Sanyou TA Series of Temperature Controller Service Manual

T A Series of Temperature Controller Instruction Manual
Thanks a lot for selecting Sanyou products! Before operating this instrument, please carefully read this manual and fully understand its contents. If have probroms, please contact our sales or distributors whom you buy from. This manual is subject to change without prior notice.
automation systems of mechanism, chemical industrial, chinaware, light industrial, metallurgy and petroleum chemical industrial. It is also applied to the production line of foodstull, packing, printing, dry machine, metal heat process equipment to control the temperature.
Name of parts
Specifications
Parameter setting Setting steps A: Select the parameter you want to modify B: Press the key to select the digit you want to modify C: Press key and key to modify the numerals D: Press SET key to confirm
Power on
Warning
Caution
This instrument should be installed in a domestic environment. Otherwires electricla shock, fire or malfunction may result. The operating temperature environment should between 0 C (32F) to 50 C (122F). To avoid using this instrument in environment full of dust or caustic gas. To avoid using this instrument in environment of strong shock or concussion. To avoid using this instrument in environment of overflow water or explosive oil. The power supply wire should not put together with large current wire to aviod electromagnetic radiation, If it must to put together, we suggest to use a individual pipe. In case the instrument is used in environment of strong noise, (such as motor, transformer, solenoid, etc.) A current suppresser or noise filter should be used.
Applications
TA series of temperature controller is available for many TC or RTD input, adopt some advanced techonology such multi digital filter circuit, autotune PID, fuzzy PID that make it is very precise, stable, strong anti-interference and simple operation. The instrument is widely applied to
1.Measured value (PV)/Various parameter symbols
2.Set value (SV)/Various parameters set value
3.Indication lamps OUT1: Heating/Main control output lamp On: Ouput Off: No output OUT2: Cooling/Alam2 output lamp On: Ouput Off: No output AT: Autotune lamp On: Autotune Off: Non-autotune AL: Alarm 1 output lamp On: Alarm Off: No Alarm
4.Set key Parameter Setting/Changing
5.Shift/Autotune key Press this key to shift digit of parameter value setting. Or hold this key for more than 3 seconds can enter/quit autotune estate. When enter autotune estate, AT lamp on. When quit autotune estate,
AT lamp off.
6.Up key Used to increase numerals
7.Down key Used to decrease numerals
Models
Mounting and Sizes
Sizes
Model
Self-check All LED on
Input type
Input up limit Input low limit
Measured displaying Set displaying
Shift and flashes
Modify
Confirm
Stop flashing
In Non-autotune estate, press and hold / key for more than 5 seconds can enter/quit the under menu: (Normally the program will refresh the value of the parameters by itself, the user no need make modifications. )
Low limit value, it is adjustable by the input signal.
Up limit value, it is adjustable by the input signal.
AL1 hysteresis setting value. Range 90, factory setting 1.0
AL2 hysteresis setting value. Range 90, factory setting 1.0
Proportional band range ( If cooling output is available.) 0.1-3600.
Application examples
1.Relay output control (for TA9)
Decimal point setting: 0: No decimal 1: One decimal
Password setting. Factory setting 015
The values on down line are the factory setting values
AL1 set range: –1999-9999
AL1 mode: 0: Deviation HI alarm 1: Deviatian LO alarm 2: Absolute value HI alarm 3: Absolute value LO alarm 4: Section outside alarm 5: Section inside alarm 6: Power off alarm 7: Low value the first time no alarm. The factory setting is 2
AL2 set range: –1999-9999. If no AL2, it is for OUT2.
AL2 mode: The same as AL1.
Modification value. Range: 100. Display value = Measured value - Modi­fication value
Input signal selection TC: K, J, T,E, S RTD: Pt100, Cu50 The factory setting is K
Proportional band (%) range 0.1-3600. If P=OFF, it means ON/OFF control
Integral time range 0.1-3600. I=OFF means cancel integral time.
Derivative time range 0.1-3600. D=OFF means cancel derivative time.
Control directions: HEAt: heating COOL: cooling
Control hysteresis, range: 100. It is not available when P OFF
The output control mode value 1-150, CtL=20 means relay output. CtL=1-3 means SSR control output.
Cooling output gap:
Cooling ouput control mode value 1-150, C-t=20 means relay output. C-t=1-3 means SSR control output.
Temperature unit. C means C degree, F means F degree.
Parameter lock code setting. LcK=000 means unlocked. LcK=010 means locked.
90.0.
Note:
1.OUT2 and AL2 use the the same output channel. It is for the user’s option. Set by the factory. When the user operate the instrument at first time, please operate according to the processes of this instruction manual. Let the instrument in autotuning, if the runing condictions keep not change (eg. Running the same equipment), the user no need to let it autotuning again. Because the instrument has recorded the previous PID parameters. When the instrument is used for huge capacity heating equipments, the user should set autotuning value lower 5%-10% than the normal control value, in order to decrease the exceed-tuning caused by control. In normally, the control cycle of the heating equipment should be 20-30 seconds. For huge capacity heating equipments, the value should be 30-120 seconds, in order to longer the use life of the relay. For non-contact output, such as SSR control output, the value should be 1-3.
Terminal configurations
(If any changed, please refer to the product showing.)
ON/OFF control: Set value
Heating
LO HI
Alarm mode:
Deviation HI alarm
Cooling
LO HI
LO HI
1:Deviatian LO alarm
LO HI
2:Absolute value HI alarm
LO HI
3: Absolute value LO alarm
4: Section outside alarm
LO HI
HI
5: Section inside alarm
Note:
HI
All the factory setting value of deiation alarm is 1.0. If the user want to change, please contact us or our distributors.
RTD
equipment
Heating
Heater
Power supply
Malfunction estimate
Check all the connection and wiring if it is all correct. Specially pay attention to the power supply terminals and signal input ternimals.
Check if the input signal is conformity with the selected symbol. For TC input, please use the relative compensation cable. For RTD input, please use low impedence cable. The 3 wires should at the same length. If all above mentioned is collect , pleaase use parameter PVF to modify.
If the instrument has been used for a long
time, the user find that the displaying float or the temperature is hard to rise up to the set value, meanwhile the outsidesystem run­ning well, there must be something wrong with the parameters of the instrument. The user need to re-autotuning the instrument. If the instrument lost control, please check if the connection of the control is correct. If external load is shorted, broken, wrong connection or compo­nents is damaged, it will cause lost control as well. When it is necessary, please push out the PCB to check the if the output terminals is damaged and not available.
“UUUU”: The input signal exeed
the measured HI range . “LLLL” : The input signal exeed the measured LO range , or input signal terminal connection is contrary.