Sapcon ELIXIR-T-UNI Instruction Manual

INSTRUCTION MANUAL
ELIXIR-T-UNI
Compact Vibrating Fork
Version 2.1
User Manual & Datasheet V 2.1
Contents
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Operating Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6 Dimensional Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8 Application Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
9 Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
10 Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
10.1 Procedure for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
10.2 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
10.3 Output Check Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
10.4 Output Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
10.5 Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
11 Order Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
12 Customer Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
List of Figures
1 Elixir-T-Uni . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Part Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Dimensional Diagram (All dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Fail-safe High . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Fail-safe Low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Sapcon Instruments Pvt.Ltd.
R
2
User Manual & Datasheet V 2.1
List of Tables
1 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Application Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sapcon Instruments Pvt.Ltd.
R
3

Revision History

Revision Date Author(s) Description
1.0 23 Feb 2014 RND First Version Editing
1.1 10 Aug 2014 MRK Applications Revision
1.2 15 Jul 2015 RND Features Revision
1.3 28 Dec 2015 RND Specs Revision
1.4 04 Sep 2016 RND Specs Revision
2.0 08 Jan 2017 BRND Revised Format
2.1 17 Sep 2017 BRND Branding Revisions
1
User Manual & Datasheet V 2.1
1
Copyright: All content on this document, such as text, graphics, logos and images is the property of Sapcon Instruments Pvt. Ltd. The selection,
arrangement and presentation of all materials on this document and the overall design of this document is the exclusive property of Sapcon Instruments Pvt. Ltd.
The images shown in this manual may differ from the actual instrument / housing in terms of dimensions, color and design. Please refer to GA drawings
for dimensional details.
Values (of performance) described in this manual were obtained under ideal testing conditions. Hence, they may differ under industrial environment and
settings.
General Instructions
Instrument shouldn’t block the material filling inlet.
Secure the cover of housing tightly. Tighten the cable glands. For side mounting, the cable glands should point downwards.
For side mounting, provide a baffle to prevent the material from falling on the probe.
When handling forks, do not lift them using their tines. While using them with solids, ensure that material size is less than 10mm.
Deforming the shape of the tines may interfere with the fork’s operating frequency.
Make all electrical connections as instructed in the manual. Don’t power on the device before verifying the connections.
R
Sapcon Instruments Pvt.Ltd.
4

1 Introduction

193
143
68
50
44
32
For Hygienic Application: Surface Finish in Ra = 0.8µm
Elixir-T-Uni is a Vibrating Fork Level Limit Switch for liquids. It is suitable for level detection in storage tanks, mixing container and pipelines, for all kinds of liquid which do not react with SS 316, viscosity does not exceed 10,000 cP and temperature lies within 0◦C to 80◦C. It is suitable for most of the applications where float switches were previously employed, as well as in places where float switches were not appropriate (due to deposition, turbulence, stresses and air bubbles). Elixir-T-Uni ignores foam deposition on its fork tines.
User Manual & Datasheet V 2.1

4 Features

Power Supply: 18-30 V DC
Output: Open collector PNP, LED Indication
Operational temperature: 0
Hygienic finish with 0.8 Ra available
No calibration required at site, easy to install
Compact in size
Service friendly plug-in connection
Rugged stainless steel housing
Operational safety ensured
Immune to foam build-up
External circuit testing by test magnet
C to 150◦C (Fork)
Figure 1: Elixir-T-Uni

2 Operating Principle

Elixir-T-Uni works on the principle of continuous vibration of the fork at its natural frequency. A specially shaped Tuning Fork is kept vibrating by piezo electric element. The resonance frequency changes when the tines are immersed in any fluid.The change in frequency is detected and used is for switching.

5 Applications

Elixir-T-Uni is suitable for the following applications and
industries:
Chemicals
Pesticides
Edible Oil
Food Industry
Dairy Industry
Packaging Industry
Pharmaceutical
Breweries
Industry

6 Dimensional Layout

Dimensional drawing for a fork length of 44 mm is shown
in Figure 3
Figure 2: Part Diagram

3 System Description

Elixir-T-Uni vibrating fork level switch detects the res­onant frequency change and changes the output signal according to fail-safe mode selection. Typically, the output is fed to a PLC which then uses it to control the process.
Sapcon Instruments Pvt.Ltd.
R
Figure 3: Dimensional Diagram
(All dimensions in mm)
5
User Manual & Datasheet V 2.1
7 Electrical Specifications
Please refer to Table 1 for Electrical Specifications.
PARAMETER VALUE
Input Power Supply 18-30 V DC
Output Open Collector - PNP Output (Load capacity upto 90 mA at
24 V DC)
Switching Indication Red /Green LED ON/OFF
Switching Behavior
ON
OFF
Fail-safe Feature Field selectable
Fail-safe High ( For Overflow Protection)
Fail-safe Low (For Dry Run Protection)
Power Consumption Without Load
480 mW @ 24 V DC
168 mW @ 12 V DC
With Load 3W @ 24 V DC
Table 1: Electrical Specifications
8 Application Specifications
Please refer to Table 2 for Application Specifications.
PARAMETER VALUE
Response Time
Covered
Uncovered
Repeatability ± 0.5mm
Switching Hysteresis* 3mm ± 0.5mm
Fork Resonance Frequency* 1500Hz approx.
Minimum Liquid Density 0.7gm/cc
Maximum Viscosity of Liquid 10,000 cp
Solid Content Diameter < 5mm
Temperature
Ambient
Process
Value
0.5 second
1 second
Value
0
C to 60◦C
0
C to 150◦C
Table 2: Application Specifications
* The reported values have been found with water as application medium, at room temperature.
R
Sapcon Instruments Pvt.Ltd.
6
User Manual & Datasheet V 2.1
9 Mechanical Specifications
Please refer to Table 3 for Mechanical Specifications.
PARAMETER VALUE
Housing Pipe SS 316 housing, Weatherproof with integral probe mount-
ing (IP65)
Mounting
Thread Mounting: 1/2”, 3/4”, 1” BSP / NPT
Flange Mounting: As per user specification
Tri-Clamp: As per user specification
Hygienic Flash Mounted Socket, SS 316 with 1” BSP
Electrical Connector Valve Connector
Gland Type PG 11, PG 9 cable gland
Dimension Refer to Figure 3
Active Fork Length 44 mm and 100 mm
Probe Length
68 mm, 105 mm, 125 to 1000 mm {For 44 mm Fork
Length}
126 mm {For 100 mm Fork Length}
Process Temperature Up to 150◦C
Sensing Fork Material SS 316
Fork Finish
Hygienic Fork
Standard Fork
Pressure Up to 10 Bar
Table 3: Mechanical Specifications
Sapcon Instruments Pvt.Ltd.
R
7
User Manual & Datasheet V 2.1

10 Installation Guidelines

Note: Elixir-T-Uni does not have any keys to oper­ate.The Fail-safe feature has been implemented in accordance with connection.
10.1
order mentioned below -

Procedure for Installation

For quick and easy installations, follow the steps in the
Remove the female socket from the top of Elixir-T-Uni
(Use Screw Driver) and you can see that there are four pins of male socket on Elixir-T-Uni.
Remove the cap from the female socket by using screw
driver.
10.2
10.2.1
instructions given below for Electrical Connections -

Electrical Connections

For Fail-safe High

If a device is mounted at top of the tank then follow the
First of all connect the positive terminal to pin no. 3 of
the device.
Now connect the negative terminal to pin no. 1 of the
device.
Connect fuse between positive terminal and pin no. 3
of the device.
Between pin no. 1 and 2 the output can be taken.
Connect all the wires from cable entry to male socket
pin through cap.
Plug-in Elixir-T-Uni to female socket.
Figure 4: Fail-safe High
10.2.2
If a device is mounted at bottom of the tank then follow
the instructions given below for Electrical Connections -

For Fail-safe Low

First of all connect the positive terminal to pin no. 2 of
the device.
Now connect the negative terminal to pin no. 1 of the
device.
Connect fuse between positive terminal and pin no. 2
of the device.
Between pin no. 1 and 3 the output can be taken.
Mount the device with the help of Mounting Socket.
R
Sapcon Instruments Pvt.Ltd.
Figure 5: Fail-safe Low
8
Note: Elixir-T-Uni is compatible only with 24V DC power supply.
User Manual & Datasheet V 2.1
10.3
change and when the magnet is released from the target area the status of the switching LED and PNP output is switched to there previous (original) state.
10.4
Output Check Test
Hold the magnet at the target place of the instrument, the current status of the switching LED and the PNP output will
Output Indications
Green LED Glows When:
Fork is Uncovered and Fail-safe is High
Fork is Covered and Fail-safe is Low
Red LED Glows When:
Fork is Covered and Fail-safe is High
Fork is Uncovered and Fail-safe is Low
10.5
1. Temperature
LED ERROR INDICATION DESCRIPTION TROUBLESHOOTING
Red and Green LEDs Glows Permanently
Error Indications
Blue LED glows when temperature of electronic insert goes above 120
No Calibration
C.
All LEDs OFF Low Voltage (Below 10V) Increase Voltage
Green LED Blinks (1 Second) It is because of Serial Communication Stop Serial Communication
Red LED Blinks (20 Seconds) Oscillator Failed/Fork is not connected
Blue LED Blinks Slowly (1 Second) Temperature goes above 100◦C
Blue LED Blinks Fast (300 MiliSec­onds)
Blue LED Glows Permanently Temperature goes above 120◦C
2. Fork Stops Vibrating
Temperature goes above 110◦C
Table 4: Error Indications
When Red LED blinks continuously and Fail-safe is High
When Green LED blinks continuously and Fail-safe is Low
Troubleshooting: The following reasons may be responsible for the absence of vibrations in the fork:
The instrument is damaged.
The instrument is working but there may be solid particles in the application medium clogging the fork.
Heavy build-up of application medium can dampen the fork oscillations. In this case, the fork requires to be cleaned.
If material is very viscous, the fork vibrations will resume when the fork is uncovered. In this case, the error
indication should be ignored.
3. No LED Glows
This would happen in absence of power supply to the instrument.
R
Sapcon Instruments Pvt.Ltd.
9
User Manual & Datasheet V 2.1
11 Customer Support
Thank you for going through the instructions given in this manual. To further ease the process of installation and use, we have developed special demo videos which are hosted on YouTube.
Sapcon’s YouTube channel, SAPCON INSTRUMENTS, lists all these videos: https://goo.gl/dnxfcz
Should you require further information regarding installation, use or working of the instrument, please don’t hesitate to contact us. Kindly provide the following information at the time of contacting:
Instrument Model and Serial Number
Purchase Order Number and Date of Purchase
Description of the query
Your contact details
In an attempt to serve you better, we are open seven days a week (9:30am to 7:30pm). We are available at:
www.sapconinstruments.com
sales@sapcon.in
+91-731-4757575
Sapcon Instruments Pvt.Ltd.