This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an
important part of your job to install or service the system so it
operates safely and efficiently.
For safe installation and trouble-free operation, you must:
●
Carefully read this instruction booklet before beginning.
●
Follow each installation or repair step exactly as shown.
●
Observe all local, state, and national electrical codes.
●
This product is intended for professional use.
Permission from the power supplier is required when
installing an outdoor unit that is connected to a 16 A
distribution network.
●
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum
fins on the air conditioner can cut your fingers.
When Installing…
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
Depending on the system type, liquid and gas lines may
be either narrow or wide. Therefore, to avoid confusion
the refrigerant tubing for your particular model is specified as either “narrow” or “wide” than as “liquid” or “gas.”
When Servicing
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical parts
and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
• Ventilate any enclosed areas when installing or testing the
refrigeration system. Escaped refrigerant gas, on contact
with fire or heat, can produce dangerously toxic gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas
water heater, electric room heater or other heat source, it
can cause the generation of poisonous gas.
NOTE
WARNING
CAUTION
WARNING
CAUTION
3
2. The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adja-
cent room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top
or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected,
the smallest room of course becomes the object.
But when mechanical ventilation is installed interlocked with a gas leakage detector in the smallest
room where the density limit is exceeded, the volume of the next smallest room becomes the object.
3. The minimum indoor floor space compared with the
amount of refrigerant is roughly as follows: (When
the ceiling is 2.7 m high)
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more
than air, it poses the risk of suffocation if its density
should rise excessively. Suffocation from leakage of
refrigerant is almost non-existent. With the recent
increase in the number of high density buildings, however, the installation of multi air conditioner systems is
on the increase because of the need for effective use
of floor space, individual control, energy conservation
by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is
able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a
single unit of the multi air conditioner system is to be
installed in a small room, select a suitable model and
installation procedure so that if the refrigerant accidentally leaks out, its density does not reach the limit
(and in the event of an emergency, measures can be
made before injury can occur).
In a room where the density may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device. The density is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
≤ Density limit (kg/m
3
)
The density limit of refrigerant which is used in multi air conditioners is 0.3 kg/m
3
(ISO 5149).
1. If there are 2 or more refrigerating systems in a single refrigerating device, the amount of refrigerant
should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms
A, B and C is 10 kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15 kg.
Outdoor unit
Refrigerant tubing
Indoor unit
Refrigerant tubing
NOTE
e.g., charged
amount (10 kg)
Indoor unit
Room A Room B Room C Room D Room E Room F
Outdoor unit
e.g., charged
amount (15 kg)
Outdoor unit
Very
small
room
Small
room
Mechanical ventilation device – Gas leak detector
Medium
room
Large room
Indoor unit
40
Range below the
2
35
m
density limit
of 0.3 kg/m
30
(countermeasures
not needed)
25
20
15
10
5
Min. indoor floor space
0
3
102030
Total amount of refrigerant
Range above
the density limit
of 0.3 kg/m
(countermeasures
needed)
3
kg
1-2. Accessories supplied with the unit
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of
instructions for the indoor unit and make sure all accessory parts listed are with the system before beginning.
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately
from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant
tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness
of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire
size varies with the total length of wiring. Refer to
3. Electrical Wiring for details.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions
or limitations.
1-1. Tools Required for Installation (not supplied)
1-2. Accessories supplied with the unit
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
2. HOW TO INSTALL THE UNIT . . . . . . . . . . . . . .5
2-1. Suspending the Indoor Unit
2-2. Preparation for suspending
2-3. Placing the Unit inside the Ceiling
2-4. Installing the Drain Piping
2-5. Checking the Drainage
2-6. Before installing the Ceiling Panel
2-7. Installing the Ceiling Panel
2-8. When removing the Ceiling Panel for Servicing
CONTENTS
Page
Page
1-1. Tools Required for Installation (not supplied)
Sealing putty1For sealing recessed portion of power supply
CAUTION
2. HOW TO INSTALL THE INDOOR UNIT
2-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
2-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs.
2-1 and 2-2), by attaching them to the ceiling
support structure, or by any other method that
ensures that the unit will be securely and safely
suspended.
(2)Follow Fig. 2-2 and Table 2-1 to make the holes
in the ceiling.
Table 2-1Unit: mm
Type
25
36, 48
Length
820566
AB
1,110856
Hole-in-anchor
Hole-in-plug
ConcreteInsert
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 2-1
X
A (Ceiling opening)
B
(Suspention bolt pitch)
Grille center
0038_T_I
Drain hose
side
32-9/32 (Ceiling opening)
29-13/16 (Suspention bolt pitch)
(3)Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 2-3 and Table 2-2) show
the relationship between the positions of the
suspension fitting, the unit, and the panel.
Refrigerant tubing joint (wide tube side)
Suspension lug
E
Fig. 2-3
Table 2-2Unit :mm
Type
Length
ABCDE
25 157182261308124
36, 48157182291338124
Fig. 2-2
Refrigerant
tubing side
1969_X_S
Drain connection (another side)
(VP25)
Refrigerant tubing joint
(narrow tube side)
D
C
B
A
30
2259_X_S
5
2-3. Placing the Unit Inside the Ceiling
I
(1)When placing the unit inside the ceiling, deter-
mine the pitch of the suspension bolts using the
supplied full-scale installation diagram. (Fig. 2-4)
The size of the opening for the indoor unit can be
confirmed by attaching the full-scale installation
diagram beneath the unit. (Fig. 2-4)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position for connection to the unit before placing the
unit inside the ceiling.
(2)The length of suspension bolt must be appropri-
ate for a distance between the bottom of the bolt
and the bottom of the ceiling of 15 mm or more
as shown in Fig. 2-4.
(3)Thread the 2 hexagonal nuts (field supply) and
washers onto the 4 suspension bolts as shown in
Fig. 2-5.
Use 2 sets of nuts and washers (upper and
lower), so that the unit will not fall off the suspension lugs.
(4)Remove the protective cardboard used to protect
the fan parts during transport.
(5)Adjust the distance between the unit and surface
of the ceiling. (48 mm) (Fig. 2-4)
Full-scale installation diagram
(printed on a cardboard packing)
15 mm or more
Nuts and washers
(Use above and below)
Double nuts
48 mm
Full-scale installation
diagram
2260_X_I
Fig. 2-4
Suspension bolt
Suspension lug
Upper
Lower
Notch
48 mm
2261_X_
Fig. 2-5
6
I
I
2-4. Installing the Drain Piping
(1)Prepare standard hard PVC pipe for the drain and
use the supplied drain hose and hose band to
prevent water leaks.
The PVC pipe must be purchased separately.
The transparent part allows you to check drainage. (Fig. 2-6)
Tighten the hose clamps
CAUTION
so their locking nuts face
upward. (Fig. 2-6)
(2)After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe.
(Fig. 2-7)
NOTE
Ensure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
Transparent part for
checking drainage
Packing
(supplied)
Drain hose
(supplied)
Drain insulator (supplied)
Hose band
(supplied)
Fig. 2-6
Fig. 2-7
Hard PVC pipe
(not supplied)
Drain hose
adapter
(supplied)
0964_X_I
0197_X_I
● Do not install an air
CAUTION
bleeder tubes, as this
may cause water to spray
from the drain tube outlet.
(Fig. 2-8)
● If it is necessary to increase the height
of the drain pipe, the section directly
after the connection port can be raised
a maximum of 50 cm. Do not raise it
any higher than 50 cm, as this could
result in water leaks.
(Fig. 2-9)
● Do not install the pipe with an upward
gradient from the connection port. It
will cause the drain water to flow
backwards and leak when the unit is
stopped. (Fig. 2-10)
● Do not apply force to the piping on the
unit side when connecting the drain
pipe. The pipe should not be allowed
to hang unsupported from its connection to the unit. Fasten the pipe to a
wall, frame, or other support as close
to the unit as possible. (Fig. 2-11)
Air bleeder
0047_X_I
Fig. 2-8
30 cm or less (as short as possible)
50 cm or less
2262_X_I
Fig. 2-9
Upward gradient
0049_X_
Fig. 2-10
● Provide insulation for any drain pipes
that are installed indoors.
Support
pieces
0050_X_
Fig. 2-11
7
2-5. Checking the Drainage
After wiring and piping are completed, use the following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth
ready to catch and wipe up spilled water.
Do not supply power to the
unit until the tubing and
wiring to the outdoor unit
are completed.
(1)Take off the tube cover and through the opening,
slowly pour about 1,200 cc of water into the drain
pan to check drainage.
(2)Do Test Run to check the drainage after complet-
ing installation. When performing Test Run, be
sure to observe the Test Run procedure.
Be careful since the fan will
CAUTION
start turning when checking
the drainage.
(3)After drain checking is finished, return the
Operation Selector switch to the RUN position
(ON position ) and remount the tube cover.
4 × 8
tapping screw
CAUTION
To mount the tube cover,
××
use 4
× 8 tapping screws. Do
××
not use long screws as they
may puncture the drain pan
and cause water leakage.
Tube cover
Siphon
2263_X_I
Fig. 2-12
8
■Ceiling Panel
Never touch or attempt to
CAUTION
move the air direction louver
by hand or you may damage
the unit. Instead, use the
remote control unit if you
want to change the direction
or air flow.
2-6. Before Installing the Ceiling Panel
(1)Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 2-13 and 2-14)
(a)Remove the 2 screws on the latch of the air-
intake grille. (Fig. 2-13)
(b)Press on the 2 latches of the air-intake grille
with your thumb in the direction of the arrow
to open the grille. (Fig. 2-13)
(c)With the air-intake grille open about 45˚,
remove the safety string (hook on the grille
side). (Fig. 2-14)
(d)Pull the air-intake grille towards you to
remove it from the ceiling panel.
Latch
Screw
Air intake grille
(2)Pull down the two panel catches on the body of
the indoor unit body. (Fig. 2-15)
Ceiling panel
0149_X_I
Fig. 2-13
Air filter
45°
Safety string
9
0150_X_I
Fig. 2-14
2-7. Installing the Ceiling Panel
10
(1)Lift the ceiling panel and position it to align the
panel hook with the panel catch of the indoor unit.
NOTE
The ceiling panel must be mounted in the correct
direction. Note that the 2 catches of the panel differ in
size.
Confirm that the catches are correctly matched between the ceiling panel and the indoor unit body.
(2)Next, check to see that the ceiling panel is prop-
erly aligned with the seamline of the ceiling. If it is
not, remove the ceiling panel and slightly readjust
the indoor unit body to the proper suspension
point.
(3)When the ceiling panel has been properly
aligned, use the supplied 4 mounting screws (M5)
with washers to permanently fasten the ceiling
panel.
(4)Install the wiring connector from the ceiling panel
to the connector in the electrical component box
of the indoor unit. After installing the connector,
use the clamp on the body of the indoor unit to
secure the wiring.
(5)Install the air filter and air-intake grille by perform-
ing the steps in section 2-6 in reverse.
NOTE
Rehook the safety string before closing the air-intake
grille.
2-8. When Removing the Ceiling Panel for
Servicing
When removing the ceiling panel for servicing, remove
the air-intake grille and air filter, disconnect the wiring
connector inside the electrical component box, and
then remove the 4 mounting screws.
Ceiling panel
Clamp
Ceiling panel wiring
connector
Electrical
component box
Panel catch
Electrical
component box
Unit body
Panel catch
(arrange facing downwards)
(2 locations)
Screws M5 with washer
(supplied)
Air filter
Fig. 2-15
Air-intake grille
1973_X_I
2-9. Duct for Fresh Air
11
● There is a duct connection part on sideface of the
indoor unit. (Fig. 2-16)
● Optional air-intake plenum (including duct connection
box and flange) can be attached to the indoor unit.
For fresh air intake
Air-intake plenumType
CMB-GSJ80U 25
CMB-GSJ140U36, 48
(1) Accessories
● Check that the following parts are in the box when unpacking.
Installation steps (a) to (e) are the same for both the
CMB-GSJ80U and the GSJ140U. The drawing
illustrates installation of air-intake plenum to the
CMB-GSJ80U.
Installation
screws
(a) Installing the air-intake plenum
● Set the air-intake plenum to the indoor unit taking
care not to set the incorrect direction. (Fig. 2-17)
● Fasten the air-intake plenum with the accessory
screws. (M5 × L125, 4pcs) (Fig. 2-17)
4-ø3.1 hole
60
55
Detail of fresh air intake
Fig. 2-16
ø112
2264_X_S
)
Socket cover
Panel lead wire (8P)
(b) Installing the duct connection box
● Fasten the duct connection flange to the duct
connection box with the accessory screws.
(M4 × L12, 4pcs) (Fig. 2-18)
● Put the duct connection box into the rectangular
hole of the air-intake plenum and fasten it to the
both sides of the indoor unit and plenum with the
accessory screws. (M4 × L12, 3pcs) (Fig. 2-18)
(c) Installing the indoor unit
● Install the indoor unit to the ceiling.
(Install the indoor unit according to items 2-1 to 2-6.)
When installing in a pre-
CAUTION
existing location, install the
indoor unit before installing
the duct connection box.
Air-intake
plenum
Indoor unit
Clamper
8P socket (red)
(electrical
component box)
8P socket (red)
(ceiling panel side)
1975_X_S
Fig. 2-17
(e) Installing the ceiling panel
12
● Attach the ceiling panel to the chamber.
Drawing the panel downwards sets the panel in
position temporarily with the panel catch (at 2
locations).
● Remove the socket cover of the air-intake plenum
and pass the 8P sockets through it. (Fix the panel
lead wire to chamber side clamper.) (Fig. 2-17)
● Connect the 8P socket (electrical component box
side) to the 8P socket (ceiling panel side) of the
indoor unit electrical component box.
● Reattach the socket cover.
Duct
connection
flange
Installation screws
(M4 × 12)
Panel catch
Ceiling panel
Duct connection box
2265_X_S
Fig. 2-18
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.