• Copyright: All content on this document, such as text, graphics, logos and images is the property of Sapcon Instruments Pvt. Ltd.
The selection, arrangement and presentation of all materials on this document and the overall design of this document is the exclusive
property of Sapcon Instruments Pvt. Ltd.
• The images shown in this manual may differ from the actual instrument / housing in terms of dimensions, color and design. Please refer
to GA drawings for dimensional details.
• Values (of performance) described in this manual were obtained under ideal testing conditions. Hence, they may differ under industrial
environment and settings.
General Instructions
• Instrument shouldn’t block the material filling inlet.
• Secure the cover of housing tightly. Tighten the cable glands. For side mounting, the cable glands should point downwards.
• For side mounting, provide a baffle to prevent the material from falling on the probe.
• When handling forks, do not lift them using their tines. While using them with solids, ensure that material size is less than 10mm.
• Deforming the shape of the tines may interfere with the fork’s operating frequency.
• Make all electrical connections as instructed in the manual. Don’t power on the device before verifying the connections.
R
Sapcon Instruments Pvt.Ltd.
4
User Manual & Datasheet V 2.1
3-wireSingleSupplyOperation
mAmp
MaximumInternalResistanceofIndicator/PLC/Scanner
[(SensorSupply-4V)x50]Ohm
Indicatoror
Scanner
orPLC
4-20mA
mAmp
MaximumInternalResistanceofIndicator/PLC/Scanner
[(LoopSupply-4V)x50]Ohm
Indicatoror
Scanner
orPLC
4-20mA
4-wireDualSupplyOperation(GalvanicIsolated)
Jumpers
(TowardsISO)
Jumpers
(TowardsLOOP)
I
SOLAT
ION
1Introduction
2Operating Principle
CAPVEL is composed of specially developed capacitance change gauging circuit. It uses fast RISC based
processor to perform all the complicated jobs of evaluating the level out of the capacitance. This capacitance is
formed by the sense rod and the metallic container wall,
where containers are non-metallic or non-uniformly wide
or having turbulent fluid, a metallic stilling well is provided. The amount of capacitance is proportional to the
level of material between the sense rod and metallic wall
of stilling tube or container.
mA input or multimeter in 40 mA range or any-other
device that takes 4-20 mA signal as input.
4Features
5Applications
6Capvel-BT Features
• User Interface : 2 DIP switches + 2 LED
• Output-1 : 4-20 mA, Galvanically Isolated
• Output-2 : Rs-485 Digital Data
7Capvel-ICT Features
• User Interface : 4 Digit Display with 4 Keys + 2
LED
• Output-1 : 4-20 mA, Galvanically Isolated
• Output-2 : Rs-485 Digital Data
Figure 1: Capvel
3System Description
CAPVEL is composed of cast aluminium housing,
supplied with suitable mounting arrangement viz.NPT,
BSP or Flanges and two metallic cable entries.An
external Earthing / Grounding terminal is also provided.
The sensing rod which is mostly Teflon coated. This
sensing rod can be replaced by flexible probe for some
applications.The stilling tube is also provided for
turbulent fluids, irregular width tanks, non-metallic
tanks or for fluids with low dielectric (e.g. diesel).
Opening the threaded aluminium cover, an electronic
insert could be found. This is the electronic unit which
converts the level into 4-20 mA signal depending on the
calibration. The status LED is a bi-color LED that blinks
alternately in Red and Green to indicate instrument is in
process of converting the level to 4-20 mA signal. Two
DIP switches are provided to calibrate the 4 mA and
20 mA points. The calibration is easy and a complete
procedure is given in "Calibration" page. The two wires
connected at the back are pre-connected sensor wires
and should not be disturbed. Also while calibration try
to keep hands away from the wires of terminal 6 and 7.
Now referring to the "Connection Diagram", Capvel can
be wired in two possible combinations. Preferred one
is galvanically isolated, 4-wire combination where only
one source of power is available, 3-wire, non-isolated
combination can also be used. The converted level signal
can be sensed using a 4-20 mA indicator or PLC 4-20
• Output-3 : Controlling Devices connected with External Relay
Figure 2: Connection Diagram
Sapcon Instruments Pvt.Ltd.
R
5
User Manual & Datasheet V 2.1
8Mechanical Specification
For Mechanical Specification please refer Table 1
PARAMETERVALUE
HousingCast aluminium weather and Flame proof suitable for
mounting in hazardous area Gas Group IIA and IIB as per
IS-2148
Mounting
• Integral with sense rod or probe with SS /MS(plated)
• Screw - 1"/1 1/2" BSP/NPT (M)
• Flanged - (As per your order)
Cable Entry2 X 1/2"/3/4" BSP/NPT, Brass
Gland typeDouble Compression Gland
SensingFully or Partially Teflon Coated Rod, Flexible Probe SS316
rLdr (Relay Drive)r. SPS.000<>S.100Set point Only in Indi-
vidual Controlling
rLdr (Relay Drive)r.SPHh.001<>h.100Higher Set point Only in
Pump Controlling
rLdr (Relay Drive)r.SPLL.000 <>L.099Lower Set point Only in
Pump Controlling
SPH must be higher
than SPL
SPH must be higher
than SPL
rLdr (Relay Drive)r.CdC.000 <>C.100Cover Delay in Seconds
rLdr (Relay Drive)r.UdU.000 <>U.100Uncover Delay in Sec-
onds
SCAL (Scal Factor)SC.-HH.020<>H.100Higher SCALE LEVELSCAL-HIGH must be
20% or more Higher
than SCAL-LOW
SCAL (Scal Factor)SC.-LL.000<>L.080Lower SCALE LEVELSCAL-HIGH must be
20% or more Higher
than SCAL-LOW
dISP(Display)d.PER<>d.AmPDisplay Options PER
: Percentage, AmP :
mAmp
Table 5: Menu
Sapcon Instruments Pvt.Ltd.
R
11
User Manual & Datasheet V 2.1
MENUSUB MENUCHANGEDESCRIPTIONREMARK
trbu (Turbulence)t.001 <>t.010Turbulence Immunity
vts (Vehicle Mode)1 = ON0 = OFFImmunity to vehicle gen-
erated fluctuations
c. IDId.00 <>id.99Communication ID of
Sensor on RS-485 Network
Com (Communication
Settings)
Com (Communication
Settings)
Com(Communication
Settings)
othro.LENLE0.0 <>LE9.9Probe Length in metersOnly for optimization
othro.PRFPR.1 <>PRF.9ProfileOnly for optimization
InFoi.SEr12345678Serial NoFactory Sated and Read
InFoi.dAt12345678Mfd. Date in DD-MM-
c.bAUb.00.3<>b.38.4Communication Baud
Rate 9.6 x 1000 =
9600bps and so on
c.FloF.CMd<>F.AUtFlow Control
• CMD : Send data
when Commanded
• AUT : Send Data
Automatically
c.durd.001<>d.250Auto Data Sending Du-
ration in Seconds
YY format
Only usefully in Vehicle
Tracking Systems
(Flow : AUT)
Only
Factory Sated and Read
Only
Table 6: Menu
16RS-485 Serial Commands for
Communication with Capvel
For RS-485 Serial Commands please refer Table 7
COMMAND DESCRIPTION
Level would be calculated
by dividing incoming five
digit number with 10.Please
note that:- Application Software must have to take care
of any possible errors during turn-on or off durations,
change in nature of service
material etc.