Sanyo SPW-XDR184GH56A, SPW-XDR184GH56B, SPW-XDR254GH56A, SPW-XDR254GH56B, SPW-XDR364GH56A Technical Data & Service Manual

...
Page 1
TECHNICAL DATA
&
SERVICE MANUAL
Indoor Unit
Class 18 25 36 48
4-Way Air Discharge
X
Semi-Concealed
4-Way Air Discharge
XM
Semi-Concealed
K Wall-Mounted
T Ceiling-Mounted
Concealed-Duct
U
US
Concealed-Duct
Concealed-Duct
D
High-Static Pressure
Indoor Unit
4-Way Air Discharge Semi-Concealed
Wall-Mounted
Ceiling-Mounted
Concealed-Duct
Concealed-Duct High-Static Pressure
SPW­XDR184GH56(A/B) X185H X255H X365H X485H
SPW­XM185H
SPW­KR184GH56(A/B)
SPW­TDR184GH56(A/B) T185H T255H T365H T485H
SPW­UR184GH56(A/B) U185H U255H U365H U485H UR184SH56B U185SHT U255SHT U365SHT U485SHT
SPW­US185H
SPW­XDR254GH56(A/B)
SPW­KR254GH56(A/B)
SPW­TDR254GH56(A/B)
SPW­UR254GH56(A/B)
UR254SH56B UR364SH56B UR484SH56B
SPW­XDR364GH56(A/B)
SPW­TDR364GH56(A/B)
SPW­UR364GH56(A/B)
SPW­XDR484GH56(A/B)
SPW­TDR484GH56(A/B)
SPW­UR484GH56(A/B)
Outdoor Unit
SPW-C706VH8, SPW-C906VH8
70 90
SPW­D705H
SPW­D905H
Outdoor Unit ( )
Class 70 90
Heat Pump Unit
C
(3-phase)
85464849261000
SPW­C706VH8
SPW­C906VH8
REFERENCE NO.
Page 2
Page 3
<
Page 4
Combination of Indoor and Outdoor Units
18 25 36 48 70 90
SPW-XDR184GH56(A/B)x4/ SPW-XDR254GH56(A/B)x3/ SPW-XDR364GH56(A/B)x2/ SPW-XDR484GH56(A/B)x2/ SPW-C706VH8
P2 SPW-C706VH8 SPW-C706VH8
P4
SPW-X185Hx4/ SPW-X255Hx3/ SPW-X365Hx2/ SPW-X485Hx2/ SPW-C706VH8
X
P3
SPW-XDR254GH56(A/B)x4/ SPW-C906VH8
P5
P6
SPW-X255Hx4/
SPW-XM185Hx4/
XM
SPW-C706VH8
SPW-C906VH8
P12
P7
SPW-KR184GH56(A/B)x4/ SPW-KR254GH56(A/B)x3/
SPW-C706VH8
K
P13 SPW-C706VH8
SPW-KR254GH56(A/B)x4/
SPW-C906VH8
P14
P15
SPW-TDR184GH56(A/B)x4/ SPW-TDR254GH56(A/B)x3/ SPW-TDR364GH56(A/B)x2/ SPW-TDR484GH56(A/B)x2/
SPW-C706VH8 SPW-C706VH8 SPW-C706VH8 SPW-C906VH8
P16
P18
SPW-T185Hx4/ SPW-T255Hx3/ SPW-T365Hx2/ SPW-T485Hx2/
SPW-C706VH8
T
P17
SPW-C706VH8 SPW-C706VH8
P19
SPW-TDR254GH56(A/B)x4/
SPW-C906VH8
P20
SPW-T255Hx4/
SPW-C906VH8
P21
SPW-UR184GH56(A/B)x4/ SPW-UR254GH56(A/B)x3/ SPW-UR364GH56(A/B)x2 SPW-UR484GH56(A/B)x2/ SPW-C706VH8 SPW-C706VH8 SPW-C706VH8 SPW-C906VH8
P26
P30
SPW-U185Hx4/ SPW-U255Hx3/ SPW-U365Hx2/ SPW-U485Hx2/ SPW-C706VH8 SPW-C706VH8 SPW-C706VH8 SPW-C906VH8
P27
P31
SPW-UR184SH56Bx4/ SPW-UR254SH56Bx3/ SPW-U364SH56Bx2/ SPW-U484SH56Bx2/ SPW-C706VH8
SPW-U185SHTx4/ SPW-C706VH8
U
SPW-C706VH8
P28
SPW-U255SHTx3/ SPW-C706VH8
P29
SPW-UR254GH56(A/B)x4/ SPW-C906VH8
SPW-C706VH8
P32
SPW-U365SHTx2/ SPW-C706VH8
P33
P34
SPW-U255Hx4/ SPW-C906VH8
P35
SPW-UR254SH56Bx4/ SPW-C906VH8
P36
SPW-U255SHTx4/
SPW-US185Hx4/
US
SPW-C706VH8
SPW-C906VH8
P46
P37
D
SPW-C906VH8
P8
SPW-C906VH8
P9
P22
P23
SPW-C906VH8
P38
P39
SPW-C906VH8
P40
SPW-U485SHTx2/ SPW-C906VH8
P41
P10
P11SPW-C706VH8 SPW-C706VH8
P24
P25
P42
P43
P44
P45
SPW-D705H SPW-D905H SPW-C706VH8 SPW-C906VH8
P47 P48
Page 5
—— CONTENTS ——
Section 1. SPECIFICATIONS ............................................................................................ 1-1
1-1. Unit Specifications ........................................................................................................... 1-2
1-2. Major Component Specifications..................................................................................... 1-49
1-3. Other Component Specifications..................................................................................... 1-69
1-4. Dimensional Data ............................................................................................................ 1-77
1-5. Refrigerant Flow Diagram................................................................................................ 1-92
1-6. Operating Range .............................................................................................................. 1-92
1-7. Capacity Correction Graph According to Temperature Condition .................................... 1-93
1-8. Noise Criterion Curves..................................................................................................... 1-94
1-9. Indoor Fan Performance.................................................................................................. 1-102
1-10. Airflow Distance Chart ..................................................................................................... 1-104
1-11. Intaking Fresh Air of Semi-Concealed Type and Concealed-Duct Type ......................... 1-113
1-12. Installation Instructions .................................................................................................... 1-115
Section 2. TEST RUN ........................................................................................................ 2-1
2-1. Preparing for Test Run ................................................................................................... 2-2
X, XM, T, U, US, D Types ................................................................................................ 2-3
K Type ............................................................................................................................. 2-9
X, T, U, D Types (for Link Wiring) .................................................................................... 2-16
K Type (for Link Wiring) .................................................................................................. 2-21
XM Type (for Link Wiring) ............................................................................................... 2-27
Section 3. ELECTRICAL DATA ......................................................................................... 3-1
3-1. Indoor Units (Electric Wiring Diagram, Schematic Diagram)........................................... 3-2
3-2. Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ........................................ 3-23
Section 4. PROCESS AND FUNCTIONS.......................................................................... 4-1
4-1. Control Functions............................................................................................................. 4-2
4-2. Outdoor Unit Control PCB .............................................................................................. 4-8
4-3. Indoor Unit Control PCB Switches and Functions ........................................................... 4-11
Section 5. SERVICE PROCEDURES ................................................................................ 5-1
5-1. Meaning of Alarm Messages ........................................................................................... 5-2
5-2. Contents of LED Display on the Outdoor Unit Control PCB ............................................ 5-4
5-3. Symptoms and Parts to Inspect ...................................................................................... 5-5
5-4. Details of Alarm Messages.............................................................................................. 5-8
5-5. Table of Thermistor Characteristics .................................................................................
5-6. How to Remove the Compressor .................................................................................... 5-15
5-7. How to Remove the Electrical Component Box .............................................................. 5-16
Section 6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL................................ 6-1
6-1. Overview.......................................................................................................................... 6-2
6-2. Functions ......................................................................................................................... 6-2
6-3. Normal Display Operations and Functions ...................................................................... 6-3
6-4.
Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures
6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ........ 6-7
6-6. Settings Modes: Setting the Outdoor Unit EEPROM ...................................................... 6-7
Section 7. REMOTE CONTROLLER FUNCTIONS SECTION.......................................... 7-1
7-1. Simple Settings Function................................................................................................. 7-2
7-2. List of Simple Setting Items ............................................................................................. 7-3
7-3. Detailed Settings Function............................................................................................... 7-4
7-4. List of Detailed Setting Items........................................................................................... 7-5
7-5. Simple Setting Items........................................................................................................
7-6. Detailed Setting Items ..................................................................................................... 7-12
7-7. Remote Controller Servicing Functions ........................................................................... 7-16
7-8. Test Run Function ........................................................................................................... 7-16
Section 8.
HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER
Warning ........................................................................................................................... 8-2
RCS-SH80BG.WL for 4-Way Cassette (X Type) ............................................................ 8-3
RCS-TRP80BG.WL for Ceiling Mounted (T Type) .......................................................... 8-6
RCS-BH80BG.WL for XM, U and US Types .................................................................. 8-9
Common to All Models .................................................................................................... 8-12
5-14
..... 6-6
7-9
.... 8-1
Page 6
1. SPECIFICATIONS
1-1. Unit Specifications................................................................................................... 1-2
4-Way Air Discharge Semi-Concealed Type ......................................................................................... 1-2
Wall-Mounted Type ............................................................................................................................... 1-13
Ceiling-Mounted Type ........................................................................................................................... 1-16
Concealed-Duct Type ............................................................................................................................ 1-26
1-2. Major Component Specifications ........................................................................... 1-49
(A) Indoor Units ..................................................................................................................................... 1-49
(B) Outdoor Units .................................................................................................................................. 1-67
1-3. Other Component Specifications ........................................................................... 1-69
4-Way Air Discharge Semi-Concealed Type ......................................................................................... 1-69
Wall-Mounted Type ............................................................................................................................... 1-71
Ceiling-Mounted Type ........................................................................................................................... 1-72
Concealed-Duct Type ............................................................................................................................ 1-73
Outdoor Units ........................................................................................................................................ 1-75
1-4. Dimensional Data ..................................................................................................... 1-77
(A) Indoor Units ..................................................................................................................................... 1-77
4-Way Air Discharge Semi-Concealed Type ................................................................................... 1-77
Wall-Mounted Type .......................................................................................................................... 1-80
Ceiling-Mounted Type ...................................................................................................................... 1-81
Concealed-Duct Type ...................................................................................................................... 1-82
(B) Outdoor Units .................................................................................................................................. 1-90
1
1-5. Refrigerant Flow Diagram ....................................................................................... 1-92
1-6. Operating Range ...................................................................................................... 1-92
1-7. Capacity Correction Graph According to Temperature Condition ...................... 1-93
1-8. Noise Criterion Curves ............................................................................................ 1-94
1-9. Indoor Fan Performance .......................................................................................... 1-102
1-10. Airflow Distance Chart ............................................................................................ 1-104
1-11. Intaking Fresh Air of Semi-Concealed Type and Concealed-Duct Type.............. 1-113
1-12. Installation Instructions .......................................................................................... 1-115
Tubing Length ....................................................................................................................................... 1-115
Optional Distribution Joint Kits .............................................................................................................. 1-119
Installing Distribution Joint Kit (for Twin & Double-Twin) ....................................................................... 1-120
Installing Distribution Joint Kit (for Triple) .............................................................................................. 1-121
SELECTING THE INSTALLATION SITE ............................................................................................... 1-122
Dimensions of Air-Discharge Chamber ................................................................................................ 1-125
Dimensions of Wind-proof Duct ............................................................................................................ 1-131
Dimensions of Snow-proof Duct ........................................................................................................... 1-132
HOW TO INSTALL THE OUTDOOR UNIT ........................................................................................... 1-135
ELECTRICAL WIRING ......................................................................................................................... 1-136
1-1
Page 7
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XDR184GH56 (A/B) x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.8 (2.2 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 9.9 9.5 9.2 9.6 9.3 9.0 Max–Running amperes** A – Power input kW 6.08 6.08 6.08 5.93 5.93 5.93 C.O.P W / W 3.29 3.29 3.29 3.78 3.78 3.78 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 291 (11-15 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25.5 (56) 118 (260) Shipping weight kg (lb.) 24 (53) 7 (16) 128 (282) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 283 (11-5 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-XDR184GH56 (A/B) x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,840 / 3,360 / 3,120 (960 / 840 / 780 x4)
dB-A 34 / 31 / 28
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.228 (8.1) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-2
1
Page 8
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-X185H x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.8 (2.2 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 9.9 9.5 9.2 9.6 9.3 9.0 Max–Running amperes** A – Power input kW 6.08 6.08 6.08 5.93 5.93 5.93 C.O.P W / W 3.29 3.29 3.29 3.78 3.78 3.78 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 291 (11-15 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25.5 (56) 118 (260) Shipping weight kg (lb.) 24 (53) 7 (16) 128 (282) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 283 (11-5 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-X185H x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,840 / 3,360 / 3,120 (960 / 840 / 780 x4)
dB-A 34 / 31 / 28
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.228 (8.1) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-3
1
1
Page 9
1
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XDR254GH56 (A/B) x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.4 (2.8 x3)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 9.9 9.4 9.1 9.6 9.3 9.0 Max–Running amperes** A – Power input kW 6.07 6.06 6.06 5.93 5.93 5.93 C.O.P W / W 3.29 3.30 3.30 3.78 3.78 3.78 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 291 (11-15 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 26.5 (58) 118 (260) Shipping weight kg (lb.) 25 (55) 7 (16) 128 (282) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 283 (11-5 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-XDR254GH56 (A/B) x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,600 / 2,880 / 2,520 (1,200 / 960 / 840 x3)
dB-A 34 / 31 / 28
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.228 (8.1) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-4
1
Page 10
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-X255H x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.4 (2.8 x3)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 9.9 9.4 9.1 9.6 9.3 9.0 Max–Running amperes** A – Power input kW 6.07 6.06 6.06 5.93 5.93 5.93 C.O.P W / W 3.29 3.30 3.30 3.78 3.78 3.78 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 291 (11-15 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 26.5 (58) 118 (260) Shipping weight kg (lb.) 25 (55) 7 (16) 128 (282) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 283 (11-5 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-X255H x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,600 / 2,880 / 2,520 (1,200 / 960 / 840 x3)
dB-A 34 / 31 / 28
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.228 (8.1) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-5
1
1
Page 11
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XDR254GH56 (A/B) x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 11.2 (2.8 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 12.6 12.1 11.7 12.1 11.6 11.2 Max–Running amperes** A – Power input kW 7.78 7.77 7.77 7.43 7.43 7.43 C.O.P W / W 3.21 3.22 3.22 3.77 3.77 3.77 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 291 (11-15 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 26.5 (58) 128 (282) Shipping weight kg (lb.) 25 (55) 7 (16) 138 (304) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 283 (11-5 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-XDR254GH56 (A/B) x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,800 / 3,840 / 3,360 (1,200 / 960 / 840 x4)
dB-A 34 / 31 / 28
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.228 (8.1) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-6
1
Page 12
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-X255H x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 11.2 (2.8 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 12.6 12.1 11.7 12.1 11.6 11.2 Max–Running amperes** A – Power input kW 7.78 7.77 7.77 7.43 7.43 7.43 C.O.P W / W 3.21 3.22 3.22 3.77 3.77 3.77 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 291 (11-15 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 26.5 (58) 128 (282) Shipping weight kg (lb.) 25 (55) 7 (16) 138 (304) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 283 (11-5 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-X255H x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,800 / 3,840 / 3,360 (1,200 / 960 / 840 x4)
dB-A 34 / 31 / 28
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.228 (8.1) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-7
1
1
Page 13
1
Simultaneous (Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XDR364GH56 (A/B) x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 7.8 (3.9 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 9.9 9.5 9.2 9.7 9.4 9.0 Max–Running amperes** A – Power input kW 6.08 6.08 6.08 5.96 5.96 5.96 C.O.P W / W 3.29 3.29 3.29 3.76 3.76 3.76 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 354 (13-30 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 30.5 (58) 118 (260) Shipping weight kg (lb.) 30 (66) 7 (16) 128 (282) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 346 (13-20 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-XDR364GH56 (A/B) x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 5,040 / 4,140 / 3,780 (1,680 / 1,380 / 1,260 x2)
dB-A 39 / 36 / 33
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.279 (9.9) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-8
1
Page 14
Simultaneous (Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-X365H x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 7.8 (3.9 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 9.9 9.5 9.2 9.7 9.4 9.0 Max–Running amperes** A – Power input kW 6.08 6.08 6.08 5.96 5.96 5.96 C.O.P W / W 3.29 3.29 3.29 3.76 3.76 3.76 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 354 (13-30 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 30.5 (58) 118 (260) Shipping weight kg (lb.) 30 (66) 7 (16) 128 (282) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 346 (13-20 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-X365H x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,360 / 1,380 / 1,260 (1,680 / 1,380 / 1,260 x2)
dB-A 39 / 36 / 33
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.279 (9.9) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-9
1
1
Page 15
1
Simultaneous (Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XDR484GH56 (A/B) x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 9.2 (4.6 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 12.7 12.2 11.8 12.2 11.7 11.3 Max–Running amperes** A – Power input kW 7.81 7.80 7.80 7.50 7.50 7.50 C.O.P W / W 3.20 3.21 3.21 3.73 3.73 3.73 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 354 (13-30 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 30.5 (58) 128 (282) Shipping weight kg (lb.) 30 (66) 7 (16) 138 (304) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 346 (13-20 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-XDR484GH56 (A/B) x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,960 / 3,000 / 2,640 (1,980 / 1,500 / 1,320 x2)
dB-A 42 / 38 / 34
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.279 (9.9) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-10
1
Page 16
Simultaneous (Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-X485H x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 9.2 (4.6 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 12.7 12.2 11.8 12.2 11.7 11.3 Max–Running amperes** A – Power input kW 7.81 7.80 7.80 7.50 7.50 7.50 C.O.P W / W 3.20 3.21 3.21 3.73 3.73 3.73 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 354 (13-30 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 30.5 (58) 128 (282) Shipping weight kg (lb.) 30 (66) 7 (16) 138 (304) Shipping volume m
Width mm (in.) 950 (37-13 / 32) 940 (37-1 / 64) Depth mm (in.) 950 (37-13 / 32) 340 (13-25 / 64)
Height mm (in.) 346 (13-20 / 32) 104 (4-3 / 32) 1676 (65-63 / 64) Width mm (in.) 892 (35-4 / 32) 1008 (39-22 / 32) 1076 (42-23 / 64) Depth mm (in.) 905 (35-20 / 32) 990 (38-31 / 32) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-X485H x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,960 / 3,000 / 2,640 (1,980 / 1,500 / 1,320 x2)
dB-A 42 / 38 / 34
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.279 (9.9) 0.104 (3.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-11
1
1
Page 17
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XM185H x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 7.6 (1.9 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.8 10.4 10.0 10.3 10.0 9.7 Max–Running amperes** A – Power input kW 6.62 6.63 6.63 6.36 6.36 6.36 C.O.P W / W 3.02 3.02 3.02 3.52 3.52 3.52 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 2.5GY 9.0 / 0.5 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 313 (12-21 / 64) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 18.4 (40.6) 118 (260) Shipping weight kg (lb.) 19 (41.9) 3.5 (7.7) 128 (282) Shipping volume m
Width mm (in.) 625 (24-39 / 64) 940 (37-1 / 64) Depth mm (in.) 625 (24-39 / 64) 340 (13-25 / 64)
Height mm (in.) 290 (11-27 / 64) 105 (4-9 / 64) 1676 (65-63 / 64) Width mm (in.) 714 (28-7 / 64) 665 (26-3 / 64) 1076 (42-23 / 64) Depth mm (in.) 630 (24-51 / 64) 678 (26-11 / 64) 420 (16-17 / 32)
NOTENOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-XM185H x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,000 / 2,520 / 2,160 (750 / 630 / 540 x4)
dB-A 41 / 37 / 33
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.13 (4.6) 0.047 (1.7) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit (include panel) Outdoor unit
Body Panel Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-12
1
Page 18
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Wall-Mounted Type SPW-KR184GH56 (A/B) x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.4 (2.1 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.3 9.8 9.5 10.2 9.9 9.5 Max–Running amperes** A –––– Power input kW 6.36 6.36 6.37 6.33 6.33 6.34 C.O.P W / W 3.14 3.14 3.14 3.54 3.54 3.53 Max.Starting amperes A ––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 3.0Y 8.6 / 0.8 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 285 (11-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 12 (27) 118 (260) Shipping weight kg (lb.) 15 (33) 128 (282) Shipping volume m
Width mm (in.) 995 (39-6 / 32) 940 (37-1 / 64) Depth mm (in.) 203 (8) 340 (13-25 / 64) Height mm (in.) 347 (13-21 / 32) 1676 (65-63 / 64) Width mm (in.) 1,065 (41-30 / 32) 1076 (42-23 / 64) Depth mm (in.) 260 (10-8 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-KR184GH56 (A/B) x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,120 / 2,640 / 1,920 (780 / 660 / 480 x4)
dB-A 38 / 34 / 30
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.096 (3.4) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1
1-13
Page 19
1
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
Wall-Mounted Type SPW-KR254GH56 (A/B) x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 12.0 (4.0 x3)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.3 9.9 9.6 10.2 9.9 9.6 Max–Running amperes** A – Power input kW 6.38 6.39 6.40 6.35 6.36 6.37 C.O.P W / W 3.13 3.13 3.13 3.53 3.52 3.52 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 3.0Y 8.6 / 0.8 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 330 (13) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 21 (46) 118 (260) Shipping weight kg (lb.) 24 (53) 128 (282) Shipping volume m
Width mm (in.) 1,140 (44-28 / 32) 940 (37-1 / 64) Depth mm (in.) 228 (8-31 / 32) 340 (13-25 / 64) Height mm (in.) 390 (15-11 / 32) 1676 (65-63 / 64) Width mm (in.) 1,215 (47-27 / 32) 1076 (42-23 / 64) Depth mm (in.) 293 (11-17 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-KR254GH56 (A/B) x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,420 / 2,880 / 2,160 (1,140 / 960 / 720 x3)
dB-A 41 / 37 / 34
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.139 (4.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1-14
Page 20
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Wall-Mounted Type SPW-KR254GH56 (A/B) x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 16.0 (4.0 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 13.8 13.3 12.8 12.9 12.4 12.0 Max–Running amperes** A –––––– Power input kW 8.56 8.57 8.58 8.01 8.02 8.03 C.O.P W / W 2.92 2.92 2.91 3.50 3.49 3.49 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 3.0Y 8.6 / 0.8 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 330 (13) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 21 (46) 128 (282) Shipping weight kg (lb.) 24 (53) 138 (304) Shipping volume m
Width mm (in.) 1,140 (44-28 / 32) 940 (37-1 / 64) Depth mm (in.) 228 (8-31 / 32) 340 (13-25 / 64) Height mm (in.) 390 (15-11 / 32) 1676 (65-63 / 64) Width mm (in.) 1,215 (47-27 / 32) 1076 (42-23 / 64) Depth mm (in.) 293 (11-17 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-KR254GH56 (A/B) x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,560 / 3,840 / 2,880 (1,140 / 960 / 720 x4)
dB-A 41 / 37 / 34
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.139 (4.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1
1-15
Page 21
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-TDR184GH56 (A/B) x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.0 (2.0 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.2 10.7 10.3 10.2 9.9 9.5 Max–Running amperes** A – Power input kW 6.85 6.85 6.85 6.27 6.27 6.27 C.O.P W / W 2.92 2.92 2.92 3.57 3.57 3.57 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units
Refrigerant tube outer diameter
Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 21 (46) 118 (260) Shipping weight kg (lb.) 24 (53) 128 (282) Shipping volume m
Width mm (in.) 910 (35-26 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 985 (38-25 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-TDR184GH56 (A/B) x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,120 / 2,640 / 2,160 (780 / 660 / 540 x4)
Wireless: RCS-TRP80BG.WL
dB-A 36 / 33 / 30
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.215 (7.6) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1-16
Page 22
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-T185H x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.0 (2.0 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.2 10.7 10.3 10.2 9.9 9.5 Max–Running amperes** A – Power input kW 6.85 6.85 6.85 6.27 6.27 6.27 C.O.P W / W 2.92 2.92 2.92 3.57 3.57 3.57 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 21 (46) 118 (260) Shipping weight kg (lb.) 24 (53) 128 (282) Shipping volume m
Width mm (in.) 910 (35-26 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 985 (38-25 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-T185H x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,120 / 2,640 / 2,160 (780 / 660 / 540 x4)
Wireless: RCS-TRP80BG.WL
dB-A 36 / 33 / 30
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.215 (7.6) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1
1-17
Page 23
1
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-TDR254GH56 (A/B) x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 9.0 (3.0 x3)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.2 10.7 10.4 10.2 9.9 9.5 Max–Running amperes** A – Power input kW 6.85 6.85 6.86 6.27 6.27 6.27 C.O.P W / W 2.92 2.92 2.92 3.57 3.57 3.57 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 118 (260) Shipping weight kg (lb.) 28 (62) 128 (282) Shipping volume m
Width mm (in.) 1,180 (46-15 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,255 (49-13 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-TDR254GH56 (A/B) x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,300 / 2,700 / 2,520 (1,100 / 900 / 840 x3)
Wireless: RCS-TRP80BG.WL
dB-A 38 / 36 / 33
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.274 (9.7) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1-18
Page 24
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-T255H x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 9.0 (3.0 x3)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.2 10.7 10.4 10.2 9.9 9.5 Max–Running amperes** A – Power input kW 6.85 6.85 6.86 6.27 6.27 6.27 C.O.P W / W 2.92 2.92 2.92 3.57 3.57 3.57 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 118 (260) Shipping weight kg (lb.) 28 (62) 128 (282) Shipping volume m
Width mm (in.) 1,180 (46-15 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,255 (49-13 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-T255H x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,300 / 2,700 / 2,520 (1,100 / 900 / 840 x3)
Wireless: RCS-TRP80BG.WL
dB-A 38 / 36 / 33
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.274 (9.7) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1
1-19
Page 25
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-TDR254GH56 (A/B) x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 12.0 (3.0 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.7 14.1 13.7 12.9 12.4 11.9 Max–Running amperes** A – Power input kW 9.05 9.05 9.05 7.93 7.93 7.94 C.O.P W / W 2.76 2.76 2.76 3.53 3.53 3.53 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 128 (282) Shipping weight kg (lb.) 28 (62) 138 (304) Shipping volume m
Width mm (in.) 1,180 (46-15 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,255 (49-13 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-TDR254GH56 (A/B) x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,400 / 3,600 / 3,360 (1,100 / 900 / 840 x4)
Wireless: RCS-TRP80BG.WL
dB-A 38 / 36 / 33
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.274 (9.7) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1-20
Page 26
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-T255H x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 12.0 (3.0 x4)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.7 14.1 13.7 12.9 12.4 11.9 Max–Running amperes** A –––––– Power input kW 9.05 9.05 9.05 7.93 7.93 7.94 C.O.P W / W 2.76 2.76 2.76 3.53 3.53 3.53 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 128 (282) Shipping weight kg (lb.) 28 (62) 138 (304) Shipping volume m
Width mm (in.) 1,180 (46-15 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,255 (49-13 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-T255H x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,400 / 3,600 / 3,360 (1,100 / 900 / 840 x4)
Wireless: RCS-TRP80BG.WL
dB-A 38 / 36 / 33
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.274 (9.7) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1
1-21
Page 27
1
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-TDR364GH56 (A/B) x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 7.8 (3.9 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.2 10.7 10.4 10.2 9.9 9.6 Max–Running amperes** A – Power input kW 6.87 6.87 6.87 6.29 6.29 6.29 C.O.P W / W 2.91 2.91 2.91 3.56 3.56 3.56 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 33 (73) 118 (260) Shipping weight kg (lb.) 37 (82) 128 (282) Shipping volume m
Width mm (in.) 1,595 (62-25 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,670 (65-24 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-TDR364GH56 (A/B) x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,300 / 2,760 / 2,400 (1,650 / 1,380 / 1,200 x2)
Wireless: RCS-TRP80BG.WL
dB-A 41 / 38 / 35
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.365 (12.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1-22
Page 28
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-T365H x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 7.8 (3.9 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.2 10.7 10.4 10.2 9.9 9.6 Max–Running amperes** A – Power input kW 6.87 6.87 6.87 6.29 6.29 6.29 C.O.P W / W 2.91 2.91 2.91 3.56 3.56 3.56 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 33 (73) 118 (260) Shipping weight kg (lb.) 37 (82) 128 (282) Shipping volume m
Width mm (in.) 1,595 (62-25 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,670 (65-24 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-T365H x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,300 / 2,760 / 2,400 (1,650 / 1,380 / 1,200 x2)
Wireless: RCS-TRP80BG.WL
dB-A 41 / 38 / 35
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.365 (12.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1
1-23
Page 29
1
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-TDR484GH56 (A/B) x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 11.2 (5.6 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.7 14.1 13.6 12.9 12.3 11.9 Max–Running amperes** A – Power input kW 9.04 9.05 9.05 7.93 7.93 7.94 C.O.P W / W 2.77 2.76 2.76 3.53 3.53 3.53 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 33 (73) 128 (282) Shipping weight kg (lb.) 37 (82) 138 (304) Shipping volume m
Width mm (in.) 1,595 (62-25 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,670 (65-24 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-TDR484GH56 (A/B) x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,600 / 3,120 / 2,640 (1,800 / 1,560 / 1,320 x2)
Wireless: RCS-TRP80BG.WL
dB-A 43 / 40 / 37
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.365 (12.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1-24
Page 30
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Ceiling-Mounted Type SPW-T485H x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 11.2 (5.6 x2)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.7 14.1 13.6 12.9 12.3 11.9 Max–Running amperes** A –––––– Power input kW 9.04 9.05 9.05 7.93 7.93 7.94 C.O.P W / W 2.77 2.76 2.76 3.53 3.53 3.53 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) Automatic (Remote control) Air filter Washable, easy access, long life (2,500 hr) Remote controller (Option) Wired: RCS-TM80BG / Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor Munsell 10Y 9.3 / 0.4 Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 210 (8-9 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 33 (73) 128 (282) Shipping weight kg (lb.) 37 (82) 138 (304) Shipping volume m
Width mm (in.) 1,595 (62-25 / 32) 940 (37-1 / 64) Depth mm (in.) 680 (26-25 / 32) 340 (13-25 / 64) Height mm (in.) 280 (11-1 / 32) 1676 (65-63 / 64) Width mm (in.) 1,670 (65-24 / 32) 1076 (42-23 / 64) Depth mm (in.) 780 (30-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-T485H x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,600 / 3,120 / 2,640 (1,800 / 1,560 / 1,320 x2)
Wireless: RCS-TRP80BG.WL
dB-A 43 / 40 / 37
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.365 (12.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
1
1-25
Page 31
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR184GH56 (A/B) x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 12.0 (3.0 x4) – External static pressure (High) Pa (mmAg) 40 (4.1): at shipment, 62 (6.3): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.5 10.1 9.8 10.3 10.0 9.7 Max–Running amperes** A – Power input kW 6.52 6.54 6.57 6.44 6.47 6.50 C.O.P W / W 3.07 3.06 3.04 3.48 3.46 3.45 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 118 (260) Shipping weight kg (lb.) 29 (64) 128 (282) Shipping volume m
Width mm (in.) 700 (27-18 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 891 (35-3 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR184GH56 (A/B) x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 2,880 / 2,520 / 2,160 (720 / 630 / 540 x4)
dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.250 (8.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-26
1
Page 32
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U185H x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 12.0 (3.0 x4) – External static pressure (High) Pa (mmAg) 40 (4.1): at shipment, 62 (6.3): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.5 10.1 9.8 10.3 10.0 9.7 Max–Running amperes** A –––––– Power input kW 6.52 6.54 6.57 6.44 6.47 6.50 C.O.P W / W 3.07 3.06 3.04 3.48 3.46 3.45 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 118 (260) Shipping weight kg (lb.) 29 (64) 128 (282) Shipping volume m
Width mm (in.) 700 (27-18 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 891 (35-3 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U185H x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 2,880 / 2,520 / 2,160 (720 / 630 / 540 x4)
dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.250 (8.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-27
1
1
Page 33
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR184SH56B x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 12.0 (3.0 x4) – External static pressure (High) Pa (mmAg) 40 (4.1): at shipment, 62 (6.3): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.5 10.1 9.8 10.3 10.0 9.7 Max–Running amperes** A – Power input kW 6.52 6.54 6.57 6.44 6.47 6.50 C.O.P W / W 3.07 3.06 3.04 3.48 3.46 3.45 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 118 (260) Shipping weight kg (lb.) 29 (64) 128 (282) Shipping volume m
Width mm (in.) 700 (27-9 / 16) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 325 (12-25 / 32) 1676 (65-63 / 64) Width mm (in.) 975 (38-3 / 8) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR184SH56B x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 2,880 / 2,520 / 2,160 (720 / 630 / 540 x4)
dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.247 (8.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-28
1
Page 34
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U185SHT x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 12.0 (3.0 x4) – External static pressure (High) Pa (mmAg) 40 (4.1): at shipment, 62 (6.3): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.5 10.1 9.8 10.3 10.0 9.7 Max–Running amperes** A – Power input kW 6.52 6.54 6.57 6.44 6.47 6.50 C.O.P W / W 3.07 3.06 3.04 3.48 3.46 3.45 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 25 (55) 118 (260) Shipping weight kg (lb.) 29 (64) 128 (282) Shipping volume m
Width mm (in.) 700 (27-9 / 16) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 325 (12-25 / 32) 1676 (65-63 / 64) Width mm (in.) 975 (38-3 / 8) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U185SHT x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 2,880 / 2,520 / 2,160 (720 / 630 / 540 x4)
dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.247 (8.9) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-29
1
1
Page 35
1
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR254GH56 (A/B) x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 10.5 (3.5 x3) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.7 10.3 10.1 10.6 10.3 10.0 Max–Running amperes** A – Power input kW 6.68 6.72 6.77 6.61 6.66 6.70 C.O.P W / W 2.99 2.98 2.95 3.39 3.36 3.34 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 118 (260) Shipping weight kg (lb.) 37 (82) 128 (282) Shipping volume m
Width mm (in.) 1000 (39-12 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,191 (46-28 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR254GH56 (A/B) x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,240 / 2,700 / 2,340 (1,080 / 900 / 780 x3)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.334 (11.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-30
1
Page 36
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U255H x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 10.5 (3.5 x3) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.7 10.3 10.1 10.6 10.3 10.0 Max–Running amperes** A –––––– Power input kW 6.68 6.72 6.77 6.61 6.66 6.70 C.O.P W / W 2.99 2.98 2.95 3.39 3.36 3.34 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 118 (260) Shipping weight kg (lb.) 37 (82) 128 (282) Shipping volume m
Width mm (in.) 1000 (39-12 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,191 (46-28 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U255H x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,240 / 2,700 / 2,340 (1,080 / 900 / 780 x3)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.334 (11.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-31
1
1
Page 37
1
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR254SH56B x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 10.5 (3.5 x3) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.7 10.3 10.1 10.6 10.3 10.0 Max–Running amperes** A – Power input kW 6.68 6.72 6.77 6.61 6.66 6.70 C.O.P W / W 2.99 2.98 2.95 3.39 3.36 3.34 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 118 (260) Shipping weight kg (lb.) 37 (82) 128 (282) Shipping volume m
Width mm (in.) 1000 (39-3 / 8) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 325 (12-25 / 32) 1676 (65-63 / 64) Width mm (in.) 1,275 (50-3 / 16) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR254SH56B x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,240 / 2,700 / 2,340 (1,080 / 900 / 780 x3)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.322 (11.6) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-32
1
Page 38
Simultaneous(Triple)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U255SHT x3 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 10.5 (3.5 x3) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.7 10.3 10.1 10.6 10.3 10.0 Max–Running amperes** A –––––– Power input kW 6.68 6.72 6.77 6.61 6.66 6.70 C.O.P W / W 2.99 2.98 2.95 3.39 3.36 3.34 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 118 (260) Shipping weight kg (lb.) 37 (82) 128 (282) Shipping volume m
Width mm (in.) 1000 (39-3 / 8) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 325 (12-25 / 32) 1676 (65-63 / 64) Width mm (in.) 1,275 (50-3 / 16) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U255SHT x3
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,240 / 2,700 / 2,340 (1,080 / 900 / 780 x3)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.322 (11.6) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-33
1
1
Page 39
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR254GH56 (A/B) x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 14.0 (3.5 x4) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.4 13.9 13.5 13.5 13.0 12.6 Max–Running amperes** A – Power input kW 8.97 9.03 9.09 8.41 8.47 8.53 C.O.P W / W 2.79 2.77 2.75 3.33 3.31 3.28 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 128 (282) Shipping weight kg (lb.) 37 (82) 138 (304) Shipping volume m
Width mm (in.) 1000 (39-12 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,191 (46-28 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR254GH56 (A/B) x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,320 / 3,600 / 3,120 (1,080 / 900 / 780 x4)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.334 (11.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-34
1
Page 40
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U255H x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 14.0 (3.5 x4) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.4 13.9 13.5 13.5 13.0 12.6 Max–Running amperes** A –––––– Power input kW 8.97 9.03 9.09 8.41 8.47 8.53 C.O.P W / W 2.79 2.77 2.75 3.33 3.31 3.28 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 128 (282) Shipping weight kg (lb.) 37 (82) 138 (304) Shipping volume m
Width mm (in.) 1000 (39-12 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,191 (46-28 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U255H x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,320 / 3,600 / 3,120 (1,080 / 900 / 780 x4)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.334 (11.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-35
1
1
Page 41
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR254SH56B x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 14.0 (3.5 x4) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.4 13.9 13.5 13.5 13.0 12.6 Max–Running amperes** A – Power input kW 8.97 9.03 9.09 8.41 8.47 8.53 C.O.P W / W 2.79 2.77 2.75 3.33 3.31 3.28 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 128 (282) Shipping weight kg (lb.) 37 (82) 138 (304) Shipping volume m
Width mm (in.) 1000 (39-3 / 8) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 325 (12-25 / 32) 1676 (65-63 / 64) Width mm (in.) 1,275 (50-3 / 16) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR254SH56B x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,320 / 3,600 / 3,120 (1,080 / 900 / 780 x4)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.322 (11.6) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-36
1
Page 42
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U255SHT x4 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 14.0 (3.5 x4) – External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.4 13.9 13.5 13.5 13.0 12.6 Max–Running amperes** A –––––– Power input kW 8.97 9.03 9.09 8.41 8.47 8.53 C.O.P W / W 2.79 2.77 2.75 3.33 3.31 3.28 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 32 (71) 128 (282) Shipping weight kg (lb.) 37 (82) 138 (304) Shipping volume m
Width mm (in.) 1000 (39-3 / 8) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 325 (12-25 / 32) 1676 (65-63 / 64) Width mm (in.) 1,275 (50-3 / 16) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U255SHT x4
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,320 / 3,600 / 3,120 (1,080 / 900 / 780 x4)
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.322 (11.6) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-37
1
1
Page 43
1
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR364GH56 (A/B) x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.4 (4.2 x2) – External static pressure (High) Pa (mmAg) 79 (8.1): at shipment, 122 (12.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.9 10.5 10.2 10.8 10.4 10.1 Max–Running amperes** A – Power input kW 6.76 6.79 6.82 6.71 6.74 6.77 C.O.P W / W 2.96 2.95 2.93 3.34 3.32 3.31 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 118 (260) Shipping weight kg (lb.) 52 (115) 128 (282) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,671 (65-25 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR364GH56 (A/B) x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,600 / 3,120 / 2,520 (1,800 / 1,560 / 1,260 x2)
dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.468 (16.5) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-38
1
Page 44
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U365H x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.4 (4.2 x2) – External static pressure (High) Pa (mmAg) 79 (8.1): at shipment, 122 (12.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.9 10.5 10.2 10.8 10.4 10.1 Max–Running amperes** A – Power input kW 6.76 6.79 6.82 6.71 6.74 6.77 C.O.P W / W 2.96 2.95 2.93 3.34 3.32 3.31 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 118 (260) Shipping weight kg (lb.) 52 (115) 128 (282) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,671 (65-25 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U365H x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,600 / 3,120 / 2,520 (1,800 / 1,560 / 1,260 x2)
dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.468 (16.5) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-39
1
1
Page 45
1
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR364SH56B x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.4 (4.2 x2) – External static pressure (High) Pa (mmAg) 79 (8.1): at shipment, 122 (12.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.9 10.5 10.2 10.8 10.4 10.1 Max–Running amperes** A – Power input kW 6.76 6.79 6.82 6.71 6.74 6.77 C.O.P W / W 2.96 2.95 2.93 3.34 3.32 3.31 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 118 (260) Shipping weight kg (lb.) 52 (115) 128 (282) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 330 (13) 1676 (65-63 / 64) Width mm (in.) 1,755 (69-3 / 32) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR364SH56B x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,600 / 3,120 / 2,520 (1,800 / 1,560 / 1,260 x2)
dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.451 (16.2) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-40
1
Page 46
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U365SHT x2 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 8.4 (4.2 x2) – External static pressure (High) Pa (mmAg) 79 (8.1): at shipment, 122 (12.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 10.9 10.5 10.2 10.8 10.4 10.1 Max–Running amperes** A – Power input kW 6.76 6.79 6.82 6.71 6.74 6.77 C.O.P W / W 2.96 2.95 2.93 3.34 3.32 3.31 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 118 (260) Shipping weight kg (lb.) 52 (115) 128 (282) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 330 (13) 1676 (65-63 / 64) Width mm (in.) 1,755 (69-3 / 32) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U365SHT x2
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,600 / 3,120 / 2,520 (1,800 / 1,560 / 1,260 x2)
dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.451 (16.2) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-41
1
1
Page 47
1
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR484GH56 (A/B) x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 13.2 (6.6 x2) – External static pressure (High) Pa (mmAg) 78 (8.0): at shipment, 113 (11.5): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.3 13.7 13.3 13.4 12.9 12.4 Max–Running amperes** A – Power input kW 8.87 8.90 8.93 8.33 8.37 8.40 C.O.P W / W 2.82 2.81 2.80 3.36 3.35 3.33 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 128 (282) Shipping weight kg (lb.) 52 (115) 138 (304) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,671 (65-25 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR484GH56 (A/B) x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,960 / 3,600 / 3,000 (1,980 / 1,800 / 1,500 x2)
dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.468 (16.5) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-42
1
Page 48
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U485H x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 13.2 (6.6 x2) – External static pressure (High) Pa (mmAg) 78 (8.0): at shipment, 113 (11.5): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.3 13.7 13.3 13.4 12.9 12.4 Max–Running amperes** A –––––– Power input kW 8.87 8.90 8.93 8.33 8.37 8.40 C.O.P W / W 2.82 2.81 2.80 3.36 3.35 3.33 Max.Starting amperes A ––––––
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 128 (282) Shipping weight kg (lb.) 52 (115) 138 (304) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64) Height mm (in.) 358 (14-3 / 32) 1676 (65-63 / 64) Width mm (in.) 1,671 (65-25 / 32) 1076 (42-23 / 64) Depth mm (in.) 783 (30-26 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U485H x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,960 / 3,600 / 3,000 (1,980 / 1,800 / 1,500 x2)
dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.468 (16.5) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-43
1
1
Page 49
1
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR484SH56B x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 13.2 (6.6 x2) – External static pressure (High) Pa (mmAg) 78 (8.0): at shipment, 113 (11.5): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.3 13.7 13.3 13.4 12.9 12.4 Max–Running amperes** A – Power input kW 8.87 8.90 8.93 8.33 8.37 8.40 C.O.P W / W 2.82 2.81 2.80 3.36 3.35 3.33 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 128 (282) Shipping weight kg (lb.) 52 (115) 138 (304) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 330 (13) 1676 (65-63 / 64) Width mm (in.) 1,755 (69-3 / 32) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-UR484SH56B x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,960 / 3,600 / 3,000 (1,980 / 1,800 / 1,500 x2)
dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.451 (16.2) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-44
1
Page 50
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U485SHT x2 / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 13.2 (6.6 x2) – External static pressure (High) Pa (mmAg) 78 (8.0): at shipment, 113 (11.5): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 14.3 13.7 13.3 13.4 12.9 12.4 Max–Running amperes** A – Power input kW 8.87 8.90 8.93 8.33 8.37 8.40 C.O.P W / W 2.82 2.81 2.80 3.36 3.35 3.33 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 58 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 9.52 (3 / 8) 12.7 (1 / 2) Gas tube mm (in.) 15.88 (5 / 8) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 47 (104) 128 (282) Shipping weight kg (lb.) 52 (115) 138 (304) Shipping volume m
Width mm (in.) 1,480 (58-9 / 32) 940 (37-1 / 64) Depth mm (in.) 686 (27) 340 (13-25 / 64) Height mm (in.) 330 (13) 1676 (65-63 / 64) Width mm (in.) 1,755 (69-3 / 32) 1076 (42-23 / 64) Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-U485SHT x2
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 3,960 / 3,600 / 3,000 (1,980 / 1,800 / 1,500 x2)
dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.451 (16.2) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-45
1
1
Page 51
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-US185H x4 / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 7.2 (1.8 x4) – External static pressure (High) Pa (mmAg) 15 (1.5): at shipment, 40 (4.1): Using short circuit connection
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.7 11.2 10.9 11.0 10.7 10.3 Max–Running amperes** A – Power input kW 7.15 7.15 7.15 6.76 6.76 6.76 C.O.P W / W 2.80 2.80 2.80 3.31 3.31 3.31 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 5.3
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8) Gas tube mm (in.) 12.7 (1 / 4) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 200 (7-7 / 8) 1526 (60-5 / 64)
Unit dimensions
Package dimensions
Net weight kg (lb.) 19 (42) 118 (260) Shipping weight kg (lb.) 23 (51) 128 (282) Shipping volume m
Width mm (in.) 750 (29-17 / 32) 940 (37-1 / 64) Depth mm (in.) 640 (25-13 / 64) 340 (13-25 / 64) Height mm (in.) 220 (8-21 / 32) 1676 (65-63 / 64) Width mm (in.) 1030 (40-35 / 64) 1076 (42-23 / 64) Depth mm (in.) 745 (29-21 / 64) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-US185H x4
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,000 / 2,760 / 2,400 (750 / 690 / 600 x4)
dB-A 35 / 33 / 31, (37 / 35 / 33: Using short circuit connection)
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 0.169 (5.97) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-46
1
Page 52
Single-Type
1-1. Unit Specifi cations
Concealed-Duct High Static Pressure Type SPW-D705H / SPW-C706VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 11.1 – External static pressure (High) Pa (mmAg) 176 (18)
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 11.4 11.0 10.7 10.4 10.1 9.8 Max–Running amperes** A – Power input kW 7.09 7.12 7.15 6.47 6.50 6.53 C.O.P W / W 2.82 2.81 2.80 3.46 3.45 3.43 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) 25A Male screw (No Drain Pump) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo Outdoor - Hi dB-A 57 57 Indoor – Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8) Gas tube mm (in.) 25.4 (1)*
Refrigerant amount at shipment kg R410A - 5.3
DIMENSIONS & WEIGHT
Height mm (in.) 467 (18-12 / 32) 1526 (60-5 / 64)
Unit dimensions
Width mm (in.) 1,428 (56-7 / 32) 940 (37-1 / 64) Depth mm (in.) 1,230 (48-14 / 32) 340 (13-25 / 64) Height mm (in.) 614 (24-11 / 64) 1676 (65-63 / 64)
Package dimensions
Width mm (in.) 1,536 (60-15 / 32) 1076 (42-23 / 64)
Depth mm (in.) 1,339 (52-23 / 32) 420 (16-17 / 32) Net weight kg (lb.) 110 (243) 118 (260) Shipping weight kg (lb.) 134 (295) 128 (282) Shipping volume m
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-D705H
Outdoor Unit SPW-C706VH8
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
3
/ h 3,360 / 3,190 / 2,980
dB-A 48 / 47 / 46
Indoor unit Outdoor unit
m (ft.)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
1
25.4 (1)*
Indoor unit Outdoor unit
3
(cu.ft) 1.268 (44.8) 0.757 (26.7)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-47
1
1
Page 53
1
Single-Type
1-1. Unit Specifi cations
Concealed-Duct High Static Pressure Type SPW-D905H / SPW-C906VH8
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity [min~max]
Air circulation (Hi / Me / Lo) m Moisture removal (High) Liters / h 13.9 – External static pressure (High) Pa (mmAg) 216 (22): at shipment 235 (24): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415 Available voltage range V 342~456(outdoor) 198~264(indoor) Running amperes* A 15.3 14.8 14.3 13.1 12.6 12.3 Max–Running amperes** A – Power input kW 9.49 9.55 9.61 8.14 8.20 8.26 C.O.P W / W 2.63 2.62 2.60 3.44 3.41 3.39 Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat Timer ON / OFF 72-hours Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Airflow direction (Indoor) – Air filter Field supply Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) 25A Male screw (No Drain Pump) Compressor Rotary (SANYO)
Operation sound
Color (Approximate value)
Indoor - Hi / Me / Lo
Outdoor - Hi dB-A 57 58
Indoor
Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Limit of tubing length m (ft.) 100 (328) Limit of tubing length at shipment m (ft.) 5~30(16~98) Limit of elevation difference
between the two units Refrigerant tube
outer diameter Refrigerant amount at shipment kg R410A - 6.5
Liquid tube mm (in.) 12.7 (1 / 2) 12.7 (1 / 2)
Gas tube mm (in.) 25.4 (1) 25.4 (1)*
DIMENSIONS & WEIGHT
Height mm (in.) 467 (18-12 / 32) 1526 (60-5 / 64) Unit dimensions
Package dimensions
Net weight kg (lb.) 120 (256) 128 (282) Shipping weight kg (lb.) 144 (317) 138 (304) Shipping volume m
Width mm (in.) 1,428 (56-7 / 32) 940 (37-1 / 64)
Depth mm (in.) 1,230 (48-14 / 32) 340 (13-25 / 64)
Height mm (in.) 614 (24-11 / 64) 1676 (65-63 / 64)
Width mm (in.) 1,536 (60-15 / 32) 1076 (42-23 / 64)
Depth mm (in.) 1,339 (52-23 / 32) 420 (16-17 / 32)
NOTE
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
Indoor Unit SPW-D905H
Outdoor Unit SPW-C906VH8
Indoor Unit 220-230-240V, 50Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
Cooling Heating
kW 25.0 [6.0~28.0] 28.0 [6.0~31.5]
BTU / h 85,300 [20,500~95,500] 95,500 [20,500~107,500]
3
/ h 4,320 / 4,200 / 3,960
dB-A 51 / 50 / 49
Indoor unit Outdoor unit
m (ft.)
3
(cu.ft) 1.268 (44.8) 0.757 (26.7)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1-48
1
Page 54
1-2. Major Component Specifi cations
(A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR184GH56 (A/B), X185H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-XDR184GH56 (A/B), X185H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Turbo (1...ø460, L140)
Fan motor
Model...Nominal output W DK8-53B280H...50W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...390
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 87.0
WHT–BLK : 87.0
BLK–RED : 87.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.25 Face area m
Panel
Model No. PNR-XD484GHAB (optional) Dew proof heater – Auto louver motor MP24GA Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC230V, 50Hz, 12W Total head & capacity 500mm, 400cc/min
2
0.36
Indoor unit
380 ± 7% / phase
ADP-1414
1
1-49
Page 55
1
1-2. Major Component Specifi cations
(A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR254GH56 (A/B), X255H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-XDR254GH56 (A/B), X255H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Turbo (1...ø460, L140)
Fan motor
Model...Nominal output W DK8-53B280H...50W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...440
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 87.0
WHT–BLK : 87.0
BLK–RED : 87.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.25 Face area m
Panel
Model No. PNR-XD484GHAB (optional) Dew proof heater – Auto louver motor MP24GA Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC230V, 50Hz, 12W Total head & capacity 500mm, 400cc/min
2
0.405
Indoor unit
380 ± 7% / phase
ADP-1414
1-50
Page 56
1-2. Major Component Specifi cations
(A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR364GH56 (A/B), X365H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-XDR364GH56 (A/B), X365H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Turbo (1...ø460, 200)
Fan motor
Model...Nominal output W DK8-93C280H...90W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...540
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 43.0
WHT–BLK : 43.0
BLK–RED : 43.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.25 Face area m
Panel
Model No. PNR-XD484GHAB (optional) Dew proof heater – Auto louver motor MP24GA Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC230V, 50Hz, 12W Total head & capacity 500mm, 400cc/min
2
0.584
Indoor unit
380 ± 7% / phase
ADP-1414
1
1-51
Page 57
1
1-2. Major Component Specifi cations
(A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR484GH56 (A/B), X485H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-XDR484GH56 (A/B), X485H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Turbo (1...ø460, 200)
Fan motor
Model...Nominal output W DK8-93C280H...90W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...620
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 43.0
WHT–BLK : 43.0
BLK–RED : 43.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.25 Face area m
Panel
Model No. PNR-XD484GHAB (optional) Dew proof heater – Auto louver motor MP24GA Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC230V, 50Hz, 12W Total head & capacity 500mm, 400cc/min
2
0.584
Indoor unit
380 ± 7% / phase
ADP-1414
1-52
Page 58
1-2. Major Component Specifi cations
(A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XM185H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
220 - 230 - 240V, single-phase, 50/60Hz
CR-XM075XH (Microprocessor), POW-XM075XH
SPW-XM185H
Turbo (1...ø322, L147)
Fan motor
Model...Nominal output W SIC-72FV-D866-1...66W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...750 Coil resistance
(Ambient temperature 20°C) Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.4 Face area m
Panel
Model No. PNR-XM185 (optional) Dew proof heater – Auto louver motor MP24ZN-12V Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC230V, 50Hz, 12W Total head & capacity 850mm, 400cc/min
2
0.27
Indoor unit
380 ± 7% / phase
PLD-12230ST-2
1
1-53
Page 59
1
1-2. Major Component Specifi cations
(A) Indoor Units Wall-Mounted Type SPW-KR184GH56 (A/B)
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-KR184GH56 (A/B)
220 - 230 - 240V, single-phase, 50/60Hz
POW-KR74GXH56 (Microprocessor)
Cross - flow (1...ø90, L746)
Fan motor
Model...Nominal output W UF4Q-31G5P...12W Source 220 - 230 - 240V, single-phase, 50/60Hz No. of pole...rpm (230V, High) rpm 4P...1,147
Coil resistance (Ambient temperature 20°C)
Safety device
Operation temperature (17AM033E5-4)
Operation temperature (9700k211-215)
Run capacitor VAC, µF 440 VAC, 1.2 µF
Open °C 130 ± 5
Close °C 83 ± 15
Open °C 130 ± 8
Close °C 79 ± 15
BRN–WHT : 490.5 ORG–YEL : 39.18
WHT–VLT : 78.43 YEL–PNK : 213.5 VLT–ORG : 62.63
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.3 Face area m
2
0.231
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W – Total head & capacity
1-54
Page 60
1-2. Major Component Specifi cations
(A) Indoor Units Wall-Mounted Type SPW-KR254GH56 (A/B)
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-KR254GH56 (A/B)
220 - 230 - 240V, single-phase, 50/60Hz
POW-KR74GXH56 (Microprocessor)
Cross - flow (1...ø100, L848)
Fan motor
Model...Nominal output W KFT4Q-31A5P-C...27W Source 220 - 230 - 240V, single-phase, 50/60Hz No. of pole...rpm (230V, High) rpm 4P...1,147
Coil resistance (Ambient temperature 20°C)
Safety device
Operation temperature (17AM033E5-4)
Operation temperature (9700k211-215)
Run capacitor VAC, µF 440 VAC, 1.8 µF
Open °C 130 ± 5
Close °C 83 ± 15
Open °C 130 ± 8
Close °C 79 ± 15
BRN–WHT : 307.5 ORG–YEL : 23.4
WHT–VLT : 54.6 YEL–PNK : 97.8 VLT–ORG : 34.5
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.3 Face area m
2
0.329
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W – Total head & capacity
1
1-55
Page 61
1
1-2. Major Component Specifi cations
(A) Indoor Units Ceiling-Mounted Type SPW-TDR184GH56 (A/B), T185H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-TDR184GH56 (A/B), T185H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Centrifugal (2...ø140, L180)
Fan motor
Model...Nominal output W DK8-63C280H...30W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...960
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 53.0
WHT–BLK : 53.0
BLK–RED : 53.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.4 Face area m
2
0.154
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W – Total head & capacity
1-56
Page 62
1-2. Major Component Specifi cations
(A) Indoor Units Ceiling-Mounted Type SPW-TDR254GH56 (A/B), T255H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-TDR254GH56 (A/B), T255H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Centrifugal (3...ø140, L180)
Fan motor
Model...Nominal output W DK8-63D280H...40W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...980
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 53.0
WHT–BLK : 53.0
BLK–RED : 53.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.4 Face area m
2
0.222
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W – Total head & capacity
1
1-57
Page 63
1
1-2. Major Component Specifi cations
(A) Indoor Units Ceiling-Mounted Type SPW-TDR364GH56 (A/B), T365H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-TDR364GH56 (A/B), T365H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Centrifugal (4...ø140, L180)
Fan motor
Model...Nominal output W DK8-123C280H...80W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...1040
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 37.0
WHT–BLK : 37.0
BLK–RED : 37.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.4 Face area m
2
0.326
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W – Total head & capacity
1-58
Page 64
1-2. Major Component Specifi cations
(A) Indoor Units Ceiling-Mounted Type SPW-TDR484GH56 (A/B), T485H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-TDR484GH56 (A/B), T485H
220 - 230 - 240V, single-phase, 50/60Hz
CR-SXRP56B-B (Microprocessor)
Centrifugal (4...ø140, L180)
Fan motor
Model...Nominal output W DK8-123C280H...80W Source 280/340V (DC), 3-phase No. of pole...rpm (230V, High) rpm 8P...1100
Coil resistance (Ambient temperature 20°C)
Run capacitor VAC, µF
Safety device
overcurrent, rotating signal detection, fuse
RED–WHT : 37.0
WHT–BLK : 37.0
BLK–RED : 37.0
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.4 Face area m
2
0.326
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W – Total head & capacity
1
1-59
Page 65
1
1-2. Major Component Specifi cations
(A) Indoor Units Concealed-Duct Type SPW-UR184GH56 (A/B), UR184SH56B, U185H
MODEL No.
Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW-UR184GH56 (A/B) SPW-U185H
220 - 230 - 240V, single-phase, 50/60Hz
CR-UXRP71B-B (Microprocessor)
Centrifugal (1...ø190, L200)
SPW-UR184SH56B SPW-U185SHT
Fan motor
Model...Nominal output W SFG4X-51C3P...50W Source 220 - 230 - 240V, single-phase, 50/60Hz No. of pole...rpm (230V, High) rpm 4P...1,191
Coil resistance (Ambient temperature 20°C)
Safety device
Operation temperature Open °C 130 ± 5 Operation temperature Close °C (115 ± 5)
Run capacitor VAC, µF 450 VAC, 2.0 µF
BRN–WHT : 76.88 ORG–YEL : 14.42
WHT–VLT : 12.66 YEL–BLK : 26.76 VLT–ORG : 21.01 BLK–PNK : 25.17
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.5 Face area m
2
0.113
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC 230V, 50Hz, 12W Total head & capacity 500mm, 400cc/min 1200mm, 400cc/min
ADP-1413 ZPLD-12230ST-XH-B
1-60
Page 66
1-2. Major Component Specifi cations
(A) Indoor Units Concealed-Duct Type SPW-UR254GH56 (A/B), UR254SH56B, U255H
SPW­UR254SH56B U255SHT
Centrifugal (2...ø190, L200)
MODEL No.
Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW­UR254GH56(A/B)
220 - 230 - 240V, single-phase, 50/60Hz
CR-UXRP71B-B (Microprocessor)
Fan motor
Model...Nominal output W SFG4X-71C3P...70W Source 220 - 230 - 240V, single-phase, 50/60Hz No. of pole...rpm (230V, High) rpm 4P...1,063
Coil resistance (Ambient temperature 20°C)
Safety device
Operation temperature Open °C 130 ± 5 Operation temperature Close °C (115 ± 5)
Run capacitor VAC, µF 450 VAC, 5.0 µF
BRN–WHT : 74.72 ORG–YEL : 9.588
WHT–VLT : 19.14 YEL–BLK : 10.52 VLT–ORG : 10.52 BLK–PNK : 21.72
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.5 Face area m
2
0.189
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC 230V, 50Hz, 12W Total head & capacity
ADP-1413
500mm, 400cc/min 1200mm, 400cc/min 500mm, 400cc/min
ZPLD-12230ST-XH-B
1
SPW­U255H
KFG4X-71B5P-S...70W
ADP-1413
1-61
Page 67
1
1-2. Major Component Specifi cations
(A) Indoor Units Concealed-Duct Type SPW-UR364GH56 (A/B), UR364SH56B, U365H
SPW­UR364SH56B U365SHT
CR-UXRP71B-B (Microprocessor)
Centrifugal (3...ø190, L200)
MODEL No.
Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW­UR364GH56 (A/B)
220 - 230 - 240V, single-phase, 50/60Hz
Fan motor
Model...Nominal output W SFC4X-141A5P...160W Source 220 - 230 - 240V, single-phase, 50/60Hz No. of pole...rpm (230V, High) rpm 4P...1,111
Coil resistance (Ambient temperature 20°C)
Safety device
Operation temperature Open °C 130 ± 5 Operation temperature Close °C (115 ± 5)
Run capacitor VAC, µF 450 VAC, 6.0 µF
BRN–WHT : 25.79 ORG–YEL : 5.792
WHT–VLT : 5.086 YEL–BLK : 6.746 VLT–ORG : 8.626 BLK–PNK : 6.361
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...2.0 Face area m
2
0.308
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC 230V, 50Hz, 12W Total head & capacity 500mm, 400cc/min
ADP-1413 ZPLD-12230ST-XH-B ADP-1413
1200mm, 400cc/min
SPW­U365H
KFC4X-141D5PS...160W
500mm, 400cc/min
1-62
Page 68
1-2. Major Component Specifi cations
(A) Indoor Units Concealed-Duct Type SPW-UR484GH56 (A/B), UR484SH56B, U485H
SPW­UR484SH56B U485SHT
CR-UXRP71B-B (Microprocessor)
Centrifugal (3...ø190, L200)
MODEL No.
Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
SPW­UR484GH56 (A/B)
220 - 230 - 240V, single-phase, 50/60Hz
Fan motor
Model...Nominal output W SFC4X-141A5P...160W Source 220 - 230 - 240V, single-phase, 50/60Hz No. of pole...rpm (230V, High) rpm 4P...1,207
Coil resistance (Ambient temperature 20°C)
Safety device
Operation temperature Open °C 130 ± 5 Operation temperature Close °C (115 ± 5)
Run capacitor VAC, µF 450 VAC, 8.0 µF
BRN–WHT : 25.79 ORG–YEL : 5.792
WHT–VLT : 5.086 YEL–BLK : 6.746
VLT–ORG : 8.626 BLK–PNK : 6.361
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...2.0 Face area m
2
0.308
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC 230V, 50Hz, 12W Total head & capacity 500mm, 400cc/min
ADP-1413 ZPLD-12230ST-XH-B ADP-1413
1200mm, 400cc/min
1
SPW­U485H
KFC4X-141D5P-S...160W
500mm, 400cc/min
1-63
Page 69
1
1-2. Major Component Specifi cations
(A) Indoor Units Concealed-Duct Type SPW-US185H
MODEL No. Source Controller P.C.B. Ass'y Fan (Number...diameter, depth)
220 - 230 - 240V, single-phase, 50/60Hz
CR-US075XH (Microprocessor)
SPW-US185H
Centrifugal (1...ø190, L200)
Fan motor
Model...Nominal output W DK8-63G280H...60W Source 280 / 340V (DC), 3-phase, 50/60Hz No. of pole...rpm (230V, High) rpm 8P...834 Coil resistance
(Ambient temperature 20°C) Run capacitor VAC, µF
Electronic expansion valve
Coil – Coil resistance (at 20°C) Valve body
Heat Exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.4 Face area m
2
0.128
Panel
Model No. – Dew proof heater – Auto louver motor – Coil resistance (at 20°C)
Drain Pump
Rated VAC, W AC 230V, 50Hz, 12W Total head & capacity 850mm, 400cc/min
PLD-12230ST-2
1-64
Page 70
1-2. Major Component Specifi cations
(A) Indoor Units Concealed-Duct High Static Pressure Type
MODEL No.
Source
Controller P.C.B. Ass'y
Fan (Number...diameter)
220 - 230 - 240V, single-phase, 50/60Hz
CR-UXRP71B-B (Microprocessor)
mm Centrifugal (2...ø220)
SPW-D705H
Fan motor
Model...Nominal output W KFC4X-201B5P...180 W
Power source 220 - 230 - 240V, single-phase, 50Hz
No. of pole...r.p.m. (230V, High) rpm 4P... 1,012
Coil resistance (Ambient temperature 20°C)
Safety device
Operating temperature
Run capacitor VAC, µF 450 VAC, 7.0 µF
Open °C 130 ± 5
Close °C (115 ± 5)
BRN – WHT : 13.75 ORG – YEL : 2.21
WHT – VLT : 4.47 YEL – BLK : 10.33
VLT – ORG : 1.20 BLK – PNK : 12.90
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Valve body
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 3...2.0
Face area m
2
0.540
1
1-65
Page 71
1
1-2. Major Component Specifi cations
(A) Indoor Units Concealed-Duct High Static Pressure Type
MODEL No.
Source
Controller P.C.B. Ass'y
Fan (Number...diameter)
220 - 230 - 240V, single-phase, 50Hz
CR-UXRP71B-B (Microprocessor)
mm Centrifugal (2...ø250)
SPW-D905H
Fan motor
Model...Nominal output W KFC4X-401B3P...400 W
Power source 220 - 230 - 240V, single-phase, 50Hz
No. of pole...r.p.m. (230V, High) rpm 4P... 1,211
Coil resistance (Ambient temperature 20°C)
Safety device
Operating temperature
Run capacitor VAC, µF 450 VAC, 5.0 µF
Open °C 130 ± 5
Close °C (115 ± 5)
BRN – WHT : 6,159 ORG – YEL : 0.87
WHT – VLT : 1.08 YEL – BLK : 2.87
VLT – ORG : 0.77 BLK – PNK : 5.98
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Valve body
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 3...2.0
Face area m
2
0.655
1-66
Page 72
1-2. Major Component Specifi cations
(B) Outdoor Units
SPW-C706VH8
MODEL No. Source
380-400-415V, 3-phase, 50/60Hz
Controller P.C.B. Ass'y
Control circuit fuse 20A
SPW-C706VH8
CR-C906VH8 (Microprocessor)
Compressor
Model....number C-9RVN273H0K
Source 246V (DC) / 3-phase / 60Hz (Inverter drive) Nominal output W 4,200 Compressor oil cc 1,400 Coil resistance
(Ambient temperatur e 25°C) Safety control
Overload relay models Discharge temperature control
Operation temperature
Crank case heater W 25
Open °C – Close °C
Refrigerant amount at shipment
kg R410A - 5.3
High pressure switch
Set pressure
OFF MPa 4.15
ON MPa 3.15 ± 0.3
C – R : 0.552 R – S : 0.552 C – S : 0.552
0 – 0.15
Fan
Number...diameter mm 2...ø490 Air circulation m
Fan speeds (Max.)
3
/ h 7,740
~860 rpm (Inverter drive control)
Fan motor
Model No. SIC-71FW-D8120 Source ~280V / 3-phase No. of pole 8 Nominal output W 120 Safety device
Operating temperature
Run capacitor VAC, µF
Open °C – Close °C
Heat exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 2...1.4 Face area m
2
1.27
1
1-67
Page 73
1
1-2. Major Component Specifi cations
(B) Outdoor Units
SPW-C906VH8
MODEL No. Source
380-400-415V, 3-phase, 50/60Hz
Controller P.C.B. Ass'y
Control circuit fuse 20A
SPW-C906VH8
CR-C906VH8 (Microprocessor)
Compressor
Model....number C-9RVN393H0U
Source 282V (DC) / 3-phase / 60Hz (Inverter drive) Nominal output W 5,500 Compressor oil cc 1,900 Coil resistance
(Ambient temperature 25°C) Safety control
Overload relay models Discharge temperature control
Operation temperature
Crank case heater W 25
Open °C – Close °C
Refrigerant amount at shipment
kg R410A - 6.5
High pressure switch
Set pressure
OFF MPa 4.15
ON MPa 3.15 ± 0.3
C – R : 0.608 R – S : 0.608 C – S : 0.608
0 – 0.15
Fan
Number...diameter mm 2...ø490 Air circulation m
Fan speeds (Max.)
3
/ h 7,080
~860 rpm (Inverter drive control)
Fan motor
Model No. SIC-71FW-D8120 Source ~280V / 3-phase No. of pole 8 Nominal output W 120 Safety device
Operating temperature
Run capacitor VAC, µF
Open °C – Close °C
Heat exchanger
Coil Aluminium plate fin / Copper tube Rows...fin pitch mm 3...1.4 Face area m
2
1.27
1-68
Page 74
1-3. Other Component Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XDR184-484GH56 (A/B), X185-485H
MODEL No.
Indoor Unit
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance Thermal cut off temperature °C
Thermistor (Coil sensor): TH
Resistance
k
–10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5% 5°C: 12.8±5% 45°C: 2.2±5% 10°C: 10.0±5% 50°C: 1.8±5% 20°C: 6.3±5% 55°C: 1.5±5% 30°C: 4.0±5%
SPW-XDR184-484GH56 (A/B) SPW-X185-485H
– – –
PB2M-41E-S3, PB3M-41E-AS1
KTEC-35-S98
Electronic expansion valve
Valve body – Coil
Drain pump
Rated
Float switch
Rated (Contact rated)
Contact open at float rising
ADP-1414
AC 230V, 12 W
FS-0218-102
1
1-69
Page 75
1
1-3. Other Component Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XM185H
MODEL No.
Indoor Unit SPW-XM185H
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance Thermal cut off temperature °C
Thermistor (Coil sensor): TH
Resistance
k
–10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5% 5°C: 12.8±5% 45°C: 2.2±5% 10°C: 10.0±5% 50°C: 1.8±5% 20°C: 6.3±5% 55°C: 1.5±5% 30°C: 4.0±5%
Electronic expansion valve
Valve body – Coil
Drain pump
Rated
Float switch
Rated (Contact rated)
Contact open at float rising
– – –
PB2M-41E-S15-1
KTEC-35-S98
PLD-12230ST-2
AC 230V, 12W
FS-0218-102
1-70
Page 76
1-3. Other Component Specifi cations
Wall-Mounted Type SPW-KR184GH56 (A/B) – 254GH56 (A/B)
MODEL No.
Indoor Unit SPW-KR184GH56 (A/B) – 254GH56 (A/B)
Power Transformer
Rated
Source VAC, Hz AC 230 V , 50/60 Hz
Secondary
Coil resistance Thermal cut off temperature °C 150°C
Thermistor (Coil sensor): TH
Resistance
k
S1: 11 V, 1.25 A S2: 14 V, 0.45 A S3: 20 V, 0.2 A
PBC-41E-AS7-1, PBC-41E-AS7-3 –10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5% 5°C: 12.8±5% 45°C: 2.2±5% 10°C: 10.0±5% 50°C: 1.8±5% 20°C: 6.3±5% 55°C: 1.5±5% 30°C: 4.0±5%
Electronic expansion valve
Valve body – Coil
Drain pump
Rated
Float switch
Rated (Contact rated)
1
ATR-IIK245
KTEC-35-S
– – – –
1-71
Page 77
1
1-3. Other Component Specifi cations
Ceiling-Mounted Type SPW-TDR184-484GH56 (A/B), T185-485H
MODEL No.
Indoor Unit
SPW-TDR184-484GH56 (A/B) SPW-T185-485H
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance Thermal cut off temperature °C
Thermistor (Coil sensor): TH
Resistance
k
PBC-41E-AS4, PBC-41E-AS8-5 –10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5% 5°C: 12.8±5% 45°C: 2.2±5% 10°C: 10.0±5% 50°C: 1.8±5% 20°C: 6.3±5% 55°C: 1.5±5% 30°C: 4.0±5%
Electronic expansion valve
Valve body – Coil
Drain pump
Rated
Float switch
Rated (Contact rated)
– – –
KTEC-35-S98
– – – –
1-72
Page 78
1-3. Other Component Specifi cations
Concealed-Duct Type SPW-UR184-484GH56 (A/B), UR184-484SH56B, U185-485H, U185-485SHT
MODEL No.
Indoor Unit
Power Transformer
Rated
Source VAC, Hz AC 230 V, 50 Hz
Secondary
Coil resistance Thermal cut off temperature °C
Thermistor (Coil sensor): TH
Resistance
Thermistor (Coil sensor):
Resistance
k
k
SPW-UR184-484GH56 (A/B) SPW-U185-485H
ATR-IL225B-T-R
S1: DC 13.0 V, 1 A S2: DC 24.0 V, 0.2 A
PBC-41E-S36, PBC-41E-AS8-1,2 –10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
KTEC-35-S85 0°C: 16.5±5% 40°C: 2.7±5% 5°C: 12.8±5% 45°C: 2.2±5% 10°C: 10.0±5% 50°C: 1.8±5% 20°C: 6.3±5% 55°C: 1.5±5% 30°C: 4.0±5%
SPW-UR184-484SH56B SPW-U185-485SHT
Electronic expansion valve
Valve body – Coil
Drain pump
Rated
Float switch
Rated (Contact rated)
ADP-1413 ZPLD-12230ST-XH-B
AC 220-240 V, 50/60 Hz, 12/11 W
FS-0218-103
Contact open at float rising
1
1-73
Page 79
1
1-3. Other Component Specifi cations
Concealed-Duct Type SPW-US185H
MODEL No.
Indoor Unit SPW-US185H
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance Thermal cut off temperature °C
Thermistor (Coil sensor): TH
Resistance
k
PB2M-41E-SI5-1 E1,E2 –10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5% 5°C: 12.8±5% 45°C: 2.2±5% 10°C: 10.0±5% 50°C: 1.8±5% 20°C: 6.3±5% 55°C: 1.5±5% 30°C: 4.0±5%
Electronic expansion valve
Valve body – Coil
Drain pump
Rated
Float switch
Rated (Contact rated)
Contact open at float rising
– – –
KTEC-35-S6
PLD-12230ST-2
AC 230V, 12W
FS-0218-102
1-74
Page 80
1-3. Other Component Specifi cations
Outdoor Units SPW-C706VH8
MODEL No. Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance Thermal cut off temperature °C
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
Thermistor (Discharge gas sensor): TH5
Resistance
Outdoor Unit SPW-C706VH8
– –
k
k
KTM-35D-S1, DTN-C532G3H –10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
60°C: 12.4±5% 90°C: 4.6±5% 70°C: 8.7±5% 100°C: 3.4±7% 75°C: 7.4±5% 110°C: 2.5±7% 80°C: 6.3±5% 120°C: 1.9±7% 85°C: 5.3±5% 130°C: 1.5±7%
CM-12
Relay (Comp. Magnetic Contactor)
Coil rated VAC – Contact rating VAC, A – Coil resistance (at 20°C)
Sol-Control-Valve
Sol-control-valve UKV-25D18 Magnetic coil UKV-A053 (062), DC 12 V
4 way valve
4 way valve STF-0401G Electro magnetic coil STF-01AI518A1, AC 220-240 V, 50Hz / 60Hz
1
1-75
Page 81
1
1-3. Other Component Specifi cations
Outdoor Units SPW-C906VH8
MODEL No. Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance Thermal cut off temperature °C
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
Thermistor (Discharge gas sensor): TH5
Resistance
Outdoor Unit SPW-C906VH8
– –
k
k
KTM-35D-S1, DTN-C532G3H –10°C: 23.7±5% 20°C: 6.5±5% –5°C: 18.8±5% 30°C: 4.4±5% 0°C: 15.0±5% 40°C: 3.1±5% 5°C: 12.1±5% 45°C: 2.6±5% 10°C: 9.7±5% 50°C: 2.1±5%
60°C: 12.4±5% 90°C: 4.6±5% 70°C: 8.7±5% 100°C: 3.4±7% 75°C: 7.4±5% 110°C: 2.5±7% 80°C: 6.3±5% 120°C: 1.9±7% 85°C: 5.3±5% 130°C: 1.5±7%
CM-12
Relay (Comp. Magnetic Contactor)
Coil rated VAC – Contact rating VAC, A – Coil resistance (at 20°C)
Sol-Control-Valve
Sol-control-valve UKV-25D18 Magnetic coil UKV-U030E, DC 12 V
4 way valve
4 way valve STF-0712G Electro magnetic coil STF-01AI518A1, AC 220-240 V, 50Hz / 60Hz
1-76
Page 82
1-4. Dimensional Data
(A) Indoor Units: 4-Way Air Discharge Semi-Concealed (X) Type
1
18, 25 Types
97
88
Ceiling opening dimensions
Suspension bolt pitch
Ceiling opening
dimensions
X
Suspension bolt pitch
790
860 – 910
120
88
860 – 910
723
Center of
panel
480
400
30
160
15
73
X View
80 160
7
8
35
256
bolts should be selected so that
there is a gap of 30 mm or
more below the lower surface of
the ceiling (15 mm or more
below the lower surface of the
main unit), as shown in the
figure at right. If the suspension
bolt is too long, it will contact
the ceiling panel and the unit
60
113
45
* The length of the suspension
950
514
cannot be installed.
2
70
6
4
250
514
950
7
347
840
30
Suspension bolt hole (4-12 × 37 hole)
Fresh air intake duct connection port (ø100)
9
10
5 3
97
Less than 35
Less than 35
188
840
120
210
480
10
382
9
Air intake
Discharge outlet
Refrigerant tubing (liquid tube) 18 type ø6.35 (flared), 25 type ø9.52 (flared)
Refrigerant tubing (gas tube) 18 type ø12.7 (flared), 25 type ø15.88 (flared)
Drain tube connection port VP25 (outer dia. ø32)
Power supply port
Discharge duct connection port (ø150)
Vaporization-type humidifier (optional) installation point
12345
678
160
2
2
1
2
8
1-77
Page 83
1
1-4. Dimensional Data
(A) Indoor Units: 4-Way Air Discharge Semi-Concealed (X) Type
36, 48 Types
Ceiling opening
dimensions
X
Suspension bolt pitch
790
860 – 910
30
183
97
88
480
X view
80 160
160
15
73
7
8
88
723
Ceiling opening dimensions
860 – 910
Suspension bolt pitch
(400)
319
60
35
* The length of the suspension
bolts should be selected so that
there is a gap of 30 mm or
more below the lower surface of
the ceiling (15 mm or more
below the lower surface of the
main unit), as shown in the
figure at right. If the suspension
bolt is too long, it will contact
the ceiling panel and the unit
113
45
950 514
cannot be installed.
2
6
Center
of panel
347
840
250 70
514
950
30
7
9
Air intake
Discharge outlet
Refrigerant tubing (liquid tube) ø9.52 (flared)
Refrigerant tubing (gas tube) ø15.88 (flared)
Drain tube connection port VP25 (outer dia. ø32)
Power supply port
Discharge duct connection port (ø150)
Vaporization-type humidifier (optional) installation point
123456789
382
Suspension bolt hole (4-12 × 37 hole)
Fresh air intake duct connection port (ø100)
10
840
5 3 4
183
210
480
160
97
Less than 35
2
2
1
2
8
10
Less than 35
188
1-78
Page 84
1-4. Dimensional Data
(A) Indoor Units: 4-Way Air Discharge Semi-Concealed (XM) Type
18 Type
195
8
125
A View
1
30
17 79
AA
600
534
Suspension bolt pitch
Ceiling opening dimensions
600
534
Center of
panel
7
Ceiling opening dimensions
Suspension bolts pitch
316
327
5
170
575
160
53
283
215
The length of the suspension
bolts should be selected so that
there is a gap of 30 mm or
the ceiling (17 mm or more
below the lower surface of the
main unit), as shown in the
figure at right. If the suspension
bolts is too long, it will contact
the ceiling panel and the unit
cannot be installed.
30
2
625
358
3
6
45
117 45
2
625
334
2
1
2
Air intake
Discharge outlet
Refrigerant tubing (liquid tube) 18 type o6.35 (flared)
Refrigerant tubing (gas tube) 18 type o12.7 (flared)
1234567
575
Drain tube connection port VP20 (outer dia. o26)
Power supply port
Suspension bolt hole (4-12 x 30 hole)
Fresh air intake duct connection port (ø100)
8
92
1-79
Less than 25 Less than 25
Page 85
1
1-4. Dimensional Data
(A) Indoor Units: Wall-Mounted Type
18 Type
7, 9, 12, 18 type
285
ø80
Gas tube ø12.7 (length: Approx. 400 mm)
LIquid tube ø6.35 (length: Approx. 470 mm)
995
Drain and wiring port (ø9.52)
Drain hose VP13 (length: Approx. 450 mm)
25 Type
25 type
330
ø80
Drain hose VP13 (length: Approx. 450 mm)
Gas tube ø15.88 (length: Approx. 500 mm)
1,140
Drain and wiring port (ø9.52)
Liquid tube ø9.52 (length: Approx. 570 mm)
1-80
Page 86
1-4. Dimensional Data
(A) Indoor Units: Ceiling-Mounted Type
1
Length
Type
18
25
36, 48
251 84 146 161
Closed with rubber stopper at time of shipment.
ABC
855
1125
1540
Left side
910
1180
1595
171
39
210
210
210
Unit: mm
Rear (Figure shows view from front)
Left drain position Right drain position
170
320
(Suspension bolt pitch)
27.5 27.5
(Suspension bolt pitch)
Liquid tubing
Gas tubing
B
Ceiling side
A
75 97 216
105
680
171
39
C
Right side
Air intake
Air
(Liquid tubing • Gas tubing)
251
1-81
Page 87
1
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct (U) Type
18 Type SPW-UR184GH56 (A/B), U185H
10
25
175
190
35
11
260
(Air outlet
duct flange)
310
25 210
10 25
24
(Hole)
19
662 (Air outlet duct flange)
12-ø3.3
3131
200
3 = 600
×
200 P
160
630
(450 × 450)
Inspection access
7030
(Field supply)
285
70 130
25
85
115
65
40700
75
(150)
290 262
780 (Suspension bolt pitch)
90
(Suspension bolt pitch)
185
580
1-82
25
Refrigerant liquid line ø6.35 (liquid tube) Refrigerant gas line ø12.7 Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 32 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150) Flange for the flexible air outlet duct (ø200)
9
Tube cover
10
Electrical component box
11
Flange for the air intake duct (Option or field supply)
Page 88
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct (U) Type
SPW-UR254GH56 (A/B), U255H
Indoor unit: 25 Type
10
25
175
1
190
35
11
260
(Air outlet
duct flange)
40
1000
70 130
(150)
285
115
65
310
25 210
10 25
24
(Hole)
19
16-ø3.3
3131
180
900
160
630
(450 × 450)
(Field supply)
Inspection access
25
7030
85
962 (Air outlet duct flange)
(Suspension bolt pitch)
185
90
580
1-83
290 290 272 75
1080 (Suspension bolt pitch)
25
Refrigerant liquid line ø9.52 (liquid tube) (Use the tube connector) Refrigerant gas line ø15.88 (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 32 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150) Flange for the flexible air outlet duct (ø200)
9
Tube cover
10
Electrical component box
11
Flange for the air intake duct (Option or field supply)
Page 89
1
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct (U) Type
SPW-UR364GH56 (A/B), U365H SPW-UR484GH56 (A/B), U485H
Indoor unit: 36, 48 Type
10
25
175
190
35
11
260
(Air outlet
duct flange)
40
1480
70 130
(150)
285
115
65
310
25 210
10 25
24
(Hole)
19
18-ø3.3
3131
230
6 = 1380
×
160
630
(450 × 450)
(Field supply)
Inspection access
25
7030
85
1442 (Air outlet duct flange)
230 P
(Suspension bolt pitch)
185
90
580
1-84
1560 (Suspension bolt pitch)
335 335 335 310 75
25
Refrigerant liquid line ø9.52 (liquid tube) Refrigerant gas line ø15.88 (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 32 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150) Flange for the flexible air outlet duct (ø200)
9
Tube cover
10
Electrical component box
11
Flange for the air intake duct (Option or field supply)
Page 90
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct (U) Type
SPW-UR184SH56B SPW-U185SHT
11
3131
175
310
262
100PX2=200
31
24
27
12
262
(Flange O.D.)
9
10
4
630
160
30
3
Inspection access
(450 x 450)
(Field supply)
Ceiling
Inspection access panel
190
70
35
25
25
40
75
130
70
1
(150)
285
65
1
2
115
6
13
18-Ø3.1
100
100PX5=500 7373
646 (Flange O.D.)
Intake port side
90
(Hole)
580
(Suspension bolt pitch)
185
161
700
12-
Ø
3.3
(Hole)
7
8
100PX3=300 9696
492 (Flange O.D.)
25
5
10043 43
186
(Flange O.D.)
780 (Suspension bolt pitch)
Outlet duct side
186
14
Refrigerant tubing joint Ø6.35Flare
1
(liquid tube) Refrigerant tubing joint
2
(gas tube) Upper drain port VP25 (O.D. 32 mm)
3
200 flexible hose supplied Bottom drain port VP25 (O.D. 32 mm)
4
Suspension lug (4 - 12 x 37 mm)
5
Power supply outlet (2 -
6
Fresh air intake port (
7
Flange for flexible air outlet duct
8
Tube cover
9
Electrical component box
10
Wind pressure endurance
11
Flange for air intake duct
12
Filter (608x241) x1
13
Flange for air outlet duct
14
Ø
12.7Flare
Ø
30 mm)
Ø
150 mm)
1-85
Page 91
1
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct (U) Type
SPW-UR254SH56B SPW-U255SHT
11
3131
175
100PX2=200
310
262
31
262
(Flange O.D.)
12
24
27
2323
10 9 4
3
160
630
Inspection access
(450 x 450)
(Field supply)
Ceiling
Inspection access panel
190
70
25
30
35
130
285
70
2
1
25
115
65
75
40
(150)
6
13
100
100PX9=900
946 (Flange O.D.)
Intake port side
90
26 -Ø3.1
(Hole)
20 -Ø3.3
(Hole)
(Suspension bolt pitch)
185
580
7
4141
171
1000
100PX7=700
1080 (Suspension bolt pitch)
782 (Flange O.D.)
Outlet duct side
25
5
1
186
(Flange O.D.)
10 11 12 13 14
2
3
4 5 6 7 8 9
8
10043 43
186
Refrigerant tubing joint Ø9.52Flare (liquid tube) Refrigerant tubing joint (gas tube) Upper drain port VP25 (O.D. 32 mm) 200 flexible hose supplied Bottom drain port VP25 (O.D. 32 mm) Suspension lug (4 - 12 x 37 mm) Power supply outlet (2 ­Fresh air intake port ( Flange for flexible air outlet duct Tube cover Electrical component box Wind pressure endurance Flange for air intake duct Filter (437x241) x2 Flange for air outlet duct
14
Ø
15.88Flare
Ø
30 mm)
Ø
150 mm)
1-86
Page 92
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct (U) Type
SPW-UR364SH56B, U365SHT SPW-UR484SH56B, U485SHT
11
3131
175
100PX2=200
310
262
31
Inspection access
262
(Flange O.D.)
12
27
10
9
3
630
(450 x 450)
(Field supply)
Ceiling
Inspection access panel
4
190
160
70
30
1
35
130
285
70
25
25
2
1
(150)
115
75
40
65
6
13
26 -Ø3.1
100
100PX13=1300 6363
1426 (Flange O.D.)
Intake port side
(Suspension bolt pitch)
185
90
(Hole)
28 -Ø3.3
(Hole)
580
182
1480
100PX11=1100 81
1262 (Flange O.D.)
81
25
5
7
8
4343
100
186
(Flange O.D.)
Outlet duct side
1560 (Suspension bolt pitch)
186
Refrigerant tubing joint Ø9.52Flare
1
(liquid tube) Refrigerant tubing joint
2
(gas tube) Upper drain port VP25 (O.D. 32 mm)
3
200 flexible hose supplied Bottom drain port VP25 (O.D. 32 mm)
4
Suspension lug (4 - 12 x 37 mm)
5
Power supply outlet (2 -
6
Fresh air intake port (
7
Flange for flexible air outlet duct
8
Tube cover
9
Electrical component box
10
Wind pressure endurance
11
Flange for air intake duct
12
Filter (677x241) x2
13
Flange for air outlet duct
14
14
Ø
15.88Flare
Ø
30 mm)
Ø
150 mm)
1-87
Page 93
1
1-4. Dimensional Data
(A) Indoor Unit: Concealed-Duct (US) Type
SPW-US185H
2- 3.1(Hole)
28
Signal output board (ACC-SG-AGB : optional)
Filter
Electrical component box
Pl cover
Frange for air inlet duct
Suspension lug
Upper and bottom drain port (O.D.26mm)
Refrigerant tubing joint (wide tube)
Refrigerant tubing joint (narrow tube) 1
Power supply outlet (2-o30)
7
6
5
4
3
2
9
8
10
59
29
26
66
3023844
10
14380
84
81
30
7
1
27
4
3
33
153
2
Water inlet
(450 x 450)
Field supply
Inspection access
200
150
8
14
10- 3.1(Hole)
14
120 40
2215523
132
220
* Filter uninstalled
220
132
15 14
23 704 23
5
150
37
9
6
(Frange for air inlet duct)
692
145
Frange for air inlet duct
5- 3.1(Hole)
640 (160 x 4)
564
640
750
824 (Suspension bolt pitch)
194
38
(Suspension bolt pitch)
680
126
10
1-88
Page 94
1-4. Dimensional Data
(A) Indoor Units: Concealed-Duct High Static Pressure Type (D Type)
SPW-D705H SPW-D905H
Refrigerant tubing joint (liquid tube ø12.7 mm) (Flare nut)
Refrigerant tubing joint (gas tube ø25.4 mm) (Brazing)
Power supply outlet
Drain port (O.D. 32 mm)
Duct connection for suction
Duct connection for discharge
1170 (Suspension bolt pitch)
110051
4 - 3712 (Hole for suspension bolt)
71
1
67
Unit: mm
1070
1310
10100P=1000
28-ø3.5 (Holes all around)
44
106
41
50
100
300
479
100
178
23
209 344
5555
1222
2
1310 1200
(Suspension bolt pitch)
Electrical
component box
964
1310
9100P=900
26-ø3.5 (Holes all around)
1200 (Suspension bolt pitch)
67
113
43320
60
100
100
Drain pan
Ceiling face
Unit: mm
364364
(236)
42
1334
1428
1170
Min. 600
1100
(Suspension bolt pitch)
service)
(Space for
Air suction
side
1-89
access
Inspection
(600 600)
tubing
Refrigerant
service)
Min. 700
(Space for
Drain port
Min. 130
Min. 610
Page 95
1
1-4. Dimensional Data
(B) Outdoor Unit: SPW-C706VH8
170 660 110
Air intake
105 219 75 75
Air discharge
940
410
10
380
20
26
290
Air intake
2 x o32 holes (holes for drain)
Of the 4 o32 holes , use 1 of the 2 holes specified for drain use to install the port. Use rubber plugs to seal the remaining 3 holes.
60 13
B
34040
18
13
1
Unit:mm
Mounting hole (4-R6.5),
1
anchor bolt : M10 Refrigerant tubing (liquid tube),
2
flared connection (o9.52) Refrigerant tubing (gas tube),
3
flared connection (o19.05) Refrigerant tubing port
4
Electrical wiring port (o16)
5 6
Electrical wiring port (o19) Electrical wiring port (o29)
7
Electrical wiring port (o38)
8
Name Figure Q’ty
Reducing Joint Tube
(o19.05 o25.4)
Joint Tube (o19.05)
Remark: There are two types of supplied tubings. The one tubing port o19.05 (flare process) is connected to the flared connection of the gas port side's service valve. The other "L" shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (o25.4).
340
1
1
Anchor bolt
R30
5
6
8
Anchor bolt
6149
VIEW A
2
22
3077
42
49
7
8
60
57
8
4
Air
3
discharge
39
586
111
111
Anchor bolt
Air intake
1526
5
6
22
30
42
49
77
60
85 64
7
8
25
4
A
33
7
58
63 80
Anchor bolt
5.5 62 49
VIEW B
Refrigerant tubing connection portBottom removable connection port
67 7.5
46
65
121
5
52
60
4
3
43
6
8
59
7
Anchor bolt
1-90
Page 96
1-4. Dimensional Data
(B) Outdoor Unit: SPW-C906VH8
410
10
380
20
170 660 110
26
Air
290
intake
Air intake
105 219 75 75
Air discharge
940
2 x o32 holes (holes for drain)
Of the 4 o32 holes , use 1 of the 2 holes specified for drain use to install the port. Use rubber plugs to seal the remaining 3 holes.
60 13
B
34040
18
13
1
Unit:mm
Mounting hole (4-R6.5),
1
anchor bolt : M10 Refrigerant tubing (liquid tube),
2
flared connection (o12.7) Refrigerant tubing (gas tube),
3
flared connection (o19.05) Refrigerant tubing port
4
Electrical wiring port (o16)
5 6
Electrical wiring port (o19) Electrical wiring port (o29)
7
Electrical wiring port (o38)
8
Name Figure Q’ty
Reducing Joint Tube
(o19.05 o25.4)
Joint Tube (o19.05)
Remark: There are two types of supplied tubings. The one tubing port o19.05 (flare process) is connected to the flared connection of the gas port side's service valve. The other "L" shaped tubing port is brazed in connection after cutting the tube at the proper length. Then make a brazing connection to the main tubing (o25.4).
340
1
1
1
Anchor bolt
R30
5
6
8
Anchor bolt
6149
VIEW A
2
22
30
42
49
7
8
8
77
60
57
4
Air
3
discharge
39
586
111
111
Anchor bolt
Air intake
1526
5
6
22
30
42
49
77
85 64
7
8
25
4
60
A
33
7
58
63 80
Anchor bolt
5.5
Refrigerant tubing connection portBottom removable connection port
62 49
VIEW B
67 7.5
46
65
121
5
52
60
4
3
43
6
8
59
7
Anchor bolt
1-91
Page 97
1
1-5. Refrigerant Flow Diagram
Accumulator Accumulator
Compressor
Cooling cycle Heating cycle
Indoor Unit: 18, 25, 36, 70 TypesOutdoor Unit: SPW-C706VH8
Solenoid valve
High pressure switch
HP
Check valve
Heat exchanger
Distributor
Accumulator Accumulator
Compressor
EC
P
Liquid tank
S
Freeze-prevention coil (Attached to the heat exchanger)
4-way valve
Solenoid valve
M
M
Strainer
Strainer
Gas line service valve
(3/4")
Liquid line service valve
ø25.4 (brazing)
ø9.52
Indoor Unit: 25, 48, 90 TypesOutdoor Unit: SPW-C906VH8
Heat exchanger
Distributor
Strainer
High pressure switch
Heat exchanger
Distributor
HP
Check valve
EC
P
S
Freeze-prevention coil (Attached to the heat exchanger)
1-6. Operating Range
Temperature Indoor air intake temp. Outdoor air intake temp.
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
Solenoid valve
Strainer
Gas line service valve
4-way valve
Solenoid valve
M
M
Strainer
(3/4")
Liquid line service valve
ø25.4 (brazing)
ø12.7
32°C DB / 23°C WB 43°C DB
18°C DB / 14°C WB –15°C DB
30°C DB / – WB 15°C WB
–20°C WB
Heat exchanger
Distributor
Strainer
1-92
Page 98
1-7. Capacity Correction Graph According to Temperature Condition
SPW-C706 / 906VH8
Max. Capacity & Input Change Characteristics When the Outdoor Air Temperature Changes :
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
1
140
120
100
80
60
40
Capacity coefficient (%)Input coefficient (%)
140
120
100
80
60
Indoor air intake temp (WB)
120
22WB 19WB 16WB
Indoor air intake temp (WB)
22WB 19WB 16WB
-5 -10 5010-5
3525155-15 45
100
80
60
40
Capacity coefficient (%)Input coefficient (%)
120
100
80
60
40
Indoor air intake temp (°C DB)
Indoor air intake temp (°C DB)
-15 15-20
16 20 24
24 20 16
Outdoor air intake temp (°C DB) Outdoor air intake temp (°C WB)
NOTE:
1. The characteristics of this table shows the values under the following condition. Piping equivalent length 7.5m High & low difference 0m Airflow rate High
2. The circle mark " " shows the maximum efficiency and maximum power consumption under the standard condition. * The maximum efficiency shows the maximum value in the parenthesis of the specifications (cooling and heating capacity).
3. The heating capacity of this table excludes the capacity failure under the condensation (including the defrosting drive).
For 50 Hz and 60 HzFor 50 Hz and 60 Hz
Outdoor unit heating capacity correction coefficient during of frosting/defrosting
Outdoor intake air temperature °C WB
Correction coefficient
-20 -15 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 6543
1.0 1.0 0.97 0.96 0.96 0.95 0.94 0.890.91 0.88 0.87 0.870.87 0.88 0.89
(RH approximately 85%)
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity found from the capacity graph by the correction coefficient from the table above.
1-93
1.00.950.91 0.92
Page 99
1
1-8. Noise Criterion Curves
(A) Indoor Units
4-Way Air Discharge Semi-Concealed Type
MODEL :
SOUND LEVEL : 31 dB(A)
CONDITION :
60
50
40
30
Approximate minimum audible
20
(0dB = 0.0002µbar)
limit for
Sound pressure level (dB)
continuous noise
10
Overall
Frequency at center of sound pressure band (Hz)
MODEL :
SOUND LEVEL : 39 dB(A)
CONDITION :
60
SPW-XDR184GH56 (A/B) SPW-X185H
STRONG
MEDIUM
WEAK
1.5 m directly below unit
SPW-XDR364GH56 (A/B) SPW-X365H
29 dB(A)
27 dB(A)
400063 125 250 800020001000500
STRONG
MEDIUM
WEAK
1.5 m directly below unit
36 dB(A)
33 dB(A)
NC-50
NC-40
NC-30
NC-20
Both 50Hz / 60Hz
MODEL :
SOUND LEVEL : 34 dB(A)
CONDITION :
60
50
40
30
Approximate minimum audible
20
(0dB = 0.0002µbar)
limit for
Sound pressure level (dB)
continuous noise
10
Overall
Frequency at center of sound pressure band (Hz)
MODEL :
SOUND LEVEL : 42 dB(A)
CONDITION :
60
SPW-XDR254GH56 (A/B) SPW-X255H
STRONG
MEDIUM
WEAK
1.5 m directly below unit
SPW-XDR484GH56 (A/B) SPW-X485H
31 dB(A)
28 dB(A)
STRONG
MEDIUM
WEAK
1.5 m directly below unit
38 dB(A)
34 dB(A)
Strong
Weak
NC-50
NC-40
NC-30
NC-20
400063 125 250 800020001000500
50
40
30
Approximate minimum audible
20
(0dB = 0.0002µbar)
limit for
Sound pressure level (dB)
continuous noise
10
Overall
Frequency at center of sound pressure band (Hz)
400063 125 250 800020001000500
NC-50
NC-40
NC-30
NC-20
50
40
30
Approximate minimum audible
20
(0dB = 0.0002µbar)
limit for
Sound pressure level (dB)
continuous noise
10
Overall
Frequency at center of sound pressure band (Hz)
NC-50
NC-40
NC-30
NC-20
400063 125 250 800020001000500
1-94
Page 100
1-8. Noise Criterion Curves
1
(A) Indoor Units
4-Way Air Discharge Semi-Concealed Type
MODEL
SOUND LEVEL 41
CONDITION
60
50
40
30
Approximate minimum audible
20
(0dB = 0.0002µbar)
limit for
Sound pressure level (dB)
continuous noise
10
Overall
Frequency at center of sound pressure band (Hz)
:
SPW-XM185H
:
STRONG
WEAK 33
1.5 m directly below unit
:
dB(A)
dB(A)
NC-50
NC-40
NC-30
NC-20
400063 125 250 800020001000500
Both 50Hz / 60Hz
Strong
Weak
1-95