Sanyo SPW-UMR94EXH56, SPW-UMR74EXH56, SPW-UMR184EXH56, SPW-UMR224EXH56, SPW-UMR124EXH56 User Manual 2

...
TECHNICAL DATA & SERVICE MANUAL
SPLIT SYSTEM AIR CONDITIONER
SPW-UMR124EXH56 SPW-UMR164EXH56 SPW-UMR184EXH56 854.0.2266 SPW-UMR224EXH56 854.0.2267
854.0.2263
854.0.2265
854.0.2301
0.8180.439.0 June 2005
SM940046
IMPORTANT! Please read before installation
This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
WARNING
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When wiring
Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing...
… In a ceiling
Make sure the ceiling is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.
… In a room
Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher then drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause
accidental injury and death.
When servicing
• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate the room during the installation or test system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
ing the refrigeration
2
Table of Contents
Page
1. SPECIFICATIONS
1-1 Unit specifications 4 1-2 Major Component specifications 7 1-3 Other Component specifications 10
2. DIMENSIONAL DATA
3. ELECTRICAL DATA
3-1 Electric Wiring Diagram 13 3-2 Control PCB switches and functions 14
4. FUNCTION
4-1 Room Temperature Control 15 4-2 Automatic control for heating and cooling 16
5. REPLACING PCB
5-1 Replacing PCB 17 5-2 How to replace PCB 18 5-3 How to replace EEPROM with EEPROM included in PCB service pack 19 5-4 Table of setting 21
4
11
13
15
17
6. SERVICING AND MAINTENANCE FUNCTIONS
6-1 Indoor unit refrigerant noise countermeasures 22 6-2 Outdoor unit noise countermeasures: EEPROM 05 22
7. TROUBLE DIAGNOSIS
7-1 Contents of remote controller switch alarm display 23 7-2 Outdoor unit control panel led display 25 7-3 Trouble indications and inspection points 26 7-4 Remote controller servicing functions 28 7-5 Super W-Multi alarm codes 7-6 Inspection of parts 35
22
23
29
3
1. SPECIFICATIONS
V
g
g
1-1 Unit Specifications
SPW-UMR74/94/124EXH56
Power source
oltage ratin
Performance
Capacity Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls Remote Controller (Option) wired
Fan speed
Air Filter Sound pressure level (*) high/med/low dB(A) Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant control
Dimensions & Wei
Dimensions Height mm
Package dimensions Height mm
Weight Net kg
ht
Width mm Depth mm
Width mm Depth mm Volume m3
Shipping kg
wireless
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
600/510/440
Microprocessor/ I.C. thermostat
RCS-SH80AG / RCS-KR1AG
RCS-BH80AG.WL
3 and Auto
Washable
54/52/49
Flare type
6,35 (1/4) 12,7 (1/2)
R410A
Electronic expansion valve
266 571 852 365 745
1086
0,3
30,0
34
DATA SUBJECT TO CHANGE WITHOUT NOTICE
(*)
Power noise level measured at operating conditions (5mmH20 external static pressure)
4
SPW-UMR164/184EXH56
V
g
g
Power source
oltage ratin
Performance
Capacity Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls Remote Controller (Option) wired
Fan speed
Air Filter Sound pressure level (*) high/med/low dB(A) Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant control
Dimensions & Wei
Dimensions Height mm
Package dimensions Height mm
Weight Net kg
ht
Width mm Depth mm
Width mm Depth mm Volume m3
Shipping kg
wireless
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
875/600/400
Microprocessor/ I.C. thermostat
RCS-SH80AG / RCS-KR1AG
RCS-BH80AG.WL
3 and Auto
Washable
54/47/42
Flare type
6,35 (1/4) 12,7 (1/2)
R410A
Electronic expansion valve
266 571
1058
365 745
1292
0,35
35 39
DATA SUBJECT TO CHANGE WITHOUT NOTICE
5
SPW-UMR224EXH56
V
g
g
Power source
oltage ratin
Performance
Capacity Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls Remote Controller (Option) wired
Fan speed
Air Filter Sound pressure level (*) high/med/low dB(A) Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant control
Dimensions & Wei
Dimensions Height mm
Package dimensions Height mm
Weight Net kg
ht
Width mm Depth mm
Width mm Depth mm Volume m3
Shipping kg
wireless
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
1000/700/600
Microprocessor/ I.C. thermostat
RCS-SH80AG / RCS-KR1AG
RCS-BH80AG.WL
3 and Auto
Washable
57/49/46
Flare type
9,52 (3/8)
15,88 (5/8)
R410A
Electronic expansion valve
266 571
1058
365 745
1292
0,35
35 39
DATA SUBJECT TO CHANGE WITHOUT NOTICE
6
1-2 Major Component Specifications
SPW-XMR74/94/124EXH56
Controller PCB
Part No. Controls
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Running Amps A Power input W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
CR-CRP50A-B
Microprocessor
Centrifugal fan
2…. Ø 160 / L 240
3RGB-CO-45-30 5V/1….1
4 … 1060
0,45
110 BLU-BRN: 95 BRN-BLK: 37 BLK-GRY: 15 GRY-VLT: 15
WLT-RED: 30
RED-YEL: 101
Internal thermal protector - 7AM 037 A 5
150 ± 5K
Run capacitor µF
Electronic expansion valve
Coil Valve body
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
1,8
VAC
Aluminium plate fin / Copper tube
DATA SUBJECT TO CHANGE WITHOUT NOTICE
450
UKV-U030E UKV-18D31
2
1,6
0,126
7
SPW-XMR164/184EXH56
Controller PCB
Part No. Controls
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Running Amps A Power input W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
CR-CRP50A-B
Microprocessor
Centrifugal fan
2…. Ø 160 / L 240
3FGB-CO-65-38 5V/1….1
4 … 1106
0,6
138 BLU-BRN: 68 BRN-BLK: 9 BLK-GRY: 36 GRY-VLT: 18
VLT-RED: 18 BRN-YEL: 105
Internal thermal protector - 7AM 037 A 5
150 ± 5K
2,0
450
Electronic expansion valve
Coil Valve body
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
UKV-U030E UKV-25D32
Aluminium plate fin / Copper tube
3
1,6
0,168
DATA SUBJECT TO CHANGE WITHOUT NOTICE
8
SPW-XMR224EXH56
Controller PCB
Part No. Controls
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Running Amps A Power input W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
CR-CRP50A-B
Microprocessor
Centrifugal fan
2…. Ø 160 / L 240
3FGB-CO-65-38 5V/1….1
4 … 1161
0,57
136 BLU-BRN: 68 BRN-BLK: 9 BLK-GRY: 36 GRY-VLT: 18
VLT-RED: 18 BRN-YEL: 105
Internal thermal protector - 7AM 037 A 5
150 ± 5K
3
450
Electronic expansion valve
Coil Valve body
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
UKV-U030E UKV-25D32
Aluminium plate fin / Copper tube
3
1,6
0,168
DATA SUBJECT TO CHANGE WITHOUT NOTICE
9
1-3 Other Component Specifications
(
)
)
)
y
Trasformer
Rating Primary
Secondary 1 Secondary 2 Secondary 3
Thermal cut-off temp.
Thermistor
Resistance
Thermistor ( Coil sensor E3
Resistance
Thermistor ( Room sensor TA, TF/BL
Resistance
Drain pump
Model Rating Voltage
Flow rate
Safet
Model
Coil sensor E1, E2
Input
float switch
ATR-IIJ225A
VAC 230V, 50Hz
AC 20V - 0.2A AC 14V - 0.3A
AC 10,2V - 1.4A
136°C
PBC-41E-S26
k
k
k
0 °C 15,0 ± 5%
PBC-41E-S42-2
0 °C 15,0 ± 4,42%
DHKTEC-35-S85N
25 °C 5,0 ± 4%
PC 309564003
220/240V - 50Hz
14W
0,4 l/min
BI 1300 2725
Contact rating
230V AC/DC - 0,5A
10
2. DIMENSIONAL DATA
SPW-UMR74/94/124EXH56
11
SPW-UMR164/184/224EXH56
12