6. Special Functions ---------------------------------------9
SANYO DENKI CO., LTD.
DWG.No. M0009173C
Introduction
Thank you for choosing this product. This document contains important safety
precautions for users and service technicians.To ensure proper operation and
reliability throughout the useful life this device, read this manual prior to use and
keep it nearby for future reference.
Safety Precautions
Read this manual carefully before installing, operating, performing maintenance, or
inspecting this device in order to understand all instructions and related safety
precautions.
Usage and Storage Precautions
!
Never operate or store the equipment in the following environmental
conditions, as doing so may cause malfunction, damage or deterioration,
which could result in fire and/or injury:
z In ambient environmental conditions other than those specified
(temperatures outside the range of 0 to 40°C (32 to 104°F), and relative
humidity outside of the range of 30% to 90%).
z Where the device is exposed to direct sunlight.
z Where the equipment is directly exposed to heat from a heat source, such
as a stove.
z Where the device may be subject to vibration or physical shock.
z Near a device that may emit sparks.
z In the presence of dust, salt, or corrosive or flammable gas.
z Outdoors.
CAUTION
1. Confirming Package Contents
When opening the package, confirm that the following items are included.
Contact your nearest sales representative if you find any discrepancy.
Fig. 2-1 Contact Signal Interface Card Exterior (Front View)
Fig. 2-2 Contact Signal Interface Card Exterior (Bottom View)
Name Description
AUX IN
①
(D-SUB 9-pin female)
CONTACTS SIGNAL
②
(TERMINAL BLOCKS)
①
Table 2-1 Parts Description
Connector for communication with the UPS:
When receiving the status signal from the UPS*,
power will also be supplied to the contact signal
interface card.
External status signal connector:
Outputs the UPS status signals via dry (no
voltage) contacts.
②
①
②
* UPS is an abbreviation for “Uninterruptible Power System”.
- 1 -
3. Contact Signal Interface Card Installation
Follow steps (1) through (6) to install the Contact Signal Interface Card.
Caution:
• If the device is shipped with the Contact Signal Interface Card preinstalled,
proceed from step (5).
(1) Preparation
The Contact Signal Interface Card should be installed only after the UPS has been
shut down completely. If the UPS is in operation, follow the instructions of “Operation
Shutdown (If UPS is not to be used for a week or more)” in the UPS Instruction
Manual, and shut down the UPS completely.
!
CAUTION
(2) Remove the protective cover
Remove the cover from the rear panel of the UPS.
① Remove the screws from both locations, and then the cover from the UPS.
Note that one of the screws will be used for securing the Contact Signal Interface
Card.
Note: The protective cover will not be used after inserting the card, but should
be stored in a safe place in case of future need.
Before installing the Contact Signal Interface Card, the UPS
must be completely shut down. Inserting the card when the
UPS is not shut down completely may result in electric shock.
①
Two screws
Fig. 3-1 Rear panel cover removal(E11A)
- 2 -
(3) Insert the Contact Signal Interface Card
Insert the Contact Signal Interface Card into the card slot on the rear panel of
the UPS as shown in the Fig. 3-2.
Fig. 3-2 Inserting the Contact Signal Interface Card (UPS rear panel)
(4) Secure the Contact Signal Interface Card
Cover securing position
Contact Signal Interface Card
Contact Signal Interface
Card securing position
Secure the Contact Signal Interface Card to the UPS using one of the screws
removed in step (2).
Insert the remaining screw into the cover securing position, to prevent losing
it.
- 3 -
(5) Connect the Contact Signal Interface Card and the UPS using the accessory
cable
Use the communication cable to connect the “CARD I/F” connector of the
UPS and the “AUX IN” connector of the Contact Signal Interface Card as
shown in the Fig.3-3.
Communication cable
(Accessory)
UPS
CARD
I/F
Contact Signal
Interface Card
AUX IN
Connect with the signal cable
Computer
(Load devices)
Fig. 3-3 Connection to the UPS using the communication cable (UPS rear panel)
(6) Connect the computer and the Contact Signal Interface Card using the
signal cable
Use the special signal cable to connect the “CONTACTS SIGNAL” TERMINAL
BLOCKS of the Contact Signal Interface Card to the computer.
When the UPS is E11A series, Installation of the Contact Signal
Interface Card and the UPS setting procedures are now complete.
Start the UPS according to the procedures in the UPS Instruction Manual.
Even if interface setteing of E11A is set to “Workstation mode” or to
“Standalone mode”, UPS works.
In addition, you cannot use the Contact Signal Interface Card and the LAN
Interface Card at the same time.
In the case of E11A, only TYPE C can be connected to this CARD.
- 4 -
4. UPS Settings(A11F series)
There are two communication mode settings for the UPS.
• Standalone mode
• W/S mode (Workstation mode)
Set the UPS to Standalone mode when using this Card.
Follow the procedures described on pages 6~7 to verify and change the UPS
mode settings.
Note that if the card was factory preinstalled, this step is unnecessary.
Caution:
If the UPS is set to W/S mode, the Interface Card cannot be used.
Also, this card cannot be used with power control software (SANUPS SOFTWARE)
that requires a PC I/F connector for serial connection. If PC shutdown capability is
required while using this Card, the communication settings in the power control
software must be set to “Contact Connection”.
- 5 -
Mode verification and setting modification
(1) Start the UPS
Operating mode verification and setting changes are done using the operating unit
and the display of the UPS front panel. Begin by starting the UPS.
Follow the procedures for startup operation as described in the UPS Instruction
Manual.
Caution:
When the UPS starts, power will be supplied from the outlet.
It is recommended to disconnect the load devices before starting the UPS.
(2) Verify the operating mode and modify settings using the operating unit and
the display
Verify the operating mode and modify settings
following the procedures described in the UPS
Instruction Manual.
● - Blinking
○ - Off
Fig. 4-1 LED display when standalone mode is selected
(3) Disable the Automatic startup
Verify and change settings following the
procedures described in the UPS Instruction
Manual.
For more information about the ring signal
startup, refer to "§6 Special Functions" of this
12
0
manual.
● - Blinking
○ - Off
- 6 -
Fig. 4-2 LED display when the ring signal is set to “Disabled”
12
0
(4) Stop the UPS
When setting modifications are complete, stop the UPS. Follow the
procedures of the UPS Instruction Manual to properly shut down the UPS.
Caution:
• If any load devices were disconnected, reconnect them at this time.
• If any settings were modified, stop the UPS completely. Otherwise,
any changes in the settings are not validated, and will not take effect.
Installation of the Contact Signal Interface Card and the UPS setting
procedures are now complete.
Start the UPS according to the instructions in the UPS Instruction Manual.
- 7 -
5. External Signals (“CONTACTS SIGNAL”)
2
JP1A
JP1C
JP1B
Note: The figure above shows the device’s status when stopped.
Signal Name Description
AC Input Fault
Low Battery voltage
Signal
output
AC Output
Bypass Output
UPS Fault
Note 1. These signal outputs are non-voltage contacts, with a contact
capacity of AC 110V/DC 24V 0.2A.
Note 2. In the case of A11F, when using OUTPUT1,2 and supplying the
output, this Card output a signal.
Note 3. “Low Battery voltage”, “Bypass Output” and “UPS Fault” can
choose of Make contact or Break contact. Default is Make contact.
AC Input Fault
1
8 (COM)
Low Battery Voltage
3
5
AC Output
4
6
Bypass Output
UPS Fault
7
TERMINAL BLOCKS
This signal is output when there is a failure in the
commercial power supply, or when voltage is
insufficient. (Make contact, Break contact)
This signal is output when the battery voltage falls
below the preset value. (Make contact or Break
contact. Default : Make contact) Note 3
This signal is output when AC output is supplied to
the load devices via OUTPUT1 or 2.
(Make contact, Break contact) Note 2
This signal is output when bypass output is
supplied to the load devices. (Make contact or
Break contact. Default : Make contact) Note 3
This signal is output when a fault occurs in the
UPS. (Make contact or Break contact.
Default : Make contact) Note 3
Make contact
①②③④⑤⑥⑦⑧
Short pin
b a
b a
b a
UPS Fault
Low Battery voltage
Bypass Output
Fig. 5-1 Contact Signal Interface Card Exterior (Bottom View)
- 8 -
b
a
Break contact
Short pin
a
b
6. Special Functions
The AC output signal is capable of sending a ring signal* (depending on the
computer type, this may be called a “modem signal”). To use the ring signal, this
setting should be modified as described below. After changing the settings, the
UPS must be completely stopped and then restarted for the setting to take effect.
E11A (TYPE C):
• Modify the settings according to the procedures in the UPS User Settings
Guide.
A11F102,A11F152:
• Modify the settings according to the procedures in the UPS Instruction
Manual.
Caution:
If the AC output signal is used as is, the following settings are necessary:
E11A (TYPE C):
• Set the " Setting a Ring Signal" of the UPS User Settings Guide to “Do
not output”
A11F102, A11F152:
• Set the " Setting the automatic start of the computer” to “Do not start”.
Ring signal startup settings
[Disabled]:
ON
UPS output (OUTPUT 1 or 2)
AC output signal (4 pin – com)
OFF
ON
OFF
[Enabled] (Factory setting):
UPS output (OUTPUT 1 or 2)
AC output signal (4 pin – com)
ON
OFF
ON
OFF
After starting the UPS output,
ON (2 sec) and OFF (1 sec) is
repeated for 30 seconds (ring
*What is a ring signal?
A ring signal is a false modem signal sent to the computer’s serial port. When
the computer receives this signal, it automatically boots up. The serial port and
the motherboard of the computer must support the ring signal feature in order
to use this function.
- 9 -