SATA STEAMaster+ SERIES Installation, Operation & Maintenance Manual

Page 1
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Frederick, Maryland, U.S.A.
STEAMaster+ SERIES
Installation, Operation
Installation, Operation
& Maintenance Manual
& Maintenance Manual
ELECTRODE STEAM HUMIDIFIERS
(10/04)
Page 2
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
IMPORTANT
BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THIS MANUAL AND ILLUSTRATED ON THE LABELS ATTACHED TO THE MACHINE.
This humidifier produces non-pressurized steam by means of electrodes immersed in the water contained in the
cylinder-boiler (hereafter called the cylinder). The electrodes pass current through the water, which also provides resistance, heating the water into steam, which is used to humidify environments or industrial processes, using special distributors.
The quality of the water used affects the process of evaporation, so the humidifier may be supplied with untreated water, as long as this is drinkable and not softened or demineralized; the evaporated water is automatically replaced using a fill valve. This humidifier has been designed exclusively to directly humidify rooms or ducts, using a distribution system. The installation, use and maintenance operations must be carried out according to the instructions contained in this manual and on the labels applied internally and externally.
The conditions of the environment and the power supply voltage must comply with the specified values.
All other uses and modifications made to the humidifier that are not authorized by the manufacturer are considered incorrect.
Liability for injury or damage caused by the incorrect use of the humidifier lies exclusively with the user.
Please note that the humidifier contains powered electrical devices and hot surfaces.
All service and/or maintenance operations must be performed by specialist and qualified personnel who are aware of the necessary precautions and are capable of performing the operations correctly.
Disconnect the humidifier from the main power supply before accessing any internal parts.
The humidifier must be installed in accordance with the local standards in force.
The local safety standards in force must be applied in all cases.
The humidifier is made up of metallic and plastic parts. All parts must be disposed of according to the local standards on waste disposal.
Warranty on materials: 2 years (from the date of installation, excluding the consumable parts, such as the cylinder and electrodes).
Certification: the quality and safety of SATS products are assured by SATS’ ISO 9001 certified design and production system, as well as listings from UL, cUL, CE, TUV and others.
(10/04)
Page 3
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
TABLE OF CONTENTS
Models And Description Of The Components ....................................................................................................... 4
How The STEAMaster+ Works ............................................................................................................................ 5
Installation ........................................................................................................................................................... 6
Positioning ...................................................................................................................................................... 6
Removing the front cover .............................................................................................................................. 7
Fastening to the wall ................................................................................................................................... 7
Plumbing ......................................................................................................................................................... 8
Water supply ............................................................................................................................................... 8
Water drain ................................................................................................................................................. 8
Steam distribution .......................................................................................................................................... 10
Duct injection ............................................................................................................................................ 10
Room distribution blower units .................................................................................................................. 12
Power wiring .................................................................................................................................................. 13
Control wiring ................................................................................................................................................. 15
ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors ........................................... 17
HC-101 and HC-201 Wall and Duct Humidistats ....................................................................................... 18
PC-301 Air Proving Switch......................................................................................................................... 19
Start-Up .............................................................................................................................................................. 20
Startup Checklist ........................................................................................................................................... 20
The HumiControl Controller ............................................................................................................................ 21
Start-up Procedure......................................................................................................................................... 21
Starting with a new cylinder ....................................................................................................................... 21
Operation ........................................................................................................................................................... 22
Display Information ........................................................................................................................................ 22
Changing The Set Point ................................................................................................................................. 22
Activating Manual Drain ................................................................................................................................. 22
Accessing/Changing Configuration Parameters ............................................................................................. 22
Notes about special parameters .................................................................................................................... 25
Standard Factory Settings ............................................................................................................................. 26
Seasonal Shut Down ..................................................................................................................................... 27
The Remote Control ....................................................................................................................................... 27
Resetting the Hour Counter ........................................................................................................................... 28
Alarms ........................................................................................................................................................... 28
Trouble-Shooting ............................................................................................................................................ 32
Resetting Factory Defaults ........................................................................................................................ 33
Maintenance ...................................................................................................................................................... 34
Periodic checks ............................................................................................................................................. 34
Cylinder maintenance .................................................................................................................................... 34
Replacing the cylinder ............................................................................................................................... 34
Maintenance of the other plumbing components ....................................................................................... 35
Replacement Parts ........................................................................................................................................ 36
Single Phase Humidifiers .......................................................................................................................... 36
Three Phase Humidifiers ............................................................................................................................ 37
Wiring Diagrams ................................................................................................................................................ 39
Technical Specifications ..................................................................................................................................... 43
IMPORTANT: BEFORE beginning installation:
••
Check for shipping damage to cartons. Mark the shipping waybill accordingly
••
Open cartons and check for any hidden damage. Mark the shipping waybill accordingly.
Check packing slip to ensure all items have been received. Notify SATS of any shortages or damaged
parts. You must notify SATS within 5 working days of any shortages.
(10/04)
i
Page 4
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Models And Description Of The Components
Model Selection
SMP 025 H D 000 U 1
=STEAMaster Capacity (KG) H Control Power Version USA Cylinder Type
Plus
008 = 17.6 lbs/hr Modulating 009 = 20 lbs/hr 010 = 22 lbs/hr
001 = 3.3 lbs/hr For use with: U = 208/1 003 = 6.6 lbs/hr
005 = 11 lbs/hr or
015 = 33 lbs/hr
025 = 55 lbs/hr
035 = 77 lbs/hr
045 = 99 lbs/hr
065 = 132 lbs/hr
On/off
or M = 460/3
DDC N = 575/3
D = 230/1
W = 208/3
K = 230/3
Internal use only
1 = Disposable
Standard Conductivity
2 = Disposable
Low Conductivity
SMP 001 through SMP 015
No. Description
1 Steam generator cylinder 2 Water drain valve 3 Power contactor 4 Fuses 5 Power transformer 6 Relay board 7 On/Off and Manual drain switch 8 Wiring terminal block 9 Water fill valve
SMP 025 through SMP065
No. Description
1 Steam generator cylinder 2 Water drain pump 3 Water fill valve 4 Amperage transformer 5 Power contactor 6 Power transformer 7 Relay 8 Fuses
9 Wiring terminal block 10 Cable raceway 11 On/Off and Manual drain switch
4
(06/06)
Page 5
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
How The STEAMaster+ Works
STEAMaster+ is an electrode humidifier. It produces steam for humidification by passing electrode current through the water in the steam generator cylinder between metal electrodes. There are no heater elements. Steam output is directly proportional to the conductivity of the water, and the amount of electrode immersed in the water.
On a call for humidity, the STEAMaster+ controller will open the water fill valve (1) and allow water to enter the system. A flow restrictor (2) prevents the unit from filling too quickly or with too much pressure. The water flows up the fill tube (3) and into the fill cup (7), where it flows over the conductivity probes (6), which feed the water conductivity back to the controller for analysis. Water then flows over the dam in the fill cup (7), which creates a 1" air gap to prevent backflow of contaminated water into the feed lines, and through the fill tube (4) and into the bottom of the steam cylinder (11).
As the water fills the cylinder, it will reach the electrodes (10) and current will begin to flow. As the water continues to fill the cylinder, the current will increase, and this is monitored by an amperage transformer placed on one of the power wires (9). When the desired current is reached, the fill valve will close (1) and the water will then begin to warm and produce steam. If the water reaches the cylinder full probes (8) prior to reaching the desired current level, the fill valve (1) will be closed to prevent overflow. If the current rises too much as the water fills the cylinder, the drain valve or pump (13) will be activated to drain away some water and reduce the current flow.
Periodically, based on the incoming water conductivity, the unit will drain some water to reduce the mineral concentration. A strainer (12) in the cylinder helps to prevent mineral debris from jamming the drain valve (13).
If there is no water in the cylinder, there will be no current flow and no steam production. The electrodes do not burn out, but they will eventually become comletely coated with mineral and the cylinder will then need to be replaced or cleaned.
5
((06/06)
Page 6
Installation, Operation & Maintenance Manual
Installation
Positioning
The STEAMaster+ has been designed for wall mounting (although it can be placed on a stand) and, since it is an atmospheric steam humidifier, should be placed close to the point where the steam will be used, to minimize the steam hose length (and condensate). Certain clearances
must be maintained around the unit:
Minimum Dimension (inches)
With room blower units, other clearances are needed:
A B C D E F
12 8 8 16 28 0.5°
STEAMaster+ SERIES
Dimensions (inches)
Weight (lbs)
* = SMP045 for 460-575/3 Vac
* = SMP045 for 460-575/3 Vac
A B C
packaged
empty
installed
001-008 009-015 025-045* 045**-065
15 15 22 26 11 11 15 18 25 28 35 38 36 44 86 113 30 38 75 97 42 60 134 207
Minimum dimension (inches)
Model - SMP
6
A B C D E F H
20 72 72 24 20 72 24
(06/06)
Page 7
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Mounting
Removing the front cover
The front cover is secured by a capture screw located underneath the SATS logo. Twist the SATS logo to reveal the screw, and use a phillips head screwdriver to remove it. Then simply lift the front cover and pull out to remove it. Return it in reverse order.
Fastening to the wall
Using the screws and anchors supplied, fasten the mounting bracket to the wall. Be sure that the screws anchor firmly into studs or supports. Note the unit installed weights from the Positioning section.
Once the mounting bracket is secured to the wall, hang the unit on the bracket. Fasten the remaining capture screws through the bottom holes in the unit to secure it to the wall
X Y Z
Z’
001-008 009-015 025-045 065
8.67 8.67 12.21 15.75
19.69 23.23 28.55 30.91
4.53 1.5
4.41
Model SMP
7
(06/06)
Page 8
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Plumbing
Water supply
The STEAMaster+ must be supplied with water (not softened) having the following characteristics:
Instant flow rate Connection Temperature limits Pressure limits Hardness limits
Conductivity range
001-008 009-015 025-045 65
0.2 gpm 0.3 gpm 1 gpm 1.9 gpm
1/4" O.D. Compression 3/8" O.D. Compression
125 to 1250
Model SMP
34 to 104°F
15 to 116 psi
<= 400 ppm CaCO3
µS/cm (micromhos)
Water drain
The STEAMaster+ also requires connection to a drain. The drain water characteristics are:
Drain rate per hour Instant drain rate Connection Typical temperature
001 003 005 008 009 010 015 025 035 045 065
0.7 gph 2.2 gph 3.7 gph 5.9 gph 6.6 gph 7.3 gph 11 gph 18.3 gph 25.7 gph 33 gph 47.7 gph
Model SMP
1.3 gpm 6 gpm 1-1/2" nominal diameter
212°F
8
(06/06)
Page 9
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Water supply and drain connections are made according to the following diagram.
NOTE: Drain line must be trapped under the unit to prevent flash steam from condensing in the unit cabinet.
Physical location of the supply and drain connections are located as shown below.
SMP 010-015 SMP 025-065
NOTE: SATS can provide a drain tempering system which limits the water drain to no more than 140°F. NOTE: Softened water should NOT be used as it is generally corrossive to the electrode plating.
9
(06/06)
Page 10
Installation, Operation & Maintenance Manual
Steam distribution
Duct injection
If your STEAMaster+ humidifier was supplied with duct steam distributor pipes, they must be mounted completely level in the duct with the steam outlet holes facing up as shown to the right. Support the end of longer distributor pipes if needed.
Distributor pipes should be mounted per the diagrams shown below, with a minimum of 6" from the center of the distributor pipe to the top of the duct and 3" minimum to the bottom.
STEAMaster+ SERIES
Generally the distribu­tor pipes should be mounted in the center of the air stream. Multiple pipes need to be staggered on a diagonal to prevent the steam discharge from the lower pipes from impinging on the upper ones.
In vertical ducts, the distributor pipes are mounted in the center with the holes facing up as shown at right. The airflow may be up or down, but when the airflow is down, maximum velocity is 1,500 fpm.
To install the distributor pipes:
1. Cut a key shaped hole in the side of the duct to match the steam pipe and condensate return.
2. Apply silicone sealant to the mounting plate and insert the pipe through the hole and secure it with 4 sheet metal screws.
3. Connect the steam and condensate hoses using the hose clamps supplied.
IMPORTANT: Allow 2 feet of straight duct downstream of the distributor pipes when the air temperature will be >55oF. Allow 3 feet of straight duct if the air temperature will be <50oF. Always allow 2 feet upstream. Turbulent air flow may require longer lengths.
10
(06/06)
Page 11
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Steam Hoses
NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM PIPING FROM THE HUMIDIFIER UNIT TO THE DUCT DISTRIBUTOR PIPES.
To avoid these problems, remember one simple fact when running the steam hose: steam naturally flows up hill, and condensate naturally flows down hill.
Nothing must impede the free flow of either steam to the distributor pipes or condensate back to the SD unit or the drain. If Copper tubing is used, use two 45° angles or sweeping elbows rather than sharp 90° elbows.
Follow one simple rule: Run the steam hose or piping to avoid any kinks, sharp elbows, or low spots that could collect or restrict the flow of steam to the distributor pipe, or the flow of condensate back to the humidifier. Support the hose adequately to avoid sags.
The following diagrams are to provide you with some guidelines. If you have a situation you are unsure of, please contact the factory for instructions.
IMPORTANT: Maximum length of rubber steam hose is 20 feet. Insulated copper tubing may be up to 40 feet. Hose sizes= 7/8" I.D. for units SMP001-003, 1 1/4" I.D. for units SMP005-015, 1-5/8" I.D. for units
SMP025-065.
11
(06/06)
Page 12
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Room distribution blower units
Refer to the manual supplied with the Room Distribution Units for specifics on the blower units themselves. Clearances required are shown below.
A B C D E F H
Minimum dimension
20 72 72 24 20 72 24
(inches)
Room Blower Unit Model
Rated Power Watts
Air Volume CFM
Noise Level dBA
Operating Temp/Humidity (°F / %RH)
Cold rooms can be humidified using a Room Distribution Unit, making sure that this operates within its operating
SMP001 SMP003 SMP005 SMP008 SMP009 SMP010 SMP015 SMP025 SMP035 SMP045 SMP065
VSDU0A VRDXL
30 35
100 380
50 40
14 to 104°F / 10 to 60%
Model
14 to 140°F / 10 to 80%
limits. The room must have operating temperatures of between -10°C and +20°C, with a percentage of relative humidity of no greater than 80% RH. If these limits are not possible, the steam can be distributed in the cold room using a distributor pipe in duct work. In any case, the steam must not come into direct contact with air discharge from the refrigeration unit in the cold room, to avoid possible condensation.
12
(06/06)
Page 13
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Power wiring
Check that the power supply voltage to be connected matches the value indicated on the rating plate inside the electrical panel. Insert the power and ground connection cables into the electrical panel compartment using the strain reliefs supplied, and connect to the terminals. An external fused disconnect must be installed.
All wiring must be in accordance with local, state and national electric codes.
NOTE: to avoid unwanted interference, the
power cables should be kept separate from any control wiring.
Per the table on the following page, make sure that the unit has the proper number of turns through the TAM (Torroid Amperage Monitor), which is on the control board in models SMP001 through SMP015, and separate in models SMP025 through SMP065. Also make sure that the TA Rate DIP switches on the control board are set correctly per the table.
Single Phase Terminals Three Phase Terminals
In models SMP001 - SMP015 make sure that the TAM on the circuit board has the proper number of power wire turns through it, and that the TA Rate DIP switches on the control board are set per the table on the following page.
In models SMP025 - SMP065 the TAM is independent and the jumper must then be on the right terminals per the table on the following page.
13
(06/06)
Page 14
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Voltage
Model
SMP001
SMP003
SMP005
SMP008
SMP009
SMP010
SMP015
SMP025
SMP035
SMP045
SMP065
Code
U 208 - 1~N 5.4 1 20 1.5 D 230 - 1~N 4.9 U 208 - 1~N 10.8 2 60 2.5 D 230 - 1~N 9.8 1 20 2.5
W 208 - 3~ 6.2 1 20 2.5
K 230 - 3~ 5.6 1 20 2.5 M 460 - 3~ 2.8 U 208 - 1~N 18 1 40 6 D 230 - 1~N 16.3 1 40 6
W 208 - 3~ 10.4 1 20 2.5
K 230 - 3~ 9.4 1 20 2.5 M 460 - 3~ 4.7 2 20 1.5 N 575 - 3~ 3.8
W 208 - 3~ 16.7 1 40 6
K 230 - 3~ 15.1 2 60 6 M 460 - 3~ 7.5 1 20 2.5 N 575 - 3~ 6 U 208 - 1~N 31.4 1 60 16 D 230 - 1~N 29.3
W 208 - 3~ 20.8 1 40 6
K 230 - 3~ 18.8 1 40 6 M 460 - 3~ 9.4 1 20 2.5 N 575 - 3~ 7.5
W 208 - 3~ 31.2 1 60 16
K 230 - 3~ 28.2 1 60 10 M 460 - 3~ 14.1 1 20 4 N 575 - 3~ 11.3
W 208 - 3~ 52 1 300 25
K 230 - 3~ 47.1 1 300 25 M 460 - 3~ 23.5 1 300 10 N 575 - 3~ 18.8
W 208 - 3~ 72.9 1 500 35
K 230 - 3~ 65.9 1 500 35 M 460 - 3~ 32.9 1 500 16 N 575 - 3~ 26.4
W 208 - 3~ 93.68 1 500 70
K 230 - 3~ 84.72 1 500 70 M 460 - 3~ 42.4 1 500 16 N 575 - 3~ 33.9 M 460 - 3~ 61.19 1 300 35 N 575 - 3~ 48.95
Voltage
Phase
Nominal
Current
(Amps)
Power
(kW)
1.12 1.5 3.3
2.25 3 6.6
3.75 5 11
6.52 9 20
7.5 10 22
11.25 15 33
18.75 25 55
26.25 35 77
33.75 45 99
48.75 65 143
Output
(kg/hr)
6 8 17.6
Output (lbs/hr)
Turns
Through
TAM
TA Rate
2 20 1.5
2 20 1.5
2 20 1.5
1 20 2.5
1 60 10
1 20 2.5
1 20 4
1 300 6
1 300 10
1 500 16
1 300 35
Wire
Size
(mm)
NOTE: Tolerance allowed on main voltage = -15%, +10%
14
(06/06)
Page 15
Installation, Operation & Maintenance Manual
Control wiring
The STEAMaster+ control system allows up to two sensors to be connected, as well as various safety devices, remote on/off, alarm and serial communications.
Generally, the control sensor or humidistat (HT) is located in the room or return air duct. In the case where the STEAMaster+ uses a direct discharge blower unit, this is the only control needed. In ducts or air handlers, a high limit humidistat or sensor is usually added to act as a safety (CR), as well as an air flow proving device. The remote terminal HumiVisor (MT) may be added.
Remote Supervisor / Serial Communications:
This is a standard RS485 serial connection. It is
STEAMaster + SERIES
recommended to keep wiring under 3,200 feet. Request SATS’s communications documentation for additional information on this option.
Control wiring is made directly to the control board terminals:
1. terminal block G (dehumidification contact);
2. terminal block H (alarm contact);
3. terminal block K (on/off, manual drain
switch);
4. terminal block I (control signals);
5. terminal block J (to remote terminal or
supervisory system);
6. dip-switch for selecting TA RATE.
For On/Off Operation:
Connect any simple humidistat, high-limits, air flow switch, and remote contacts in series from terminals 7I to 8I.
Circuits must be completed from 4I to 5I by a jumper and from 7I to 8I for the unit to operate. Use jumpers if devices are not connected.
Parameter A0 must be set to 0.
15
(06/06)
Page 16
For Modulating Operation with External Controller:
Connect any external controller (0-1 Vdc, 0-10 Vdc Parameter A0 must be set to 1. Parameter A2 must be set per the OUT signal from the regulator:
• voltage: 0 to 1 Vdc; 0 to 10 Vdc; 2 to 10 Vdc;
• current: 0 to 20 mA; 4 to 20 mA.
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
NOTE: Safeties are high-limit humidistat, air flow switch, and/or external enable.
For Stand-Alone Modulating Operation:
Connect a high limit sensor and control sensor per the diagram at right.
Parameter A0 must be set to 2 if no high limit sensor, 3 if a high limit sensor is used. Parameter A2 must be set per the OUT signal from the sensor:
• voltage: 0 to 1 Vdc; 0 to 10 Vdc; 2 to 10 Vdc;
• current: 0 to 20 mA; 4 to 20 mA.
Terminal 4I (+(G)) = 12 Vdc Terminals 2I & 6I (M) = common
For Steam Baths (Turkish Baths):
In this case a temperature sensor is used to control the humidifier. Connect sensors per the diagrams below .
ASDH10000
ASWH10000
SIGNAL
COMMON
HC-201 HI-LIMIT
out H
M
+G
+G
out H
PC-301
&
AIRFLOW
SIG
COM 24 Vdc
12 Vdc
SIG
M
COM
Parameter A0 must be set to 4. Parameter A2 must be set to 0.
Alarm Output:
The H terminals allows connection to an on-board SPDT alarm relay that provides No and NC contacts for remote indication of alarms.
Dehumidify Output:
Dehumidify contacts are also provided which can be used to control a dehumidifier from the humidifier control system (stand-alone modulating mode only). The contact is rated for 250 V ac, 8 Amp resistive and 2 Amp inductive loads.
16
(06/06)
Page 17
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors
Model Description
Humidity (0-1 VDC or 4-20 mADC)
ASWH100000 Wall Humidity sensor (replaces SHWOOP)
ASDH100000 Duct Humidity sensor (replaces SSDOMH00/1)
Temperature & Humidity (NTC temp, 0-1 VDC or 4-20 mADC humidity)
ASWC111000 Wall Temp/hum sensor (replaces SWNTCTH0/1 & STHONTC0/1)
ASWC110000 Wall Temp/hum sensor (replaces STHOAP)
Temperature & Humidity (0-1 VDC or 4-20 Madc temp & humidity)
ASDC111000 Duct temp/hum sensor (replaces SDNTCTH0/1)
ASDC110000 Duct temp/hum sensor (replaces SSDOMHT0/1)
Temperature: NTC thermistor, 10 Kohm at 25°C (77°F) (ASWC/ASDC only) Accuracy: +- 0.25°C from 0 to 50°C (32 to 122°F)
Humidity: Thin film capacitor Linear 0-1 Vdc or 4-20 mAdc from 10 to 90%RH Accuracy: +- 3%RH from 20 to 90%RH calibrated at 55%RH and 25°C (77°F) +- 5%RH above 90%RH and below 20%RH
Response time: 60 seconds Power: 12 to 24 Vac/dc or +12 to –12 Vdc Housing: Wall: ABS with glassfiber fill Certifications: Calibrated to NIST traceable
humidity/temperature standard, CE Approved
17
(06/06)
Page 18
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
HC-101 and HC-201 Wall and Duct Humidistats
Mounting the HC-101 room humidistat: Mount the HC-101
humidistat to an inside wall or post in the area to be humidified. Position it so that no drafts from registers or outlets are blowing on it. Be sure that it is not placed over a device that could gener­ate heat or vapor ie: stove, machinery, cleaning vat. The unit has three wire leads, Orange, Brown and Red. Use the Orange and Brown leads for control operation. Use the Orange and Red leads for hi-limit operation.
Mounting the HC-201 duct humidistat: Cut a hole in the side of the duct and mount the HC-201 humidistat to the duct, using the screws provided, at least 6 feet down stream of any live steam or mist. The unit has three wire leads, Orange, Brown and Red. Use the Orange and Brown leads for hi-limit operation.
Wiring Diagram
Brown (N.O.)
Red (N.C.)
Brown makes on Drop in R.H. drop in humidity
TABLE 1. SPECIFICATIONS
Part
No.
HC-101
HC-201
TABLE 2. MAXIMUM ELECTRICAL RATINGS
Type Scale
Range
%RH
Wall 10 to 90 5 40 to 125
Duct 15 to 95 5 40 to 125
Diff.
%RH
Operating
Limits
°F (°C)
(4 to 2)
(4 to 2)
Shipping
& Storage
°F (°C)
-40 to 140
(-40 to 60)
-40 to 140
(-40 to 60)
Orange Common
Connection Cover Dimensions
In. (mm)
6" (150 mm)
color coded
leads
Coded
screw
terminals
Beige
plastic
Metal 4-3/4 x 6-1/2 x 2-1/4
4-3/8 x 2-7/8 x 1-5/8
(111 x 73 x 41)
(121 x 165 x 57)
Part No. AC Volt
50/60 Hz HC-101 HC-201
24 - - 8 60 120 7.2 43.2 8 345 240 3.6 21.6 8 345
FLA LRA Resistive
Amps
18
Pilot Duty
VA
(06/06)
Page 19
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
PC-301 Air Proving Switch
Mounting the PC-301 air flow switch:
Mount the airflow switch in the supply or return duct using the screws supplied. Mount the device so that the diaphragm is in a vertical position as shown at right.
If the airflow switch is to be mounted on the return duct (vacuum), then mount it in a vertical position by the small plate. Drill a 7/16" hole in the side of the duct and connect the supplied tubing to the low pressure tap on the airflow switch and then run it through the drilled hole in the duct. Put no more than 2" of tubing into the duct. Caulk around the tubing where it enters the duct. The high pressure tap is left open to atmosphere.
If the airflow switch is to be mounted to the supply duct (pres­sure), then simply drill a 7/16 hole in the side of the duct, apply caulking to the large plate, and mount the device with the large plate to the duct and the high pressure tap/tubing mated the hole. The low pressure tap is left open to atmosphere.
MOUNTING DIAGRAMS
TABLE 1. MAXIMUM ELECTRICAL SWITCH RATINGS
Vac Full Load
Amps
24V - - 60 10 120V 6.25 37.5 300 10 240V 3.1 18.6 300 10 277V 2.7 16.2 300 10
WIRING DIAGRAM
N.C.
Locked Rotor
Amps
Pilot Duty
(VA)
Non-
Inductive
Amps
Common Increase Pressure
N.O. makes on increase N.O. in pressure.
19
(06/06)
Page 20
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Start-Up
IMPORTANT WARNINGS:
1. Before starting, check that the humidifier is in perfect condition, that there are no water leaks and that the electrical parts are dry;
2. Do not connect power if the humidifier is damaged or even partially wet!
When installation is completed, flush the supply pipe for around 30 minutes by piping water directly into the drain, without sending it into the humidifier; this will eliminate any scale or residues that may cause foam
when boiling.
NOTE: For humidifiers with control H only, the same function can be performed automatically after starting the appliance.
Startup Checklist
Before starting the humidifier, the following should be checked:
_____ Water is connected, the line has been flushed, and external valves are open.
_____ Drain is connected, run to an open drain, and has a trap under the unit.
_____ Electricity is connected in accordance with instructions, local codes and data labels in the unit.
_____ The power fuses are installed and intact.
_____ All control wiring is done and tested.
_____ Airflow switch is wired to open on air flow loss.
_____ Hi-limit humidistat is wired to open on humidity rise above set point.
_____ Unit wires have been checked to make sure they and all connectors are tight from shipping.
_____ The steam hose(s) are run correctly with no sags or kinks and sloped properly according to the manual.
_____ Condensate hoses are run correctly with no sags or kinks and sloped properly according to the manual.
NOTE: If you ordered a factory startup, this checklist will be required. Failure to complete this checklist may result in additional charges.
20
(06/06)
Page 21
The HumiControl Controller
1: PRG - Access to most frequently used parameters. Also resets alarm relay.
2: SEL - Displays unit of measure. Press for 2 seconds to access set point. Press with PRG for 5 seconds to enter parameters.
3: Ç - Displays control sensor value. In programming mode increases value or moves to previous parameter.
4: È - Displays high limit sensor value. In program- ming mode decreases value or moves to following parameter.
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
5: 2-1/2 digit display for values and parameters.
6: LED to indicate decimal point.
7: LED to indicate value must be multiplied by
1000.
8: LED to indicate dehumidify mode.
9: LED to indicate alarm.
10: LED to indicate humidifier is producing steam.
Flashing indicates lower than required production.
11: LED to indicate when unit is filling.
12: LED to indicate when unit is draining.
Start-up Procedure
After closing the external fused disconnect to put power to the humidifier, press the top (I) part of the I/O switch on the side of the unit
Initially, all LEDs light - this lasts about 1-2 seconds.
Then the initialization phase begins with 3 dashes. During this phase diagnostics are conducted. This phase lasts about 4 seconds.
After running the diagnostics, the unit will start operation and display either the % of steam production (On/off and Modulating modes), the %RH (Stand-Alone Modulating mode), or two dashes will light, indicating the humidifier is disabled or in alarm. The alarm code will flash.
Starting with a new cylinder
When starting with a new cylinder, you should activate the cylinder cleaning function by pressing the SEL and buttons simultaneously for 2 seconds after the initialization phase. This forces the unit to open both the drain and fill valves for 10 minutes to flush the lines, then fills and drains the cylinder 3 times to wash out any mold release or dirt. Once started, this function can be stopped by pressing the SEL and again.
When starting the unit with a new or empty cylinder, it may take a significant amount of time (hours) for the unit to build up enough mineral concentration to reach rated capacity. This time can be shortened by the addition of Alka-Seltzer or salt (teaspoon) through the steam outlet on top of the cylinder.
21
ÈÈ
È
ÈÈ
ÈÈ
È buttons simultaneously for 2 seconds
ÈÈ
(06/06)
Page 22
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Operation
Display Information
Pressing the SEL button displays the unit of measure currently in use for the main display Holding the Holding the
Changing The Set Point
Press the SEL button for 2 seconds until “St” appears. On releasing the button, the unit of measure is displayed followed by the current set point value. To change the set point, press the increase or decrease the value. Press SEL or PRG to lock in the new set point. Waiting 5 seconds without pressing SEL or PRG will revert to the old value.
Activating Manual Drain
In addition to the manual drain switch on the side of the humidifier, pressing the neously for 2 seconds will force a manual drain which will completely empty the cylinder without having to hold the manual drain switch. This procedure can be stopped at any time by pressing the simultaneously for 2 seconds again.
ÇÇ
Ç button displays the value of the control sensor preceded by the unit of measure.
ÇÇ ÈÈ
È button displays the value of the high-limit sensor preceded by the unit of measure.
ÈÈ
ÇÇ
ÈÈ
Ç or
È button to
ÇÇ
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons simulta-
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons
ÈÈ
Accessing/Changing Configuration Parameters
The numerical, configuration and control parameters are grouped into three levels:
LEVEL 1 - set point parameters: the value of the humidifier’s main set point “St”, accessible directly via the keypad for both reading and modification. See “Changing The Set Point”.
LEVEL 2 - control parameters and measurements: the physical values measured and the operat­ing parameters involving the control of the humidification process; these too can be accessed directly via the keypad for reading and modification.
LEVEL 3 - configuration parameters: consisting of the data needed to customize the controller’s operation. These parameters can be accessed only by password.
To display the Level 2 Control Parameters:
Press and hold the PRG button for 5 seconds until P0 is displayed;
Press the
ÇÇ
Ç and
ÇÇ
Press the SEL button to display the value of any parameter (the unit of measure will display first for 1
second).
Code Range Default Unit Description
P0 20 to 100
P1 2.0 to 19.9 5 %RH, °C Hum idification differential
P2 (1)
P3 (1) 0 to P2 0 %RH, °C
P3 to 100 100 %RH
P3 to 60 60 °C
P4 0 to 100 1 min Alarm delay (0*= 30 s)
P5 2 to 100 10 %RH Dehumidification dead zone
P6 1.0 to 19.9 5 %RH Dehumidification differential
ÈÈ
È buttons to scroll through the Px and dx parameters;
ÈÈ
100 Maximum output for H controllers 100
%
Maximum output for P controllers
High humidity or high temperature alarm set point
Low humidity/temp. alarm set point
22
accessible only in control mode (A0=2, 3 or 4)
accessible only with the dehumidification function enabled
(b1 odd number) in humidity control mode (A0 = 2 or 3)
(06/06)
Page 23
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Code Range Default Unit Description
P7 (1) St to 100 100 %RH Hi-limit set point
P8 2.0 to 19.9 5 %RH Hi-limit differential P9 0 to 100 100 %RH Hi-limit alarm set point
Code Range Default Unit Description
d1 (2) 0.0 to 199
d2 0.0 to 199
read only
%RH, °C, % Signal from external controller
or sensor
%RH
Signal from hi-limit or temperature sensor
d3 0.0 to 199 kg/h Steam output (actual)
d4
0.0 to
19999
h Run time hours
d5 0 to 1555 µS/cm Conductivity of the feed water d6 0.0 to 199 A Current (Amperage) d9 0.0 to 199 kg/h Rated steam output
(1): when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding default value. (2): in proportional operation (A0=1), d1 displays the % of the control signal
Accessible only with hi-limit control (A0=3)
Not accessible in on/off mode (A0=0)
Accessible only with hi-limit control (A0=3)
To display the Level 3 Configuration Parameters:
Press and hold the PRG and SEL buttons simultaneously for 5 seconds until 00 is displayed;
Press the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons to enter the password value of 77;
ÈÈ
Press the SEL button and A0 should display;
Press the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons to scroll through the configuration parameters;
ÈÈ
Press the SEL button to display the value of any parameter (the unit of measure will display first for 1
second);
Press the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons to change the value;
ÈÈ
Press SEL when the change is complete and then continue scrolling through the parameters;
To leave the programming mode, press PRG at any time. NOTE: after more than 5 seconds without a
button press, the display will begin to blink. 60 seconds after a button press, the controller will erase all changes and return to operating mode with the previous parameters.
Parameters for configuring standard operation:
Code Range Default Unit Description
0=ON/OFF control 1=modulating
A0 (1) 0 to 4 2 Operating mode
A1 0, 1 0 Unit of measure
Type of room sensor; not
A2 0 to 4 0
A3 (2) 0 to A4 0 %RH, ºC Room sensor minimum A4 (2) A3 to 255 100 %RH, ºC Room sensor maximum
A5 -10.0 to 10.0 0 %RH, ºC Room sensor offset
accessible in ON/OFF mode (A0=0)
2=humidity control 3=humidity control with hi-limit control 4=steam baths 0=°C, kg/h 1=°F, lbs/hr
0=0 to 1V; 1=0 to 10V; 2=2 to 10V; 3=0 to 20mA;
4=4 to 20mA
Accessible only in control mode (A0=2, 3 or 4) Used for scaling sensors
23
(06/06)
Page 24
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Code Range Default Unit Description
Type of outlet sensor;
A6 0 to 4 0
A7 0 to A8 0 %RH Hi-limit sensor minimum A8 A7 to 100 100 %RH Hi-limit sensor maximum A9 -10.0 to 10.0 0 %RH Hi-limit sensor offset
(1): when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding default value.
Parameters for configuring the operation of accessory devices:
Code Range Default Unit Description
b1 0 to 127 0
b2 0 to 120 0 s Shut-down delay time b3 -10.0 to 10.0 0 % Current measurement gain
0 to 199
b4
0k2, ….2k0
0 to 199
b5
0k2, ….2k0
0 to 199
b6
0k2, …, 2k0
b7 0 to 100 50 % Foam detection set point (0=no foam detect, 1=max sens., 100=min sens.)
b8 50 to 200 100 %
b9 50 to 200 100 % Adjust the duration of the drain for dilution
bb 0* to 4000 1500 h
bE 1 to 120 24 h
bF 1 to 199 3 days Days to wait to drain due to inactivity
0 µS/cm Water conductivity (0=automatic measurement)
1k5 µS/cm Conductivity pre-alarm set point
2k0 µS/cm Conductivity alarm set point
accessible only in humidity control with outlet limiting (A0=3)
Special functions To enable more than one, sum the 0= no function corresponding values and assign 1= dehumidifier management active them to b1; e.g.: b1=1+2+8=11 2= drain under power
dehumidifier management active +
drain under power + disable draining 8= disable draining for inactivity for inactivity of at least 7 consecutive 16= disable cylinder being depleted days (the other functions are
deactivated)
64= enable periodic draining
Internal conductivity reached by the cylinder in stable conditions against rated value
Cylinder maintenance limit time (in hours) 0*= disable life alarm “Cy” and maintenance alarm “Mn” 100 hour step if bb>199 hours, hour step if bb<199 hours Time limit between two periodic
drain cycles
0=0-1V; 1=0-10V; 2=2-10V; 3=0-20mA;
4=4-20mA
Accessible only in humidity control with outlet limiting, (A0=3)
4= disable draining on set point reduction
and cylinder depleted warnings
32= reverse the operation of the alarm relay
Accessible only if periodic draining is enabled (64 in "b1")
Not accessible if draining due to inactivity is disabled, (8 in "b1")
24
(06/06)
Page 25
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Parameters for setting the serial connections and remote control:
Code Range Unit Description
1= room sensor measurement 2= outlet sensor measurement
C0 1 to 6 1 Value normally displayed
Enable keypad and remote control keypad: remote control: 0= read of all param., (modify C1 only) read and modify param. P, d and St
C1 0 to 4 4
C2 0 to 99 0 Remote control enabling code (see paragraph 8.2) C3 0 to 199 1 Serial address C4 0 to 3 3 Supervisor: baud-rate 0=1200, 1=2400, 2=4800, 3=9600
C5 0 to 11 0
C6 0 to 199 0 Ms serial reply send delay
C7 0 to 3 0
1= read and modifiy all parameters read and modify param. P, d and St 2= read of all param., (modify C1 only) read parameters P, d and St 3= read and modify all parameters read parameters P, d and St 4= read and modify all parameters read and modify all parameters
Supervisor: frame (character bits, parity, stop bits) 0=8,N.2 6=7,N.2 1=8,N,1 7=7,N,1 2=8,E.2 8=7,E.2 3=8,E,1 9=7,E,1 4=8,O.2 10=7,O,2 5=8,O,1 11=7,O,1
Graphic terminal configuration in cases 1,2,3 the OFF command is forced on start-up
Notes about special parameters
3= steam output 4= hour counter 5= conductivity 6= current
0=terminal 1=terminal with ON/OFF control 2=term. with ON/OFF and room sensor 3=term. with ON/OFF and hi-limit
sensor
b1, setting 2: Drain under power
If parameter b1 includes setting 2, the humidifier will continue to produce steam during drain cycles. If this setting is turned off, the humidifier will open the power contactor during drain cycles.
b1, setting 4: Draining due to a significant reduction in the demand
If parameter b1 includes setting 4, then the humidifier will not drain if the demand for humidification decreases. This helps to conserve conductivity and is useful in low conductivity waters. If b1, setting 4 is off, then the humidifier will drain to reduce the output if the demand is reduced by 33%.
b1, setting 8: Automatic draining of the cylinder after period of non-use
If parameter b1 includes setting 8, parameter “bF” may be used to cause the humidifier to empty the steam cylinder if there has been no demand for humidification for an extended period of time. This helps prevent premature corrosion of the electrodes and/or contamination of the water in the cylinder. The default setting is for 3 days. The unit will display “idr” when this drain function occurs.
b1, setting 64: Complete periodic draining
If parameter b1 includes setting 64, then parameter “bE” can be used to set the hours between total drains of the cylinder. This is useful if the water contains impurities that can cause erratic behavior.
25
(06/06)
Page 26
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
STANDARD FACTORY SETTINGS
STEAMaster+ Parameters
H Controller
Parameter
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 b1 b2 b3 b4 b5 b6 b7 b8 b9 bb bE bF C0 C1 C2 C3 C4 C5 C6 C7 d1
d2 d3 d4 d5 d9 P0
P1 P2 P3 P4 P5 P6 P7 P8 P9 ST
N/A - Not Accessible
- Read Only
DDC
0-10 vdc
1 1 0 2 3 1 1 1 1 1
1 4 N/A 0 0 N/A N/A N/A 0 0 N/A N/A N/A 100 100 N/A N/A N/A 0 0 N/A N/A N/A N/A 0 N/A N/A N/A N/A 0 N/A N/A N/A N/A 100 N/A N/A N/A N/A 0
2 2 2 2 2
0 0 0 0 0
0.0 0.0 0.0 0.0 0.0 0 0 0 0 0
15 15 15 15 15 20 20 20 20 20
75 75 75 75 75 100 100 100 100 100 100 100 100 100 100
0 0 0 0 0
N/A N/A N/A N/A N/A
3 3 3 3 3 1 1 1 1 1 4 4 4 4 4 0 0 0 0 0 1 1 1 1 1 3 3 3 3 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
100 100 100 100 100 N/A N/A N/A 5 5 N/A N/A N/A 100 100 N/A N/A N/A 0 0 N/A N/A N/A 1 1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 N/A N/A N/A N/A 5 N/A N/A N/A N/A 100 N/A N/A N/A 50 50
DDC
4-20ma
ON / OFF
STAND ALONE
STAND ALONE
WITH HIGH LIMIT
26
(06/06)
Page 27
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Seasonal Shut Down
During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the plumb­ing, the humidifier should be placed out-of-service.
NOTE: the water cylinder should be emptied before shutting down the humidifier, to prevent corrosion of the electrodes.
Follow these instructions:
Press and hold the manual drain switch until the
steam cylinder is empty, or use the Manual Drain procedure listed under “Activating Manual Drain”;
Turn off the On/Off (I/O) rocker switch on the side of
the humidifier, and disconnect power from the humidi­fier;
Shut off the water to the humidifier.
In the event of malfunction of the drain valve, the cylinder can be emptied manually by lifting it out of the drain manifold and pouring the water into the bottom drain pan. For SMP026 and larger humidifiers, use the manual drain device on the manifold, pulling the manual drain tab until it releases (see sketch at right).
The Remote Control
A hand-held infra-red remote control is available for the STEAMaster+. This device permits programming the humidifier(s) from across the room and also makes available buttons with specific functions.
NOTE: To use the remote control, parameter C2 must be set on each humidifier to give it an access code so that the remote control can address it. If all humidifiers in range of the remote control have the same access code, then they will respond simultaneously to commands from the remote control. Setting C2 to 0 on the humidifier will allow the remote control to be used without the need of a code.
To use the remote control, aim it at the humidifier and press ENABLE. All the humidifiers in range will display their activation codes. If a humidifier has its C2 parameter set to 0, it will skip this step and display the first parameter.
To program a humidifier, enter its access code into the remote control. If successful, the humidifier will display the first parameter.
To program main parameters, simply press the + or - button on the remote control of the parameter you want to modify and the humidifier will display that parameter code. Press the SEL button on the remote control and the value will be displayed. Modify the value by using the are saved when you exit the programming phase.
To program other parameters, press any + or - button on a parameter, then use the SEL and remote control in the same way as the buttons on the front of the humidifier controller.
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons on the remote control. Then press the next parameter button and so on. Values
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons on the
ÈÈ
To exit the programming phase and save the modifications made to the parameters, press the PRG button. To exit without saving the modifications, press the ESC button. To exit the programming phase without confirming the modifications made:
do not press any button for 60 seconds, if the parameter code is displayed;
do not press any button for 120 seconds, if the value of the parameter is displayed.
27
(06/06)
Page 28
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Resetting the Hour Counter
To reset the hour counter (parameter d4), proceed as follows:
press the PRG button for 5 seconds, until the code P0 is displayed, indicating the first modifiable parameter;
using the
press the SEL button to display the value of the hour counter (preceded for 1 second by the unit of measure);
press the
ÇÇ
Ç and
ÇÇ
ÇÇ
Ç and
ÇÇ
Alarms
In the event of an alarm, the alarm LED (9) will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple alarms will flash in sequence, alternating with the main display. Pressing the PRG button will reset the alarms, although still active alarms will continue to display.
ÈÈ
È buttons, scroll the parameters until d4 is displayed;
ÈÈ
ÈÈ
È buttons together for 5 seconds until the value is set to zero, preceded by a brief flash.
ÈÈ
Controller Action
EH
EL
EC
EP
Humivisor Causes Solution
H
Over-current at the
E102
E103
E105
E113
electrodes; probable electrode malfunction or water conductivity temporarily too high (especially when starting after a short stop)
Power not available; no steam production when on
High supply water conductivity
Excessive reduction in output
1. Check the operation of the drain valve
2. Check for fill valve leakage
3. Drain part of the water and re-start
1. With the machine off and disconnected from the main power, check the internal electrical connections
1. Check limit set for b6
2. Turn the machine off and clean the water conductivity probes
3. If the problem persists, change the source of supply water or install a suitable treatment system (demineralization, even partial). Note: the problem will not be resolved by softening the supply water.
1. Cylinder completely spent or water with excessive foam. Perform maintenance on the cylinder.
Shut­down
Shut­down
Shut­down
Shut­down
Reset
display
H
N/A Active N/A
N/A Active N/A
N/A Active N/A
Manual Active Manual
Alarm
relay
Reset
relay
28
(06/06)
Page 29
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Controller Action
EF
EA
Ed
Ec
Humivisor Causes Solution
H
1. Check that the fill pipe from the main to the humidifier and the internal pipe are not blocked or bent and that there is sufficient pressure (0.1-0.8 mpa, 1-8 bar)
2. Check the operation of the
E114 Lack of water
E115
E116 Drain malfunction
E131
Excessive foam in the cylinder during boiling
High water conductivity pre-alarm
fill valve
3. Check that the steam outlet is not working against excessive back-pressure, preventing the flow of water into the cylinder by gravity
4. Check that the steam outlet pipe is not is kinked and that there are no sags. The formation of foam is generally due to the presence of surfactants in the water (lubricants, solvents, detergents, water treatment agents, softeners) or an excessive concentration of dissolved salts:
1. Drain the water supply lines
2. Clean the cylinder
3. Check for the presence of softeners (in this case, use another type of water or reduce the softening)
Check the drain circuits and the correct operation of the drain valve
Check the conductivity of the supply water if necessary, install a suitable treatment system Note: the problem will not be resolved by softening the supply water.
Shut­down
Signal
only
Shut­down
Signal
only
Reset
display
H
Automatic
when water
returns
Manual
Manual Active Manual
Auto
Alarm
relay
Active
Active Manual
Not
active
Reset
relay
Automatic
when water
returns
-
High humidity in the
E-
E-
E=
E121
E122
E124 High hi-limit humidity
room (high temp.for T control)
Low humidity in the room (low temp.for T control)
Check the operation of the probe and the limit set for parameter P2
Check the operation of the probe and the limit set for parameter P3
Check the operation of the outlet probe
29
Signal
only
Signal
only
Signal
only
Manual
Manual
Manual Active Auto
Active Auto
Active Auto
(06/06)
Page 30
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Controller Action
H
E0
EI
E2
E3
E4
Humivisor Causes Solution
1. Reset the default parameters
E101
E112
E130
E120
E123
Internal memory error
Error in the user parameters
Hour counter error
Room sensor not connected
Hi-limit sensor not connected
(see Chap. 7.5)
2. If the problem persists, contact the CARE service center
1. With the machine off check that there are no defective electrical connections or faults, then reprogram the parameters
2. Reset the default parameters (see Chap. 7.5)
3. If the problem persists, contact the CARE service center With the machine off check that there are no defective electrical connections or faults, then reset the hour counter (see par. 7.6) Check the connection of the probe, parameter A2 for the room probe and the setting of parameter A0 (see chap. 7) Check the connection of the probe, parameter A6 for the outlet probe and the setting of parameter A0 (see chap. 7)
H
Shut­down
Shut­down
Hour
counter
Shut­down
Signal
only
Reset
display
Reprog.
By
SATS
Reprog.
Params.
Reset
manual
Manual Active Auto
Manual Active Auto
Alarm
relay
Active
Active
Not
active
Reset
relay
Reprog.
By
SATS
Reprog.
Params.
N/A
CP CL
EU
PC
Cy
Nn
E132
E133
E134
-
E135
E136
Cylinder being depleted signal
Cylinder depleted signal cylinder
Cylinder full with machine off signal
Cleaning cylinder started signal
Timeout signal (see parameter "bb") for maintenance exceeded
Reached final limit (1.5xbb) of cylinder operating life
Perform maintenance and/or replace the cylinder
Perform maintenance and/or replace the only
With the machine off:
1. Check for any leaks from the fill valve or the condensate return pipe
2. Check that the level sensors are clean total shut-down
You have activated the automatic cylinder flushing sequence
Perform maintenance and/or replace the cylinder
Replace the cylinder
30
Signal
only
Signal
only
Shut­down
Signal
only
Shut­down
Manual
Not
available
Manual Active Manual
- - - -
Manual
reset
hour
counter
Manual
reset
hour
counter
Not
active
Not
active
Active
Active
Auto
N/A
After
the
manual
reset
hour
counter
After
the
manual
reset
hour
counter
(06/06)
Page 31
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Controller Action
H
Dr
Idr
Dr
AF
Humivisor Causes Solution
Complete draining of the
­cylinder
activated Complete draining for
­extended
inactivity Complete
-
periodical draining active
Anti-foam
­algorithm active
You have activated the manual drain sequence. Sequence ends on its own.
The unit is emptying the cylinder after an extended period of non-use. Sequence ends on its own.
The unit has activated the periodic drain to flush excessive minerals. Sequence ends on its own.
The unit is working to eliminate foaming.
Reset
display
H
- - - -
- - - -
- - - -
- - - -
Alarm
relay
Reset
relay
32
(06/06)
Page 32
Trouble-Shooting
problem causes solutions
the humidifier does not turn on
the humidifier does not start operation
Installation, Operation & Maintenance Manual
1. no electrical power
2. on/off switch of the humidifier in position 0 (open)
3. control connectors improperly connected
4. blown fuses
5. transformer failure
1. remote ON/OFF contact open (relay/terminals AB - AB or 7I - 8I)
2. the humidistat has not been connected correctly
3. humidistat failure
4. control signal not compatible with the type set
5. value measured by the sensor/s higher than the corresponding set point
STEAMaster+ SERIES
1. check the safety devices upstream from the humidifier and the presence of power
2. close the switch on the panel: position I
3. check that the connectors are properly inserted in the terminal block
4. check the condition of fuses F1/F2/F3
5. check that the voltage across the secondary winding of the transformer is 24Vac
1. close ON/OFF contacts (relay/terminals 7I - 8I)
2. check the external connection
3. replace the humidistat
4. set parameters A0, A2-A9 correctly
5. check the values of the set point St and P7
the humidifier fills with water without producing steam
the thermal-magnetic overload switch is activated
the humidifier wets the duct
the humidifier wets the floor below
1. high steam back pressure
2. fill valve strainer clogged
3. mineral in the fill cup
4. drain solenoid valve leaking
1. thermal-magnetic overload switch is under-rated
2. over-current at the electrodes
1. the distributor is not installed correctly (too near the top of the duct or the condensate return is blocked)
2.system over-sized
3.humidifier active when the fan in the duct is off
1. the humidifier drain is blocked
2. the supply water or overflow circuit has leaks
3. the condensate drain pipe does not bring the water back to the drain pan
4. the steam hose is not properly fastened to the cylinder
1. check that the steam hose is not kinked or sagging, trapping condensate
2. clean the fill valve strainer
3. clean the fill cup
4. check for 24Vac at the drain solenoid valve and/or drain solenoid replacement
1. check that the thermal-magnetic overload switch is rated for a current of at least 1.5 times the rated current of the humidifier
2. see description for alarm EH
1. check that the steam distributor is installed correctly
2. decrease the steam production set on the control
3. check the connection of the device (flow switch or differential pressure switch) slaving the humidifier to the ventilation in the duct (terminals 7I - 8I)
1. clean the drain assembly and pan
2. check the entire water circuit
3. check the correct position of the condensate drain hose in the drain pan
4. check the fastening of the hose clamps on the steam outlet
32
(06/06)
Page 33
Installation, Operation & Maintenance Manual
problem causes solutions
Water in the cylinder turns black 1. minerals in the cylinder have
overconcentrated and are deteriorating the electrodes.
Heavy arcing occurs within hours of startup
Humidifier continuously fills and drains without producing steam
1. The feed water contains large amounts of Iron, Copper or other conductive contaminants.
1. Mineral has bridged between the electrodes.
2. There is back pressure from the steam hoses or duct.
3. The flow regulator in the fill valve is broken or out of place.
4. Water conductivity is very high.
5. Water is foaming excessively.
STEAMaster + SERIES
1. Check for sags & kinks that could trap condensate in the steam hoses that could cause a back pressure on the cylinder.
2. Check the duct static pressure.
3. Check the fill valve and inlet strainer.
4. Check the drain valve operation.
5. Correct installation problems and replace cylinder.
1. Contact the factory for an optional drain timer to force additional drains to control the minerals.
2. If you are using a softener, check the salt being used. If it contains any additives, discontinue use, flush all lines and convert to pure salt or unsoftened water.
3. Check the electrodes in the cylinder to be sure they were not damaged in shipping.
1. Clean or replace the cylinder.
2. Check the steam hoses for kinks or gullys that might be trapping condensate.
3. Replace the fill valve.
4. Consider using a mix of demineralized water with raw water.
5. Check cylinder - replace if exhausted. If feed water contains silica or nitrates, install a 1 micron water filter.
Resetting Factory Defaults
If errors have occurred when setting the parameters, the controller may be reset to the factory default values:
in the first 5 seconds from start-up (while the three
dashes are displayed), press the PRG button (2) until the upper dash in the center flashes (1);
release the PRG button within 3 seconds to confirm
the permanent reset of the factory defaults; to confirm the reset, the upper dash will stay on for 2 seconds;
the factory reset is not carried out if the PRG button is
pressed for more than 3 seconds, until the upper dash disappears.
Recalling the default parameters does not change the parameter relating to the unit of measure (A1), and it is thus recommended to check and if necessary select and save the unit of measure as required, and then recall the default parameters. In this way the default values will automatically be converted.
33
(06/06)
Page 34
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Maintenance
Periodic checks
After one hour of operation: For both disposable and cleanable cylinders, check that there are no
significant water leaks.
Every fifteen days or no more than 300 operating hours: For both disposable and openable cylinders
check operation, that there are no significant water leaks and the general condition of the cylinder. Check that during operation there is no arcing between the electrodes.
Every three months or no more than 1000 operating hours: For disposable cylinders, check operation,
that there are no significant water leaks and, if necessary, replace the cylinder; for cleanable cylinders, check that there are no blackened parts of the cylinder. If there are blackened parts of the cylinder, check the condition of the electrodes, and if necessary replace them together with the o-rings and the cover gasket.
Annually or no more than 2500 operating hours: For disposable cylinders, replace the cylinder; for
cleanable cylinders check operation, that there are no significant water leaks, the general conditions of the cylinder, check that there are no blackened parts of the cylinder: if this is the case, check the condition of the electrodes, and if necessary replace them together with the o-rings and the cover gasket.
After five years or no more than 10,000 operating hours: For both disposable and openable cylinders,
replace the cylinder. After extended use or alternatively when using water with a high salt content, the solid deposits that naturally form on the electrodes may reach the stage where they also stick to the inside wall of the cylinder; in the event of especially conductive deposits, the consequent heat produced may overheat the plastic and melt it, and, in more severe cases, puncture the cylinder, allowing water to leak out. As a precaution, check the deposits and the blackening of the wall of the cylinder, and replace the cylinder if necessary.
CAUTION: always disconnect the main power before touching the cylinder in the event of leaks, as current may flow through the water.
Cylinder maintenance
The life of the cylinder depends on a number of factors, including: the amount and type of mineral in the water, the correct use and sizing of the humidifier, and the output, as well as careful and regular maintenance. Due to the aging of the plastic and the consumption of the electrodes, even an openable steam cylinder has a limited life, and it is therefore recommended to replace it after 5 years or 10,000 operating hours.
Important warnings
The humidifier and its cylinder contain live electrical components and hot surfaces, and therefore all service and/or maintenance operations must be performed by expert and qualified personnel, who are aware of the necessary precautions. Before performing any operations on the cylinder, check that the humidifier is disconnected from the power supply. Remove the cylinder from the humidifier only after having drained it completely using the manual drain button or procedure. Check that the model and the power supply voltage of the new cylinder correspond to the data on the rating label.
Replacing the cylinder IMPORTANT WARNING: the cylinder may be hot. Allow it to cool before touching it or use protective gloves.
To replace the cylinder:
completely drain the cylinder by pressing and holding the manual drain switch or by pressing the
buttons simultaneously for 2 seconds to force a manual drain. This procedure can be stopped at any time by again pressing the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons for 2 seconds;
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È
ÈÈ
turn the humidifier off and disconnect the main power;
open and remove the cover;
remove the steam hose from the cylinder;
disconnect the electrical connections from the top of the cylinder;
release the cylinder from its holding bracket and lift it up to remove it;
install the new cylinder in the humidifier by performing the previous operations in reverse.
WARNING: Electrical connections to the cylinder must be tight or possible fire hazard may result.
34
(06/06)
Page 35
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Maintenance of the other plumbing components
IMPORTANT WARNINGS:
When cleaning the plastic components do not use detergents
or solvents;
Scale can removed using a solution of Lime-A-Way
or 5% phosphoric acid, then rinse with water.
External power must always be disconnected when perform-
ing any maintenance on the humidifier.
®
, CLR®,
••
Drain valve /drain pump:
••
Remove the valve body or pump, clean if necessary using the same cleaning solution as for the steam cylinder and a soft brush.
••
Drain pan:
••
Clean the pan of any mineral deposits and check that the water flows freely from the pan to the drain at the drain valve.
••
Supply, fill, overflow pipes:
••
Check that these are clear and clean or replace if necessary.
••
Fill valve:
••
After having disconnected the cables and the hoses, remove the valve and check the condition of the inlet filter; clean if neces­sary using the same cleaning solution as for the steam cylinder and a soft brush.
••
Supply and drain manifold:
••
Check that there are no mineral deposits in the cylinder attachment and clean if neces­sary. Check that the seal (o-ring) is not damaged or cracked; replace if necessary.
IMPORTANT WARNING: after having
replaced or checked the plumbing, check that components have been reconnected correctly with the proper seals. Re-start the humidifier and perform a number of supply and drain cycles (from 2 to 4), then check for any water leaks.
Item No. Description
1 fill/drain manifold 2 fill valve 3 drain valve 4 fill cup fill pipe 5 cylinder supply pipe 6 overflow pipe 7 fill cup 8 drain pan
9 drain column 10 drain pipe 11 drain pump 12 conductivity meter
35
(06/06)
Page 36
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Replacement Parts
Single Phase Humidifiers
Standard spare parts Model
Water parts
fill cup + conductivity meter 18C453A008 18C453A008 18C453A008 18C453A008 fill valve kit KITVC00006 KITVC00006 KITVC00006 KITVC00012 drain valve kit 13C499A030 13C499A030 13C499A030 13C499A030 internal pipe kit UEKT00000S UEKT00000S UEKT00000S UEKT00000M
Non-openable cylinders
200/230 VAC 1~, conductivity 350-1250 µS/cm SMP0S1F00H1 SMP0S1F00H1 SMP0S2F00H0 SMP0S3F00H0
Electrical parts
Contactor 0203000AXX 0203000AXX 0203001AXX 0203001AXX power transformer: 208/230/460/575-24 Vac fuse holder 0606192AXX 0606192AXX 0606192AXX 0606192AXX fuse 0605319AXX 0605319AXX 0605319AXX 0605319AXX
Electronic parts
LED display ver.C-P UEKDP00000 UEKDP00000 UEKDP00000 UEKDP00000 control module ver.H-T UEH0000001 control board ver.C-P ** UEP0000001 control board ver.H-T UEI0000000 UEI0000000 UEI0000000 UEI0000000 flat connection cable 59C460A003 59C460A003 59C460A003 59C460A003 remote control TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000
SMP001 SMP003 SMP005 SMP009
09C476A027 09C476A027 09C476A027 09C476A027
UEH0000001 UEH0000001 UEH0000001 UEP0000001 UEP0000001 UEP0000001
Spare parts for special applications
Non-openable cylinders
200/230 VAC 1~, conductivity 125/350 µS/cm SMP0S1E00H1 SMP0S1E00H1 SMP0S2E00H0 SMP0S3E00H0
Openable cylinders
200/230 VAC 1~, conductivity 125/350 µS/cm SMP CS2E00W0 SMP CS3E00W0 200/230 VAC 1~, conductivity 350/1250 µS/cm SMP CS2F00W0 SMP CS3F00W0 electrode kit (200/230 VAC 1~, 125/350 µS/cm) KITBLCS2E0 KITBLCS3E0 electrode kit (200/230 VAC 1~, 350/1250 µS/cm) KITBLCS2F0 KITBLCS3F0 electrode gasket kit KITBLC2FG0 KITBLC3FG0
SMP001 SMP003 SMP005 SMP009
36
Model
(06/06)
Page 37
Three Phase Humidifiers
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Standard Spare Parts
Model SMP003 SMP005 SMP008 SMP010 SMP015 SMP025 SMP035 SMP045 SMP065
Water Parts
Fill Cup + Conductivity Meter 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008
Fill Valve Kit KITVC00006 KITVC00006 KITVC00006 KITVC00012 KITVC00012 KITVC00040 KITVC00040 KITVC00040 KITVC00070
Drain Valve Kit 13C499A030 13C499A030 13C499A030 13C499A030 13C499A030 KITPS00000 KITPS00000 KITPS00000 KITPS00000
Internal Pipe Kit UEKT00000S UEKT00000S UEKT00000S UEKT00000M UEKT00000M UEKT00000L UEKT00000L UEKT00000L UEKT0000XL
Conductivity Probe:
208-230V 18C431A004
400-460-575V 18C431A004
Disposable Cylinders:
200/230 Vac 3~, Conductivit y 350/1250 µS/cm
400 Vac 3~, Conductivity 350/750 µS/cm
460 Vac 3~, Conductivity 350/1250 µS/cm
575 Vac 3~, Conductivity 350/1250 µS/cm
Electrical Parts
Contactors 0203000AXX 0203000AXX 0203000AXX 0203001AXX 0203001AXX 0203001AXX 0203008AXX 0203009AXX(5) 0203007AXX(2)(3)
Power Transformers:
208/230/460/575-24 Vac 09C476A027 09C476A027 09C476A027 09C476A027 09C476A027 09C479A062 09C479A062 09C479A062 09C479A062
Fuse Holders 0606192AXX 0606192AXX 0606192AXX 0606192AXX 0606192AXX 0606193AXX 0606193AXX 0606193AXX 0606193AXX
Fuses 1,2:
208-230V 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX
400-460-575V 0605318AXX 0605318AXX 0605318AXX 0605318AXX
Fuse 3 0605319AXX 0605319AXX 0605319AXX 0605319AXX
Fuse 4 0605624AXX 0605624AXX 0605624AXX 0605624AXX
Pump Relay 0102001AXX 0102001AXX 0102001AXX 0102001AXX
Electrical Parts
Led Display Ver. C-P UEKDP00000 UEKDP00000 UEKDP00000 UEKDP00000 UEKDP00000 UEKDP00000 UEKDP00000 UEKDP00000 UEKDP00000
Control Module Ver. H-T UEH0000001 UEH0000001 UEH0000001 UEH0000001 UEH0000001 UEH0000001 UEH0000001 UEH0000001 UEH0000001
Control Board Ver. C-P ** UEP0000001 UEP0000001 UEP0000001 UEP0000001 UEP0000001 UES0000001 UES0000001 UES0000001 UES0000001
Control Board Ver. H-T UEI0000000 UEI0000000 UEI0000000 UEI0000000 UEI0000000 UEIN000000 UEIN000000 UEIN000000 UEIN000000
Flat Connection Cable 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003
Remote Control TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELEUE*000
SMP0T1D00H1
SMP0T1D00H1
SMP0T2D00H0
SMP0T2B00H0 SMP0T2B00H0 SMP0T3B00H0 SMP0T3B00H0 SMP0T4C00H0 SMP0T4B00H0 SMP0T5B00H0
SMP0T2C00H0 SMP0T2C00H0 SMP0T3C00H0 SMP0T3C00H0 SMP0T4D00H0 SMP0T4D00H0 SMP0T4D00H0 SMP0T5D00H0
SMP0T2D00H0 SMP0T2D00H0 SMP0T3D00H0 SMP0T3D00H0 SMP0T4D00H0 SMP0T4D00H0 SMP0T4D00H0 SMP0T5D00H0
SMP0T2D00H0 SMP0T2D00H0 SMP0T3D00H0 SMP0T3D00H0 SMP0T4D00H0 SMP0T4D00H0 SMP0T4D00H0 SMP0T5D00H0
0203007AXX
(2,3,4)
37
(06/06)
Page 38
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Spare parts for special applications
The following spare parts are supplied separately from the standard humidifier, that is, must be ordered separately.
Disposable Cylinders:
200/*230 Vac 3~, Conductivity 125/350 µS/Cm
400 Vac 3~, Conductivity 125/350 µS/Cm
400 Vac 3~, Conductivity 750/1250 µS/Cm
460 Vac 3~, Conductivity 125/350 µS/Cm
575 Vac 3~, Conductivity 125/350 µS/Cm
Cleanable Cylinders:
200/230 Vac 3~, Conductivity 125/350 µS/Cm
200/230 Vac 3~, Conductivity 350/1250 µS/Cm
400 Vac 3~, Conductivity 125/350 µS/Cm
400 Vac 3~, Conductivity 350/750 µS/Cm
400 Vac 3~, Conductivity 750/1250 µS/Cm
460/575 Vac 3~, Conductivity 125/350 µS/Cm
460/575 Vac 3~, Conductivity 350/1250 µS/Cm
Electrode Kit (200/230 Vac 3~, 125/350 µS/Cm) KITBLCT2A0 KITBLCT2A0 KITBLCT3A0 KITBLCT3A0
Electrode Kit (200/230 Vac 3~, 350/1250 µS/Cm) KITBLCT2B0 KITBLCT2B0 KITBLCT3B0 KITBLCT3B0
Electrode Kit (400 Vac 3~, 125/350 µS/Cm) KITBLCT2B0 KITBLCT2B0 KITBLCT3B0 KITBLCT3B0
Electrode Kit (400 Vac 3~, 350/750 µS/Cm) KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0
Electrode Kit (400 Vac 3~, 750/1250 µS/Cm) KITBLCT2D0 KITBLCT2D0 KITBLCT3D0 KITBLCT3D0
Electrode Kit (460/575 Vac 3~, 125/350 µS/Cm) KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0
Electrode Kit (460/575 Vac 3~, 350/1250 µS/Cm) KITBLCT2D0 KITBLCT2D0 KITBLCT3D0 KITBLCT3D0
Electrode Gasket Kit KITBLC2FG0 KITBLC2FG0 KITBLC3FG0 KITBLC3FG0
SMP003 SMP005 SMP008 SMP010 SMP015
SMP0T1A00H1 SMP0T2A00H0 SMP0T2A00H0 SMP0T3A00H0 SMP0T3A00H0
SMP0T1A00H1 SMP0T2B00H0 SMP0T2B00H0 SMP0T3B00H0 SMP0T3B00H0
SMP0T1D00H1 SMP0T2D00H0 SMP0T2D00H0 SMP0T3D00H0 SMP0T3D00H0
SMP0T1B00H1 SMP0T2C00H0 SMP0T2C00H0 SMP0T3C00H0 SMP0T3C00H0
SMP0T2C00H0 SMP0T2C00H0 SMP0T3C00H0 SMP0T3C00H0
SMPCT2A00W0 SMPCT2A00W0 SMPCT3A00W0 SMPCT3A00W0
SMPCT2B00W0 SMPCT2B00W0 SMPCT3B00W0 SMPCT3B00W0
SMPCT2B00W0 SMPCT2B00W0 SMPCT3B00W0 SMPCT3B00W0
SMPCT2C00W0 SMPCT2C00W0 SMPCT3C00W0 SMPCT3C00W 0
SMPCT2D00W0 SMPCT2D00W0 SMPCT3D00W0 SMPCT3D00W 0
SMPCT2C00W0 SMPCT2C00W0 SMPCT3C00W0 SMPCT3C00W 0
SMPCT2D00W0 SMPCT2D00W0 SMPCT3D00W0 SMPCT3D00W 0
38
(06/06)
Page 39
Wiring Diagrams
SMP001, SMP003, SMP005, SMP009 Single Phase
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
39
(06/06)
Page 40
Installation, Operation & Maintenance Manual
SMP003, SMP005, SMP008, SMP010, SMP015 Three Phase
STEAMaster+ SERIES
40
(06/06)
Page 41
SMP025, SMP035, SMP045, SMP065 Three Phase
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
41
(06/06)
Page 42
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Wiring of cylinders for SMP025, SMP035, SMP045, SMP065 units and voltages
There are 6 electrodes in these cylinders
Model
SMP025
SMP035
SMP045
SMP065
If arcing occurs during operation, then try changing the wiring pattern to the next level, A being the lowest level and C being the highest and therefore least susceptible to arcing.
Conductivity
Micromhos
125 to 350
350 to 1250
125 to 350
350 to 1250
125 to 350
350 to 1250
125 to 350
350 to 1250
Power Supply - Vac
208 230 460 575
A A B B B B B C A A B B A A B C A A B B
A A B C N/A N/A B B N/A N/A B C
42
(06/06)
Page 43
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Technical Specifications
VAC UNIT MODEL NUMBER: CAPACITY, AMPERAGE, WATTAGE
Ph.
Lbs/hr 3.3 6.6 11 20
208 (U) kg/h 1.5 3 5 9
1 Amps 5.4 10.8 18 31.4
KW 1.13 2.25 3.75
Lbs/hr 3.3 6.6 11 20
230 (D) kg/h 1.5 3 5 9
1 Amps 4.9 9.8 16.3 29.3
KW 1.13 2.25 3.75
Lbs/hr 6.6 11 17.6 22 33 55 77 99
208 (W) kg/h 3 5 8 10 15 25 35 45
3 Amps 6.2 10.4 16.7 20.8 31.2 52.1 72.9 93.7
KW
Lbs/hr 6.6 11 17.6 22 33 55 77 99
230 (K) kg/h 3 5 8 10 15 25 35 45
3 Amps 5.6 9.4 15.1 18.8 28.2 47.1 65.9 84.7
KW
Lbs/hr 6.6 11 17.6 22 33 55 77 99 143 198 286
460 (M) kg/h 3 5 8 10 15 25 35 45 65 90 130
3 Amps 2.8 4.7 7.5 9.4 14.1 23.5 33 42.4 61.2 84.7 122.4
KW
Lbs/hr 11 17.6 22 33 55 77 99 143 198 286
575 (N) kg/h 5 8 10 15 25 35 45 65 90 130
3 Amps 3.8 6 7.5 11.3 18.8 26.4 33.9 49 67.8 97.9
KW
Height
Width Depth
Dry weight Lbs. (kg) 35.3 (16) 44.0 (20) 85.8 (39)
Wet weight Lbs. (kg) 41.9 (19) 59.5 (27) 133.4 (60.5)
Water Feed gpm (l/min) 0.16 (0.6) 0.32 (1.2) 1.06 (4.0) 1.85 (7) 3.7 (14)
Water Inlet In. (mm) 1/4" O.D. Comp. 3/8" O.D. Comp.
Max. Drain gpm (l/min) 1.32 (5) 6 (22.5) 12 (45)
Drain Size In. (mm) 1-5/8" hose (40)
Min. Drain In. (mm) 3/4 (19) 1-1/2 (38) 2-1/4 (58)
Cylinders 1 2
Steam outlets In. (mm) 7/8" (22) x 1 1-1/4" (30) x 1 1-5/8" (40) x 1 1-5/8" (40) x 2 1-5/8" (40) x 4
Pressure In. WC (Pa) 8" WC (2000) 6.4" WC (1600) 6.8" WC (1700) 9.2" WC (2300)
Control 24 VAC 50/60 Hz., 30 VA 24 VAC 50/60 Hz., 40 VA
Operating °F (°C) 34-140 °F (1-40°C), 10-60 %RH
Water Type 15 - 116 psi (1-8 bar), 125-1250 MicroMhos conductivity
Ventilated steam distributor
Factor
In. (mm)
001 003 005 008 009 010 015 025 035 045 065 090 130
6.52
6.52
2.25 3.75 6 7.5 11.25 18.76 26.26 33.76
2.25 3.75 6 7.5 11.25 18.76 26.26 33.76
2.25 3.75 6 7.5 11.25 18.76 26.26 33.76 48.76 67.52 97.53
3.75 6 7.5 11.25 18.76 26.26 33.76 48.76 67.52 97.53
24.4 (620)
14.4 (365)
10.8 (275)
VSDU0A
30 Watts
100 CFM (170 m3/h)
50 dBA
10 to 104°F (-10 to 40°C)
10 to 60%RH
28.0 (710)
14.4 (365)
10.8 (275)
43
Frederick, Maryland USA 21704
37.2
35.0 (890)
21.9 (555)
14.2 (360)
VRDXL (X 2 for SMP090 & SMP130
382 CFM (650 m3/h)
14 to 140°F (-10 to 60°C)
(945)
25.6
(650)
17.9
(455)
112.2 (51)
206.8 (94)
35 Watts
40 dBA
0 to 80%RH
37.2 (945)
45.5 (1155)
17.9 (455)
162.8 (74)
352 (160)
1-5/8" hose (40)
x 2
24 VAC 50/60
Hz.,
80 VA
(06/06)
Page 44
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
1572 Tilco Drive Frederick, MD 21704 USA
Corporate Headquarters:
Telephone: (301) 620-2033 Facsimile: (301) 620-7820
CyberAiR Sales / Applications:
Telephone: (301) 620-2033 Facsimile: (301) 662-5487
Product Support Group (Service, Warranty and Parts)
Telephone: (301) 620-2033 Facsimile: (301) 620-1396 E-mail (parts only): parts@stulz-ats.com 24 Hr Hot Line (301) 414-4514
*Specifications are subject to change without notice.
Form: HUM-IOM-10/27-04
Revision A, 06/06
©
10/04
(10/04)
Loading...