BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE
INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THIS MANUAL AND ILLUSTRATED ON THE
LABELS ATTACHED TO THE MACHINE.
This humidifier produces non-pressurized steam by means of electrodes immersed in the water contained in the
cylinder-boiler (hereafter called the cylinder). The electrodes pass current through the water, which also provides
resistance, heating the water into steam, which is used to humidify environments or industrial processes, using
special distributors.
The quality of the water used affects the process of evaporation, so the humidifier may be supplied with untreated
water, as long as this is drinkable and not softened or demineralized; the evaporated water is automatically
replaced using a fill valve. This humidifier has been designed exclusively to directly humidify rooms or ducts, using
a distribution system. The installation, use and maintenance operations must be carried out according to the
instructions contained in this manual and on the labels applied internally and externally.
The conditions of the environment and the power supply voltage must comply with the specified values.
All other uses and modifications made to the humidifier that are not authorized by the manufacturer are
considered incorrect.
Liability for injury or damage caused by the incorrect use of the humidifier lies exclusively with the user.
Please note that the humidifier contains powered electrical devices and hot surfaces.
All service and/or maintenance operations must be performed by specialist and qualified personnel who
are aware of the necessary precautions and are capable of performing the operations correctly.
Disconnect the humidifier from the main power supply before accessing any internal parts.
The humidifier must be installed in accordance with the local standards in force.
The local safety standards in force must be applied in all cases.
The humidifier is made up of metallic and plastic parts. All parts must be disposed of according to the
local standards on waste disposal.
Warranty on materials: 2 years (from the date of installation, excluding the consumable parts, such as the cylinder
and electrodes).
Certification: the quality and safety of SATS products are assured by SATS’ ISO 9001 certified design and
production system, as well as listings from UL, cUL, CE, TUV and others.
(10/04)
Page 3
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
TABLE OF CONTENTS
Models And Description Of The Components ....................................................................................................... 4
How The STEAMaster+ Works ............................................................................................................................ 5
Removing the front cover .............................................................................................................................. 7
Fastening to the wall ................................................................................................................................... 7
Water supply ............................................................................................................................................... 8
Water drain ................................................................................................................................................. 8
Steam distribution .......................................................................................................................................... 10
Room distribution blower units .................................................................................................................. 12
Power wiring .................................................................................................................................................. 13
Control wiring ................................................................................................................................................. 15
The HumiControl Controller ............................................................................................................................ 21
Starting with a new cylinder ....................................................................................................................... 21
Display Information ........................................................................................................................................ 22
Changing The Set Point ................................................................................................................................. 22
Notes about special parameters .................................................................................................................... 25
Standard Factory Settings ............................................................................................................................. 26
Seasonal Shut Down ..................................................................................................................................... 27
The Remote Control ....................................................................................................................................... 27
Resetting the Hour Counter ........................................................................................................................... 28
Replacing the cylinder ............................................................................................................................... 34
Maintenance of the other plumbing components ....................................................................................... 35
Replacement Parts ........................................................................................................................................ 36
Single Phase Humidifiers .......................................................................................................................... 36
Three Phase Humidifiers ............................................................................................................................ 37
STEAMaster+ is an electrode humidifier. It produces steam for humidification by passing electrode
current through the water in the steam generator cylinder between metal electrodes. There are no
heater elements. Steam output is directly proportional to the conductivity of the water, and the amount
of electrode immersed in the water.
On a call for humidity, the STEAMaster+ controller will open the water fill valve (1) and allow water to enter the system. A
flow restrictor (2) prevents the unit from filling too quickly or with too much pressure. The water flows up the fill tube (3)
and into the fill cup (7), where it flows over the conductivity probes (6), which feed the water conductivity back to the
controller for analysis. Water then flows over the dam in the fill cup (7), which creates a 1" air gap to prevent backflow of
contaminated water into the feed lines, and through the fill tube (4) and into the bottom of the steam cylinder (11).
As the water fills the cylinder, it will reach the electrodes (10) and current will begin to flow. As the water continues to fill
the cylinder, the current will increase, and this is monitored by an amperage transformer placed on one of the power wires
(9). When the desired current is reached, the fill valve will close (1) and the water will then begin to warm and produce
steam. If the water reaches the cylinder full probes (8) prior to reaching the desired current level, the fill valve (1) will be
closed to prevent overflow. If the current rises too much as the water fills the cylinder, the drain valve or pump (13) will be
activated to drain away some water and reduce the current flow.
Periodically, based on the incoming water conductivity, the unit will drain some water to reduce the mineral concentration.
A strainer (12) in the cylinder helps to prevent mineral debris from jamming the drain valve (13).
If there is no water in the cylinder, there will be no current flow and no steam production. The electrodes do not burn out,
but they will eventually become comletely coated with mineral and the cylinder will then need to be replaced or cleaned.
5
((06/06)
Page 6
Installation, Operation & Maintenance Manual
Installation
Positioning
The STEAMaster+ has been designed for wall mounting
(although it can be placed on a stand) and, since it is an
atmospheric steam humidifier, should be placed close to
the point where the steam will be used, to minimize the
steam hose length (and condensate). Certain clearances
must be maintained around the unit:
Minimum
Dimension
(inches)
With room blower units, other clearances are needed:
The front cover is secured by a capture screw located underneath the SATS
logo. Twist the SATS logo to reveal the screw, and use a phillips head
screwdriver to remove it. Then simply lift the front cover and pull out to
remove it. Return it in reverse order.
Fastening to the wall
Using the screws and anchors supplied, fasten the mounting bracket to the
wall. Be sure that the screws anchor firmly into studs or supports. Note
the unit installed weights from the Positioning section.
Once the mounting bracket is secured to the wall, hang the unit on the bracket. Fasten the remaining capture
screws through the bottom holes in the unit to secure it to the wall
X
Y
Z
Z’
001-008 009-015 025-045 065
8.67 8.67 12.21 15.75
19.69 23.23 28.55 30.91
4.53 1.5
4.41
Model SMP
7
(06/06)
Page 8
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Plumbing
Water supply
The STEAMaster+ must be supplied with water (not softened) having the following characteristics:
Instant flow rate
Connection
Temperature limits
Pressure limits
Hardness limits
Conductivity range
001-008 009-015 025-045 65
0.2 gpm 0.3 gpm 1 gpm 1.9 gpm
1/4" O.D. Compression 3/8" O.D. Compression
125 to 1250
Model SMP
34 to 104°F
15 to 116 psi
<= 400 ppm CaCO3
µS/cm (micromhos)
Water drain
The STEAMaster+ also requires connection to a drain. The drain water characteristics are:
Drain rate per hour
Instant drain rate
Connection
Typical temperature
Water supply and drain connections are made according to the following diagram.
NOTE: Drain line must be trapped under the unit to prevent flash steam from condensing in the unit cabinet.
Physical location of the supply and drain connections are located as shown below.
SMP 010-015SMP 025-065
NOTE: SATS can provide a drain tempering system which limits the water drain to no more than 140°F.
NOTE: Softened water should NOT be used as it is generally corrossive to the electrode plating.
9
(06/06)
Page 10
Installation, Operation & Maintenance Manual
Steam distribution
Duct injection
If your STEAMaster+ humidifier was supplied with duct steam
distributor pipes, they must be mounted completely level in the
duct with the steam outlet holes facing up as shown to the right.
Support the end of longer distributor pipes if needed.
Distributor pipes should be mounted per the diagrams shown
below, with a minimum of 6" from the center of the distributor
pipe to the top of the duct and 3" minimum to the bottom.
STEAMaster+ SERIES
Generally the distributor pipes should be
mounted in the center
of the air stream.
Multiple pipes need to
be staggered on a
diagonal to prevent
the steam discharge
from the lower pipes
from impinging on the
upper ones.
In vertical ducts, the distributor pipes are mounted in the center
with the holes facing up as shown at right. The airflow may be up or
down, but when the airflow is down, maximum velocity is 1,500
fpm.
To install the distributor pipes:
1. Cut a key shaped hole in the side of the duct to match the steam pipe and
condensate return.
2. Apply silicone sealant to the mounting plate and insert the pipe through the
hole and secure it with 4 sheet metal screws.
3. Connect the steam and condensate hoses using the hose clamps supplied.
IMPORTANT: Allow 2 feet of straight duct downstream of the distributor pipes when the air temperature will be
>55oF. Allow 3 feet of straight duct if the air temperature will be <50oF. Always allow 2 feet upstream. Turbulent
air flow may require longer lengths.
10
(06/06)
Page 11
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Steam Hoses
NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM PIPING
FROM THE HUMIDIFIER UNIT TO THE DUCT DISTRIBUTOR PIPES.
To avoid these problems, remember one simple fact when running the steam hose: steam naturally flows up
hill, and condensate naturally flows down hill.
Nothing must impede the free flow of either steam to the distributor pipes or condensate back to the SD unit or
the drain. If Copper tubing is used, use two 45° angles or sweeping elbows rather than sharp 90° elbows.
Follow one simple rule: Run the steam hose or piping to avoid any kinks, sharp elbows, or low spots that could
collect or restrict the flow of steam to the distributor pipe, or the flow of condensate back to the humidifier.
Support the hose adequately to avoid sags.
The following diagrams are to provide you with some guidelines. If you have a situation you are unsure of,
please contact the factory for instructions.
IMPORTANT: Maximum length of rubber steam hose is 20 feet. Insulated copper tubing may be up to 40
feet. Hose sizes= 7/8" I.D. for units SMP001-003, 1 1/4" I.D. for units SMP005-015, 1-5/8" I.D. for units
SMP025-065.
11
(06/06)
Page 12
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Room distribution blower units
Refer to the manual supplied with the Room Distribution Units for specifics on the blower units themselves.
Clearances required are shown below.
A B C D E F H
Minimum
dimension
20 72 72 24 20 72 24
(inches)
Room Blower
Unit Model
Rated Power
Watts
Air Volume
CFM
Noise Level
dBA
Operating Temp/Humidity
(°F / %RH)
Cold rooms can be humidified using a Room Distribution Unit, making sure that this operates within its operating
limits. The room must have operating temperatures of between -10°C and +20°C, with a percentage of relative
humidity of no greater than 80% RH. If these limits are not possible, the steam can be distributed in the cold room
using a distributor pipe in duct work. In any case, the steam must not come into direct contact with air discharge
from the refrigeration unit in the cold room, to avoid possible condensation.
12
(06/06)
Page 13
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Power wiring
Check that the power supply voltage to be
connected matches the value indicated on the
rating plate inside the electrical panel. Insert
the power and ground connection cables into
the electrical panel compartment using the
strain reliefs supplied, and connect to the
terminals. An external fused disconnect must
be installed.
All wiring must be in accordance with local, state
and national electric codes.
NOTE: to avoid unwanted interference, the
power cables should be kept separate from any
control wiring.
Per the table on the following page, make sure
that the unit has the proper number of turns
through the TAM (Torroid Amperage Monitor),
which is on the control board in models
SMP001 through SMP015, and separate in
models SMP025 through SMP065. Also make
sure that the TA Rate DIP switches on the
control board are set correctly per the table.
Single Phase Terminals Three Phase Terminals
In models SMP001 - SMP015 make sure that the TAM on
the circuit board has the proper number of power wire
turns through it, and that the TA Rate DIP switches on the
control board are set per the table on the following page.
In models SMP025 - SMP065 the TAM is independent and the jumper must then be on the right terminals per the
table on the following page.
13
(06/06)
Page 14
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Voltage
Model
SMP001
SMP003
SMP005
SMP008
SMP009
SMP010
SMP015
SMP025
SMP035
SMP045
SMP065
Code
U 208 - 1~N 5.4 1 20 1.5
D 230 - 1~N 4.9
U 208 - 1~N 10.8 2 60 2.5
D 230 - 1~N 9.8 1 20 2.5
W 208 - 3~ 6.2 1 20 2.5
K 230 - 3~ 5.6 1 20 2.5
M 460 - 3~ 2.8
U 208 - 1~N 18 1 40 6
D 230 - 1~N 16.3 1 40 6
W 208 - 3~ 10.4 1 20 2.5
K 230 - 3~ 9.4 1 20 2.5
M 460 - 3~ 4.7 2 20 1.5
N 575 - 3~ 3.8
W 208 - 3~ 16.7 1 40 6
K 230 - 3~ 15.1 2 60 6
M 460 - 3~ 7.5 1 20 2.5
N 575 - 3~ 6
U 208 - 1~N 31.4 1 60 16
D 230 - 1~N 29.3
W 208 - 3~ 20.8 1 40 6
K 230 - 3~ 18.8 1 40 6
M 460 - 3~ 9.4 1 20 2.5
N 575 - 3~ 7.5
W 208 - 3~ 31.2 1 60 16
K 230 - 3~ 28.2 1 60 10
M 460 - 3~ 14.1 1 20 4
N 575 - 3~ 11.3
W 208 - 3~ 52 1 300 25
K 230 - 3~ 47.1 1 300 25
M 460 - 3~ 23.5 1 300 10
N 575 - 3~ 18.8
W 208 - 3~ 72.9 1 500 35
K 230 - 3~ 65.9 1 500 35
M 460 - 3~ 32.9 1 500 16
N 575 - 3~ 26.4
W 208 - 3~ 93.68 1 500 70
K 230 - 3~ 84.72 1 500 70
M 460 - 3~ 42.4 1 500 16
N 575 - 3~ 33.9
M 460 - 3~ 61.19 1 300 35
N 575 - 3~ 48.95
Voltage
Phase
Nominal
Current
(Amps)
Power
(kW)
1.12 1.5 3.3
2.25 3 6.6
3.75 5 11
6.52 9 20
7.5 10 22
11.25 15 33
18.75 25 55
26.25 35 77
33.75 45 99
48.75 65 143
Output
(kg/hr)
6 8 17.6
Output
(lbs/hr)
Turns
Through
TAM
TA Rate
2 20 1.5
2 20 1.5
2 20 1.5
1 20 2.5
1 60 10
1 20 2.5
1 20 4
1 300 6
1 300 10
1 500 16
1 300 35
Wire
Size
(mm)
NOTE: Tolerance allowed on main voltage = -15%, +10%
14
(06/06)
Page 15
Installation, Operation & Maintenance Manual
Control wiring
The STEAMaster+ control system allows up to two sensors to
be connected, as well as various safety devices, remote on/off,
alarm and serial communications.
Generally, the control sensor or humidistat (HT) is located in the
room or return air duct. In the case where the STEAMaster+
uses a direct discharge blower unit, this is the only control
needed. In ducts or air handlers, a high limit humidistat or
sensor is usually added to act as a safety (CR), as well as an
air flow proving device. The remote terminal HumiVisor (MT)
may be added.
Remote Supervisor / Serial
Communications:
This is a standard RS485
serial connection. It is
STEAMaster + SERIES
recommended to keep wiring under 3,200
feet. Request SATS’s communications
documentation for additional information
on this option.
Control wiring is made directly to the
control board terminals:
1. terminal block G (dehumidification
contact);
2. terminal block H (alarm contact);
3. terminal block K (on/off, manual drain
switch);
4. terminal block I (control signals);
5. terminal block J (to remote terminal or
supervisory system);
6. dip-switch for selecting TA RATE.
For On/Off Operation:
Connect any simple humidistat, high-limits, air flow
switch, and remote contacts in series from terminals
7I to 8I.
Circuits must be completed from 4I to 5I by a jumper
and from 7I to 8I for the unit to operate. Use
jumpers if devices are not connected.
Parameter A0 must be set to 0.
15
(06/06)
Page 16
For Modulating Operation with External Controller:
Connect any external controller (0-1 Vdc, 0-10 Vdc
Parameter A0 must be set to 1.
Parameter A2 must be set per the OUT signal from the
regulator:
• voltage: 0 to 1 Vdc; 0 to 10 Vdc; 2 to 10 Vdc;
• current: 0 to 20 mA; 4 to 20 mA.
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
NOTE: Safeties are high-limit humidistat, air flow
switch, and/or external enable.
For Stand-Alone Modulating Operation:
Connect a high limit sensor and control sensor per the
diagram at right.
Parameter A0 must be set to 2 if no high limit sensor, 3
if a high limit sensor is used.
Parameter A2 must be set per the OUT signal from the
sensor:
In this case a temperature sensor is used to control the
humidifier. Connect sensors per the diagrams below .
ASDH10000
ASWH10000
SIGNAL
COMMON
HC-201
HI-LIMIT
out H
M
+G
+G
out H
PC-301
&
AIRFLOW
SIG
COM
24 Vdc
12 Vdc
SIG
M
COM
Parameter A0 must be set to 4. Parameter A2 must be set to 0.
Alarm Output:
The H terminals allows connection to an on-board SPDT alarm relay that provides
No and NC contacts for remote indication of alarms.
Dehumidify Output:
Dehumidify contacts are also provided which can be used to control a dehumidifier
from the humidifier control system (stand-alone modulating mode only). The
contact is rated for 250 V ac, 8 Amp resistive and 2 Amp inductive loads.
Temperature: NTC thermistor, 10 Kohm at 25°C (77°F)
(ASWC/ASDC only)
Accuracy: +- 0.25°C from 0 to 50°C (32 to 122°F)
Humidity: Thin film capacitor
Linear 0-1 Vdc or 4-20 mAdc from 10 to 90%RH
Accuracy: +- 3%RH from 20 to 90%RH
calibrated at 55%RH and 25°C (77°F)
+- 5%RH above 90%RH and below 20%RH
Response time: 60 seconds
Power: 12 to 24 Vac/dc or +12 to –12 Vdc
Housing: Wall: ABS with glassfiber fill
Certifications: Calibrated to NIST traceable
humidity/temperature standard, CE Approved
17
(06/06)
Page 18
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
HC-101 and HC-201 Wall and Duct Humidistats
Mounting the HC-101 room humidistat: Mount the HC-101
humidistat to an inside wall or post in the area to be humidified.
Position it so that no drafts from registers or outlets are blowing
on it. Be sure that it is not placed over a device that could generate heat or vapor ie: stove, machinery, cleaning vat. The unit has
three wire leads, Orange, Brown and Red. Use the Orange and
Brown leads for control operation. Use the Orange and Red leads
for hi-limit operation.
Mounting the HC-201 duct humidistat: Cut a
hole in the side of the duct and mount the HC-201 humidistat to the duct, using the screws provided, at least 6 feet
down stream of any live steam or mist. The unit has three wire leads, Orange, Brown and Red. Use the Orange and
Brown leads for hi-limit operation.
Wiring Diagram
Brown (N.O.)
Red (N.C.)
Brown makes onDrop in R.H.
drop in humidity
TABLE 1. SPECIFICATIONS
Part
No.
HC-101
HC-201
TABLE 2. MAXIMUM ELECTRICAL RATINGS
Type Scale
Range
%RH
Wall 10 to 90 5 40 to 125
Duct 15 to 95 5 40 to 125
Diff.
%RH
Operating
Limits
°F (°C)
(4 to 2)
(4 to 2)
Shipping
& Storage
°F (°C)
-40 to 140
(-40 to 60)
-40 to 140
(-40 to 60)
Orange
Common
Connection Cover Dimensions
In. (mm)
6" (150 mm)
color coded
leads
Coded
screw
terminals
Beige
plastic
Metal 4-3/4 x 6-1/2 x 2-1/4
4-3/8 x 2-7/8 x 1-5/8
(111 x 73 x 41)
(121 x 165 x 57)
Part No. AC Volt
50/60 Hz
HC-101
HC-201
24 - - 8 60
120 7.2 43.2 8 345
240 3.6 21.6 8 345
FLA LRA Resistive
Amps
18
Pilot Duty
VA
(06/06)
Page 19
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
PC-301 Air Proving Switch
Mounting the PC-301 air flow switch:
Mount the airflow switch in the supply or return duct using the
screws supplied. Mount the device so that the diaphragm is in a
vertical position as shown at right.
If the airflow switch is to be mounted on the return duct (vacuum),
then mount it in a vertical position by the small plate. Drill a 7/16"
hole in the side of the duct and connect the supplied tubing to
the low pressure tap on the airflow switch and then run it through
the drilled hole in the duct. Put no more than 2" of tubing into the
duct. Caulk around the tubing where it enters the duct. The high
pressure tap is left open to atmosphere.
If the airflow switch is to be mounted to the supply duct (pressure), then simply drill a 7/16 hole in the side of the duct, apply caulking to the large plate, and mount the device
with the large plate to the duct and the high pressure tap/tubing mated the hole. The low pressure tap is left open
to atmosphere.
1.Before starting, check that the humidifier is in perfect condition, that there are no water leaks and that the
electrical parts are dry;
2.Do not connect power if the humidifier is damaged or even partially wet!
When installation is completed, flush the supply pipe for around 30 minutes by piping water directly into
the drain, without sending it into the humidifier; this will eliminate any scale or residues that may cause foam
when boiling.
NOTE: For humidifiers with control H only, the same function can be performed automatically after starting the
appliance.
Startup Checklist
Before starting the humidifier, the following should be checked:
_____ Water is connected, the line has been flushed, and external valves are open.
_____ Drain is connected, run to an open drain, and has a trap under the unit.
_____ Electricity is connected in accordance with instructions, local codes and data labels in the unit.
_____ The power fuses are installed and intact.
_____ All control wiring is done and tested.
_____ Airflow switch is wired to open on air flow loss.
_____ Hi-limit humidistat is wired to open on humidity rise above set point.
_____ Unit wires have been checked to make sure they and all connectors are tight from shipping.
_____ The steam hose(s) are run correctly with no sags or kinks and sloped properly according to the manual.
_____ Condensate hoses are run correctly with no sags or kinks and sloped properly according to the manual.
NOTE: If you ordered a factory startup, this checklist will be required. Failure to complete this checklist may
result in additional charges.
20
(06/06)
Page 21
The HumiControl Controller
1: PRG - Access to most frequently used parameters.
Also resets alarm relay.
2: SEL - Displays unit of measure. Press for 2
seconds to access set point. Press with PRG for 5
seconds to enter parameters.
3:Ç - Displays control sensor value. In programming
mode increases value or moves to previous parameter.
4:È- Displays high limit sensor value. In program-
ming mode decreases value or moves to following
parameter.
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
5: 2-1/2 digit display for values and parameters.
6: LED to indicate decimal point.
7: LED to indicate value must be multiplied by
1000.
8: LED to indicate dehumidify mode.
9: LED to indicate alarm.
10: LED to indicate humidifier is producing steam.
Flashing indicates lower than required production.
11: LED to indicate when unit is filling.
12: LED to indicate when unit is draining.
Start-up Procedure
After closing the external fused disconnect to put power to the humidifier, press the top (I) part
of the I/O switch on the side of the unit
Initially, all LEDs light - this lasts about 1-2 seconds.
Then the initialization phase begins with 3 dashes. During this phase
diagnostics are conducted. This phase lasts about 4 seconds.
After running the diagnostics, the unit will start operation and display either
the % of steam production (On/off and Modulating modes), the %RH
(Stand-Alone Modulating mode), or two dashes will light, indicating the
humidifier is disabled or in alarm. The alarm code will flash.
Starting with a new cylinder
When starting with a new cylinder, you should activate the cylinder cleaning function by pressing the SEL and
buttons simultaneously for 2 seconds after the initialization phase. This forces the unit to open both the drain and
fill valves for 10 minutes to flush the lines, then fills and drains the cylinder 3 times to wash out any mold release or
dirt. Once started, this function can be stopped by pressing the SEL and
again.
When starting the unit with a new or empty cylinder, it may take a significant amount of time (hours) for
the unit to build up enough mineral concentration to reach rated capacity. This time can be shortened
by the addition of Alka-Seltzer or salt (teaspoon) through the steam outlet on top of the cylinder.
21
ÈÈ
È
ÈÈ
ÈÈ
È buttons simultaneously for 2 seconds
ÈÈ
(06/06)
Page 22
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Operation
Display Information
Pressing the SEL button displays the unit of measure currently in use for the main display
Holding the
Holding the
Changing The Set Point
Press the SEL button for 2 seconds until “St” appears. On releasing the button, the unit of measure is
displayed followed by the current set point value. To change the set point, press the
increase or decrease the value. Press SEL or PRG to lock in the new set point. Waiting 5 seconds without
pressing SEL or PRG will revert to the old value.
Activating Manual Drain
In addition to the manual drain switch on the side of the humidifier, pressing the
neously for 2 seconds will force a manual drain which will completely empty the cylinder without having to
hold the manual drain switch. This procedure can be stopped at any time by pressing the
simultaneously for 2 seconds again.
ÇÇ
Ç button displays the value of the control sensor preceded by the unit of measure.
ÇÇ
ÈÈ
È button displays the value of the high-limit sensor preceded by the unit of measure.
ÈÈ
ÇÇ
ÈÈ
Ç or
È button to
ÇÇ
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons simulta-
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons
ÈÈ
Accessing/Changing Configuration Parameters
The numerical, configuration and control parameters are grouped into three levels:
LEVEL 1 - set point parameters: the value of the humidifier’s main set point “St”, accessible
directly via the keypad for both reading and modification. See “Changing The Set Point”.
LEVEL 2 - control parameters and measurements: the physical values measured and the operating parameters involving the control of the humidification process; these too can be accessed directly
via the keypad for reading and modification.
LEVEL 3 - configuration parameters: consisting of the data needed to customize the controller’s
operation. These parameters can be accessed only by password.
To display the Level 2 Control Parameters:
•Press and hold the PRG button for 5 seconds until P0 is displayed;
•Press the
ÇÇ
Ç and
ÇÇ
•Press the SEL button to display the value of any parameter (the unit of measure will display first for 1
second).
Code Range Default Unit Description
P0 20 to 100
P1 2.0 to 19.9 5 %RH, °C Hum idification differential
P2 (1)
P3 (1) 0 to P2 0 %RH, °C
P3 to 100 100 %RH
P3 to 60 60 °C
P4 0 to 100 1 min Alarm delay (0*= 30 s)
P5 2 to 100 10 %RH Dehumidification dead zone
P6 1.0 to 19.9 5 %RH Dehumidification differential
ÈÈ
È buttons to scroll through the Px and dx parameters;
ÈÈ
100 Maximum output for H controllers
100
%
Maximum output for P controllers
High humidity or high
temperature alarm set point
Low humidity/temp. alarm set
point
22
accessible only in control mode (A0=2, 3
or 4)
accessible only with the dehumidification
function enabled
(b1 odd number) in humidity control
mode (A0 = 2 or 3)
(06/06)
Page 23
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Code Range Default Unit Description
P7 (1) St to 100 100 %RH Hi-limit set point
P8 2.0 to 19.9 5 %RH Hi-limit differential
P9 0 to 100 100 %RH Hi-limit alarm set point
Code Range Default Unit Description
d1 (2) 0.0 to 199
d2 0.0 to 199
read
only
%RH, °C, % Signal from external controller
or sensor
%RH
Signal from hi-limit or
temperature sensor
d3 0.0 to 199 kg/h Steam output (actual)
d4
0.0 to
19999
h Run time hours
d5 0 to 1555 µS/cm Conductivity of the feed water
d6 0.0 to 199 A Current (Amperage)
d9 0.0 to 199 kg/h Rated steam output
(1): when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding
default value.
(2): in proportional operation (A0=1), d1 displays the % of the control signal
Accessible only with hi-limit control
(A0=3)
Not accessible in on/off mode (A0=0)
Accessible only with hi-limit control
(A0=3)
To display the Level 3 Configuration Parameters:
•Press and hold the PRG and SEL buttons simultaneously for 5 seconds until 00 is displayed;
•Press the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons to enter the password value of 77;
ÈÈ
•Press the SEL button and A0 should display;
•Press the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons to scroll through the configuration parameters;
ÈÈ
•Press the SEL button to display the value of any parameter (the unit of measure will display first for 1
second);
•Press the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons to change the value;
ÈÈ
•Press SEL when the change is complete and then continue scrolling through the parameters;
•To leave the programming mode, press PRG at any time. NOTE: after more than 5 seconds without a
button press, the display will begin to blink. 60 seconds after a button press, the controller will erase all
changes and return to operating mode with the previous parameters.
Parameters for configuring standard operation:
Code Range Default Unit Description
0=ON/OFF control
1=modulating
A0 (1) 0 to 4 2 Operating mode
A1 0, 1 0 Unit of measure
Type of room sensor; not
A2 0 to 4 0
A3 (2) 0 to A4 0 %RH, ºC Room sensor minimum
A4 (2) A3 to 255 100 %RH, ºC Room sensor maximum
A5 -10.0 to 10.0 0 %RH, ºC Room sensor offset
accessible in ON/OFF
mode (A0=0)
2=humidity control
3=humidity control with hi-limit control
4=steam baths
0=°C, kg/h
1=°F, lbs/hr
0=0 to 1V; 1=0 to 10V; 2=2 to 10V; 3=0 to 20mA;
4=4 to 20mA
Accessible only in control mode (A0=2, 3 or 4)
Used for scaling sensors
23
(06/06)
Page 24
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Code Range Default Unit Description
Type of outlet sensor;
A6 0 to 4 0
A7 0 to A8 0 %RH Hi-limit sensor minimum
A8 A7 to 100 100 %RH Hi-limit sensor maximum
A9 -10.0 to 10.0 0 %RH Hi-limit sensor offset
(1): when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding
default value.
Parameters for configuring the operation of accessory devices:
Code Range Default Unit Description
b1 0 to 127 0
b2 0 to 120 0 s Shut-down delay time
b3 -10.0 to 10.0 0 % Current measurement gain
0 to 199
b4
0k2, ….2k0
0 to 199
b5
0k2, ….2k0
0 to 199
b6
0k2, …, 2k0
b7 0 to 100 50 % Foam detection set point (0=no foam detect, 1=max sens., 100=min sens.)
b8 50 to 200 100 %
b9 50 to 200 100 % Adjust the duration of the drain for dilution
bb 0* to 4000 1500 h
bE 1 to 120 24 h
bF 1 to 199 3 days Days to wait to drain due to inactivity
0 µS/cm Water conductivity (0=automatic measurement)
1k5 µS/cm Conductivity pre-alarm set point
2k0 µS/cm Conductivity alarm set point
accessible only in
humidity control with
outlet limiting (A0=3)
Special functions
To enable more than one, sum the 0= no function
corresponding values and assign 1= dehumidifier management active
them to b1; e.g.: b1=1+2+8=11 2= drain under power
dehumidifier management active +
drain under power + disable draining 8= disable draining for inactivity
for inactivity of at least 7 consecutive 16= disable cylinder being depleted
days (the other functions are
deactivated)
64= enable periodic draining
Internal conductivity reached by the cylinder in stable conditions against
rated value
Cylinder maintenance limit time (in hours)
0*= disable life alarm “Cy” and maintenance alarm “Mn”
100 hour step if bb>199 hours, hour step if bb<199 hours
Time limit between two periodic
drain cycles
0=0-1V; 1=0-10V; 2=2-10V; 3=0-20mA;
4=4-20mA
Accessible only in humidity control with outlet
limiting, (A0=3)
4= disable draining on set point
reduction
and cylinder depleted warnings
32= reverse the operation of the
alarm relay
Accessible only if periodic draining is
enabled (64 in "b1")
Not accessible if draining due to
inactivity is disabled, (8 in "b1")
24
(06/06)
Page 25
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Parameters for setting the serial connections and remote control:
Enable keypad and remote control keypad: remote control:
0= read of all param., (modify C1 only) read and modify param. P, d and St
C1 0 to 4 4
C2 0 to 99 0 Remote control enabling code (see paragraph 8.2)
C3 0 to 199 1 Serial address
C4 0 to 3 3 Supervisor: baud-rate 0=1200, 1=2400, 2=4800, 3=9600
C5 0 to 11 0
C6 0 to 199 0 Ms serial reply send delay
C7 0 to 3 0
1= read and modifiy all parameters read and modify param. P, d and St
2= read of all param., (modify C1 only) read parameters P, d and St
3= read and modify all parameters read parameters P, d and St
4= read and modify all parameters read and modify all parameters
Graphic terminal configuration in cases 1,2,3
the OFF command is forced on start-up
Notes about special parameters
3= steam output
4= hour counter
5= conductivity
6= current
0=terminal
1=terminal with ON/OFF control
2=term. with ON/OFF and room sensor
3=term. with ON/OFF and hi-limit
sensor
b1, setting 2: Drain under power
If parameter b1 includes setting 2, the humidifier will continue to produce steam during drain cycles. If this setting
is turned off, the humidifier will open the power contactor during drain cycles.
b1, setting 4: Draining due to a significant reduction in the demand
If parameter b1 includes setting 4, then the humidifier will not drain if the demand for humidification decreases.
This helps to conserve conductivity and is useful in low conductivity waters. If b1, setting 4 is off, then the
humidifier will drain to reduce the output if the demand is reduced by 33%.
b1, setting 8: Automatic draining of the cylinder after period of non-use
If parameter b1 includes setting 8, parameter “bF” may be used to cause the humidifier to empty the steam cylinder
if there has been no demand for humidification for an extended period of time. This helps prevent premature
corrosion of the electrodes and/or contamination of the water in the cylinder. The default setting is for 3 days. The
unit will display “idr” when this drain function occurs.
b1, setting 64: Complete periodic draining
If parameter b1 includes setting 64, then parameter “bE” can be used to set the hours between total drains of the
cylinder. This is useful if the water contains impurities that can cause erratic behavior.
During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the plumbing, the humidifier should be placed out-of-service.
NOTE: the water cylinder should be emptied before shutting down the humidifier, to prevent corrosion
of the electrodes.
Follow these instructions:
•Press and hold the manual drain switch until the
steam cylinder is empty, or use the Manual Drain
procedure listed under “Activating Manual Drain”;
•Turn off the On/Off (I/O) rocker switch on the side of
the humidifier, and disconnect power from the humidifier;
•Shut off the water to the humidifier.
In the event of malfunction of the drain valve, the
cylinder can be emptied manually by lifting it out of the
drain manifold and pouring the water into the bottom
drain pan. For SMP026 and larger humidifiers, use the
manual drain device on the manifold, pulling the
manual drain tab until it releases (see sketch at right).
The Remote Control
A hand-held infra-red remote control is available for the STEAMaster+. This device
permits programming the humidifier(s) from across the room and also makes available
buttons with specific functions.
NOTE: To use the remote control, parameter C2 must be set on each humidifier to give
it an access code so that the remote control can address it. If all humidifiers in range of
the remote control have the same access code, then they will respond simultaneously
to commands from the remote control. Setting C2 to 0 on the humidifier will allow the
remote control to be used without the need of a code.
To use the remote control, aim it at the humidifier and press ENABLE. All the
humidifiers in range will display their activation codes. If a humidifier has its C2
parameter set to 0, it will skip this step and display the first parameter.
To program a humidifier, enter its access code into the remote control. If successful,
the humidifier will display the first parameter.
To program main parameters, simply press the + or - button on the remote control of the
parameter you want to modify and the humidifier will display that parameter code.
Press the SEL button on the remote control and the value will be displayed. Modify the
value by using the
are saved when you exit the programming phase.
To program other parameters, press any + or - button on a parameter, then use the SEL and
remote control in the same way as the buttons on the front of the humidifier controller.
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons on the remote control. Then press the next parameter button and so on. Values
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons on the
ÈÈ
To exit the programming phase and save the modifications made to the parameters, press the PRG button.
To exit without saving the modifications, press the ESC button.
To exit the programming phase without confirming the modifications made:
•do not press any button for 60 seconds, if the parameter code is displayed;
•do not press any button for 120 seconds, if the value of the parameter is displayed.
27
(06/06)
Page 28
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Resetting the Hour Counter
To reset the hour counter (parameter d4), proceed as follows:
•press the PRG button for 5 seconds, until the code P0 is displayed, indicating the first modifiable parameter;
using the
•press the SEL button to display the value of the hour counter (preceded for 1 second by the unit of measure);
•press the
ÇÇ
Ç and
ÇÇ
ÇÇ
Ç and
ÇÇ
Alarms
In the event of an alarm, the alarm LED (9) will flash, the alarm relay will close, and the alarm code will flash in the
display. Multiple alarms will flash in sequence, alternating with the main display. Pressing the PRG button will
reset the alarms, although still active alarms will continue to display.
ÈÈ
È buttons, scroll the parameters until d4 is displayed;
ÈÈ
ÈÈ
È buttons together for 5 seconds until the value is set to zero, preceded by a brief flash.
ÈÈ
Controller Action
EH
EL
EC
EP
Humivisor Causes Solution
H
Over-current at the
E102
E103
E105
E113
electrodes; probable
electrode malfunction
or water conductivity
temporarily too high
(especially when
starting after a short
stop)
Power not available;
no steam production
when on
High supply water
conductivity
Excessive reduction in
output
1. Check the operation of the
drain valve
2. Check for fill valve leakage
3. Drain part of the water and
re-start
1. With the machine off and
disconnected from the main
power, check the internal
electrical connections
1. Check limit set for b6
2. Turn the machine off and
clean the water conductivity
probes
3. If the problem persists,
change the source of supply
water or install a suitable
treatment system
(demineralization, even
partial).
Note: the problem will not be
resolved by softening the
supply water.
1. Cylinder completely spent
or water with excessive foam.
Perform maintenance on the
cylinder.
Shutdown
Shutdown
Shutdown
Shutdown
Reset
display
H
N/A Active N/A
N/A Active N/A
N/A Active N/A
Manual Active Manual
Alarm
relay
Reset
relay
28
(06/06)
Page 29
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Controller Action
EF
EA
Ed
Ec
Humivisor Causes Solution
H
1. Check that the fill pipe from
the main to the humidifier and
the internal pipe are not
blocked or bent and that there
is sufficient pressure (0.1-0.8
mpa, 1-8 bar)
2. Check the operation of the
E114 Lack of water
E115
E116 Drain malfunction
E131
Excessive foam in the
cylinder during boiling
High water
conductivity pre-alarm
fill valve
3. Check that the steam outlet
is not working against
excessive back-pressure,
preventing the flow of water
into the cylinder by gravity
4. Check that the steam outlet
pipe is not is kinked and that
there are no sags.
The formation of foam is
generally due to the presence
of surfactants in the water
(lubricants, solvents,
detergents, water treatment
agents, softeners) or an
excessive concentration of
dissolved salts:
1. Drain the water supply lines
2. Clean the cylinder
3. Check for the presence of
softeners (in this case, use
another type of water or
reduce the softening)
Check the drain circuits and
the correct operation of the
drain valve
Check the conductivity of the
supply water if necessary,
install a suitable treatment
system
Note: the problem will not be
resolved by softening the
supply water.
Shutdown
Signal
only
Shutdown
Signal
only
Reset
display
H
Automatic
when
water
returns
Manual
Manual Active Manual
Auto
Alarm
relay
Active
Active Manual
Not
active
Reset
relay
Automatic
when
water
returns
-
High humidity in the
E-
E-
E=
E121
E122
E124 High hi-limit humidity
room (high temp.for T
control)
Low humidity in the
room (low temp.for T
control)
Check the operation of the
probe and the limit set for
parameter P2
Check the operation of the
probe and the limit set for
parameter P3
Check the operation of the
outlet probe
29
Signal
only
Signal
only
Signal
only
Manual
Manual
Manual Active Auto
Active Auto
Active Auto
(06/06)
Page 30
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Controller Action
H
E0
EI
E2
E3
E4
Humivisor Causes Solution
1. Reset the default parameters
E101
E112
E130
E120
E123
Internal memory
error
Error in the user
parameters
Hour counter
error
Room sensor
not connected
Hi-limit sensor
not connected
(see Chap. 7.5)
2. If the problem persists, contact
the CARE service center
1. With the machine off check that
there are no defective electrical
connections or faults, then
reprogram the parameters
2. Reset the default parameters
(see Chap. 7.5)
3. If the problem persists, contact
the CARE service center
With the machine off check that
there are no defective electrical
connections or faults, then reset the
hour counter (see par. 7.6)
Check the connection of the probe,
parameter A2 for the room probe
and the setting of parameter A0
(see chap. 7)
Check the connection of the probe,
parameter A6 for the outlet probe
and the setting of parameter A0
(see chap. 7)
H
Shutdown
Shutdown
Hour
counter
Shutdown
Signal
only
Reset
display
Reprog.
By
SATS
Reprog.
Params.
Reset
manual
Manual Active Auto
Manual Active Auto
Alarm
relay
Active
Active
Not
active
Reset
relay
Reprog.
By
SATS
Reprog.
Params.
N/A
CPCL
EU
PC
Cy
Nn
E132
E133
E134
-
E135
E136
Cylinder being
depleted signal
Cylinder
depleted signal
cylinder
Cylinder full with
machine off
signal
Cleaning
cylinder started
signal
Timeout signal
(see parameter
"bb") for
maintenance
exceeded
Reached final
limit (1.5xbb) of
cylinder
operating life
Perform maintenance and/or
replace the cylinder
Perform maintenance and/or
replace the only
With the machine off:
1. Check for any leaks from the fill
valve or the condensate return pipe
2. Check that the level sensors are
clean total shut-down
You have activated the automatic
cylinder flushing sequence
Perform maintenance and/or
replace the cylinder
Replace the cylinder
30
Signal
only
Signal
only
Shutdown
Signal
only
Shutdown
Manual
Not
available
Manual Active Manual
- - - -
Manual
reset
hour
counter
Manual
reset
hour
counter
Not
active
Not
active
Active
Active
Auto
N/A
After
the
manual
reset
hour
counter
After
the
manual
reset
hour
counter
(06/06)
Page 31
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Controller Action
H
Dr
Idr
Dr
AF
Humivisor Causes Solution
Complete
draining of the
cylinder
activated
Complete
draining for
extended
inactivity
Complete
-
periodical
draining active
Anti-foam
algorithm active
You have activated the manual
drain sequence. Sequence ends on
its own.
The unit is emptying the cylinder
after an extended period of non-use.
Sequence ends on its own.
The unit has activated the periodic
drain to flush excessive minerals.
Sequence ends on its own.
The unit is working to eliminate
foaming.
Reset
display
H
- - - -
- - - -
- - - -
- - - -
Alarm
relay
Reset
relay
32
(06/06)
Page 32
Trouble-Shooting
problem causes solutions
the humidifier does not turn on
the humidifier does not start
operation
Installation, Operation & Maintenance Manual
1. no electrical power
2. on/off switch of the humidifier in
position 0 (open)
3. control connectors improperly
connected
4. blown fuses
5. transformer failure
1. remote ON/OFF contact open
(relay/terminals AB - AB or 7I - 8I)
2. the humidistat has not been
connected correctly
3. humidistat failure
4. control signal not compatible
with the type set
5. value measured by the sensor/s
higher than the corresponding set
point
STEAMaster+ SERIES
1. check the safety devices upstream from
the humidifier and the presence of power
2. close the switch on the panel: position I
3. check that the connectors are properly
inserted in the terminal block
4. check the condition of fuses F1/F2/F3
5. check that the voltage across the
secondary winding of the transformer is
24Vac
1. close ON/OFF contacts (relay/terminals
7I - 8I)
2. check the external connection
3. replace the humidistat
4. set parameters A0, A2-A9 correctly
5. check the values of the set point St and
P7
the humidifier fills with water
without producing steam
the thermal-magnetic overload
switch is activated
the humidifier wets the duct
the humidifier wets the floor
below
1. high steam back pressure
2. fill valve strainer clogged
3. mineral in the fill cup
4. drain solenoid valve leaking
1. thermal-magnetic overload
switch is under-rated
2. over-current at the electrodes
1. the distributor is not installed
correctly (too near the top of the
duct or the condensate return is
blocked)
2.system over-sized
3.humidifier active when the fan in
the duct is off
1. the humidifier drain is blocked
2. the supply water or overflow
circuit has leaks
3. the condensate drain pipe does
not bring the water back to the
drain pan
4. the steam hose is not properly
fastened to the cylinder
1. check that the steam hose is not kinked
or sagging, trapping condensate
2. clean the fill valve strainer
3. clean the fill cup
4. check for 24Vac at the drain solenoid
valve and/or drain solenoid replacement
1. check that the thermal-magnetic
overload switch is rated for a current of at
least 1.5 times the rated current of the
humidifier
2. see description for alarm EH
1. check that the steam distributor is
installed correctly
2. decrease the steam production set on
the control
3. check the connection of the device (flow
switch or differential pressure switch)
slaving the humidifier to the ventilation in
the duct (terminals 7I - 8I)
1. clean the drain assembly and pan
2. check the entire water circuit
3. check the correct position of the
condensate drain hose in the drain pan
4. check the fastening of the hose clamps
on the steam outlet
32
(06/06)
Page 33
Installation, Operation & Maintenance Manual
problem causes solutions
Water in the cylinder turns black 1. minerals in the cylinder have
overconcentrated and are
deteriorating the electrodes.
Heavy arcing occurs within hours
of startup
Humidifier continuously fills and
drains without producing steam
1. The feed water contains large
amounts of Iron, Copper or other
conductive contaminants.
1. Mineral has bridged between the
electrodes.
2. There is back pressure from the
steam hoses or duct.
3. The flow regulator in the fill valve
is broken or out of place.
4. Water conductivity is very high.
5. Water is foaming excessively.
STEAMaster + SERIES
1. Check for sags & kinks that
could trap condensate in the steam
hoses that could cause a back
pressure on the cylinder.
2. Check the duct static pressure.
3. Check the fill valve and inlet
strainer.
4. Check the drain valve operation.
5. Correct installation problems
and replace cylinder.
1. Contact the factory for an
optional drain timer to force
additional drains to control the
minerals.
2. If you are using a softener,
check the salt being used. If it
contains any additives, discontinue
use, flush all lines and convert to
pure salt or unsoftened water.
3. Check the electrodes in the
cylinder to be sure they were not
damaged in shipping.
1. Clean or replace the cylinder.
2. Check the steam hoses for kinks
or gullys that might be trapping
condensate.
3. Replace the fill valve.
4. Consider using a mix of
demineralized water with raw
water.
5. Check cylinder - replace if
exhausted. If feed water contains
silica or nitrates, install a 1 micron
water filter.
Resetting Factory Defaults
If errors have occurred when setting the parameters, the
controller may be reset to the factory default values:
•in the first 5 seconds from start-up (while the three
dashes are displayed), press the PRG button (2) until
the upper dash in the center flashes (1);
•release the PRG button within 3 seconds to confirm
the permanent reset of the factory defaults; to confirm
the reset, the upper dash will stay on for 2 seconds;
•the factory reset is not carried out if the PRG button is
pressed for more than 3 seconds, until the upper dash
disappears.
Recalling the default parameters does not change the parameter relating to the unit of measure (A1), and it is thus
recommended to check and if necessary select and save the unit of measure as required, and then recall the
default parameters. In this way the default values will automatically be converted.
33
(06/06)
Page 34
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Maintenance
Periodic checks
•After one hour of operation: For both disposable and cleanable cylinders, check that there are no
significant water leaks.
•Every fifteen days or no more than 300 operating hours: For both disposable and openable cylinders
check operation, that there are no significant water leaks and the general condition of the cylinder. Check
that during operation there is no arcing between the electrodes.
•Every three months or no more than 1000 operating hours: For disposable cylinders, check operation,
that there are no significant water leaks and, if necessary, replace the cylinder; for cleanable cylinders,
check that there are no blackened parts of the cylinder. If there are blackened parts of the cylinder, check
the condition of the electrodes, and if necessary replace them together with the o-rings and the cover
gasket.
•Annually or no more than 2500 operating hours: For disposable cylinders, replace the cylinder; for
cleanable cylinders check operation, that there are no significant water leaks, the general conditions of the
cylinder, check that there are no blackened parts of the cylinder: if this is the case, check the condition of
the electrodes, and if necessary replace them together with the o-rings and the cover gasket.
•After five years or no more than 10,000 operating hours: For both disposable and openable cylinders,
replace the cylinder. After extended use or alternatively when using water with a high salt content, the solid
deposits that naturally form on the electrodes may reach the stage where they also stick to the inside wall
of the cylinder; in the event of especially conductive deposits, the consequent heat produced may overheat
the plastic and melt it, and, in more severe cases, puncture the cylinder, allowing water to leak out. As a
precaution, check the deposits and the blackening of the wall of the cylinder, and replace the cylinder if
necessary.
CAUTION: always disconnect the main power before touching the cylinder in the event of leaks, as current may flow
through the water.
Cylinder maintenance
The life of the cylinder depends on a number of factors, including: the amount and type of mineral in the water, the
correct use and sizing of the humidifier, and the output, as well as careful and regular maintenance. Due to the aging
of the plastic and the consumption of the electrodes, even an openable steam cylinder has a limited life, and it is
therefore recommended to replace it after 5 years or 10,000 operating hours.
Important warnings
The humidifier and its cylinder contain live electrical components and hot surfaces, and therefore all service and/or
maintenance operations must be performed by expert and qualified personnel, who are aware of the necessary
precautions. Before performing any operations on the cylinder, check that the humidifier is disconnected from the
power supply. Remove the cylinder from the humidifier only after having drained it completely using the manual drain
button or procedure. Check that the model and the power supply voltage of the new cylinder correspond to the data
on the rating label.
Replacing the cylinder
IMPORTANT WARNING: the cylinder may be hot. Allow it to cool before touching it or use protective gloves.
To replace the cylinder:
•completely drain the cylinder by pressing and holding the manual drain switch or by pressing the
buttons simultaneously for 2 seconds to force a manual drain. This procedure can be stopped at any time
by again pressing the
ÇÇ
Ç and
ÇÇ
ÈÈ
È buttons for 2 seconds;
ÈÈ
ÇÇ
Ç and
ÇÇ
ÈÈ
È
ÈÈ
•turn the humidifier off and disconnect the main power;
•open and remove the cover;
•remove the steam hose from the cylinder;
•disconnect the electrical connections from the top of the cylinder;
•release the cylinder from its holding bracket and lift it up to remove it;
•install the new cylinder in the humidifier by performing the previous operations in reverse.
WARNING: Electrical connections to the cylinder must be tight or possible fire hazard may result.
34
(06/06)
Page 35
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Maintenance of the other plumbing components
IMPORTANT WARNINGS:
•When cleaning the plastic components do not use detergents
or solvents;
•Scale can removed using a solution of Lime-A-Way
or 5% phosphoric acid, then rinse with water.
•External power must always be disconnected when perform-
ing any maintenance on the humidifier.
®
, CLR®,
••
•Drain valve /drain pump:
••
Remove the valve body or pump, clean if necessary using the same cleaning
solution as for the steam cylinder and a soft brush.
••
•Drain pan:
••
Clean the pan of any mineral deposits and check that the water flows freely from the pan to the drain at the
drain valve.
••
•Supply, fill, overflow pipes:
••
Check that these are clear and clean or replace if necessary.
••
•Fill valve:
••
After having disconnected the cables and
the hoses, remove the valve and check the
condition of the inlet filter; clean if necessary using the same cleaning solution as for
the steam cylinder and a soft brush.
••
•Supply and drain manifold:
••
Check that there are no mineral deposits in
the cylinder attachment and clean if necessary. Check that the seal (o-ring) is not
damaged or cracked; replace if necessary.
IMPORTANT
WARNING: after having
replaced or checked the
plumbing, check that
components have been
reconnected correctly with
the proper seals. Re-start
the humidifier and perform
a number of supply and
drain cycles (from 2 to 4),
then check for any water
leaks.
Item No. Description
1 fill/drain manifold
2 fill valve
3 drain valve
4 fill cup fill pipe
5 cylinder supply pipe
6 overflow pipe
7 fill cup
8 drain pan
SMP003, SMP005, SMP008, SMP010, SMP015 Three Phase
STEAMaster+ SERIES
40
(06/06)
Page 41
SMP025, SMP035, SMP045, SMP065 Three Phase
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
41
(06/06)
Page 42
STEAMaster+ SERIES
Installation, Operation & Maintenance Manual
Wiring of cylinders for SMP025, SMP035, SMP045, SMP065 units and voltages
There are 6 electrodes in these cylinders
Model
SMP025
SMP035
SMP045
SMP065
If arcing occurs during operation, then try changing the wiring pattern to the next level, A being the lowest level and
C being the highest and therefore least susceptible to arcing.
Conductivity
Micromhos
125 to 350
350 to 1250
125 to 350
350 to 1250
125 to 350
350 to 1250
125 to 350
350 to 1250
Power Supply - Vac
208 230 460 575
A A B B
B B B C
A A B B
A A B C
A A B B
A A B C
N/A N/A B B
N/A N/A B C
42
(06/06)
Page 43
STEAMaster + SERIES
Installation, Operation & Maintenance Manual
Technical Specifications
VAC UNIT MODEL NUMBER: CAPACITY, AMPERAGE, WATTAGE