T A Series of Temperature Controller
Instruction Manual
Thanks a lot for selecting Sanyou products!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If have probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstull,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Name of parts
Specifications
Parameter setting
Setting steps
A: Select the parameter you want to modify
B: Press the key to select the digit
you want to modify
C: Press key and key to modify the numerals
D: Press SET key to confirm
Power on
Warning
Please do not turn on the power supply until all of the wiring is
completed. Otherwise electrical shock, fire or malfunction may
result.Do not wire when the power is on. Do not connect the
unused terminals. Do not turn on the power supply when
cleaning this instrument. Do not disassemble, repair or modify
the instrument. This may cause electrica shock, fire or
malfunction.Use this instrument in the scope of its
specifications. Otherwise fire or malfunction may result.The
use life of the output relay is quite different according to is
capacity and condictions. If use out of its scope, fire or
malfunction may result.
Caution
This instrument should be installed in a domestic environment.
Otherwires electricla shock, fire or malfunction may result.
The operating temperature environment should between
0 C (32F) to 50 C (122F).
To avoid using this instrument in environment full of dust or
caustic gas.
To avoid using this instrument in environment of strong shock
or concussion.
To avoid using this instrument in environment of overflow
water or explosive oil.
The power supply wire should not put together with large
current wire to aviod electromagnetic radiation, If it must to
put together, we suggest to use a individual pipe.
In case the instrument is used in environment of strong noise,
(such as motor, transformer, solenoid, etc.) A current suppresser
or noise filter should be used.
Applications
TA series of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
1.Measured value (PV)/Various parameter symbols
2.Set value (SV)/Various parameters set value
3.Indication lamps
OUT1: Heating/Main control output lamp On: Ouput
Off: No output
OUT2: Cooling/Alam2 output lamp On: Ouput Off: No output
AT: Autotune lamp On: Autotune Off: Non-autotune
AL: Alarm 1 output lamp On: Alarm Off: No Alarm
4.Set key Parameter Setting/Changing
5.Shift/Autotune key Press this key to shift digit of
parameter value setting. Or hold this key for more than 3
seconds can enter/quit autotune estate. When enter
autotune estate, AT lamp on. When quit autotune estate,
AT lamp off.
6.Up key Used to increase numerals
7.Down key Used to decrease numerals
Models
Mounting and Sizes
Sizes
Model
Self-check
All LED on
Input type
Input up limit
Input low limit
Measured displaying
Set displaying
Shift and flashes
Modify
Confirm
Stop flashing
In Non-autotune estate, press and hold / key for more
than 5 seconds can enter/quit the under menu: (Normally
the program will refresh the value of the parameters
by itself, the user no need make modifications. )
Low limit value, it is adjustable
by the input signal.
Up limit value, it is adjustable
by the input signal.
AL1 hysteresis setting value.
Range 90, factory setting 1.0
AL2 hysteresis setting value.
Range 90, factory setting 1.0
Proportional band range ( If cooling output is
available.) 0.1-3600.
Application examples
1.Relay output control (for TA9)
Decimal point setting:
0: No decimal 1: One decimal
Password setting.
Factory setting 015
The values on down line are the factory setting values
AL1 set range: –1999-9999
AL1 mode: 0: Deviation HI alarm 1: Deviatian
LO alarm 2: Absolute value HI alarm
3: Absolute value LO alarm 4: Section outside
alarm 5: Section inside alarm 6: Power off
alarm 7: Low value the first time no alarm.
The factory setting is 2
AL2 set range: –1999-9999. If no AL2,
it is for OUT2.
AL2 mode: The same as AL1.
Modification value. Range: 100.
Display value = Measured value - Modification value
Input signal selection TC: K, J, T,E, S
RTD: Pt100, Cu50 The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600. I=OFF means
cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
Control directions: HEAt: heating
COOL: cooling
Control hysteresis, range: 100.
It is not available when P OFF
The output control mode value 1-150,
CtL=20 means relay output. CtL=1-3 means
SSR control output.
Cooling output gap:
Cooling ouput control mode value 1-150,
C-t=20 means relay output. C-t=1-3 means SSR
control output.
Temperature unit. C means C degree,
F means F degree.
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
90.0.
Note:
1.OUT2 and AL2 use the the same output channel. It is for
the user’s option. Set by the factory.
When the user operate the instrument at first time, please
operate according to the processes of this instruction
manual. Let the instrument in autotuning, if the
runing condictions keep not change (eg. Running the
same equipment), the user no need to let it autotuning
again. Because the instrument has recorded the previous
PID parameters. When the instrument is used for huge
capacity heating equipments, the user should set
autotuning value lower 5%-10% than the normal control
value, in order to decrease the exceed-tuning caused by
control.
In normally, the control cycle of the heating equipment
should be 20-30 seconds. For huge capacity heating
equipments, the value should be 30-120 seconds, in
order to longer the use life of the relay. For non-contact
output, such as SSR control output, the value should be 1-3.
Terminal configurations
(If any changed, please refer to the product showing.)
ON/OFF control: Set value
Heating
LO HI
Alarm mode:
Deviation HI alarm
Cooling
LO HI
LO HI
1:Deviatian LO alarm
LO HI
2:Absolute value HI alarm
LO HI
3: Absolute value LO alarm
4: Section outside alarm
LO HI
HI
5: Section inside alarm
Note:
HI
All the factory setting value of deiation alarm is 1.0. If the
user want to change, please contact us or our distributors.
RTD
equipment
Heating
Heater
Power supply
Malfunction estimate
Check all the connection and wiring if it is all
correct. Specially pay attention to the power supply terminals
and signal input ternimals.
Check if the input signal is conformity
with the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
If the instrument has been used for a long
time, the user find that the displaying float or the temperature is
hard to rise up to the set value, meanwhile the outsidesystem running well, there must be something wrong with the parameters of
the instrument.
The user need to re-autotuning the instrument. If the instrument
lost control, please check if the connection of the control is correct.
If external load is shorted, broken, wrong connection or components is damaged, it will cause lost control as well. When it is
necessary, please push out the PCB to check the if the output
terminals is damaged and not available.
“UUUU”: The input signal exeed
the measured HI range . “LLLL” : The input signal exeed
the measured LO range , or input signal terminal connection
is contrary.