.2 kbps
The port baud rate
Data/Parity
Data format and parity
7E, 8N, 8E
8N
7E data format should not be used with the MODBUS RTU and DNP3 protocols
Send Delay
Response delay
0-1000 ms
5 ms
The minimum time after the last request character is received to start the transmission.
Chr.Timeout
Character timeout
0-1000 ms
4 ms
The maximum time the line is allowed to idle before closing a connection in the MODBUS RTU and DNP3 protocols
The meter automatically detects replaceable communication modules and does not allow you to change the baud rate and data format for the Dial-up GSM/GPRS modem.
Chapter 5 Configuring the EM13X Series Configuring Communications
76 EM13x Series SMART MULTIFUNCTION METER
Setting up the Ethernet
Using the Front Display
Select Net from the main menu. See Viewing and Changing Setup
Options in Chapter 3 for information on navigating in menus.
See the table below for available network options.
Using PAS
Select Communications Setup from the Meter Setup menu, and then click on the Network Setup tab.
Figure 5-2: Communication Setup Dialog Box – Network Setup Tab
The following table lists available network options.
Table 5: Ethernet Setup Options
Display Label
Parameter
Default
IP Address
Device IP Address
192.168.0.203
Subnet Mask
Network Subnet Mask
255.255.255.0
Def. Gateway
Network Default Gateway
192.168.0.1
TCPServicePort
502 = Modbus/TCP 20000 = DNP3/TCP
502
NOTES
The meter provides the permanent MODBUS TCP server on port 502. Selecting the DNP3 TCP service port launches the second DNP3 TCP
server allowing simultaneous connections on both TCP ports. Selecting the Modbus TCP port disables the DNP3 TCP server.
The TCP service port can also be changed trough the COM2 serial port setup. Changing the communication protocol for the port automatically changes the TCP port for the Ethernet.
When you change the device network settings through the Ethernet port,
the device port restarts so communication will be temporarily lost. You
Net IP Address
192.168.000.203
Chapter 5 Configuring the EM13X Series Configuring Communications
EM13x Series SMART MULTIFUNCTION METER 77
may need to wait some additional time until PAS restores a connection with your device.Setting-Up Dial-Up GPRS Network
Setting up GPRS Network
Using the Front Display
The EM13X Series can provide wireless GPRS communications with the remote Modbus/TCP server via an external Enfora GSM1308 SA-G+ GSM/GPRS modem. See Connecting a GSM/GPRS modem in Chapter 2 on how to connect a modem to your meter.
Using PAS
Select Communications Setup from the Meter Setup menu, and then
click on the GPRS Setup tab.
Select Communications Setup from the Meter Setup menu, and then click on the GPRS Setup tab.
Figure 5-3: Communication Setup Dialog Box – GPRS Setup Tab
Chapter 5 Configuring the EM13X Series Configuring Communications
78 EM13x Series SMART MULTIFUNCTION METER
The following table lists available GPRS options.
Table 6: GPRS Setup Options
Parameter
Default
Description
Access Point Name (APN)
internetg
The mobile network APN name
User name
Username (if required)
Password
Password (if required)
Configure your mobile network APN, username and password. Consult
your network operator regarding proper network settings. Leave the username and password fields blank if network authorization is not required.
Send your GPRS settings to the meter. Select the GPRS interface in the COM2 port setup (see Setting Up Serial
Communication Ports).
Configure your eXpertPower client (see Setting Up eXpertPower Client)
or/and TCP Notification client (see Setting Up TCP Notification Client) for communicating with a remote server.
You can check the status of the GPRS communications from the front panel via the Status Display or via the Device Control dialog in PAS (see Viewing Communication Status and Statistics).
Setting Up eXpertPower Client
The PM130 PLUS has an embedded eXpertPower
TM
client that provides communications with the eXpertPowerTM server – the SATEC proprietary Internet services. Connections to the eXpertPowerTM server are handled on a periodic basis.
To set up communications with the eXpertPowerTM server, select Communication Setup from the Meter Setup menu, and then click on the ExpertPower Client Setup tab.
Chapter 5 Configuring the EM13X Series Configuring Communications
EM13x Series SMART MULTIFUNCTION METER 79
Figure 5-4: eXpertPower Client Setup Tab
The following table lists available options. Refer to your eXpertPower service provider for the correct network settings.
Table 6: eXpertPower Client Setup Options
Parameter
Options
Default
Description
XPW Server IP Address
207.232.60.18
The IP address of the eXpertPower server
XPWServerPort
0-65535
5001
The TCP service port of the eXpertPower server
XPW Client Enabled
NO, YES
NO
Enables operations of the eXpertPower client
Time to Next Session, min
1-99999
The time remaining to the next connection session
NOTES
Do not enable the eXpertPower client in your meter if you do not use the
eXpertPowerTM service.
Do not change the connection time setting. It is for information only. The
eXpertPower server updates it automatically.
Setting Up TCP Notification Client
The TCP notification client can establish connections with a remote Modbus/TCP server and send notification messages either on events, or periodically on a time basis.
To set up communications with a remote TCP Notification server, select Communication Setup from the Meter Setup menu, and then click on the TCP Notification Client Setup tab.
Figure 5-5: TCP Notification Client Setup Tab
The following table lists available client options.
Chapter 5 Configuring the EM13X Series General Meter Setup
80 EM13x Series SMART MULTIFUNCTION METER
Table 7: TCP Notification Client Setup Options
Parameter
Options
Default
Description
Client Enabled
NO, YES
NO
Enables operations of the notification client
Server IP Address
192.168.0.3
The IP address of the notification server
ServerPort
0-65535
502
The TCP service port of the notification server
Message Exchange Address
0-65535
1000
The start address of a block of 16 Modbus registers for receiving notification messages
Connections with a remote server are triggered via programmable setpoints. To send event notifications to a server, configure a setpoint to respond to desired triggers or to periodic time events and put the "Notification" action to the setpoint action list (see Configuring
Alarm/Control Setpoints).
See the PM130 PLUS Modbus Reference guide for more information on operation of the notification client and the notification message structure.
5.2 General Meter Setup
Basic Meter Setup
This section describes how to configure the EM13X Series for your particular environment and application.
Before operating your meter, provide the device with basic information about your electrical network.
Using the Front Display
Select the Basic entry from the main menu. See Viewing and Changing
Setup Options in Chapter 3 for information on configuring parameters
via the front display.
See the table below for the Basic Setup options.
Basic Exit
LONG PRESS
Basic Conf 4Ln3
SCROLL until
CT menu
Basic CT 50
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 81
Using PAS
Select General Setup from the Meter Setup menu. See the table below for the Basic Setup options.
Table 8: Basic Setup Options
Display
Label
Parameter
Options
Default
Description
Conf
Wiring Mode
See Table 9
4Ln3
The wiring connection of the device
PT Ratio
PT Ratio
1.0-6500.0
1.0
The phase potential transformer’s
primary to secondary ratio
PT Factor
PT Ratio Multiplier
×1, ×10
×1
PT Ratio multiplication factor. Used in extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks.
CT
CT Primary Current
1-50000 A
5 A
The primary rating of the phase current transformer
PowDmdPer
Power block demand period
1, 2, 3, 5, 10, 15, 20, 30, 60 min, E=external sync
15 min
The length of the demand period for power demand calculations. If the external synchronization is selected, a pulse front on the digital input DI1 denotes the start of the demand interval.
Num.Per.
The number of blocks in the sliding demand window
1-15
1
The number of blocks to be averaged for sliding window demands
ADmdPer.
Volt/Ampere Demand Period
0-1800 sec
900 sec
The length of the demand period for ampere and volt demand calculations
Freq
Nominal Frequency
50,60,25,400 Hz
60 Hz
The nominal line frequency
MaxDmdLd
Maximum Demand Load Current
0-50000 A
0
The maximum demand load current (0 = CT primary current)
1. Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs.
2. The maximum value for the product of the phase CT primary current and PT ratio is 57,500,000. If the product is greater, power readings are zeroed.
Chapter 5 Configuring the EM13X Series General Meter Setup
82 EM13x Series SMART MULTIFUNCTION METER
Figure 5-6: General Setup Dialog Box – Basic Setup Tab
Table 9 lists the available wiring modes.
Table 9: Wiring Modes
Wiring Mode
Description
3OP2
3-wire Open Delta using 2 CTs (2 element)
4LN3
4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings
3DIR2
3-wire Delta Direct Connection using 2 CTs (2 element)
4LL3
4-wire Wye using 3 PTs (3 element), line-to-line voltage readings
3OP3
3-wire Open Delta using 3 CTs (2½ element)
3LN3
4-wire Wye using 2 PTs (2½ element), line-to-neutral voltage readings
3LL3
4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings
3BLN3
3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-neutral voltage readings
3BLL3
3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-line voltage readings
In 4LN3, 3LN3 and 3BLN3 wiring modes, Min/Max volts, volt demands and voltage harmonics represent line-to-neutral voltages; otherwise, they will be line-to-line voltages.
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 83
Device Options
The Device Options setup allows changing user-configurable device options or putting the meter into energy test mode.
Using the Front Display
Select Options from the main menu. See Viewing and Changing Setup
Options in Chapter 3 for information on configuring parameters via the
front display.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Device Options tab.
Table 10 lists available device options.
Table 10: User-configurable Device Options
Display
Label
Parameter
Options
Default
Description
TestMode
Energy Test Mode
Three options: OFF = disabled Wh pulses varh pulses
Disabled
Setting this option puts the meter into the energy test mode (see Energy Pulse
LED in Chapter 3)
PowMode
Power Calculation Mode
Reactive = using reactive power S=f(P, Q), NonActive = using non-active power Q=f(S, P)
S=f(P, Q)
The method used for calculating reactive and apparent powers (see
Power Calculation Modes
below)
EngyRoll
Energy Roll Value
10000 = 10000 kWh 100000 = 100000 kWh 1000000 = 1000000 kWh 10000000 = 10000000kWh 100000000 = 100000000 kWh 1000000000 = 1000000000 kWh
10000000
The value at which energy counters roll over to zero
Phs.Engy
Phase Energy Calculation
Disabled Enabled
Disabled
Enables phase energy calculations
StrtVolt
Starting Voltage
1.5-5.0%
1.5%
The device starting voltage in percent of FS (120V or 400V)
Resolution
Device Resolution
Low High
Low
The voltage, current and power resolution on the front display (see
Measurement Units in
Chapter 3) and in communications (see communication guides)
Options TestMode OFF
Chapter 5 Configuring the EM13X Series General Meter Setup
84 EM13x Series SMART MULTIFUNCTION METER
Figure 5-7: General Setup Dialog Box – Device Options Tab
Power Calculation Modes
The power calculation mode option allows you to change the method for calculating reactive and apparent powers in presence of high harmonics. The options work as follows:
When the reactive power calculation mode is selected, active and
reactive powers are measured directly and apparent power is calculated as:
22
QPS
This mode is recommended for electrical networks with low harmonic
distortion, commonly with THD < 5% for volts, and THD < 10% for currents. In networks with high harmonics, the second method is preferable.
When the non-active power calculation mode is selected, active
power is measured directly, apparent power is taken as product S = V x I, where V and I are the RMS volts and amps, and reactive power (called non-active power) is calculated as:
22
PSN
Configuring Digital Inputs
The EM13X Series can be provided with two digital inputs (standard) and 4, 8 or 12 optional digital inputs that can be linked to control setpoints to give an indication on input status change (see Configuring
Alarm/Control Setpoints), or can be linked to general pulse counters to
count incoming pulses (see Configuring Counters). They can also be linked to the Billing/TOU registers to count pulses from external wattmeters or gas and water meters.
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 85
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Digital Inputs tab.
Figure 5-8: General Setup Dialog Box – Digital Inputs Dialog Box
The available options are shown in Table 11.
Chapter 5 Configuring the EM13X Series General Meter Setup
86 EM13x Series SMART MULTIFUNCTION METER
Table 11: Digital Inputs Options
T h e
d e b o u n c e
t i m e
i s
a p a
The debounce time is applied the same for all digital inputs. If you change the debounce time for a digital input, the same debounce time is automatically assigned to the others.
Configuring Relay Outputs
The PM130 PLUS can be provided with one relay (standard) and 2 or 4 optional relay outputs. Each relay can be operated either locally from the alarm/control setpoints in response to an event or by a remote command sent through communications. It can also be linked to an internal pulse source to produce energy pulses.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Relay Outputs tab.
Parameter
Options
Default
Description
Input Polarity
NORMAL INVERTING
NORMAL
For the normal polarity, the open to closed transition is considered closed. For the inverting polarity, the closed to open transition is considered a closed
Pulse Input Mode
PULSE MODE KYZ MODE
PULSE MODE
In pulse mode, either leading, or trailing edge of the input pulse is recognized as an event. In KYZ mode, both leading and trailing edges of the input pulse are recognized as separate events.
Pulse Polarity
NORMAL (N.O.), INVERTING (N.C.)
NORMAL
For the normal polarity, the open to closed transition is considered a pulse. For the inverting polarity, the closed to open transition is considered a pulse. It has no meaning in KYZ mode where both transitions are used.
Debounce Time
1-100 ms
10 ms
The amount of time while the state of the digital input should not change to be recognized as a new state. Too low debounce time could produce multiple events on the input change.
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 87
Figure 5-9: General Setup Dialog Box – Relay Outputs Tab
Chapter 5 Configuring the EM13X Series General Meter Setup
88 EM13x Series SMART MULTIFUNCTION METER
The available relay outputs options are shown in Table 12.
Table 12: Relay Output Options
Parameter
Options
Default
Description
Operation mode
UNLATCHED LATCHED PULSE KYZ
UNLATCHED
Unlatched mode: the relay goes into its active state when the control setpoint is in active (operated) state, and returns into its non­active state when the setpoint is released. Latched mode: the relay goes into its active state when the control setpoint goes into active state and remains in the active state until it is returned into its non-active state by a remote command. Pulse mode (normal pulse): the relay goes into its active state for the specified time, goes into non-active state for the specified time and remains in the non-active state. KYZ mode (transition pulse): the relay generates transition pulses. The relay changes its output state upon each command and remains in this state until the next command.
Polarity
NORMAL (N.O.) INVERTING (N.C.)
NORMAL
Normal polarity: the relay is normally de-energized in its non-active state and is energized in its active (operated) state. Inverting polarity: the relay is normally energized in its non­active state and is de­energized in its active (operated) state. It is called failsafe relay operation.
Pulse width
20-1000 ms
100 ms
The actual pulse width is a multiple of the 1-cycle time rounded to the nearest bigger value. The pause time between pulses is equal to the pulse width.
Pulse source
NONE Ac.Ei = kWh IMP Ac.EE = kWh EXP rE.Ei = kvarh IMP rE.EE = kvarh EXP rE.Et = kvarh TOT AP.Et = kVAh TOT
NONE
Links a pulse relay to the internal energy pulse source. The relay must be set into either pulse, or KYZ mode.
Pulse rate, kWh/Pulse
0.1-1000.0
1.0 kWh/Pulse
Defines the pulse weight in kWh units per pulse
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 89
Generating Energy Pulses through Relay Outputs
To generate energy pulses through a relay output:
Set a relay to either pulse, or KYZ mode, and then select a polarity
(active pulse edge) for energy pulses and a pulse width.
Select a source energy accumulator and the pulse rate for your output Send your new setup to the meter
Configuring Analog Outputs
The meter can be ordered with four optional analog outputs with options for 0-1mA, ±1mA, 0-20mA and 4-20mA current outputs.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Analog Outputs tab.
Figure 5-10: General Setup Dialog Box – Analog Outputs Tab
Chapter 5 Configuring the EM13X Series General Meter Setup
90 EM13x Series SMART MULTIFUNCTION METER
The available analog output options are described in Table 13.
Table 13: Analog Output Options
Option
Range
Description
AO type
0-1mA ±1mA 0-20mA 4-20mA
The analog output type. When connected to the meter, shows the actual AO type received from the device. When working off-line, select the analog output option corresponding to your analog module.
Output parameter
See Appendix B
Selects the measured parameter to be transmitted through the analog output channel.
Zero scale
Defines the low engineering scale (in primary units) for the analog output corresponding to a lowest (zero) output current (0 or 4 mA)
Full scale
Defines the high engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA)
When you select an output parameter for the analog output channel, the default engineering scales are set automatically. They correspond to the maximum available scales. If the parameter actually covers a lower range, you can change the scales to provide a better resolution on an analog output.
Scaling Non-Directional Analog Outputs
For non-directional analog outputs with a 0-1mA, 0-20mA or 4-20mA current option, you can change both zero and full engineering scales for any parameter. The engineering scale need not be symmetrical.
Scaling Directional Power Factor
The engineering scale for the signed power factor emulates analog power factor meters.
The power factor scale is -0 to +0 and is symmetrical with regard to 1.000 (-1.000 +1.000). The negative power factor is scaled as
-1.000 minus the measured value, and non-negative power factor is scaled as +1.000 minus the measured value. To define the entire power factor range from -0 to +0, the default scales are specified as -
0.000 to 0.000.
Scaling ±1mA Analog Outputs
Programming engineering scales for directional ±1mA analog outputs depends on whether the output parameter represents unsigned (as volts and amps) or signed (as powers and power factor) values.
For an unsigned output value, you can change both zero and full engineering scales.
For a signed (directional) value, you should only provide the engineering scale for the +1 mA output current.
The engineering scale for the 0 mA output current is always equal to zero for all values except the signed power factor, for which it is set to
1.000 (see Scaling Directional Power Factor above).
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 91
The meter does not allow access to the low scale setting if the parameter is directional. Whenever the sign of the output parameter is changed to negative, the meter automatically uses the full engineering scale setting for +1 mA with a negative sign.
Scaling Analog Outputs for 0-2 mA and ±2 mA
The 0-1mA and ±1mA current outputs provide a 100% overload, and actually output currents up to 2 mA and ±2mA whenever the output value exceeds the engineering scale you set for the 1 mA or ±1mA.
The output scales for 0-1 mA and ±1 mA analog outputs are programmed for 0 mA and +1 mA regardless of the required output current range.
To use the entire output range of 2 mA or ±2 mA, set the analog output scales as follows:
0-2 mA: set the 1 mA scale to ½ of the required full scale output for
uni-directional parameters, and set the 0 mA scale to the negative full scale and the 1 mA scale to zero for bi-directional parameters.
±2 mA: set the 1 mA scale to ½ of the required full-scale output for
both uni-directional and bi-directional parameters.
For example, to provide the 0 to 2 mA output current range for Volts measured by the meter in the range of 0 to 120V, set the 1 mA scale to 60V; then the 120V reading will be scaled to 2 mA.
Configuring Counters
The EM13X Series has four six-digit general counters that can count pulses delivered through the device digital inputs with a programmable scale factor. Each counter can also be incremented in response to any internal or external event, checked and cleared through the Control Setpoints.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Pulse/Event Counters tab.
Chapter 5 Configuring the EM13X Series General Meter Setup
92 EM13x Series SMART MULTIFUNCTION METER
Figure 5-11: General Setup Dialog Box – Pulse/Event Counters
Table 14 lists available counter options.
Table 14: Counter Options
Option
Range
Default
Description
Pulse Input
None,
DI1 DI2 DI3
DI4 DI5
DI6 DI7
--­DI14
None
Links a digital input to the counter
Multiplier
1-9999
1
The value added to the counter when a pulse is detected on the pulse source input
Counter Value
Displays the present counter contents
You can preset a counter to a required value or clear it without affecting the counter setup.
To preset or clear a counter:
Click the Online button on the PAS toolbar before accessing the setup
dialog box.
Type in the required value into the Counter Value field Click Send
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 93
Configuring Alarm/Control Setpoints
The EM13X Series has an embedded logical controller that can perform different actions in response to user-defined internal and external events. Unlike a PLC, the meter uses a simplified programming technique based on setpoints that allows the user to define a logical expression based on measured analog and digital values that produce a required action.
The meter provides 16 control setpoints with programmable operate and release delays. Each setpoint evaluates a logical expression with
one trigger argument. Whenever an expression is evaluated as “true”,
the setpoint performs a programmable action that can send a command to the output relay, or increment a counter.
The logical controller provides very fast response to events. The scan time for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400 Hz).
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Control/Alarm Setpoints tab.
Figure 5-12: General Setup Dialog Box – Control/Alarm Setpoints Tab
Chapter 5 Configuring the EM13X Series General Meter Setup
94 EM13x Series SMART MULTIFUNCTION METER
The following table lists the available setpoint options.
Table 15: Setpoint Options
Option
Range
Description
Trigger parameter
See Appendix C
The trigger parameter that is used as an argument in the logical expression
Operate limit
The threshold (in primary units) at which the conditional expression would be evaluated to true. Not applicable for digital triggers.
Release limit
The threshold (in primary units) at which the conditional expression would be evaluated to false. Defines the hysteresis for analog triggers. Not applicable for digital triggers.
Operate delay
0.1-999.9 sec
The time delay before operation when the operate conditions are fulfilled
Release delay
0.1-999.9 sec
The time delay before release when the release conditions are fulfilled
Action
See Appendix C
The action performed when the setpoint expression is evaluated to true (the setpoint is in operated state)
Using Numeric Triggers
For numeric (analog) triggers, you can specify two thresholds for each trigger to provide hysteresis (dead band) for setpoint operations.
The Operate Limit defines the operating threshold, and the second Release Limit defines the release threshold for the trigger. The trigger thresholds are specified in primary units.
If you do not want to use hysteresis for the trigger, set the Release Limit to the same value as the Operate Limit.
Using Binary Triggers
Binary (digital) triggers like digital inputs and relays are tested for ON/CLOSED or OFF/OPEN status.
In the PM130, the binary events are level-sensitive events. An event is asserted all the time while the corresponding condition exists.
Delaying Setpoint Operations
Two optional delays can be added to each setpoint to extend monitoring triggers for a longer time before reaching a decision on whether the expected event occurred or not. When a delay is specified, the logical controller changes the setpoint status only if all conditions are asserted for a period of at least as long as the delay time.
Using Setpoint Events and Actions
When a setpoint status changes, i.e., a setpoint event is either asserted or de-asserted, the following happens in your meter:
The new setpoint status is logged to the setpoint status register that
can be monitored through communications from the SCADA system or from a programmable controller in order to give an indication on the expected event.
The operated setpoint status is latched to the setpoint alarm latch
register that can be inspected through communications and via the display (see Status Display in Chapter 3). The register holds the last
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 95
setpoint alarm status until it is explicitly cleared through communications or via the display.
A programmable action is performed on setpoint status transition
when a setpoint event is asserted.
Generally, setpoint actions are performed independently for each setpoint and can be repeated a number of times for the same target. The exceptions are relay operations that are shared for each target relay between all setpoints using an OR scheme.
A relay output is operated when one of the setpoints linked to the relay is activated and remains operated until all of these setpoints are released (except for latched relays that require a separate release command to be deactivated).
Using Time Counters
Any of the general counters can be used to count the setpoint operation time. If you select the TIME CNT n action for a setpoint, the target counter measures the time while the setpoint is in the operated state. The counter resolution is 0.1 hour. See Status Display in Chapter 3 on how to examine the counters via the front display.
Chapter 5 Configuring the EM13X Series General Meter Setup
96 EM13x Series SMART MULTIFUNCTION METER
Configuring the Display
This setup allows configuring the meter display. It also has an entry for launching the meter Flash Loader.
Using the Front Display
Select the Disp entry from the main menu. See Viewing and Changing
Setup Options in Chapter 3 for information on configuring parameters
via the front display.
See Table 16 for the available options.
Table 16: Display Setup Options
Display
Label
Parameter
Options
Default
Description
AutuoScroll
Display update rate
Disabled 2 – 30sec
5 sec
Defines the interval between display updates
AutoReturn
Auto return to the main screen
Disabled, 1 – 30 mn
5 mn
Enables automatic return to the main display if no buttons are pressed for 5 minutes
Backlight
Display Backlight period
Continuous, 1 – 10 mn
1
Defines the display backlight light on time duration
Phas.Power
Phase powers display mode
Enabled Disabled
Disabled
Disables or enables phase powers in the main display
Fund.Power
Fundamental component display mode
Enabled Disabled
Disabled
Disables or enables fundamental values in the main display
Disp AutoScroll 5
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 97
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Display Setup tab.
Figure 5-13: General Setup Dialog Box – Display Setup Tab
The available options are listed in the table 17 below.
See Display Operations in Chapter 3 for more information on display functionality and configuring display options. See Data Displays for information on display page contents and enumeration.
Chapter 5 Configuring the EM13X Series General Meter Setup
98 EM13x Series SMART MULTIFUNCTION METER
Table 17: Display Setup Options
Display Label
Parameter
Options
Default
Description
Auto-Scroll
Auto-Scroll Interval
Disabled, 2-10, 15, 20, 25, 30 seconds
5
Defines the display scroll interval or disables auto-scroll
Scroll Seq.
Auto-Scroll Sequence
1 1-2 to 1-7 1, 5 1, 5-6, 1, 5-7, 1-2, 5-7 1-3, 5-7 1, 6-7 1-2, 6-7 1-3, 6-7 1-4, 6-7 1, 7 1-2, 7 1-3, 7 1-4, 7 1-5, 7 3 3-4 3-5 3-6 3-7 3, 5 3, 5-6 3, 5-7 3, 7 5 5-6 5-7 5,7
1
Selects the display sequence for auto­scrolling from 9 data displays (see
Data Displays for
display enumeration)
Auto-Return
Auto-Return
Disabled, 1-5, 10, 15, 20, 25, 30 min
5
Defines the time delay before returning to the default page
Backlight
Backlight Time
Continuous, 1-10 min
1
Defines the time while the backlight is ON
Phase Power
Phase powers display mode
Enabled Disabled
Disabled
Disables or enables phase powers in the main display
Fundamental Power
Fundamental component display mode
Enabled Disabled
Disabled
Disables or enables fundamental values in the main display
Local Time Settings
This setup allows you to specify your time zone, daylight saving time, and clock synchronization options.
Using the Front Display
Select Local from the main menu. See Viewing and Changing Setup
Options in Chapter 3 for information on configuring parameters via the
front display.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Local Settings tab.
Locak Exit
Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 99
Figure 5-14: General Setup Dialog Box – Local Settings Tab
The available options are described in Table 18.
Table 18: Local Time Options
Display
Label
Parameter
Options
Default
Description
Date Order
Day/month/year order
DD/MM/YY MM/DD/YY YY/MM/DD
DD/MM/YY
Defines date order presentation
Country
Country code
Default, or country name
Default
Defines calendar setting. The default setting stands for the U.S.A.
Daylight
Daylight Saving Time
Disabled Enabled
Disabled
When DST is disabled, the RTC operates in standard time only. When enabled, the meter automatically updates the time at the pre­defined DST switch dates.
Start Mon
DST Start Month
January to December
March
The month when Daylight Saving Time begins.
Start Week
DST Start Week
1st to 4th and last
Second
The 2nd week of the month when Daylight Saving Time begins.
Start Day
DST Start Day
The weekday
Sunday
The 2nd Sunday of the month when Daylight Saving Time begins.
Start Hour
DST Start Hour
1-6 2 The hour when Daylight Saving Time begins.
dSt.E
DST End Weekday
Month-week-weekday Week = 1, 2, 3, 4 or L (last week of the month)
First Sunday in November
The date when Daylight Saving Time ends.
End Mon
DST End Month
January to December
November
The month when Daylight Saving Time ends.
Chapter 5 Configuring the EM13X Series Configuring Meter Security
100 EM13x Series SMART MULTIFUNCTION METER
Display
Label
Parameter
Options
Default
Description
End Week
DST End Week
1st to 4th and last
First
The 1st week of the month when Daylight Saving Time ends.
End Day
DST End Day
The weekday
Sunday
The 1st Sunday of the month when Daylight Saving Time ends.
End Hour
DST End Hour
1-6 2 The hour when Daylight Saving Time ends.
Clock Sync
Time Synchronization Input
None
DI1 1PPM DI2 1PPM DI3 1PPM DI4 1PPM DI5 1PPM DI6 1PPM DI7 1PPM DI14 1PPM
None
The external port receiving the time synchronization pulses
Daylight Saving Time
When the daylight saving time is enabled, the meter automatically advances the device clock by one hour when daylight saving time begins and puts the clock back one hour when it ends. The default daylight saving time change points are preset for the U.S.A.
The daylight saving time option is disabled in the PM130 by default. If the daylight saving time option is disabled, you need to manually adjust the device clock for daylight saving time.
Time Synchronization Pulses
External time synchronization pulses can be delivered through one of the digital inputs.
If a digital input is selected as the time synchronization source, the edge of an external pulse adjusts the device clock at the nearest whole minute. The time accuracy could be affected by the debounce time of the digital input, and by the operation delay of the external relay.
5.3 Configuring Meter Security
This setup allows changing the user password and enabling or disabling password protection. The EM13X Series provides 3 configurable passwords.
The password in your meter is preset to 0 at the factory, and password protection is disabled.
Using the Front Display
Select the Access entry from the main menu. See Viewing and
Changing Setup Options in Chapter 3 for information on configuring
parameters via the front display.
Loading...