Sartorius DCU 3 Operator's Handbook Manual

Page 1
Operators Handbook
BAEDCU3 - Rev. 4.6 - 0504
D C U 3 - S y s t e m
Digital Measurement and Control System for Fermentors
Page 2
Page 3
Operators Handbook DCU3 – System
Introduction
BAEDCU3 - Rev. 4.6 - 0504
Introduction
Sartorius BBI Systems´ digital measurement and control system for fermentors, the DCU3 – system, is available as stand-alone unit for operation of Sartorius BBI Systems´ laboratory scale fermentors and as a rack version for the measurement and control cabinets of pilot plant fermentors. All information given in the handbook refer to the operation of these fermentors, unless otherwise specified. Above this the DCU3-system can be applied as universal measurement and control system for fermentor automation and for customized general measurement and control tasks.
This „Operator's Handbook“ describes all standard functions available with the software version 4.6 of the DCU3 - system. In general the range of functions implemented for a specific fermentor is smaller than the range that this manual describes. The DCU system can be adapted to the different fermentor types by means of the software configuration and fermentor specific features.
Besides the standard configurations the DCU3 - system can have customized configura-
tions, as required for special applications. The description of such configurations can be added to this document or can be combined into a project-specific document.
Design, installation, start-up and use of the fermentor system are shown in the extra operating manual of this unit. More detailed technical information on the hard- and software structure, the system instal­lation, etc., is given in the extra „Technical Manual DCU3 - system“. If the DCU3 - system should be used together with a host computer the corresponding protocol for communication is described in the manual „DCU-Host Communication“. Both these manuals are available on request.
The digital control system DCU3 is one example of Sartorius BBI Systems´ product program of sophis­ticated fermentation and peripheral laboratory equipment. For further information about this device and our complete product program please contact the
Sartorius BBI Systems GmbH
Schwarzenberger Weg 73-79 D - 34212 Melsungen Tel.: +49 (0) 56 61 - 71 34 00, Fax: +49 (0) 56 61 - 71 37 02 e-mail: info@sartorius-bbi-systems.com
WebSite http://www.sartorius-bbi-systems.com or your local representative of Sartorius BBI Systems GmbH or Sartorius AG. Printed in Germany
© Sartorius BBI Systems GmbH. This document describes the device at the time of it s publication. Modification s
of the equiment and changes of the related documentation are preserved. No part of the documentation shall be changed or duplicated or reprocessed for other purposes by third parties without our written permission.
Printed in Germany
Page 4
Operators Handbook DCU3 – System
Introduction
BAEDCU3 - Rev. 4.6 - 0504
Page 5
Operators Handbook DCU3 – System
Contents
BAEDCU3 - Rev. 4.6 - 0504
Contents Page
Introduction
1 Design and Function 1 - 1
2 Operating Behaviour
2.1 Switching „off“ and „on“ 2 - 1
2.2 Mains Failure 2 - 1
2.3 Shut Down Function 2 - 2
2.4 Interlocking Functions 2 - 2
3 Function Selection and Inputs
3.1 Operating Terminal 3 - 1
3.2 Inputs 3 - 7
4 Start-Menü „Main“
4.1 General Notes 4 - 1
4.2 Process Information Provided by the „Main“ Menu 4 - 1
5 Main Function „Calibration“
5.1 General Note 5 - 1
5.2 pH - Calibration 5 - 2
5.3 pO2 - Calibration 5 - 4
5.4 Redox - Calibration 5 - 5
5.5 Calibration of Turbidimetry Measurement 5 - 6
5.6 Totalizer for Pumps and Valves 5 - 8
5.7 Calibration of a Balance System 5 - 10
5.8 Flow Calibration 5 - 11
6 Main function „Control Loops“
6.1 Equipment and Functional Principles 6 - 1
6.2 Selection of Controller 6 - 2
6.3 Controller Operation in General 6 - 3
6.4 Parametrization of Controllers, in General 6 - 4
6.5 Temperature Controller 6 - 7
6.6 Stirrer Speed Controller 6 - 9
6.7 Airflow Controller 6 - 10
Page 6
Operators Handbook DCU3 – System
Contents
BAEDCU3 - Rev. 4.6 - 0504
6.8 pH - Control Function Operating as PID - Controller 6 - 11
6.9 pO2-Control Methods 6 - 12
6.10 pO2 - Cascade Controller with 3 Servo Controllers 6 - 12
6.11 pO2 - Cascade Controller with 4 Servo Controllers 6 - 16
6.12 pO2-Gasmix Controller / O2 – Enrichment 6 - 18
6.13 pO2 - Gasflow Ratio Controller 6 - 19
6.14 Oxygen (O2) – Enrichment Using 2 Massflow Controllers 6 - 22
6.15 Foam Controller 6 - 24
6.16 Dosing Pump Controller 6 - 26
6.17 Level Controller 6 - 27
6.18 Weight Controller 6 - 29
6.19 Pressure Controller 6 - 30
6.20 Gravimetric Dosing Controller 6 - 31
6.21 Setpoint Profiles 6 - 33
6.22 Timers 6 - 35
6.23 Alarm Limits of Process Values 6 - 37
6.24 Alarms of Digital Inputs 6 - 39
7 Main function „Batch Control“
7.1 General 7 - 1
7.2 Sequences 7 - 1
7.3 Process Time 7 - 5
8 Main Function „Recipes“
8.1 Overview 8 - 1
8.2 Recipe Selection 8 - 1
8.3 Controller Parameters in Recipes 8 - 3
8.4 Setpoint Profiles 8 - 4
8.5 Timers in Recipes 8 - 5
8.6 Process Value Alarms in Recipes 8 - 6
8.7 Digital Input Alarms 8 - 7
9 Main function „Maintenance“
9.1 Overview 9 - 1
9.2 Manual Operation in General 9 - 2
9.3 Manual Operation for Digital Inputs 9 - 2
9.4 Manual Operation for Digital Outputs 9 - 4
9.5 Manual Operation of Analog Inputs 9 - 6
Page 7
Operators Handbook DCU3 – System
Contents
BAEDCU3 - Rev. 4.6 - 0504
9.6 Manual Operation for Analog Outputs 9 - 8
9.7 Settings of Measurement Ranges 9 - 10
9.8 Connection of External Devices 9 - 11
9.9 Host Interface 9 - 12
9.10 Peripheral Interface 9 - 14
9.11 Balance Interface 9 - 15
9.12 System Settings 9 - 16
9.13 Service / Diagnostics 9 - 17
10 Main Function „Documentation“
10.1 Selection Menu 10 - 1
10.2 Report Printer 10 - 1
10.3 Recorder Configuration 10 - 3
11 Main Function „Password“ 11 - 1
12 Main Function „INFO“ 12 - 1
13 Alarms
13.1 Alarm Messages 13 - 1
13.2 Alarm Menu 13 - 2
14 Supplement
14.1 Alarms, Meanings and Remedial Measures (Troubleshooting) 14 - 1
14.2 Trouble Shooting for the DCU-System 14 - 5
14.3 Interlocking Functions 14 - 5
14.4 Abbreviations 14 - 6
14.5 Fermentor - Specific Adjustments of Balance Systems 14 - 8
14.6 Arrangement and Assignment Plans 14 - 9
14.7 Declaration of Conformity with EC-Directives, Standards and
Technical Specifications 14 - 9
Page 8
Operators Handbook DCU3 – System
Contents
BAEDCU3 - Rev. 4.6 - 0504
Page 9
Operators Handbook DCU3 – System
1., Design and Function
BAEDCU3 - Rev. 4.6 - 0504 1 - 1
1 DESIGN AND FUNCTION
The Digital Measurement and Control System DCU3 has been especially developed for the automa­tion of fermentor systems. The hardware is based on an industrial 32 bit VME bus micro processor system. All measurement and control functions are implemented in the software. The software is stored on a PC-card, which can easily be replaced for extensions of the system by new versions.
For the fermentors of the BIOSTAT
®
series the Sartorius BBI Systems GmbH offers a broad range of standard configurations of the DCU3 – system, which consider the features of the individual type of fermentor. However, the extent of functions implemented for a delivered system will always depend on the specifications of the customer, as agreed prior to ordering of the fermentor system. Therefore even specific customized configurations are possible.
Standard functions are data acquisition, sensor calibration, alarm monitoring and control of operation conditions. Additional software modules provide control of process conditions by changing parameters depending on running time and state of the process. This includes setpoint profiles for controllers, timer functions for pulsed actuators, dosing counters, etc. Complete sets of process parameters may be predefined as recipes to allow performing of reproducible process sequences.
The DCU3 can be integrated into hierarchical automation systems via its remote interfaces. A host computer system can be connected, such as the proven MFCS-Systems, for instance, providing func­tions like graphical visualization of processes, data acquisition and storage, process protocols, etc.
Page 10
Operators Handbook DCU3 – System
1., Design and Function
BAEDCU3 - Rev. 4.6 - 0504 1 - 2
Page 11
Operators Handbook DCU3 – System
2., Operating Behaviour
BAEDCU3 - Rev. 4.6 - 0504 2 - 1
2 OPERATING BEHAVIOUR
The DCU3 - system stores all parameters which are adjustable by the operator (setpoint, calibration parameters, profiles, etc.) in a battery buffered memory. Hence these parameters are still available when the DCU3 system is switched off and restarted again.
For enabling the outputs of the DCU3 - system and of several system functions, which directly act on the fermentor system, 4 categories of switching-off or power failure, respectively, are differentiated:
1. Switching „off“ and „on“ using the mains switch at the front panel (see pos. 3 in fig. 1-1).
2. Shut down due to mains failure.
3. Emergency cut-off via the „SHUT-DOWN“-key at the operating terminal or using the mains switch of the supply unit or cabinet of the fermentor (see BIOSTAT
®
MD, ED or BIOSTAT®
C-DCU3, UD, for instance).
4. Interlocking functions for system outputs.
2.1 Switching „off“ and „on“
The DCU3 - system is switched-on or off, respectively, via the mains switch on the front panel. After being switched-on (again) the DCU3 will start at (return to) a defined state of operation:
All controllers are „off“, a ctuators are in rest position All timers are „off“ (stopped ) No recip e loaded, no program (sterilization for example) active
2.2 Mains Failure
In the case of a (mains) power failure, after being restarted, the DCU3 - system continues its activities as follows:
Controllers ru n on with the setpoint, which has been adjusted at the time of the power failure Timers and setpoint profiles will be continued Sequence s, such as sterilization programs, and recipes will be continued
The operator can set a maximum power failure time (FAILTIME) in the „maintenance“ menu. This is a specific feature of the DCU3 - system. When the power failure lasts longer than the preset FAILTIME, then the DCU3 - system behaves as if being switched-off with the mains switch, i.e. the system will be shut down and set to a defined basic state.
After a power failure the system generates the message „Power Failure“, together with the time and duration of the failure. If the maximum power failure time has expired (see „FAILTIME“), the system displays the message „Pwf stop ferm“ with time and duration of the failure. See also the description of the „Alarm messages“ in the supplement.
Page 12
Operators Handbook DCU3 – System
2., Operating Behaviour
BAEDCU3 - Rev. 4.6 - 0504 2 - 2
2.3 Shut Down Function
The shut down function can be released by :
Enabling the „SHUT DOWN“ key on the operating terminal and Enabling the mains switch of the fermentor (located on the supply unit or cabine t).
In the shut down state all outputs are switched over to their predefined safe state. Other active func­tions of controllers, timers, profiles, recipes and sterilization are not effected.
During the SHUT DOWN state you can change any of the active functions, as required. If the SHUT DOWN state is enabled, the DCU3 - system displays the alarm message „Shut
Down DCU“ or „SHUT DOWN FERMENTOR“
Pressing the „SHUT DOWN“ key again or restarting the fermentor supply unit with the emergency switch terminates the shut down function. Then all outputs of the DCU are reactivated.
2.4 Interlocking Functions
Interlocking functions trigger the outputs for functions which are important for operational safe ty, i.e.:
Fixed safety functions which cannot be changed by the user. User-definable safety functions.
An interlocking function switches certain outputs of the DCU3 over into their predefined safety state. However, this will not effect the course of controllers, timers, profiles, recipes and of the sterilization. For details about specific functions see section „Interlocking functions“ in the supplement.
If the cause for release of an interlocking function is no longer present, the safety state of the corre­sponding output will be cancelled and the output returns into its operating state.
The safety state of an output is the same as the state during SHUT DOWN. The state of the output displayed in the menu „MAINTENANCE, MANUAL OPERATION,
DIGITAL OUTPUTS“ and „ANALOG OUTPUTS“ is „lock“.
Page 13
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 1
3 FUNCTION SELECTION AND INPUTS
3.1 Operating Terminal
The DCU3 - system has an especially developed touch screen terminal for display of all process pa­rameters and for operation of the entire unit. This „touch terminal“ has integrated „touch keys“ where the operator can select the menus and the related subfunctions, enter data and select and switch-over the modes for fermentor operation. In general the terminal is operated simply by pressing the screen at the position of the displayed keys.
The touch terminal is adjustable to provide an optimum angle of vision: DCU-Tower : BIOSTAT
®
B-DCU
1. Unscrew the locating screw of the support at the rear of the terminal a little.
2. Push the terminal backward at its upper edge or pull until the display can be read best. Tighten the screw again.
DCU3-System in table top housing: BIOSTAT
®
MD-DCU3, Q-DCU-
3, C/CT-DCU3
1. Push the locking device on right hand of the terminal (see push button 4 in fig. 1-1)
2. Pull the terminal at its lower edge or push backward, until you achieve an angle where the display can be read best.
3. Release the locking device to fix the arrangement.
Rack version of DCU3 systems : BIOSTAT
®
D-DCU3, customized
pilot- and production fermentors
The possible way of setting the angle depend s on the
mounting of the terminal in the rack.
3.1.1 Structure of the Touch Screen Display
Page 14
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 2
Structure of the Touch Screen Display, on the page above shown for the „Main“ menu: 1. line: Status line:
TAG Used for
hhhh:mm Display and Input of process time Fermentation (etc.) Display of operating state. Possible displays are:
Fermentation: System is in „Fermentation“ state
Sequence: System runs a sequence
Recipe 1..4: System runs a recipe (1..4)
18.01.00 14:03:11 Display of actual date and time in formate: dd.mm.yyyy hh:mm:ss
2. line: Alarm line, display of alarms (showing the latest alarm) 3. line: name of active function in the workin g area Workin g area: display of schematic setup of fermentor system and peripheral equipment;
– MAIN 2 : next „Main“-page – the items displayed depend on the active function a nd can include symbols for devices,
process values, parameters, modes and settings;
– the displays of the items are designed as touch keys for direct access to submenus for
selecting functions and entering parameters.
Lowest line: Main function keys (also designed as touch-keys) for selection of submenus
and subfunctions, where parameters should be entered and operating modes should be set.
Page 15
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 3
3.1.2 Function al Keys of the Working Area
For a selected function the lowest line of the working area can have additional touch keys, which are especially assigned to this function and allow for direct access to the corresponding submenus.
Example: Operating display of the pO
2
- controller with touch keys:
The following touch keys for function selection are available in the working area of the oper-
ating displays:
Selection key Function
Exit Closes the actual display PARAM Request for display of related parameters PV - Alarm Request for display of related process value alarms PROFILE Request for display of related setpoint profiles CALIB Request for display of related calibration function
Available keys not shown in this example are
CLOOP Selection of the related controller menu CLOOPx Selection of additional controller displays MAINx Request for display of related process overviews TIMER Request for display of related timer functions DI ALARM Request for display of related digital input alarms
Page 16
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 4
3.1.3 Selection of Menus and Entering of Parameters
The operation of the DCU3 - system is organized systematically. Related tasks of fermentor operation are combined in functional groups - the „main functions“ listed below. A main function can be directly activated at any time during the running process from any submenu by pressing the corresponding main function touch key at the screen.
Main function Display, use
Main Graphic overview of the entire fermentor system showing the most important
process parameters and allowing for direct access to the related functions. Calibration Calibration of sensors and pumps, taring of balance systems Control Loops Operation of the controllers and related setpoint profiles and timers Batch Control Operation of serial steps, batch processes, etc., such as sterilization runs Recipes Operation of 4 recipes with preset controller parameters, setpoint profiles, tim-
ers and alarm parameters Maintenance Manual access to inputs and outputs, measurement ranges of process values,
parameters of remote systems (such as host computers, balance systems) and
to the maintenance (service) functions Documentation Operation of recorders and printers for documentation of the process Info Information about the installed software / general notes
There are two possible methods to select a menu, step forward to a subfunction and enter parame­ters. As an example here are the possible methods for setpoint adjustment of the stirring speed:
Stepping through the menu tree as known from the former DCU1- and DCU2- systems:
1. Select the main function „Control Loops“ by pressing the touch key
2. Select the „Stirrer“ controller from the overview of controllers
3. Adjust the setpoint
Enabling the data entry function directly from the main menu. This is accomblished by object
(based) linking of the actual stirrer speed display in the main menu to the related controller functions, i.e. „stirrer controller, setpoint profile and alarm limits“:
4. Press the „Stirrer“ - touch key in the working area of the main menu. The display directly switches over to the menu of the stirrer controller.
5. Adjust the setpoint.
Page 17
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 5
3.1.4 „Tou ch keys“ in the Menu „Main“
After switching on of the system the graphical overview in the menu „Main“ provides a schematic dis­play of the main functional elements of the individual fermentor system, together with the most import process parameters and the „touch keys“ for selection of the related functions:
Only for the single unit at fermentor systems with one culture vessel As an overview of all subunits at fermentor systems with 2…4 culture vessels
At multible vessel fermentor systems the main menus of the subunits can be accessed as follows:
Via the touch key integrate d in the overview display showing the vessel no. of the subunit
(only for DCU3 systems available from about April 2002 on and as far as implemented).
Via the direct function key CHANGE UNIT
Menu „Main“: Direct access to the main menus of subunits at fermentors with 2..4 culture vessels: Example: BIOSTAT
®
B-DCU twin Example: BIOSTAT® B-DCU quattro
The touch key „All vessel“ can be used to return to the overview display of all units.
The direct function key CHANGE UNIT cyclically switches over the displays of the main menus of all units and the individual subunits:
All vessels v essel 1 vessel 2 (vessel 3, 4, if available) all vess els
Page 18
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 6
Switching over the main menu dis­plays for 2…4 culture vessels via direct function key CHANGE UNIT:
CHANGE UNIT
CHANGE UNIT
.....
Page 19
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 7
3.1.5 Direct Function Keys
The direct function keys on right hand of the „Touch Terminal“ allow for direct access to the system:
SHUT DOWN : Pressingthis key sets all analog and digital outputs into a safe state. An active
SHUT DOWN state is indicated by lighting LED in the key. Repeatedly pressing the key cancels (releases) the SHUT DOWN state and the system returns to its previous state.
ACK : If an alarm message occurs, a red LED in the ACK - key lights. Pressing the ACK - key then
enables the alarm menu on the display.
REM : Pressing the REMote control key allows for the transmission of data from the host to the
DCU system. Effective only if a host computer is connected to the DCU-system.
CHANGE UNIT : Switching-over of the operating terminal. Applicable for DCU3-system which are
prepared for controlling several fermentors/culture vessels.
3.2 Inputs
3.2.1 Numerical and Non-numerical Inputs
Example for entering numerical inputs, shown here for the temperature setpoint:
1. Press either the touch-key „Temp“ in the work­ing area of the „main“ menu or the key “SETP” in the menu TEMP Control Loop A touch key pad fades in for data input.
2. Enter the new setpoint. For this consider the permissible setpoint range, as indicated.
3. At erroneous inputs delete the entry with CAN­CEL and enter the correct numbers.
4. Confirm the input with the „Ok“-key.
5. The system closes automatically the touch key pad. The new setpoint is displayed.
Input of operating mode, i.e. controller modes:
1. Press the touch key „MODE“; a window with the selectable modes fades in.
2. Press the touch key of the intended mode, i.e. „off“.
3. At selection of a wrong mode, delete with CAN­CEL and select again the correct mode
4. The selection window closes and the display shows the new mode.
Page 20
Operators Handbook DCU3 – System
3., Function Selection and Inputs
BAEDCU3 - Rev. 4.6 - 0504 3 - 8
Input of text:
1. Enter the text with a max. number of letters (Range).
2. At wrong inputs delete the entry using the „<-“ key or CANCEL.
3. Confirm the Entry with „Ok“. The system closes the keypad and displays the text.
Selection boxes (slide r): The slider can be moved as follows:
1. Pressing the arrow key
2. Moving the white zone within the slider
3. Pressing the shaded zone at the relative posi­tion of the table, which should be accessed
Special Notes
What do touch keys indicate, whose label appears in black & white dithered („light“) letters? If a controller´s mode is set to „auto“, for instance, the data entry for the controller output is
locked. This locking of an entry against inputs is indicated on the „OUT“ key. The letters then are displayed in black & white dithering („light“).
3.2.2 Password - System
System settings and functions, that are restricted for use by authorized personnel only, are protected by a password. Among others these are, for instance, the setting of controller parameters (such as PID), the setting of interface parameters and the manual operating mode.
For more detailed information refer to section “Main function “Password””.
Page 21
Operators Handbook DCU3 – System
4., Start-Menü „Main“
BAEDCU3 - Rev. 4.6 - 0504 4 - 1
4 START-MENÜ „MAIN“
4.1 General Notes
The „Main“ menu is displayed after switching on the DCU3 - system. With the new „object-based“ dis­play of entries and the direct selection of submenus and functions for data input and mode selection, the main menu is the control center for operation during a fermentation run.
The schematic display of the culture vessel together with the connected peripheral assemblies, the symbols for stirrers, pumps, totalizers, balance system and the location of the electrodes facilitates the overview over the state of the process parameters. Above this it is the starting point for easy access to the submenus and subfunctions for inputs and selections.
4.2 Process Information Provided by the „Main“ Menu
The main menu displays the process values together with schematics of the related component parts of the fermentor system:
Measured values for pH, pO
2
, foam, etc.;
Inputs of external actuators, such a s motor control, massflow controller; Processed values, such as dosing volumes of pumps, totalizers, calculated values of arith-
metic functions, etc.;
Signals of external device s connected to the DCU3 - system, such as a balance system;
The extent of displayed entries, process values and parameters depends on the configuration of the DCU3 - system for the related fermentor system. The table on next page gives an overview on com­mononly applied tags and entries.
Page 22
Operators Handbook DCU3 – System
4., Start-Menü „Main“
BAEDCU3 - Rev. 4.6 - 0504 4 - 2
4.2.1 Alarms
If a process value exceeds its alarm limit or if a device is switched over to an alarm state the
backround color of the corresponding symbol changes to red (in this „laser-printed“ manual shown light-grey, see example for the entry of foam measurement).
4.2.2 Invalid Process Values
If a process value is „invalid“ the display changes to „---„, see example „flow“:
4.2.3 Direct Function Keys and Headline Text at the Touch Display
Direct Fun ction keys on the touch display have the background colour grey/white. Headline texts (background colour white) label indicate a correlation of the functions of the
subsequent keys
Page 23
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 1
5 MAIN FUNCTION „CALIBRATION“
5.1 General Note
All calibration functions required for routine operation of the fermentor can be executed using the main function „calibration“. You can select the following functions via the corresponding selection menu:
Selection menu „Calibration“:
The entries refer to the following functions:
– „Sensors“ : calibration of the electrodes using calibration buffers and standard conditions – „Totalizer“ : calculation of the delivery of the addition agent pumps for dosing counters – „Balance“ : the functions required for (pre)setting of balan ce systems, such as zero taring
and tare correction
You will enter all inputs at the touch terminal. Context based information displayed on the
terminal will guide you through the individual menus, telling you which inputs and selections are required. The DCU3 - system automatically adapts the related (measured or calculated) process values to the settings resulting from the calibration.
The calibration parameters will be stored when the DCU3 - system is switched off. Hence
the DCU3 - system will use these settings again for the calculation of parameters, when it is restarted for continueing a process or for a new process, until the calibration is done again.
Page 24
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 2
5.2 pH - Calibration
The pH electrode is calibrated by a two-point calibration using liquid buffers. The calibration is done before the electrode is installed in the culture vessel. For details about preparing of the pH-electrode and handling during calibration see the operating information delivered by the manufacturer. For de­tails about mounting the electrode into the culture vessel, see the fermentor´s operating manual.
The calibration determines the „zero drift“ and „slope“ of the electrode. The measured pH-value is cal­culated from the electrode voltage using the Nernst equation, considering the „zero drift“, „slope“ and „temperature“. During calibration the temperature is entered manually. For pH-measurement during the process temperature effects are compensated via the measured temperature in the fermentor.
The impact of heat during the sterilization can cause a zero drift of the electrode. To compensate for such effects the DCU3 - system allows to recalibrate the pH-electrode during the process. You can measure the pH-value in a sample taken from the fermentor and enter this value into a corresponding menu. The software recalculates the zero drift and displays the corrected „in-situ“ pH-value afterwards.
The operating display for the pH - electrode shows the pH value, the electrode voltage and the elec­trode parameters „zero drift“ and „slope“. Thus the functioning of the electrode can be easily checked.
5.2.1 Operating Display
Tag Entry Displayed value or function, required input
pH pH Display of measured pH value,
input of pH-value measured in sample for recalibration ELEC mV Display of measured electrode voltage (raw signal) TCOMP Display “temperature compensation” TEMP Display of temperature for temperature compensation ZERO mV Display of zero drift SLOPE mV/pH Display of slope Start Calibration Enabling the calibration function Start Recalibration Enabling the recalibration function (during the process)
Page 25
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 3
Additional touch keys, tags and entries displayed depending on the selected function:
Tag Entry Displayed value or function, required input
TMPCO degC Input of temperature for manual temperature compensation BUFFZ pH Input of pH-value of zero buffer
note pH-value on the buffer bottle for the actual temperature
BUFFS pH Input of pH-value of slope buffer
note pH-value on the buffer bottle for the actual temperature
5.2.2 Calibration
The pH - electrode is calibrated before installation into the culture vessel, e.g. prior to the sterilization.
Tip: Since the heat impact during the sterilization and chemical compounds of the culture me-
dium may effect the measurement characteristics of the electrode, it must be calibrated and checked for proper function regularly (i.e. prior to any new fermentation run).
1. Start the calibration routine by pressing the „Start Calibration“ touch key.
2. Follow the instructions given in the related submenus.
5.2.3 Recalibration
Via these steps you can adapt the pH-measurement function to changing measuring char-
acteristics of the electrode, as it may be caused by heat impact during the sterilization or by chemical reactions of the electrolyte with the culture medium, for instance:
1. Measure the actual pH-value in a sample taken from the running fermentation, using con­ventional pH-measuring techniques.
2. Start the calibration by pressing the „Start Recalibration“ touch key.
3. Follow the instructions given in the related submenus.
The DCU-system automatically recalculates the zero drift caused by the sterilization and
displays the corrected pH-value.
5.2.4 Special Notes
If necessary the values for „zero drift“ and „slope“ can also be entered directly in the corre-
sponding sections of the display.
The electrode has a restricted maximum lifetime which depends on the operating conditions
and the application. The electrode should be serviced or replaced, whenever the functional check and the calibration indicate a malfunctioning.
The pH - electrode must be serviced or replaced if :
– the zero drift is beyond the range of -30 ...+30 mV – the slope is beyond the range of 56...59 mV/pH
You'll find specific information about recommended service periods and estimated lifetime of
the electrode in the manufacturer´s documentation included in the delivery of the electrode.
Depending on the type of fermentor and the delivered pH-electrode, the operation and main-
tenance measures required for the electrode may differ from the information herein. You'll find more detailed information about proper handling of the electrode during calibration and installation into the culture vessel in the Operating Manual of the fermentor.
Page 26
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 4
5.3 pO2 - Calibration
The pO2 - electrode is calibrated in terms of percentage oxygen saturation, „% pO2“. The calibration is a two-position calibration. In a fermentor the oxygen-free culture medium is the zero reference and the medium saturated with oxygen is the „100 % pO
2
“ - reference. The pO2-electrode is calibrated while it is installed in the culture vessel and after the sterilization. Therefore the calibration considers possible interferences resulting from heat impact or chemical effects during sterilization.
In in-situ sterilized culture vessels you can enter the current of the electrode measured at
the end of the sterilization cycle as zero reference of the electrode.
If it is impossible to measure the zero current before air is introduced, you can connect a ni-
trogen source to the air input and gas the vessel with oxygen-free nitrogen to replace the oxygen dissolved in the medium.
The slope can be measured after gassing the medium with air (or gas mixtures containing
oxygen) at the operating conditions intended for the process. During the process the DCU ­system calculates the actual pO
2
considering the zero reference, slope and temperature.
The structure of the operating display for calibration of the pO
2
-electrode is nearly the same as for the pH-calibration. See the display on your DCU - system for details or refer to the pH - calibration display. The display shows the „pO
2
-saturation“ (% pO2), the actually measured electrode current, the actual temperature and the zero and slope current together with the calibration conditions. This, in addition, allows a simple function control of the pO
2
-electrode.
5.3.1 Calibration
5.3.1.1 Zero Calibration
1. Before starting the zero calibration: sterilize the vessel (i.e. run the sterilization cycle at in­situ sterilizable fermentors) or – connect a supply of oxygen-free nitrogen and ga s the medium until any dissolved oxygen
is exhausted.
2. Inititate the calibration of the electrode´s zero via „Start ZERO Calibration“. Follow the in­structions given in the calibration menu.
If the displayed zero current (ZERO: ....) is not in the range of 0 ... +10 nA, the pO
2
-
electrode must be checked and serviced.
5.3.1.2 Calibration of Slope
1. Gas the medium with air (or the intended gas mixture containing oxygen) at the conditions (flow rate, pressure, temperature) intended for optimum oxygen supply. A constant elec­trode current will indicate that the medium is saturated with oxygen.
2. Inititate the slope calibration via „Start SLOPE Calibration“ and follow the instructions given in the calibration menu.
If the measured current re mains below 30 nA, the electrode must be checked and serviced.
5.3.2 Special Notes
At a first use or at any time the pO
2
-electrode has been disconnected from the amplifier for more than 5 ... 10 min. it must be polarized. This polarization takes at least 6 h (the time will be shorter, if the electrode is disconnected for only a few minutes). See information in the Operating Manual of the fermentor or in the documentation delivered with the electrode.
If necessary the „Ze ro“ and „Slope“ can be entered manually into the corresponding fields.
Page 27
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 5
5.4 Redox - Calibration
The Redox calibration is in fact a functional check. You will measure a calibration buffer and compare the measured value with the reference indicated on the buffer bottle. If these values are different, the Redox can be entered manually. The DCU - system then calculates a corresponding correction factor.
5.4.1 Operating Display
Tag Entry Displayed value or function, required input
REDOX mV Display of combined electrode voltage CHECK mV Display of combined electrode voltage of last calibration Start Check Electrode Enabling calibration of the Redox electrode
Additional touch keys, values and functions available in this display:
REFBU mV Enter reference voltage of redox buffer
5.4.2 Functional Check
The electrode function is checked before it is mounted into the culture vessel and therefore prior to the sterilization. Since the heat impact of sterilization or chemical reactions with compounds of the culture medium may effect the measuring characteristics of the electrode its function should be checked regu­larly, i.e. prior to any next use and, if wrong operation is suspected, after a fermentation run.
1. Place Redox electrode in a beaker filled with the reference buffer
2. Enable functional check via „Start check electrode“. Follow the instructions of the menu.
5.4.3 Special Notes
If the measured buffer Redox and the value on the buffer bottle deviate by more than 6 mV
(about 3%) the electrode must be serviced. See documentation delivered with the electrode.
Page 28
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 6
5.5 Calibration of Turbidimetry Measurement
Calibration of the turbimetry measurement probe is a „single-step“ procedure evalulating the „zero de­viation“ of the sensor is. For this the sensor is placed into particle- and bubble-free deinonized water.
The system calculates the turbidimetry as the arithmetical mean of the value measured during a de­fined measuring time in terms of „absorption units, AU“. For calculation the system considers the zero deviation and a selectable damping factor „DAMP”. To obtain stable turbidimetry measurements, the damping factor „DAMP“ can be selected in 4 stages.
The operating display of the turbidimetry sensor includes the data field for absorption units (AU), the percentage sensor raw signal [%] and the zero deviation against „0 AU“. This allows for an easy func­tional check of the sensor. The lamp contained in the turbidimetry sensor can be switched on and off via the „Sensor Calibration“ - menu, see LAMP-entry
1)
.
5.5.1 Operating Display
Tag Entry Displayed value or function, required input
TURB AU Display of process value in 0...6 AU (Absorbing Units) ELEC % Display of percentage raw signal of the sensor ZERO % Display of zero deviation after calibration LAMP
1)
On/off Display and selection of switching state of lamp in the sensor
DAMP 1 ... 4 Display and input of signal damping. The input signal is proc-
essed as the mean value of a floating reference window. Damping factors base upon 4 selectable reference windows:
- step 1 = 6 s; step 2 = 12 s; step 3 = 30 s; step 4 = 60 s
Start Calibration Enabling the calibration routine
Additional touch keys, values and functions available in this display:
BUFFZ AU Display of zero solution
1)
Only Fundalux I – system, not applied with Fundalux II (available as option from 2004 on)
Page 29
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 7
5.5.2 Calibration
For calibration of the turbidimetry sensor proceed as follows.
1. Start the calibration via „Start Calibration“
2. Follow the instructions of the calibration menu.
5.5.3 Special Notes
1. If the lamp
1)
is switched on, it will be kept in „on“-state when the DCU3 - system is switched
off and on again.
2. If required, the percentage zero deviation can directly be entered in the ZERO-entry.
Page 30
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 8
5.6 Totalizer for Pumps and Valves
For monitoring of the corrective agent consumption the dosing times of the pumps or of the dosing valves are totalized and used as process values. The DCU3 - system converts the dosing times into delivered volumes considering the specific flowrates of the pumps or of the dosing valves.
The dosing counters can be zeroed at any time via the operating display. If the specific flowrates are known, you can enter them directly via the touch display. If the flowrates must be evaluated you can use the „Calibration Totalizer“ function. Furthermore the flowrates can be calculated automatically dur­ing the calibration process from the measured running time and the entered delivery volume.
The standard configurations of the DCU-system include calibration routines and dosing counters for acid, base, antifoam, feed, harvest and substrate. Since the calibration and dosing counter functions are the same for all pumps and dosing valves, only those for the acid pumps will be described herein.
5.6.1 Operating Display
Tag Entry Displayed value or function, required input
ACID ml Display of delivered volume of liquid FLOW ml/min Display of calculated delivery or input of either specific
pump delivery or valve flow, as far as known Start Calibration Enabling the calibration Reset Totalizer Resetting the dosing counter to zero PV ALARM Enabling the alarm display CLOOP Selection of the controller menu
Additional touch keys, values and functions available in this display::
VOLUME ml Input of volume delivered during calibration
Page 31
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 9
5.6.2 Calibration of a Pump
For calibration allways use tubings of the same type and dimensions as for the delivery of
media during the process.
1. Place one end of the tubing into a beaker filled with water and the other end into a measur­ing beaker. Complete fill the tubing with water. For this you can manually activate the pump.
2. Start the calibration of the pump via „Start Calibration“.
3. Follow the instructions shown at in the DCU3 - display. The DCU - system automatically calculates the flowrate considering the internally recorded
running time and measured delivery and displays the result in the entry „FLOW : x /min“).
5.6.3 Activation of the Dosing Counter
The dosing counter will automatically be started when the calibration of the pump is finished
and the corresponding controller is activated.
5.6.4 Special Notes
If already known, the delivery rate of the pump or of the dosing valve can be directly entered
into the FLOW - entry.
Page 32
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 10
5.7 Calibration of a Balance System
The fermentor weight (the „vessel content“) can be measured by balance platforms or load cells (i.e. optional accessories). They will be connected to the DCU3 via a strain gauge measuring amplifier. The measurement amplifier is scaled to a gross weight output signal. The gross weight comprises the empty vessel with the drive system, the individual vessel equipment and the vessel content (medium).
„Zero-taring“ using the calibration function is done by measuring the weight of the completely equipped culture vessel without the culture medium and setting this weight as the „net weight“. How­ever, tare correction is possible after changing the equipment of the culture vessel during a running process. For this the net weight is stored and the tare weight will be adapted to the changing gross weight.
5.7.1 Operating Display
Tag Entry Displayed value or function, required input
WEIGV kg display of net weight (WEIGH = GROSS - TARE) GROSS kg display of gross weight TARE kg display of tare weight Start Taring Enabling the taring function Start Hold Enabling the „hold“ function PV ALARM Enabling the alarm display CLOOP Selection of the controller menu
5.7.2 Calibration
1. For zero taring with the culture vessel being fully equipped, but without culture medium, start the calibration with „Start taring“. Follow the instruction shown in the calibration menu.
2. If the culture vessel equipment is changed during the process, you can recalibrate the tar­ing. Start the „Hold“ function for this and follow the instructions in the menü.
Page 33
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 11
5.8 Flow Calibration
The dosing control function of the DCU3 - system operates with a remote balance system, which measures the weight of the substrate. The balance system is connected to the DCU3 - system via a serial interface. By default the actually measured weight will be transmitted to the DCU3 every five seconds. The menu has an optional manual refilling function. This allows the use of low cost balance systems which offer only small weight ranges.
Connecting a balance system via the serial interface also allows for measuring external weights. At an existing FLOW-CALIBRATION menu one remote balance with serial interface can be connected to the DCU3 without hardware extensions. One extension allows for up to 12 measurements.
The system calculates the volume delivered per time, the „massflow“, considering the actual weight measured with the balance and the spent time. To minimize disturbances the calculation is based upon a „dynamic calculation“ of the mean value. All values measured within a passed interval of either 1 min, 10 min or 60 min will be considered. The user can select this interval according to the process.
5.8.1 Operating Display
Tag Entry Displayed value or function, required input
FLOW kg/h Display of actual flow WEIGF kg Display of net weight Refill Enabling the refill function Reset Flow Reset of the displayed flow (enable start with „0.00“) CYCLE Input of calculation interval (cycle)
1
interval of 1 minute
10
interval of 10 minutes (recommend setting)
60
interval of 60 minutes PV ALARM Enabling the alarm display CLOOP Selection of the controller menu
Page 34
Operators Handbook DCU3 – System
5., Main Function „Calibration“
BAEDCU3 - Rev. 4.6 - 0504 5 - 12
5.8.2 Special Notes
1. It is recommende to set a cycle interval of 10 minutes.
2. When selecting an interval of 10 or 60 minutes, respectively, the calculation and display of the flowrate starts with the shortest interval and automatically switches over to the next longer one. The flowrate of the initial phase is calculated from the shortest interval. This is also true when a new setpoint is defined for the dosing controller.
The same is true for presetting a new setpoint of the dosing controller.
3. For manual refilling switch over to „Refill“-mode.
The automatic calculation of the actual flow will be stopped. The dosing controller continues
to act upon the last flow calculated. You can now refill the substrate storage vessel (bottle) and tare the balance again. After switching over to „contr.“ mode the system starts with re­calculation of the flow and continues dosing, now considering the actual values.
Page 35
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 1
6 MAIN FUNCTION „CONTROL LOOPS“
6.1 Equipment and Functional Principles
All control loops in the DCU3 - system are DDC controllers. They operate either as PID controllers, setpoint controllers or on/off controllers and are adapted to the related control loops. Depending on the actuator their output is either continuous or pulsewidth-modulated (pwm). Both single- and split-range controls are possible. The controller structure (PID) can be parametrized, if necessary. Switching over between the operating modes is carried out with bumpless transfer.
These modes can be selected:
Mode State of controller
off controller switched off with defined output auto controller in operation manual manual control of controller / actuator profile time profile for setpoint cascade servo controller in cascade control loop
In the controller display you can enter actual values, operating modes and controller outputs. Effective ranges depend on the configuration implemented for a specific fermentor. The parametrization display for adjustment of PID parameters, output limits and deadband is accessible via a password. In remote operation setpoint and operating mode are specified by the host computer.
The extent of implemented controllers depend on the fermentor system and/or the individual
customized configuration. The controllers shown below can be implemented at present.
Temperature controller PID cascade controller, pwm-splitrange outputs for heating /
cooling Stirrer controller Setpoint controller for external motor control pH controller PID controller with pwm-split-range outputs for acid/base pO
2
controller PID cascade controller for speed, airflow or pressure servo
controller (switchable) pO
2
gasflow ratio controller Master controller for gasflow ratio controller Gasflow ratio controller Ratio controller of two external massflow controllers pO
2
Gasmix controller PID controller, with pwm continuous outputs for control of
N
2/O2
Airflow controller Setpoint controller for external massflow controller Foam controller On/off controller for antifoam Level controller On/off controller external harvest and/or feed pump Feedpump controller Setpoint controller for external dosing pump Pressure controller PID controller, continuous output pressure control valve Weight controller PID controller, pwm-output for external harvest pump Dosing controller PID controller for control of a external dosing pump
Note: Additional or alternate controller functions can be implemented into existing DCU-systems
lateron by changing the configuration, for instance. Above this, the software allows imple­menting of special control functions, if necessary.
Page 36
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 2
6.2 Selection of Controller
6.2.1 Operating Display
Tag Entry Displayed value or function, required input
PV [PV] Display of actual process value, entry (= physical unit) depending on
process value SETP [PV] input of setpoint, entry (= physical unit) depending on process value MODE
input of controller mode
off
master controller and servo controller switched off
auto
master controller switched on, servo controller switched to „cascade“
manual
manual access to controller output
prof
timer profile for setpoint
TEMP, etc. selection of controller display TIMER selection of timer for digital output CLOOP selection of the controller menu
Page 37
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 3
6.3 Controller Operation in General
In general the operation of the DDC-controller is almost the same. Operation in cludes the necessary changes of the setpoints, of the controller modes and of the controller outputs. Additional controller settings not required for routine operation, will be done via the parametrization functions.
6.3.1 Operating Display (Example for Temperature Controller)
Tag Entry Displayed value or function, required input
TEMP, etc [PV] Display of physical unit of actual value, such as „degC“ for TEMP,
„rpm“ for STIRR, „pH“ for pH-value, „% sat“ for O
2
saturation, etc.
SETP [PV] Input of setpoint in the physical unit of the process value, such as
„degC“ for TEMP, „rpm“ for STIRR, „pH“ for pH-value, etc.
MODE Input of controller mo de
off
master controller and servo controller switched off
auto
master controller on, servo controller switched to „cascade“ mode;
cascade
servo controller operating in cascade mode (only some controlle rs)
profile
timer profile for setpoint running (only some controllers)
manual
manual access to controller output;
OUT % Display of controller output in [%]; inputs possible in mode „manual PARAM Input of password for access to controller parameter PV ALARM Enabling the alarm display PROFILE request for setpoint profile CALIB request for calibration function (only some controllers)
Page 38
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 4
6.4 Parametrization of Controllers, in General
For optimum adaptation of the DDC controllers to the control loops of the fermentor, the operator can change important control parameters of individual controllers via the parametrization displays:
MIN, MAX : Minimum and maximum limits for the controller output  DEADB : Deadband adjustment (only for PID controllers)  XP, TI, TD : PID-Parameter (only PID controllers)
The parametrization display combined with a controller display is only accessible by entering a pass­word. On delivery a DCU3 - system is configured with such control parameters that ensure a stable control of the fermentor system it is designed for. For details about the parameters preset in the fac­tory see the corresponding table in the supplement or in the documentation delivered extra for custom­ized configurations of the DCU3 – system.
Changing the preset control parameters is not necessary under normal use. An exception are control loops which vary with the fermentation process, such as for pH- and pO
2
-control.
6.4.1 Output Limits
For setpoint controllers and PID controllers the controller outputs can be limited (MIN and MAX). Thus unintended high actuator changes can be avoided and, for cascade controllers, the setpoint for the servo controller can be limited.
The limits must be entered at MIN for the „minimum output“ and MAX for the „maximum
output“. All settings are in terms of [%].
For full contro ller output range the following limits must be entered:
– single controller output : MIN = 0%, MAX = 100 % – splitrange controller output : MIN = -100 %, MAX = 100 %
6.4.2 Deadband
For PID controllers a deadband can be adjusted. If the control deviation is within this deadband the controller output remains constant or is set to zero (specific feature of the pH controller). By means of the deadband a more stable control with minimized actuator changes can be achieved for actual val­ues which vary stochastically. Furthermore, this will avoid oscillating of the controller output for spli­trange controller outputs (e.g. continuously alternating acid-alkali dosag e by the pH - controller).
The deadband is adjusted in the entry DEADB as percentage [%] of the measurement span
of the corresponding actual value. It is symmetrical to the adjusted setpoint.
example for pH controller: - measurement range pH = 2 - 12 pH
- measurement span 10 pH
- adjusted deadband ± 0.1 pH
- adjusted setpoint 6.0 pH
Then the pH-control is inac tive at an actual value of 5.9 pH - 6.1 pH
Page 39
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 5
6.4.3 Operating Display
Tag Entry Displayed value or function, required input
MIN % Input of minimum output limit, representing the setpoint minimum for
the servo controller (0 ... 100 % = measuring range of process value)
MAX % Input of minimum output limit, representing the setpoint minimum for
the servo controller (0 ... 100 % = measuring range of process value) DEADB [PV] Input of deadband; physical unit depending on process value XP % Input of proportional range in [%] of the measuring range
(100 % = maximum measuring range of process value) TI sec Input of reset time TD sec Input of rate (delay) time Process
Value
Selection of intended process value for control if double measurements
are applied
Page 40
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 6
6.4.4 PID-Parameter
The PID - controllers can be optimized via the PID - parameters Xp, TI and TD in the corresponding entries of the menu. The implemented digital controllers allow changes of the control behavior (P, PI, PD, PID) and of the parameters during operation, which simplifies the optimization of the controllers.
Xp: Proportional ran ge in [%] of measurement range (P-section) TI: Reset time in seconds (I-section) TD: Rate time in seconds (D-section) The control structure can be adjusted by setting the individual PID - parameters to zero :
– P-controller -> TI = 0, TD = 0 – PI-controller -> TD = 0 – PD-controller -> TI = 0 – PID-controller -> alle PID-Parameter defined.
6.4.5 PID Controller Optimization
An optimum adaptation of a PID - controller to its control loop requires detailed knowledge in control theory. You may refer to any standard literature for proven adjustment rules (e.g. Ziegler Nichols). Thus the following details are only general guidlines:
The D section (TD) should only be activated in the case of quite stable actual values. Oth-
erwise, if the actual values are varying stochastically the controller output will change con­siderably and fast. This will lead to an unstable control behavior.
As a general rule the TI : TD ratio should be 4 : 1. In the case of a periodic oscillating control loop the following measures are recommended:
– increase Xp – increase TI/TD
If the readjustm ent is too slow after setpoint jumps or if the actual value drifts, the following
measures are recommended: – decrease Xp – decrease TI/TD
Page 41
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 7
6.5 Temperature Controller
The temperature is controlled via a cascade control with a master controller for the vessel temperature and a servo controller for the jacket temperature. The output of the servo controller controls the steam valve (or an electric heater) and the cooling valve in split-range operation via pulsewidth-modulated or continuous outputs.
The master controller can be switched from PD-behavior at start-up to PID when approaching the set­point, which minimizes overshooting. When the temperature controller is switched off, an additional digital output switches off the circulation pump and the heating contactor in the fermentor.
The temperature control is operated via the displays for the master controller [TEMP] and the servo controller [JTEMP]. However, since all operations for the servo controller are activated automatically, the adjustment of setpoints and operating modes need only be carried out at the master controller.
6.5.1 Operating Display for Master Controller (Vessel Temperature)
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
Page 42
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 8
6.5.2 Operating Display for Servo Controller (Jacket Temperature)
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.5.3 Operation
For routine adjustment of setpoint and operating mode only the master controller [TEMP]
must be operated. Direct manual adjustment of the heating and cooling system is possible at the servo controller [JTEMP], when it is switched over into „manual“ mode.
For test purposes it is possible to split the cascade control and specify a setpoint for the
jacket temperature in „auto“ mode via the servo controller [JTEMP].
6.5.4 Special Notes
When the master controller is in „auto“ or „profile“ mode, the servo controller is automatically
switched over into „cascade“ mode. When the master controller is in „off“ mode, the servo controller is also automatically switched to „off“ mode.
The servo controller cannot be operated with time profiles. A setpoint limit for the servo con-
troller can be parametrized via the MAX output limit of the master controller, for instance: – BIOSTAT
®
MD: MAX = 63,3 [%] (corresponding to 95 °C, for prevention of excessive
jacket temperature during the process)
– BIOSTAT
®
ED and UD: MAX = 98,3 [%] (corresponding to 147 °C; for prevention of
overheating during sterilization)
For the default output limits of your fermentor system, see the configuration documentation
delivered extra. As a general guideline, the output limits for autoclaveable fermentors may be preset like the BIOSTAT
®
MD, the limits for insitu-sterilizable fermentors may be preset
like the BIOSTAT
®
ED.
Page 43
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 9
6.6 Stirrer Speed Controller
The speed of the stirrer motor is controlled via an external, extra motor controller. You will adjust all stirrer speed parameters at the DCU3 system. The control function of the DCU3 system works as a setpoint controller and supplies the analog setpoint signal to the motor controller. Furthermore the menu displays the stirrer speed signal delivered from the motor controller.
When the stirrer speed controller is switched to „off“, an additional digital output switches off the motor contactor. If the fermentor is equipped with a pO
2
- controller the stirrer speed controller can be
switched as a servo controller in the pO
2
cascade control loop.
6.6.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.6.2 Special Notes
In „manual“ mode, when entering the MIN/MAX output limits and entering data into OUT,
allways observe the permissible measuring range of the corresponding speed control: – BIOSTAT
®
ED : 0 - 100 % = 0 - 1500 rpm
For further information on the permissible speed range of your fermentor check the preset
configuration of your DCU3 – system or refer to the configuration documentation of your fer­mentor system delivered extra.
Basic stirrer speed and/or maximum permitted speed during operation as a servo controller
in pO
2
cascade control are entered via the MIN/MAX output limits.
Page 44
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 10
6.7 Airflow Controller
The airflow is controlled via an external massflow controller. The airflow control function of the DCU3 ­system works as a setpoint controller. It supplies the analog setpoint signals to the external massflow controller . The menu at the DCU-system is used for entering the setpoints and display of the flowrate signal coming from the massflow controller. For pO
2
control the airflow controller can be switched over
to be servo controller in the pO
2
cascade control loop.
6.7.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.7.2 Special Notes
In „manual“ mode, when entering the MIN/MAX output limits and entering data into OUT,
allways observe the permissible measuring range of the corresponding airflow rate: – BIOSTAT
®
ED : 0 - 100 % = 0 - 20 l / min
For further information on the permissible airflow range of your fermentor check the preset
configuration of your DCU3 – system or refer to the configuration documentation of your fer­mentor system delivered extra.
The basic airflow rate is entered via the MIN/MAX-output limits. If the airflow controller is
used as servo controller in the pO
2
cascade control, you can enter the maximum allowable
airflow rate here.
For standard laboratory scale fermentors the control valve of the external massflow control-
ler will be fully closed when the airflow controller is switched off.
When the pressure setpoint is rather high and the pressure controller is activated at this
time, the air supplied to the fermentor cannot be controlled up to its maximum aeration rate.
Page 45
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 11
6.8 pH - Control Function Operating as PID - Controller
The pH - control function of the DCU system usually works in PID - behavior. The pH - control function triggers the corrective agent pumps (or dosing valves) in split-range mode via two pulsewidth­modulated outputs. This allows a simultaneous control of both the acid and base pump (or valves).
As a special feature the acid and base control signals remain „off“ as long as the deviation
of the actual value lies within the parametrized dead band. This feature prevents unneces­sary dosage of acid or base.
6.8.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.8.2 Operating Information
For entering controller parameters in the parametrization menu see the section „Controller
Parametrization in General“ further above.
6.8.3 Special Notes
The dead ba nd is the percent span of the measuring range; it is symmetrical to the setpoint.
– Example: measuring range: 2 - 12 pH, span: 10 pH, DEADB: 0,1 pH, SETP: 7,0 pH
In this example the controller output is inactive in the range of 6.9 pH to 7.1 pH
When a gas mixing system is connected, the CO
2
valve is controlled via the negative output
signal of the pH controller (0 ... (-100) %)
If you select one of the operation modes „auto“, „profile“ or „manual“, the dosing counters
ACID and BASE will automatically be switched over to the „tlize“-mode.
Page 46
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 12
6.9 pO2-Control Methods
Contrary to the other controls of fermentor systems (temperature, pH etc.) the pO2 - control is adapted to the specific process requirements. For this the DCU3 - system comprises different pO
2
- controllers
that can be implemented according to the selected process. These control strategies can be realized:
pO
2
- cascade control with the following possible servo controllers: – Stirrer – Airflow (Massflow Controller) – Substrate – Pressure – Gasmix (pulsed valves) – Gasflow Ratio (two Massflow-Controllers with O
2
-enrichment)
The controller configuration can be especially matched to the fermentor system and process. Several of the above controllers can be implemented. Besides the controllers mentioned above, customized DCU configurations with other pO
2
- control strategies can be realized.
6.10 pO2 - Cascade Controller with 3 Servo Controllers
In the cascade system the pO2-controller is the master controller. Its output directly triggers the set­point input of the servo controller.
Optionally a sequential mode can be selected for the pO
2
-cascade control. Then the pO2 - controller
triggers two or three servo controllers sequentially, in order of their priority. In the pO
2
- controller you
can define a specific „MIN/MAX“ range for the setpoint signal transmitted to each servo controller:
When the pO
2
control is switched on, at first the output of the pO2 controller operates the setpoint input of the priority 1 - servo controller (CASC1). Optionally defined servo control­lers 2 and 3 get the setpoint, which is defined as „MIN“ in the pO
2
controller.
At increase of O
2
-consumption, when the setpoint output of the 1st servo controller reaches
its „MAX“ limit, the output of the pO
2
controller is automatically switched over to the priority 2
- servo controller (CASC2). The user can adjust the delay time for switching-over, default delay time is 5 minutes. Then the outputs are controlled as follows: – servo controller 1: the predefined „MAX“ - output – servo controller 2: controlled output of the pO
2
-controller
– servo controller 3: the predefined „MIN“ - output
After switching over to the 3rd servo controller, the outputs are controlled as follows:
– servo controller 1: the predefined „MAX“ - output – servo controller 2: the predefined „MAX“ - output – servo controller 3: controlled output of the pO
2
-controller
If the O
2
-consumption decreases the controller setting is switched back in reverse order.
Such a control strategy allows to keep the pO
2
value constant over prolonged periods of the process without further manual intervention. The PID parameters for servo controllers of priority 1, 2 and 3 can be adjusted independently of each other in order to allow maximum adaptation to the process­dependent behavior of the control system.
Page 47
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 13
6.10.1 Operating Display pO2 - Cascade Controller
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
Additional functions of this Operating Display are the following:
Tag Entry Displayed value or function, required input
CASCADE Input of servo controller for sequential cascade control
STIRR
stirrer speed controller
AIRFL
airflow controller (if installed)
GASMIX
gasmix controller
OUT [Controller] % Display of the controller output for the active servo controller
during sequential cascade control, with actual controller output
Page 48
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 14
6.10.1.1 Parametrization Display pO2 - Cascade Controller with 3 Servo Controllers
Tag Entry Displayed value or function, required input
DEADB % Input of dead band in relation to measuring range (0 - 100 % sat) Hyst. Time m:s Delay time for cascade switch over in [minutes:seconds] Cascade [Controller] Display of the selected servo controller with its parameters Minimum % Input of minimum output limit, considering the minimum setpoint
for servo controller (0 - 100 % = measuring range process valu e)
Maximum % Input of maximum output limit, i.e. the maximum setpoint for
servo controller (0 - 100 % = measuring range process value)
XP % Input of proportional range for servo controller [PARAM] in rela-
tion to measuring range TI sec Input of reset time ifor servo controller [PARAM] TD sec Input of rate time for servo controller [PARAM]
6.10.1.2 Operation of the Multistep Cascade Control
1. Assign the servo controllers to CASCADE, according to their intended priority.
2. Adjust the permitted minimum and maximum controller setpoint limits for the selected servo controllers via their output limits MIN/MAX in the parametrization display of the pO
2
-
controller.
3. When the pO
2
-controller is switched on, the setpoint currently controlled by the pO2 control-
ler is indicated by „active“ on the display.
4. To achieve a reverse control, you can set the MIN->MAX limits correspondingly.
Page 49
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 15
6.10.1.3 Special Notes When the pO
2
controller is in „auto“ or „profile“ mode, the selected servo controllers are
automatically switched to „cascade“ mode.
When the pO
2
controller is in „off“ mode, the selected servo controllers are switched auto-
matically to „off“.
Switching over from servo controller 1 to servo controller 2, then to servo controller 3 (and
vice versa) only occurs when the output limit concerned is out of its range for the delay time set in „HTIME“. After this delay period the switch-over condition will be checked again and the controllers then be switched over only if the condition is still true. The delay time for switching over can be set in the parametrization display of the pO
2
-controller.
The setpoint limits of servo controllers must be set by the master controller (pO
2
-controller).
A reverse switch-over sequence of one or more servo controllers (addition pumps, etc.) can
be achieved via reverse setting of the setpoint output limits (MIN > MAX).
The working range of the pO
2
- master controller is allways defined by the MIN/MAX-limits of
the corresponding servo controller.
Page 50
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 16
6.11 pO2 - Cascade Controller with 4 Servo Controllers
This cascade controller operates in the same manner as the pO2 cascade controller with 3 servo con­trollers. The only difference is the fact, that 4 of the possible 4 servo controllers can be controlled.
6.11.1 Operating Display pO
2
- Cascade Controller with 4 Servo Controllers
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
Additional functions of this Operating Display are the following:
Tag Entry Displayed value or function, required input
CASCADE Input of servo controller for sequential cascade control
STIRR
stirrer speed controller
AIRFL
Flow controller for air (if installed)
O2FL
Flow controller for O2
PRESS
Pressure controller
OUT [Controller]
%
Display of the controller output for the active servo controller dur­ing sequential cascade control, with actual controller output
Page 51
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 17
6.11.2 Parametrization Display pO2 - Cascade Controller with 4 Servo Controllers
Tag Entry Displayed value or function, required input
DEADB % Input of dead band in relation to measuring range (0 - 100 % sat) Cascade [Controller] Display of the selected servo controller with its parameters Minimum % Input of minimum output limit, considering the minimum setpoint
for servo controller (0 - 100 % = measuring range process valu e)
Maximum % Input of maximum output limit, i.e. the maximum setpoint for servo
controller (0 - 100 % = measuring range process value)
XP % Input of proportional ran ge for servo controller [PARAM] in relation
to measuring range TI sec Input of reset time ifor servo controller [PARAM] TD sec Input of rate time for servo controller [PARAM] Hysteresis m:s Delay time for switching over to cascade Mode off / auto Mode of servo controller after switching off the pO
2
controller
Page 52
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 18
6.12 pO2-Gasmix Controller / O2 – Enrichment
The DCU3 - system can control the pO2 by mixing of two gases, e.g. N2 and O2, via the pO2 Gasmix controller. This controller directly triggers the valves for N
2/O2
in splitrange mode via pwm outputs. The control method is preferably used for gas supplies which are connected to a tubing gas supply system for bubble free gas input into the culture medium.
When the O
2
-enrichment method is applied the controller increases the oxygen portion in the inlet air
by controlling a 3/2-valve of the air supply.
6.12.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.12.2 Special Notes
Dependin g on the process requirements the control can be based on the following gases:
– alternate supply of N
2
and air at low O2 consumption
– alternate supply of air and O
2
at high O2 consumption
– alternate supply of N
2
and O2 at considerably varying O2 consumption
Which ga ses are supplied depend on the gas sources connected to the gas mixing unit. For better control results we recommend to supply a carrier gas (such as air) at a constant
flow, which is then enriched by O
2
and N2. You can connect the carrier gas to the Auxiliary
inlet of the Gasmix unit.
You will have to adjust the max. gasflow rate for the current process via the rotameters in
the O
2
and N2 line of the gasmix unit. For this the O2/N2 valves must be fully open). The
max. flowrates depend on the Gas mixing unit applied and the intended process.
For the O
2
-enrichment method the controller parameter “MIN” must be set to “MIN: 0%” in-
stead of “MIN: -100%”.
Page 53
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 19
6.13 pO2 - Gasflow Ratio Controller
To improve the control quality, the pO2 can also be controlled by means of continuously mixing of two gases, e.g. O
2
and air, via an external massflow controller. The DCU3 - system realizes such a control
strategy by a cascade control with a pO
2
gasflow controller as the master controller and a gasflow ratio
controller as the servo controller. The pO
2
gasflow controller is a PID controller and controls the gas-
flow ratio controller, which is the servo controller. The gasflow ratio controller acts as a ratio controller and can be used in two modes:
Control of the total gas flow (TOTAL): The setpoint for the total flow is manually adjusted.
The pO
2
gasflow controller provides a setpoint for the portion of Gas 1 (RATIO) in relation to
the total flow.
Connection of specific gasses to the massflow controller, depending on the oxygen con-
sumption of the culture and the available gasses. The following gasses can be connected: – Air (GAS 1) and N2 (GAS 2) for low O
2
requirements
– O
2
(GAS 1) and air (GAS 2) for high O2 requirements
– O
2
-(GAS 1) and N2 (GAS 2) for processes with considerably varying O2 requirements
6.13.1 Operating Display Master Controller (pO
2
-Gasflow Controller)
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
Page 54
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 20
6.13.2 Operating Display Servo Controller (Gasflow Ratio Controller)
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General. Above this the display has the following entries and functions for these inputs:
Tag Entry Displayed value or function, required input
PV GAS1 slpm Flowrate Gas1, e.g. O
2
PV GAS2 slpm Flowrate Gas2, e.g. air RATIO % Input of ratio of Gas 1 to total flowrate;
external setpoint in mode „cascade“;
master controller (Contr.) has access to RATIO
TOTAL slpm Input of total flowrate of Gas1 and Gas2 :
external setpoint in mode „cascade“,
master controller (Contr.) has access to TOTAL
MODE Input of controller mode
off
controller off, both outputs 0
auto
manually enter TOTAL and RATIO
manual
inactive
cascade
servo controller in pO
2
gasflow control circuit,
access to RATIO and TOTAL
profile
setpoint for TOTAL or RATIO (depending on CONTROL setting)
CONTROL Enter access of master controller or of profile
TOTAL
total flowrate controlled
RATIO
ratio controlled In mode „auto“ or „casc.“ inputs are impossible.
Page 55
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 21
6.13.3 Parametrization Display Servo Controller (Gasflow ratio controller)
Tag Entry Displayed value or function, required input
TOTAL MIN % Enter minimum output limit for total flow TOTAL MAX % Enter maximum output limit for total flow RATIO MIN % Enter minimum output limit for ratio of gas 1 RATIO MAX % Enter maximum output limit for ratio of gas 1
6.13.4 Operation
For routine adjustment of the pO
2
gasflow controller the operation mode (CONTR: to­tal/ratio) and the setpoint, which is not triggered by the master controller, must be defined only once. Afterwards only setpoint and controller mode of the master controller (pO2GF) need be set.
6.13.5 Special Notes
In the operating modes „auto“ and „profile“ of the master controller the servo controller is
automatically set into „cascade“ - mode. If the master controller is in the operating mode „off“, the servo controller is automatically set into the mode „off“.
In the mode „cascade“ either the total flowrate (TOTAL) or the ratio of gas 1 (RATIO) is con-
trolled by the master controller; the other variable must be manually adjusted.
Timer profiles for the servo controller can either control TOTAL or RATIO; this can be ad-
justed in CONTR of the servo controller.
You can switch over the access of the master controller from TOTAL to RATIO (and vice
versa) only when the servo controller is switched off (Mode „off“).
Page 56
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 22
6.14 Oxygen (O2) – Enrichment Using 2 Massflow Controllers
6.14.1 Functional Principles
The control method „O
2
-Enrichment using 2 massflow controllers“ acts in two phases, „Gasflow Total“
and „Gasflow Ratio“:
1. The pO2 is controlled by air supply until a user definable maximum flowrate is achieved. For this the DCU3 - system controls one massflow controller, which used for air supply. This phase is specified as „Gasflow Total“ in the display of the controller.
2. If the oxygen demand exceeds the supply possible at maximum airflow rate, the input air can be enriched by oxygen. While the total flowrate is kept constant at its maximum the DCU3 - system reduces the flow rate of the massflow controller for air supply and triggers a second massflow controller to add oxygen to the air inlet.
The increase of oxygen input is propertional to the decrease of air input. This phase is
specified as „Gasflow Ratio“ in the DCU - display of the controller.
The „O
2
-Enrichment“ control method can be extended by an additional control of other process pa-
rameters, such as the stirring speed.
6.14.2 Realization and Operation with the DCU3 - System
The “O
2
-Enrichment” control method is implemented as a „cascade control“. The pO2-controller acts as the master controller. You will enter all settings, such as the controller mode, setpoint or intended servo controller, in the menu of the pO
2
-controller.
See the description of the „pO
2
cascade controller“ for details on how to proceed.
The DCU3 - system automatically activates the „Gasflow-Total / Gasflow-Ratio“ - controller to operate as servo controller.
Page 57
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 23
6.14.3 Operating Display O2-Enrichment Controller
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
Additional functions of this Operating Display are the following:
Tag Entry Displayed value or function, required input
CASCADE Input of servo controller for sequential cascade control
GFTOT
servo controller 1 for gasflow control
GARAT
servo controller 2 for gasflow ratio control
None
no servo controllers assigned
Page 58
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 24
6.15 Foam Controller
When foam comes into contact with the antifoam sensor, the foam measurement amplifier generates a limit value signal for the antifoam controller. This signal is active as long as foam has contact with the probe. The sensitivity of the foam detection can be adjusted via the display of the foam controller.
The output of the antifoam control function in the DCU system triggers a pump or a dosing valve to supply antifoam agent to the culture. The pump or dosing valve is switched on and off periodically. The dosing times and cycle time for intermittent operation can be entered into the control display.
6.15.1 Operating Display
Tag Entry Displayed value or function, required input
FOAM on / off Display of foam signal („on“ = foam) SENSI low / high Input of sensitivity of foam signal amplifier MODE Input of operating mode of controller
off
controller off, OUT = off
auto
controller on
manual
manual access to controller output OUT on / off Controller output („on“ = active); data entry only in „manual“ mode CYCLE m:s Input of cycle time in [minutes:seconds] PULSE m:s Input of running time of pump [minutes:seconds] DI ALARM Enabling the display of digital input alarms
Page 59
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 25
6.15.2 Operation
Leakage currencies or deposits on the sensor can cause erroneous activation of the foam
control, resulting in an excess dosage of antifoam agent. In order to avoid such an errone­ous activation the sensitivity of the foam sensor should be set as low as possible.
1. Reduce the sensitivity down from position „high“ until only foam is just detected.
2. Adjust the cycle time (CYCLE) and the dosing time according to your process requirements. In mode „manual“ the p ump can be switched „off“ or „on“ for continuous operation.
6.15.3 Special Notes
The foam amplifier has a response delay (5 sec) in order to avoid wrong dosage due to
splashes of liquid, etc.
If either the mode „auto“ or „manual“ is selected, the dosing counter AFOAM is automatically
activated.
Page 60
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 26
6.16 Dosing Pump Controller
The implemented dosing pump controller can control an external, continuous pump for the addition of nutrient solution. The dosing pump control function provides a setpoint control of the external pump (remote control) and transmits the analog setpoint signals to the pump. It also displays the measured signal for the flowrate if the pump is equipped with an output for measured signal.
Above this the extended functions of the DCU3 - system allow the specification of time profiles for set­points as well as recipe-dependent setpoints for the external pump.
6.16.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.16.2 Special Notes
External pumps, like a FE 211, 411, etc., can be connected via corresponding signal cables. Commercially available laboratory pumps can be connected when they have a remote set-
point input for signals of 0 ... 0 V, 0 ... 20 mA.
Page 61
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 27
6.17 Level Controller
6.17.1 Control Principles
The level control function of the DCU3 - system allows for a simple level control by means of height­adjustable conductive level probes. The probe will be connected to the „Level“ measurement amplifier of the DCU3 system whose the limit output signal acts as input on the level controller. The limit value signal is active as long as the probe is in contact with liquid.
The sensitivity of the amplifier can be adjusted to different conductivities of the culture liquid to avoid unintended controller activities due to splashing, for instance. An adjustable delay time for controlled pumps assures stable operation of the level controller.
The level control function of the DCU3 - system offers several control strategies that can be selected the operator according to the requirements of the process.
6.17.1.1 Single Sensor Control with Harvest Pump Control
This control method enables a feed pump to continuously supply a substrate to the vessel. When the culture medium exceeds the max. filling volume (as adjusted with the insertion height of the sensor), the sensor has contact with the medium and the limit signal is released. The level control switches the harvest pump to either „on“ or „off“ state, i.e. it activates the pump as long as the limit signal is „on“.
6.17.1.2 Single Sensor Control with Feed Pump Control
When this control method is applied, a harvest pump can be run continuously at a fixed pump rate, removing medium from the vessel. Hence the medium level in the vessel decreases. When the sensor has no longer contact with the medium, the level control function activates a feed pump to supply fresh medium into the vessel. The feed pump is operated in „on/off“ mode.
Page 62
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 28
6.17.2 Operating Display
Tag Entry Displayed value or function, required input
LEVHI on / off Signal of level sensor (on = level exceeds the limit) MODE Input of controller mode
off
controller off, harvest and feed pump off
auto
controller on
manual
manual access to controller output
PUMP Feed /
Harvest
Selection of pump function
Either a pump for dosing or a harvest pump can be controlled OUT on /off Output state (on=active), inputs only in mode „manual“ PULSE m:s Input of reset time for the pump in [minutes:seconds] SENSI low / high Setting of the sensitivity for the amplifier DI ALARM Enabling the display of digital input alarms
6.17.3 Operation
1. Adjust the sensitivity of level sensor as low as possible to avoid unintended activation of pump by foam. In addition the level amplifier acts using a delay time (5 sec.) to avoid unin­tended activation of the level control due to splashing medium.
2. Adjust the reset time of the pump (PULSE) so that the number of pump cycles is minimized.
6.17.4 Special Notes
The dosing counter LEVEL will automatically be activated, whenever the modes „auto“ and
„manual“ are selected.
Page 63
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 29
6.18 Weight Controller
Fermentation processes often require to keep the culture volume precisely constant, i.e. during con­tinuous or „repeated fed batch“ operation. Compared to level control the weight control is another suit­able, more precise method to control the vessel contents.
The contents of the culture vessel will be measured using balance platforms or load cells. The weight controller in the DCU system is a PID controller and controls a harvest pump or a harvest valve via pulse-width modulated outputs.
6.18.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.18.2 Special Notes
To avoid unintended controller actions during manipulations at the culture vessel the weight
control mode should be set to „hold“ in the calibration routine for the balance system. This will disable the weight control temporarily.
Since the level and the weight controller trigger the same control signal output, only one of
these functions can be implemented in one DCU system.
The dosing counters HARV and FEEDP will automatically be activated, whenever one of the
modes „auto“, „profile“ or „manual“ is selected.
Page 64
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 30
6.19 Pressure Controller
For control of the pressure inside a culture vessel the DCU system comprises a PID controller with continuous output. The corresponding analogue output signal 0...20 mA of the DCU3 - system controls a continuous control valve in the exhaust line via an I/P converter.
The pressure controller can operate as a servo controller in the pO
2
cascade control circuit.
6.19.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.19.2 Special Notes
When the pressure controller is switched off, the control valve fully opens. Depending on the flow rate adjusted at the fermentor, the pressure controller can only work
at pressure setpoints exceeding approx. 200 ... 400 mbar.
Page 65
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 31
6.20 Gravimetric Dosing Controller
The „Flow controller“ is a precise gravimetric dosing controller. It will be used together with a balance system. Balance systems suited and tested for the DCU - system are the MC1-type balance by Sarto­rius, Fed. Rep. of Germany, or Mettler Balances type AM/PM/SM, offering a RS232-type interface.
The storage vessel will be placed on a balance system, which is connected to the DCU - system via the serial interface. The flow controller controls a peristaltic pump (any commercially available pump for continuous control) to supply substrate from the storage vessel into the culture vessel. The DCU ­system calculates the delivered volume considering the weight change. It can ensure a constant flow by continuous control of the external pump.
This control function directly acts upon the input weight signal delivered from the balance system. Therefore the gravimetric dosing controller provides a precise dosing for days and week s.
6.20.1 Operating Display
For a description of the tags, the physical units or entries, the displayed value or function
and of the required inputs see the table in section 6.3, Controller Operation in General.
6.20.2 Operating Information
To operate th e substrate supply with the flow controller proceed as follows:
1. Fill storage vessel, sterilize, if necessary, and place onto balance platform
2. Adjust the zero point of the balance
3. Adjust the setpoint for the flow controller in the DCU - system
4. Switch operating mode of the flow controller to „auto“ Check display of the weight, a negative value indicates the delivered volume (weight)
Page 66
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 32
6.20.3 Special Notes
When errors occur during communication with the balance system (SIO01 I/O error....) the
controller output will remain at its last value. After elimination of the error the DCU3 - system automatically requests the balance to continue with the communication.
Depending on the configuration of the system the calculation of the controller can take up to
20 s. Thus any inputs into the menu will also be processed within such a cycle.
The measurement ranges for the flow (entry „FLOW“) and for the weight measured by the
Sartorius balance system (entry „FWEIGH“) must be identical.
The delivery of the applied dosing pump considerably interferes with the controlled system.
Therefore the delivery of the pump must be adapted to the required flow.
For precise dosing the working range of the controller output „OUT“ must be within
15 ... 90 %. For this the delivery of the pump can be preselected by use of a tubing of the appropriate size or a pump head with an appropriate membrane, which can deliver within the intended delivery range.
6.20.4 Precision of Dosing Control
The precision of the dosing control depends on the following factors :
Resolution and precision of the balance system Delivery of the pump Flow rates Environmental con ditions (stable and interference-free support of the balance system
The accuracy given below for the FLOW-controller has been evaluated using a balance system type MC1 - LC 6200, by Sartorius, Fed. Rep. of Germany and a dosing pump FE 211 by Sartorius BBI Sys­tems GmbH. The working range of the balance system was 0 ... 6,200 g at a resolution of 0.1 g. The pump was equipped with pump head type „F: 0.1“ and „F: 1“.
Sartorius- balance type, resolution: [g]
FE211 with pump head [factor F]
flow [g/h]
accurace [g/h], [g/day], [g/week]
LC/IC, 0,1 g 0.1 50 .. 500 +/-1g, +/-2g, +/-5g
1 500 .. 5000 +/-2g, +/-3g, +/-5g
LC/IC, 1 g 0.1 50 .. 500 +/-3g, +/-5g, +/-10g
1 500 .. 5000 +/-5g, +/-8g, +/-10g
Page 67
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 33
6.21 Setpoint Profiles
Most of the configured control loops can be operated with time-based setpoint profiles („control loop profiles“). A profile will be entered into a table via the operator terminal. A profile can include step changes and ramp changes with a maximum of 16 segments. Setpoint profiles can be started and stopped at any time. At an active profile the current running time is displayed.
6.21.1 Operating Display (Example for Temperature Control Profile)
Tag Entry Displayed value or function, required input
MODE Input of status of the profile
stop
profile inactive after loading of recipe
start
setpoint profile automatically started and running
ELAPT h:m Display of elapsed time since start of profile in [hours:minutes];
graphical display of the elapsed time in the profile display TIME h:m Input of time of the break point of the setpoint profile SETP [PV] Display of active controller setpoint in the physical unit of the
process value (degC for temperature in this case) TIME h:m Display of actual controller output SETPOINT [PV] Input of setpoint for profile break point in the physical unit of
the process value (degC for temperature in this case)
Page 68
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 34
6.21.2 Operation
We recommend to prepare a scheme of the intended profile with all break points and the
corresponding setpoints (see example below). The breakpoints of the scheme will give you the time settings and setpoints, which must be programmed.
A profile must have at least one breakpoint with a time different from zero. Otherwise the
profile cannot be started.
6.21.3 Special Notes
When the setpoint profile is started the controller mode in the main menu CONTROL
LOOPS is automatically switched over to „profile“.
If the time for the first breakpoint is not set to „00:00 h:m“ the system uses the current set-
point for the start of a profile.
In a program for a setpoint jump two setpoints can have the same time. When a profile is defined and started for pO
2
-control, correlating active profiles for „STIRR“, „AIR“ or „PRESS“ will be stopped automatically. The controller will be switched over to „cas­cade“-mode.
Depending on the selected control principle (CONTR) the setpoint profile of the Gasflow-
Ratio - controller is to be set for the total flowrate (TOTAL) or to the ratio of Gas 1 (RATIO).
Page 69
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 35
6.22 Timers
The timers implemented in the DCU3 - system can switch off and on discontinuous actuators and pumps, for instance, via digital outputs. For this the timers can be operated in these operating modes:
In cycle mode the output is switched on and off periodically. Both „on“-time and „total cycle
time“ will be predefined for this.
In profile mode the output is switched on and off at times, which are entered into a table via
the operator terminal. Up to 16 different switching times can be processed.
The timers can be started and stopped at any time. For running timers the display shows the passed time („ELAPT“).
6.22.1 Operator Display
Tag Entry Displayed value or function, required input
MODE Display of / Enter the timer status
stop
timer inactive
start
timer not started
profile
timer runs in “profile” mode
cycle
timer runs in “cycle” mode
elaps
profile finished, the digital output has the latest setting
ELAPT h:m Display of elapsed time since start of timer];
graphical display of the elapsed time in the profile display CYCLE m:s Input of cycle time in [minutes:seconds] PULSE m:s Input of pulse time in [minutes:seconds] TIME h:m Input of time for the switch point of the timer profile SETPOINT on / off Input of switching condition for switch point timer profile
Page 70
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 36
6.22.2 Operation
The timers can run in profile mode or in cyclical mode. See below some examples for such modes.
Fig. 7-2 Example for timer operation in cyclical mode
Fig. 7-3 Example for timer operation in profile mode
6.22.3 Special Notes
If the timer runs in the „MODE: profile“ the program must start at the time [00:00 h:m]. In the profile mode the last condition programmed for the timer output is stored until the
timer is stopped.
A timer in the „Mode: profile“ must have at least one breakpoint of a time different from zero.
Otherwise it cannot be started.
A timer in „Mode: cycle“ must have a time for „CYCLE“ and „PULSE“. Otherwise it cannot be
started.
Page 71
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 37
6.23 Alarm Limits of Process Values
The DCU3 - system includes alarm handling routines which monitor all process values (measured val­ues and derived process values), whether they are within their alarm limits. For the monitored process values the high/low alarm limits are entered via the operator terminal at first. Then the alarm handling routines can be enabled or disabled for each process value which should be monitored.
The High/Low alarm limits must be within the measuring ranges. If the alarm limits are exceeded, a warning message is displayed and an acoustic signal is activated. The alarm can be confirmed via the ACK key, and the next alarm is displayed. An alarm buffer stores up to 20 alarm messages not being confirmed. The latest alarm is displayed on the alarm line on the screen.
Current process value alarms are shown in the related process display by white letters on red back­round. Depending on the process value alarm, certain process outputs can be set to their „shut down“ state via locking functions. Such locking functions will be implemented in customized configurations of the DCU3 - system.
6.23.1 Operating Display
Tag Entry Displayed value or function, required input
LOW LIMIT Input of low limit alarm (LOW) in terms of its physical unit HIGH LIMIT Input of high limit alarm (HIGH) in terms of its physical unit ALARM MODE Input of status for alarm monitoring
disab
Alarm monitoring for high/low alarm locked
enabl
Alarm monitoring for high/low alarm released
Page 72
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 38
6.23.2 Special Notes
Alarms will be displayed and can be answered as follows :
1. When an alarm occurs for the first time, an alarm message is generated and displayed. Press the „ACK"nowledge key to confirm. This also deletes this alarm message.
2. The display of the process value changes its colour to red.
The DCU-System displays an alarm as long as the process value exceeds the alarm limits. If the same process value alarm occurs several times, all alarms are stored and must be
confirmed extra.
At more than 20 unconfirmed alarms in the alarm buffer, the system generates the message
„too many alarms“ and does not store additional alarms.
Page 73
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 39
6.24 Alarms of Digital Inputs
The DCU3 - system can also monitor the status of digital inputs for alarm conditions. This includes monitoring of limiters, motor protectors and circuit breakers. The digital alarms must be enabled via the operator terminal. In case of an alarm a warning message appears in the alarm line showing the time when it occurred. Above this an audible signal is generated. Current alarms are shown in the dis­play for „Digital inputs“ within the „Process Display Menu“ and can be confirmed.
Digital alarms can swich over certain process outputs to a „shut down“ state via integrated locking functions. Such locking functions will be implemented in customized DCU configurations.
6.24.1 Operating Display
Tag Entry Displayed value or function, required input
ALARM MODE Input for selection of the alarm monitoring
disab
Alarm monitoring of digital alarm disabled
enabl
Alarm monitoring of digital alarm enabled
6.24.2 Special Notes
1. An active alarm is indicated in two different ways: – When the alarm occurs for the first time an alarm message is generated and indicated in
the alarm line of the display. Press „ACK"nowledge to confirm and delete this message.
– The display of the process value change s to red. Thi s state is a ctive in the display as long
as the digital input is in the alarm state.
1. If the same digital alarm occurs several time all alarms are stored in the alarm buffer. Each alarm must be confirmed extra.
2. If more than 20 unconfirmed alarms are transferred to the alarm buffer, the system gener­ates the message „too many alarms“ and does not store additional alarm messages.
Page 74
Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 40
Page 75
Operators Handbook DCU3 – System
7., Main function „Batch Control“
BAEDCU3 - Rev. 4.6 - 0504 7 - 1
7 MAIN FUNCTION „BATCH CONTROL“
7.1 General
The main function „Batch control“ is used for supervisory functions for process control and running of automatic processes (such as a „sterilization program“, for instance). You can select the following functions via a corresponding selection menu:
Selection Menu „Batch Control“:
7.2 Sequences
The DCU3 - system can store up to 24 sequences which can be configured according to the type and specifications of the fermentor system. The programs can consider, for instance, empty vessel sterili­zation, medium sterilization, sterilization of transfer installations, intermediate sterilization for air inlet filter and for exhaust filter, etc. The structure of sterilization programs, such as step change conditions for single steps and process outputs during the steps, can be adap ted to different requirements.
Detailed descriptions of sequences, such as the sterilization of the culture vessel or of pe-
ripheral equipment can either be supplied in the supplement of this manual, in the configura­tion documentation of the delivered DCU3 - system or in other documentation delivered ex­tra with the fermentor system.
Note: For fermentor systems w ith autoclaveable culture vessels and peripherals (such as
the BIOSTAT® B-DCU, BIOSTAT® MD, BIOSTAT® BF or BIOSTAT® Q, for instance) no sterilization function is available.
Page 76
Operators Handbook DCU3 – System
7., Main function „Batch Control“
BAEDCU3 - Rev. 4.6 - 0504 7 - 2
7.2.1 Sterilization Programs
The sterilization programs in general are phase controls. They have automatic access to digital out­puts for valve control (max. 64 outputs), to controller setpoints and modes and to alarm parameters for limit monitoring. The programs can be automatic sequential controls or single step controls.
7.2.1.1 Automatic Sequential Controls
Automatic sequential controls are used for the sterilization of the fermentor vessel with peripheral as­semblies connected, for instance. The complete sterilization is a time and event driven sequential con­trol and the individual phases are run automatically.
The required parameters, such as sterilization temperature, sterilization time and the fer-
mentation temperature after the sterilization, must be entered in the operating display.
The sterilization can also be started (and be interrupted, if necessary) via the operator ter-
minal. The display shows the running sterilization phase and the elapsed sterilization time.
If additional manual operations are necessary during the sterilization, such as opening or
closing manual valves, a corresponding message appears on the display. The automatic sterilization will only continue after the required step is done and you have confirmed the message via 'ACK'nowledge.
7.2.1.2 Single-step Controls
Single-step controls are necessary for the intermediate sterilization of the air inlet or exhaust filter, for instance. You will manually activate the steps necessary for the sterilization process in the mode „step“. The sterilization program determines the sequence of the sterilization.
Within a single-step control certain steps can be run automatically using timers, such as the
sterilization time, for instance, which must be entered in a corresponding operating display.
You will start the single-step control via the operator terminal and continue the phases via
„step“. If necessary you can interrupt the sequence. The display shows the active step and the elapsed sterilization time (if applicable).
7.2.1.3 Status Displays during Phase Controls For both types of phase controls the process status is displayed in the head line of the op-
erating terminal during the running process, such as „STATE: sequence“, for instance.
After the last step of the sequence (i.e. sterilization) is accomplished the operator terminal
displays the message „sterilization finished“.
Page 77
Operators Handbook DCU3 – System
7., Main function „Batch Control“
BAEDCU3 - Rev. 4.6 - 0504 7 - 3
7.2.2 Operating Display „Automatic Sequential Control“
Note: This example is only valid for BIOSTAT
®
ED:
Tag Entry Displayed value or function, required input
STATE Enter the sterilization program mode „start“ or „stop“
start
start sterilization
stop
stop sterilization
step
not allowed (only valid for single step controls)
Display of the status of the sterilization program:
active
sterilization program running
lock
start is impossible since another sequence or recipe is active
inactive
sterilization program inactive
ACK Request for „Acknowledgement-display“, see „alarm messages“ in
the supplement
PHASE Display of the sterilization step
----
sterilization program inactive
HEAT
heating to sterilization temperature
STERI
control of sterilization temperature
COOL1
cooling to 80 degC
COOL2
cooling from 80 degC to process temperature
READY
process temperature reached (message: „sterilization finished“) TEMP Display of the current fermentor temperature ELAPS Display of elapsed sterilization time in the sterilization phase STEMP Input of sterilization temperature FTEMP Input of fermentor (process) temperature STIME Input of sterilization time
Page 78
Operators Handbook DCU3 – System
7., Main function „Batch Control“
BAEDCU3 - Rev. 4.6 - 0504 7 - 4
7.2.3 Operation Automatic Sterilization Control
1. Carry out the operations at the fermentor required for preparing the sterilization sequence, see the Operating Manual of the fermentor for details. If necessary, adjust the sterilization parameters (sterilization temperature, time etc.)
2. Start the sterilization program with [STATE: start]. When requested by the system, carry out a necessary manual step according to instructions on the display and confirm the message.
3. Confirm the message „Sterilization finished“ with the [ACK] key after completion of the automatic sterilization process.
If necessary, you can stop the automatic sterilization with [STATE: stop]. This automatically
initiates the cooling phase.
7.2.4 Special Notes
During the running sterilization program the top line displays the process status
„STATE:active“.
If the process time has not yet been activated, it will automatically start when the sterilization
program is started.
Running sterilization programs can be stopped at any time. In this case the cooling phase is
automatically started to cool down the fermentor to ambient or the previously adjusted proc­ess temperature as soon as possible.
If required an interrupted sterilization program can be restarted before the fermentor
reaches the preset process temperature.
In some fermentors a separate temperature controller is configured for the control of the
sterilization temperature.
If the display shows „STATE: lock“, the sequence is locked and cannot be started. Another
program (sequence, recipe or batch control) is active at this time. The lock will be released and the program starts, when the running program is finished. You will find the specific in­formation about the programs, which will lock the sequence due to equal or superior priority, in the configuration documentation.
Page 79
Operators Handbook DCU3 – System
7., Main function „Batch Control“
BAEDCU3 - Rev. 4.6 - 0504 7 - 5
7.3 Process Time
A „process time“ can be displayed in the headline of the operating display in addition to the continuous display of the actual date and time. For this the DCU3 - system includes an extra process time clock.
It is possible to start the process time clock at zero or at a predefined time. If no process time is active the clock starts automatically with the sterilization program or when a recipe is loaded for the first time.
7.3.1 Operating Display
Tag Entry Displayed value or function, required input
PTIME Input and start of the process time
0000:00
start from zero
hhhh:mm
start from preset time in [hours:minutes]
7.3.2 Special Notes
The process time can be set via the stop watch in the 1
st
line at any time.
The display range of the process time is 9,999 hours and 59 minutes.
Page 80
Operators Handbook DCU3 – System
7., Main function „Batch Control“
BAEDCU3 - Rev. 4.6 - 0504 7 - 6
Page 81
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 1
8 MAIN FUNCTION „RECIPES“
8.1 Overview
All process parameters that you usually enter or alter manually during the fermentation process, can be predefined and stored in recipes. Hence they can be activated as complete parameter sets during the running process. The definition of complete sets of process parameters in recipes simplifies the operation of the DCU3 - system and allows reproducible processes.
You can create up to four different recipes from the following sets of parameters :
Setpoints and operating modes of controllers Setpoint profiles for controllers Timer parameters Alarm limits and enabling of alarm handling routines for process values and digital alarms
Recipes can be entered via the operator terminal during a running process. However, the settings of recipes have no effect on active process parameters. For processing of a predefined recipe the recipe parameters must be loaded and hence overwrite the current process parameters.
8.2 Recipe Selection
You can chose between 4 different recipes for the input of process parameters via a selection menu:
Page 82
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 2
After selecting a recipe you can select the recipe parameter sets via the following menu:
Page 83
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 3
8.3 Controller Parameters in Recipes
For all configured controllers you can specify and store the controller parameters „setpoints“, „control­ler modes“ or „controller outputs“ in recipes. Inputs will be made similar to those in the main function „Control Loops“. If a controller should not be controlled via the recipe, you can switch over the mode for this controller to „no change“ during input of the recipe parameters.
8.3.1 Operating Display (Example for Temperature Controller)
Tag Entry Displayed value or function, required input
MODE
Additional input of controller mode for recipe
-----
(no change) recipe does not effect the controller
8.3.2 Special Notes
See the chap ter „Main Function Control Loops“ for a detailed description of the controllers. Controllers that should not be changed by the recipe, must be set into „no change“ mode.
Then the current parameters will not be overwritten when a recipe is started.
Page 84
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 4
8.4 Setpoint Profiles
In recipes you can specify setpoint profiles for all configured controllers. Inputs will be made similar to those within the main function „Parameters“. When a recipe is loaded all profiles can be started simul­taneously, if they all are set to „start“ in the recipe.
8.4.1 Operating Display (Example for Temperature Controller)
Tag Entry Displayed value or function, required input
MODE Additional input of state of profile for recipe
----- Setpoint profile will not be effected by the recipe
8.4.2 Special Notes
See also deta iled descriptions of profiles in chapter 6.21, Setpoint Profiles If a profile should be processed immediately after the recipe is loaded, set the MODE to
„start“ during input of the recipe.
If a recipe sh ould not effect a profile, the MODE „-----“ (no ch ange) must be entered. The breakpoint of a profile must have at least one time setting different from zero. Otherwise
the profile cannot be started.
Page 85
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 5
8.5 Timers in Recipes
You can also activate all configured timers via the recipe. All timers can be started simultaneously while a recipe is loaded. For this the timers must be set to „start“ in the recipe. If a timer should not be started when the recipe is loaded, they must be set to „no change“ in the recipe.
8.5.1 Operating Display
Tag Entry Displayed value or function, required input
MODE Additional state of timer for recipe
----- (no change): recipe does not effect the timer
8.5.2 Special Notes
Detailed information abo ut the timers is included in section 6.22, Timers Timers that should not be affected by the recipes, must be set to „no change“ in the recipe.
Then the current parameters are not overwritten after the recipe is loaded.
If the timers should be processed immediately after the recipe is loaded, they must be set to
„start“ in the recipe.
In the „Mode: profile“ the breakpoint of a timer profile must have at least one time different
from zero.
In „Mode: cycle“ a timer must have a time for „CYCLE“ and „PULSE“. Otherwise the profile
cannot be started.
Page 86
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 6
8.6 Process Value Alarms in Recipes
You can specify the upper and lower alarm limits and the alarm status for each process variable in a recipe. All inputs must be made as described in chapter 6.23, Alarm Limits of Process Values.
If the recipes should not influence the alarm monitoring for certain process variables, the alarm state must be set to „no change“ while entering the corresponding recipe.
8.6.1 Operating Display
Tag Entry Displayed value or function, required input
ALARM MODE Additional input of state for alarm monitoring in the recipe
----- (no change): recipe does not effect the alarm limit monitoring
8.6.2 Special Notes
Process variables which should not be affected by the recipe, must be set to the state „no
change“ when entering the recipe.
Page 87
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 7
8.7 Digital Input Alarms
An alarm monitoring for digital inputs („Digital Input Alarms“) can also be specified in a recipe. For this all inputs must be made as described in chapter 6.24.
If the alarm monitoring of a digital input should not be influenced by a recipe, the alarm state of this digital input must be set to „no change“ when entering the recipe.
8.7.1 Operating Display
Tag Entry Displayed value or function, required input
ALARM MODE Additional input of state for alarm monitoring in the recipe
----- (no change): recipe does not effect the alarm monitoring
8.7.2 Special Notes
A digital input, that should not be switched on for alarm monitoring by the recipe, must be
set to „no change“ in the recipe.
Page 88
Operators Handbook DCU3 – System
8., Main Function „Recipes“
BAEDCU3 - Rev. 4.6 - 0504 8 - 8
Page 89
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 1
9 MAIN FUNCTION „MAINTENANCE“
9.1 Overview
The DCU3 - system offers several functions for system maintenance and trouble shooting in the main function „Maintenance“. The operator can select the functions listed below via a selection menu:
9.1.1 Selection Menu „Maintenance“
Note: Most of the functions for system maintenance and trouble shooting are password - pro-
tected to prevent unauthorized access.
Access to mainten ance functions should be restricted to administrative personell
and qualified users. Changes of these functions can change the basic configuration of the DCU3 - system. Unauthorized changes of parameters and settings can cause unpredictable malfunctions of the unit and of the controlled fermentor system.
Page 90
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 2
9.2 Manual Operation in General
During start-up of the DCU3 - system together with the fermentor and for trouble shooting all analog and digital process inputs and outputs and the DCU - internal in- and outputs can be switched over to manual operation. This disconnects the outputs from the DCU - internal functions and allows for direct access to the outputs via the corresponding operating display.
For inputs you can disconnect the external signals and manually enter process input signals into their corresponding menu to simulate a process. Settings entered in manual mode have top priority, they will override all other settings and functions of inputs and outputs of the DCU - system.
9.3 Manual Operation for Digital Inputs
For manual operation you will disconnect the intended digital input from the external unit,
such as a threshold controller, and manually enter the state of the digital input, „on“ or „off“.
9.3.1 Operating Display
Column Entry Meaning
I/O Addr., Tag Name
DIM1 TEMPC,
DIM2 LEVHI, etc.
Display of digital input, setting of operating “MODE”
and the state of the “value”-entry MODE auto normal operation, external input is active manual manual operation, setting of digital input has priority VALUE off digital input switched off on digital input switched on
Page 91
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 3
9.3.2 Abbreviations (TAGs) for Digital Process Inputs
For a complete listing of the tags for digital inputs please refer to the supplement. Reserve
inputs are defined by their physical channel assignment: – DIMnn (Digital Input Measurements): internal digital inputs of measurement amplifiers, – DIPnn (Digital Input Process): digital input from process
9.3.3 Special Notes
The following signal levels correspond with the possible states: state : signal level
off : 0 V on : 5 V for internal DCU inputs, 24 V for process inputs
After operation in „manual“ mode all digital inputs must be reset to „auto“. Other-
wise the functions of the DCU3 - system will be restricted.
Page 92
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 4
9.4 Manual Operation for Digital Outputs
For manual operation you can disconnect a digital output from its internal DCU - function
and adjust manually. You can switch static outputs, such as valve controllers, „on“ and „off“. For pulse-width modulated outputs you can enter the pulse control factor in terms of [%].
Internally several functions are able to trigger one digital output. The active function will be
displayed in the „Mode:...“-section. The following order of priority is valid for functions being active at the same time (i.e. for controller outputs controlled by the sterilization sequence) :
highest priority - shut down
- manual operation
- locking
- sterilization
- pump calibration
- controllers, timers, sensors, balance systems
lowest priority - operating state (OPS)
9.4.1 Operating Display
Page 93
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 5
Column Entry Meaning
I/O Addr., Tag Name DOP01 HEAT,
DOP02 FEEDP, etc.
Tag of digital output; setting of operating
“MODE” and status of “value” entry Mode auto normal operation, DCU triggers the output lock (display only) output is switched via locking
function, such as alarm locking shut (display only) output switched to safe state
via shut-down function manual manual operation, manual setting of digital
output sequ (display only) output switched by sequence,
such as sterilization program pump output triggered by pump calibration function host output triggered by host computer opst output switched to rest state;
no internal function triggers output Value off digital output switched off on digital output switched on nn% pulse control factorfor pwm digital outputs, in
the range of 0 ... 100%
9.4.2 Abbreviations (TAGs) for Digital Outputs
For a complete listing of the abbreviations (TAGs) for digital outputs refer to the supplement. Unas signed outputs are defined by the name of their physical channel:
- DOM : Digital Output Measurements: internal DCU digital outputs of measurement amplifiers
- DOP : Digital Output Process
- DO : Digital Outputs
9.4.3 Special Notes
The status can have the following signal levels
- off : 0 V
- on : 5 V for internal DCU outputs (DOM) 24 V for process outputs (DOP, DO)
For pulse-width modulated (pwm) outputs the relative pulse control factor is displayed or
preset. The cycle time is determined by the fermentor specific configuration.
Example: If the cycle time is set to 10 sec. and the pwm output is 40%, the digital output will be
„on“ for 4 sec. and „off“ for 6 sec.
After operation in „manual“ mode all digital inputs must be reset to „auto“. Other-
wise the functions of the DCU3 - system will be restricted.
Page 94
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 6
9.5 Manual Operation of Analog Inputs
In the manual mode you can disconnect an analog input, e.g. a measurement amplifier signal, from the external equipment and simulate the input by entering a relative signal level (0 ... 100%).
9.5.1 Operating Display
Column Entry Meaning
I/O Addr., Tag Name
AI 01 pHR,
AI 02 TEMP, etc.
Display of tag of analog input, manual setting of operating mode and input signal
MODE auto normal operation, external input triggers function of the
DCU3 - system manual manual operation, input of input signal in [%] has priority VALUE 0 ... 100% represents input signal 0 ... 10 V or 0/4 ... 20 mA
9.5.2 Abbreviations (Tags) for Analog Inputs
For a complete listing of the TAGs for analog inputs please refer to the supplement. Unas-
signed inputs use the name of their physical channel as TAG: – AIMnn (Analog Input Measurements): internal analog inputs of measurement amplifiers – AIPnn (Analog Input Process): external analog outputs from p ro ce ss
Page 95
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 7
9.5.3 Special Notes
The physical signal level for internal analog inputs (AIM) is always 0 ... 10 V (= 0 ... 100%). For external analog inputs (AIP) the physical signal level can configured within :
– 0 ... 10 V (0 ... 100%) – 0 ... 20 mA (0 ... 100%) – 4 ... 20 mA (0 ... 100%)
In the manual operating mode only the relative signal level (0 ... 100 %) for the analog in-
puts is displayed or must be entered. The assignment to the physical value can be derived from the measurement range of the corresponding process value.
After operation in „manual“ mode all analog inputs must be reset to „auto“. Other-
wise the functions of the DCU3 - system will be restricted.
Page 96
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 8
9.6 Manual Operation for Analog Outputs
You can disconnect all analog outputs from the internal DCU functions and adjust the output signal manually within a relative signal level of 0 ... 100 %. Output signals have the following order of priority:
Highest priority - shut down
- manual operation
- locking
Lowest priority - controllers, etc.
9.6.1 Operating Display
Column Entry Meaning
I/O Addr., Tag Name
AO 01 STIRR,
AO 02 AIRFL, etc.
Display of tag of analog output, manual input of operating
mode and output signal
MODE auto normal operation, DCU triggers analog output lock (display only) analog output switched over to safe state
via locking function
shut (display only) analog output switched over to safe state
via shut down function
manual manual operation, manual output has priority VALUE 0 ... 100 % relative setting, corresponds to 0 ... 10 V or 0/4 ... 20 mA
Page 97
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 9
9.6.2 Abbreviations (TAGs) of Analog Outputs
For a complete list of abbreviations (TAGs) of analog outputs refer to the supplement. Unas signed spare outputs have their physical channel assignment as TAG. Example:
– AOPnn (Analog Output Process): analog output for process
9.6.3 Special Notes
The physical signal level of the analog outputs (AOM) can be configured within :
– 0 ... 10 V (0 ... 100 %) – 0 ... 20 mA (0 ... 100 %) – 4 ... 20 mA (0 ... 100 %)
After operation in „manual“ mode all analog oututs must be reset to „auto“. Other-
wise the functions of the DCU3 - system will be restricted.
Page 98
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 10
9.7 Settings of Measurement Ranges
The main function „Maintenance“ allows for changing the thresholds (lower and upper limits) of the measuring ranges for all process values. The settings preconfigured on delivery correspond with the fermentor system to which the DCU3 - system is assigned to.
Only authorized service personnel is allowed to change the settings of this menu.
9.7.1 Operating Display
Tag Entry Displayed value or function, required input
No 1 ... n Logical table number of process value Tag Name [PV] Display of the name of the process value, whose measurement
range thresholds can be changed MINIMUM [PV] Input of lower limit for measuring range MAXIMUM [PV] Input of upper limit for measuring range
Page 99
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 11
9.8 Connection of External Devices
The DCU3 - system has, by default, 2 serial interfaces for the connection of external devices, such as printers, recorders, host computer, etc. The adjustments required for communication will be done in the function „External Systems“ for the following interfaces:
Host computer (HOST) RS 422/485 or Ethernet - interface for communication with a host
computer
Peripheral equipment (PERI) RS 232 - interface for connection of peripheral units, such as pro-
tocol printers or a laboratory balance system
The parameters for connection of a protocol printer to the DCU3 - system can be entered via the func­tion „Documentation/Protocol“. Additional information about connection of external devices and the (necessary) signal assignment of the plugs of the signal cables is available in the „Technical Manual DCU - System“.
9.8.1 Operating Display
Tag Entry Displayed value or function, required input
FUNCTION Display of function PORT Input of the interface used PARAMETER Input of the interface parameters Offline Connection to external device interfered or interrupted Online Connection to external device operating properly
Page 100
Operators Handbook DCU3 – System
9., Main function „Maintenance“
BAEDCU3 - Rev. 4.6 - 0504 9 - 12
9.9 Host Interface
For communication with a host computer via the serial interface RS 422/485 or the Ethernet interface (HOST) the DCU system offers a flexible communication protocol. By means of the RS422 /485 or the Ethernet interface you can establish a bus system for communication with several DCU systems. Each DCU is separately addressed and can be directly triggered by the host computer. The RS422 interface can also be used for peer-to-peer connection. In addition, a host computer can be connected via a se­rial interface RS 232 (available via the peripheral interface PERI).
You must enable the data transmission between DCU and host system via the REMOTE
key of the DCU3 - system, see key pad at the front panel. During remote operation of the DCU system the parameters of the assigned data groups can be changed manually.
9.9.1 Operating Display
Tag Entry Displayed value or function, required input
ADDRESS 1 ... n Input of DCU - adress BAUDRATE baud Input of signal transfer rate DATABIT bit Input of number of data bit STOPBIT bit Input of number of stop bit PARITY even /no Input of type of parity check BREAK Input of use of BREAK command during communication
enable
with BREAK
disable
without BREAK
Loading...