Sanyo SGP-EZ240M2G2, SGP-WE80M1, SGP-EZ150M2G2, SPW-GU105XH, SGP-WE170M1 User Manual

...
Gas Driven VRF
GAS DRIVEN VRF
ELECTRIC VRF
COMMERCIAL SPLIT SYSTEMS
ROOM AIR CONDITIONERS
M Series
SANYO Air Conditioners. The natural choice.
2
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
3
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
SANYO GHP - the natural choice
Discharge of heat absorbed from the inside of the room by liquefaction of refrigerant.
Heat Heat
Refrigerant gas
Refrigerant liquid
Refrigerant liquid
Outdoor unit
Outdoor unit
Warm air
Warm air
Cold air
Cold air
Compressor
Gas engine
Compressor
Gas engine
Absorption of heat from the outside air by evaporation of refrigerant.
Refrigerant gas
Engine waste heat
Hot water function
Absorption of heat from the room by liquefaction of refrigerant.
Discharge of heat generated by condensation of refrigerant.
Gas Heat Pump M Series - the perfect solution when you’re short of power
SANYO benets
What is a GHP?
The application principle of Variable Refrigerant Flow (VRF) systems for projects with multiple indoor unit is now
very much an integral element of the UK air conditioning
market place.
SANYO has been developing GHP VRF systems since 1980, during which time we have been committed to delivering ground-breaking technology. As a result, the commercial range of GHP VRF systems is leading the industry in the development of ecient and exible systems, making them the natural choice for commercial projects, especially for those projects where power restrictions apply. As you would expect, all of our gas driven VRF systems have the highest reliability rates in the industry and a leading customer service programme.
The M Series of gas driven VRF systems oers increased eciency and performance across the range. Now more powerful than ever before, it can connect to up to 48 indoor units.
Improvements include increased part load performance, reduced gas consumption with a Miller-cycle engine and reduced electrical consumption from using DC fan motors.
• Up to 71kW of cooling from a maximum running capacity of 5
AMPs
• Single phase power supply across the range
• The option of natural gas or LPG as its main power source
• Free hot water! A water heat exchanger to connect to domestic
hot water systems 13-25 HP (Heat Pump only)
• Option of DX or chilled water for indoor heat exchange
• Option to connect to third party Air Handling Units
• Reduced CO
emissions
2
Power supply problems?
If you are short of electrical power, gas heat pump could be the perfect solution.
High-eciency operation
13-25 HP models are equipped with a high-performance air exchanger and a newly developed refrigerant heat exchanger for high-eciency operation, making them one of the most energy-ecient solutions on the market.
Lowest nitrogen oxide emissions
The GHP VRF systems have the lowest nitrogen oxide emissions, 66% below the standard. In a pioneering development, the SANYO GHP features a brand new lean-burn combustion system that utilises air fuel ratio feedback control to reduce NOx emissions to an all-time low.
Excellent economy
The SANYO GHP provides quick and powerful cooling/ heating and increases delivery of heat into the space by the ecient recovery of heat from the engine cooling water, which is injected into the refrigerant circuit.
In addition, the use of engine waste heat ensures that our gas heat pump air conditioner requires no defrost cycle, therefore providing continuous 100% heating performance in severe weather conditions with an outside air temperature as low as
-20°C. During cooling mode the rejected heat from the engine is available for use within a hot water system and can supply up to 25kW of hot water at 75 °C.
High performance
With its advanced heat exchanger design, this new GHP system oers improved eciency and reduced running costs, which, coupled with improved engine management systems, have greatly improved the system COP rating.
New electrical power generator model
The biggest breakthrough in recent GHP technology is the launch of the ECO G Power, which provides 4.0kW of power. That’s enough electricity to power 8 computers or other applications.
A GHP is no dierent in principle, however, developed by SANYO in 1980 the GHP outdoor unit is tted with a combustion engine, powered by
Natural gas or LPG, to drive the refrigerant compressor.
Variable capacity is achieved via the engine speed being altered up and down just as an inverter compressor speed is controlled in the electric VRF equivalent. The GHP therefore is an ideal solution where electrical power is at a premium (or no 3 phase available) however it also boasts a number of additional benets/functions that are not
available on an electric equivalent
.
High eciency heat exchanger
The ‘M’ series GHP continues to use a ‘hybrid’ heat exchanger for improved eciency. By interlacing the refrigerant coil with the radiator carrying the coolant from the engine, the condensing capacity and radiator performance is balanced to an optimum level. This combination ensures the cooling eciency drop in cold ambient is kept to a minimum, heating performance is down to -20oc and maintain a high COP.
Higher engine eciency
Air
By utilising a Miler-Cycle engine, the compression stroke is reduced and therefore pumping losses are minimised. As a result the expansion volume ratio increases and the eciency improves.
Miller cycle: This heat cycle has the characteristic that the closing time for the suction valve in regard to the base engine is late. As a result, the expansion stroke becomes relatively longer in comparison to the compression stroke.
Refrigerant heat exchanger
By tting a new plate heat exchanger the engine waste heat is recovered eciently and reused to improve performance. In addition a proportionate control 3 way change over valve is used for control of the engine cooling water to increase eciency in heating operation
How a GHP works - High performance and low operating costs by using gas fuel
Exhaust
Fan
Accumulator
Compressor
• Runs on gas and just needs single phase supply.
• Enables the building’s electrical power supply to be
used for other critical electrical demands.
• Reduces capital cost to upgrade power substations
to run heating and cooling systems.
• Reduces power loadings within a building especially
• Electricity supply freed up for other uses such as IT
during peak periods.
servers, commercial refrigeration, manufacturing, lighting etc.
GHP features at a glance
• Power generation of up to 4kW on ECO G Power version
Up to 25kW hot water generation on all 2 pipe heat pump
versions
• Chiller module available for water based solutions
• 100% heating performance even at -200c ambient
• 180% indoor connectability (Single heat pump module)
• Single phase power required through the range
Cooling Heating
4
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
5
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
Still the only heat recovery (3 way) GHP system in
Comparison of the start times for heating operation
Room temperature (˚C )
Gas heat pump
Electric heat pump
Time axis (in case of the same load) Outside air temperature (˚C)
Electric heat pump
Gas heat pump
Comparison of heating capacity
Heating capacity (% )
Electric heat pump
Gas heat pump
Comparison of heating capacity
Heating capacity (% )
Rear View Front View
Left Side View
at least 2000
Service Clearances for installation
(Units: mm)
Rear (refrigerant tubing)
Rear (refrigerant tubing)
at least
600
at least
600
at least
1000
at least
1000
at least
100
at least
100
at least
100
at least
350
at least
350
Front View Front View
(Single-unit installation)
(Multi-unit series installation)
Suction refrigerant pipe
ø28.58
ø22.22
Size (mm)
Model Type 150
190 240
ø25.4
ø19.05
ø28 ø28
G: R3/4
ø20
4 - ø20 4 - ø24
OD: ø25 Length: 200
1
Discharge refrigerant pipe
2
Liquid refrigerant pipe
3
Exhaust gas drain hose
4
Inter-unit cable port
5
Electrical power supply port
6
Fuel gas port
7
Condensation drain opening
8
Rain and condensation outlet
9
Engine exhaust outlet
10
Suspension holes
11
Anchor holes
12
Segmented display
13
Coolant intake (top)
14
Vent
15
Top View
1800 (external)
2248 (+30)
(181)
400
1014
(anchor pitch)
1000
(anchor pitch)
10
14
12
13
1030
(suspension holes)
1000 (external)
ø736
1060
(frame width)
9
15
11
27
54
147
22
99
108
181
57
207 242 279 312
555
271
7
6
5
4
3
1
2
8
Europe.
The new M Series ECO G 3 Way oers even more performance and outstanding features when you need simultaneous heating and cooling. Now with increased capacities available from 16HP to 25HP, SANYO oers the greatest choice and exibility to solve any power problem or site requirement.
• Simultaneous heating and cooling for total control
• Reduced gas consumption by Miller-cycle engine
• Reduced electrical power consumption by using DC motors
• New lightweight design by use of aluminium engine block
reduces weight by 110kg
• Part load eciencies increased
• Connectability increased to up to 36 indoor units
• Now available in 16, 20 and 25HP
• 200m maximum allowable piping length (L1) (equivalent - refer
to technical manual)
ECO G 3 Way Outdoor Unit SpecicationsECO G 3 Way Heat Recovery VRF System
HP 16 20 25
Model SGP-EZ150M2G2 SGP-EZ190M2G2 SGP-EZ240M2G2
Capacity
Electricity
Gas
COP
Size
Weight kg 845 875 Starter amperes A 30
Piping connection
Pipe fuel gas R3/4 (bolt thread) Pipe exhaust drain mm ø 25 rubber hose Operation sound dB(A) 57 58 62 Indoor/outdoor capacity ratio 50-180% *1 Number of indoor connections 36 * 1: Low temp condition: Outdoor temperature 2 C˚.
Condenser actual pipe connec tions may vary from above pipe connections shown, please refer to technical manuals for full details. Please refer to tube sizing charts for pipe selections and pipe length parameters.
Cooling kW 45.0 56.0 71.0 Heating STD Heating Low temp* 53.0 67.0 75.0 Cooling kW 1.35 Heating kW 1.01 1.54 Cooling kW 31.6 38.3 60.9 Heating STD Heating LOW 47.3 56.4 64.9 Cooling 1.37 1.41 1.14 Heating 1.35 1.43 1.34 AVE 1.36 1.42 1.24
Gas
Discharge 7/8 (22.22)
Inches (mm)
Liquid 3/4 (19.05)
kW
kW
Height
mm
Width 1,800
Depth 1,000 (+60)
50.0 63.0 80.0
36.1 43.0 58.0
2,248
1 1/8 (28.58)
• Diversity ratio 50% - 130%
• Extended pipe runs (total 500m)
• Silent mode oers a further 2dB(A) reduction
• 10,000 run hours between engine service intervals (equivalent
to one maintenance every 3.2 years*)
• Full heating capacity down to -20°C
• No defrost cycle
* Assuming 3120 running hrs per year - 12 hrs x 5 days x 52 week s
ECO G 3 Way is ideal for the following types of application:
• Oce buildings with a diverse range of room temperatures
due to diering load proles.
• Buildings with computer rooms requiring year round cooling.
Additional parts
By taking its power supply from the nearest indoor unit, the SANYO solenoid valve (change-over box) does not require any additional fused spur and at only 150mm high can be easily installed within a 200mm void space.
LPG option
The option of using LPG as a power supply increases exibility
and avoids the problems of potential site restrictions in the future. The purer fuel is also excellent for further reductions in CO2 emissions - a fact recognised by the government.
Dimensions ECO G 3 Way (16-25HP)
6
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
7
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
ECO G 2 Way Heat Pump VRF System
Rear View Front View
Left Side View
at least 2000
Service Clearances for installation
(Units: mm)
Rear (refrigerant tubing)
Rear (refrigerant tubing)
at least
600
at least
600
at least
1000
at least
1000
at least
100
at least
100
at least
100
at least
350
at least
350
Front View Front View
(Single-unit installation)
(Multi-unit series installation)
Gas refrigerant pipe (Gas tube)
ø25.4 ø28.58
ø12.7
Size (mm)
120Model Type 150
190 and 240
ø15.88
ø9.52
ø28 ø28
ø28
G: R3/4
ø20
4 - ø20 4 - ø24
Rp3/4 Rp3/4
OD: ø25 Length: 200
1
Liquid refrigerant pipe (Liquid tube)
2
Refrigerant balance pipe (Balance tube)
3
Exhaust gas drain hose
4
Electrical power supply port
5
Inter-unit cable port
6
Fuel gas port
7
Condensation drain opening
8
Rain and condensation outlet
9
Engine exhaust outlet
10
Suspension holes
11
Anchor holes
12
Segmented display
13
Coolant intake (top)
14
Vent
15
Hot water intake
16
Hot water outlet
17
Cable inlet for interlock and the like
18
Top View
1800
2248
400
1014
(anchor pitch)
1000
(anchor pitch)
10
14
12
12
1040
1000 ø736
1060
9
15
11
27
118 50
55
54 147 207 242 275 312 461
5583999522
555
163
271
3
17
16
7
2
1
4
8
18
6
5
ECO G W-Multi for Heat Pump Applications
The new and improved M Series heat pump (2 Way) not only oers improved performance but also increased exibility. Now available as multi-systems, many combinations are possible, from 13HP to 50HP, allowing for more power and enabling accurate matching of a system building load. Additional new features include part load engine management and compressor run hour equalisation.
• Reduced gas consumption by Miller-cycle engine
• Reduced electrical power consumption by using DC motors
• New lightweight design by use of aluminium engine block
reduces weight by 110kg
ECO G 2 Way Outdoor Unit Specications
Dimensions ECO G W-Multi 2 Way
• Part load eciencies increased
• Connectability increased - now up to 48 indoor units
• Multi-systems with combinations from 13HP up to 50HP
• 200m maximum allowable piping length (L1) (equivalent - refer
to technical manual)
• Diversity ratio 50-180%
• Extended pipe runs (total 500m)
• Industry leading sound levels
• Silent mode oers a further 2dB(A) reduction
• Chiller option
- 13HP (25kW cooling - 30kW heating)
- 25HP (56kW cooling - 67kW heating)
• 10,000 run hours between engine service intervals (equivalent
to one maintenance every 3.2 years*)
• Full heating capacity down to -20°C
• No defrost cycle
* Assuming 3120 running hrs per year - 12 hrs x 5 days x 52 weeks
HP 13 16 20 25 26 29 32 33* 36* 40* 45* 50
Model name
Capacity
Electricity
Gas consumption
COP
Max COP (inc hot water) Cooling 1.87 1.85 1.92 1.54 1.87 1.86 1.85 1.90 1.89 1.92 1.69 1.54
Size
Cooling kW 35.50 45.00 56.00 71.00 80.50 90.00 91.50 101.00 112..0 127.00 142.00 Heating STD Heating Low temp*1 42.50 53.00 67.00 75.00 85.00 95.50 106.00 109.50 120.00 134.00 142.00 150.00 Hot water 12.00 16.00 20.00 25.00 24.00 28.00 32.00 32.00 36.00 40.00 45.00 50.00 Cooling kW 0.85 1.35 1.70 2.20 2.70 2.20 2.70 Heating 1.01 1.54 2.02 2.55 3.08 Cooling kW 24.50 31.60 38.30 60.90 49.00 56.10 63.20 62.80 69.90 76.60 99.20 121.80 Heating STD Heating LOW 36.80 47.30 56.40 64.90 73.60 84.10 94.60 93.20 103.70 112.80 121.30 129.80
kW
kW
Cooling 1.40 1.37 1.41 1.14 1.40 1.38 1.37 1.41 1.39 1.41 1.25 1.14 Heating 1.37 1.35 1.43 1.34 1.37 1.36 1.35 1.41 1.39 1.43 1.38 1.34 AVE 1.39 1.36 1.42 1.24 1.39 1.37 1.36 1.41 1.39 1.42 1.31 1.24
Height
mm
Width 1,800 1,800 + 100 (min distance) + 1,800 (in a straight installation)
SGP-EW120M2G2W SGP-EW150M2G2W SGP-EW190M2G2W SGP-EW240M2G2W SGP-EW120M2G2W SGP-EW120M2G2W SGP-EW150M2G2W SGP-EW120M2G2W SGP-EW150M2G2W SGP-EW190M2G2W SGP-EW190M2G2W SGP-EW240M2G2W
SGP-EW120M2G2W SGP-EW150M2G2W SGP-EW150M2G2W SGP-EW190M2G2W SGP-EW190M2G2W SGP-EW190M2G2W SGP-EW240M2G2W SGP-EW240M2G2W
40.00 50.00 63.00 80.00 90.00 100.00 103.00 113.00 126.00 143.00 160.00
28.10 36.10 43.00 58.00 56.20 64.20 72.20 71.10 79.10 86.00 101.00 116.00
2,248
Depth 1,000 (+60) Weight kg 790 820 850 1,580 1,610 1,640 1,670 1,700 Starter amperes (A) 30
Gas
Piping connection
Liquid 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Inches (mm)
Balance 3/8 (9.52) Pipe fuel gas R3/4 (bolt thread) Pipe exhaust drain ø25 rubber hose Operation sound dB(A) 57 58 62 60 61 63 65 Indoor/outdoor capacity ratio 50-180 % 50-130 % Number of indoor connections 32 36 48 * In case of these combinations EGW190M2G2W is able to connect as W-multi instead of EW190M2G2w.
* 1: Low temp condition: Outdoor temperature 2 C˚. Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details. Please refer to tube sizing charts for pipe selections and pipe length parameters.
Capacity Hot Water is available when outside ambient air temperature is above 7C˚.
1 1/8 (28.58) 1 3/8 (34.92) 1 5/8 (41.27)
8
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
9
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
ECO G Power - GHP with electricity generation
Service Clearances for installation
Top View
Rear View Front View
Left Side View
at least 2000
(Units: mm)
Rear (refrigerant tubing)
Rear (refrigerant tubing)
at least
600
at least
600
at least
1000
at least
1000
22
50
271
54 147 207 242 275 312 461
27
83
99
138
163
178
193
555
at least
100
at least
100
1000 (external)
1800 (external)
1040
(suspension holes)
1100
(frame width)
ø736
at least
100
at least
350
400
(169)
2248 5
1014
(anchor pitch)
1000
(anchor pitch)
at least
350
Front View Front View
(Single-unit installation) (Multi-unit series installation)
Gas refrigerant pipe (Gas tube) ø28.58
Size (mm)
ø15.88 ø9.52
ø28 ø28
ø20
ø28 ø40 G: R3/4
Rp3/4 Rp3/4
OD: Length:
1
Liquid refrigerant pipe (Liquid tube)
2
Refrigerant balance pipe (Balance tube)
3
Exhaust gas drain hose
4
Electrical power supply port
5
Inter-unit cable port
6
Inverter cable port
7
Inverter cable port
8
Fuel gas port
9
Condensation drain opening
10
Rain and condensation outlet
11
Engine exhaust outlet
12
Suspension holes 4 - ø20
13
Anchor holes 4 - ø24
14
Segment display
15
Coolant intake (top)
16
Vent
17
Hot water intake
18
Hot water outlet
19
12
14 16
9
11
17
13
15
8
3
4
2
10
1
19
18
7
5
6
& hot water supply
NEW 2 way gas driven VRF with electrical power generator
SANYO’s ECO G Power is a revolution in air conditioning design. Fitted with a permanent magnet, non-bearing type generator, it is the rst VRF system that can supply heating, cooling, hot water and now also a supply of electrical power.
Each ECO G Power unit has a 4.0kW generator, which provides enough electricity to power 8 computers or other applications.
• Innovative technology that reduces CO2 emissions by up to
30%
• Heat pump air conditioning system providing cooling or heating
• Can provide both electricity and hot water in heating and
cooling mode
• Up to 4kW electricity generated
• Very ecient generator
• Hot water provided when cooling or heating when outside
ambient air temperature is above 7°C
• 22kW hot water generation capacity
• 20HP model provides 56kW cooling or 63kW heating
• Can connect to up to 36 indoor units
• 200m maximum allowable piping length (L1) (equivalent - refer
to technical manual)
• IU/OU capacity ratio 50 - 130%
NEW
High power engine
Line linkage
inverter
Production of electricity
Generates from 2kW to 4kW depending on air conditioning load
4.5
4
3.5
3
2.5
2
1.5
1
Production of electricity (kW)
0.5
0
0 10 20 30 40 50 60 70 80 90 100
Air conditioning load (%)
Generate electricity during heating or cooling operation
Generate electricity and air conditioning (heating or cooling) at the same time by using remaining engine power. ECO G Power can generate from 2.3 to 4.0kW electricity at a generation eciency of more than 40%.
Power generator
• permanent magnet type
• non-bearing
Double clutch compressor
HP 20 33 36 40 45
Model
Cooling kW 56.0 91.50 101.00 112.00 127.00
Capacity
Power generater capacity at rating
Electricity
Gas consumption
COP Air conditioning only
Max COP (Inc generater, hot water) Cooling
Height
Weight kg 875 1,660 1,685 1,740 1,720 Starter amperes A 30
Pipe
Pipe fuel gas R3/4 (bolt, thread) Pipe exhaust drain port mm ø25 rubber hose Operation sound dB(A) 58 61 63 Indoor/outdoor capacity ratio 50-130% Number of indoor connections* 32 48 Condenser actual pipe connec tions may vary from above pipe connections shown, please refer to technical manuals for full details.
Please refer to tube sizing charts for pipe selections and pipe length parameters.
Capacit y Hot Water is available when outside ambient air temperature is above 7˚C.
Heating STD Heating Low temp*1 67.0 109.50 120.00 134.00 142.00 Hot water 22.0 34.0 38.0 44.0 47 .00
Cooling kW 1.35 2.20 2.70 Heating kW 1.01 2.02 2.55
Cooling kW 44.0 (38.3)* 68.50 75.60 88.00 104.90 Heating STD Heating
LOW
Height Width 1,800 1,800 + 100 (Min distance) + 1,800 Depth 1,000 (+60)
Gas Liquid 5/8 (15.88) 3/4 (19.05) Balance 3/8 (9.52)
kW
kW DC 2.5 (Max 4.3)
kW
Cooling 1.33 (1.41)* 1.29 1.23 1.18 Heating 1.34 (1.43)* 1.31 1.30 1.27 1.38 AVE 1.34 (1.42)* 1.30 1.25 1.28
mm
Inches (mm)
SGP-EGW190M2G2W SGP-EW120M2G2W SGP-EW150M2G2W SGP-EGW190M2G2W SGP-EGW190M2G2W
SGP-EGW190M2G2W SGP-EGW190M2G2W SGP-EGW190M2G2W SGP-EW240M2G2W
63.0 103.0 113.00 126.00 143.00
48.7 (43.0)* 76.80 84.80 97.40 101.00
62.1 (56.4)* 98.90 109.40 124.20 121.30
1.78 1.81 1.80 1.78 1.69
2,248
1 1/8 (28.58) 1 3/8 (34.92) 1 5/8 (41.27)
Dimensions ECO G Power
System configured at site
Main Hot Water Boiler
Hot water inlet: Rø3/4
Hot water outlet: Rø3/4
Hot Water Storage Tank
Water piping
GHP
OUT
IN
Additional GHP Functions
Water Heat Exchanger
Air Handling Unit
Water Piping
Duct
Outdoor unit
GU Type Heat Exchanger & CFR Units
GHP Chiller available with outdoor unit capacities from 71kW
The SANYO ECO G Water Heat Exchanger can provide water at a wide range of temperatures suitable for a variety of commercial applications ranging from comfort air conditioning to food processing or the replacement of boilers and other systems.
• New 25 kW and 50 kW capacity models
• In cooling (chiller) mode provides water from -15°C to 15°C
• In heating mode can provide hot water up to 55°C, for example
for under oor heating applications
• Includes water ow protection to prevent freezing
• Temperature sensor included
• S-Link communication is connectable with any controllers
• Split system means reduced installation cost and the use of a
less powerful circulation pump
One touch changeover between cooling and heating operation
• The system can accommodate up to 120m (actual length) of
piping between the outdoor unit and the water heat exchanger, allowing exibility of installation location
• The system uses antifreeze coolant, so it can produce cold water
even at -15°C, thereby complying with “brine specications”
Model No. SGP-WE80M1 SGP-WE170M1
SGP-EW120M2G2W
SGP-EW150M2G2W
SGP-EW190M2G2W and SGP-EGW190M2G2W
SGP-EW240M2G2W
Electrical rating
Power supply 220/230/240V Single Phase 50Hz
Size
Weight kg 125 160 Standard cold/hot water ow rate m Hydrostatic loss kPa 8.5 11.3 Holding water quantity inside the unit m Minimum holding water quantity outside the unit
Piping refrigerant
Heat exchanger hot/cold heat exchanger Water circuit limit pressure MPa 0.686 Anti-freezing protection system Protective thermostat Specications subject to change without notice.
Operating condition Cooling
Water temperature of water heat exchanger unit Outdoor side intake air temperature 35°C DB 7°C DB, 6°C WB 2°C DB, 1°C WB Note: The gas consumption can be 110% of the specication value depending on the
operating conditions.
Cooling capacity kW 25 30 Heating capacity kW 30 35.5 Cooling capacity kW 25 37.5 Heating capacity kW 30 45 Cooling capacity kW 25 50 Heating capacity kW 30 60 Cooling capacity kW 25 56 Heating capacity kW 30 67 Cooling power input Heating power input
Height mm 1,000 Width mm 550 Depth mm 965
Gas pipe mm ø22.22 ø28.58 Liquid pipe mm ø9.52 ø15.88
kW 0.01 kW 0.01
3
/h 4.3 8.6
3
3
m
Outlet 7°C
(standard)
Outlet 45°C Outlet 45°C
Heating
Hot water supply function (during cooling or heating operation)
SGP-EW120M2G2W SGP-EW150M2G2W SGP-EW190M2G2W SGP-EW240M2G2W SGP-EGW190M2G2W
The engine waste heat, which is normally exhausted into the atmosphere, is recovered via the heat exchanger and eectively used as hot water, so the GHP system acts as a subsystem that alleviates the load on the client’s main hot water system and therefore oers “free” hot water.
10
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
Water heating capacity up to 65 kW (of 75°C hot water)
Hot water piping allowable pressure 0.7 MPa
3
Hot water circulation rate 2 - 3.9m
/h
Hot water pipe size 3/4 inch
0.01 0.02
0.28 0.50
Heating
(low temperature)
SANYO’s new heat recovery ventilation system allows total control via a system network whilst modulating the temperature and humidity of incoming air supply.
• Integration of heat recovery ventilation and DX coil technology
for optimum air temperature control
• Connects to all ECO & GHP outdoor units with a lter option
• 3 Way: Solenoid valve kit is required for each unit
• 2 Way: RAP kit is required for each unit
Indoor unit specications
Model Name SPW-GU055XH SPW-GU075XH SPW-GU105XH
Air circulation (H) m³/h 500 750 1,000 Power source 220/230/240V, 1 phase - 50 Hz Fresh air load
treatment capacity
Enthalpy exchange eciency
Temp exchange eciency 75
Equivalent cooling capacity
Power input
Running current
Fan motor
Sound pressure level (C/H) db(A) 46 (Cooling), 47 (Heating) 47 (Cooling), 48 (Heating) 48 (Cooling), 49 (Heating)
Dimensions
Piping connections
Connection duct diameter mm 250 300 Net weight kg 134 153 168 The values in ( ) for the external static pressure and operating sound are for use of booster cable. *1: Heat recovery capacity by heat exchanger. Data subject to change without notice.
UK Cooling kW 5.3 (1.7)*¹ 8.2 (2.6)*¹ 10.7 (3.4)*¹ UK Heating kW 6.5 (2.3)*¹ 9.8 (3.5)*¹ 12.6 (4.6)*¹
UK Cooling % 59 UK Heating % 67
kW 3.6 5.6 7.3
BTU/h 12,000 19,000 25,000 Cooling kW 0.532 0.737 0.798 Heating kW 0.532 0.737 0.798 Cooling Amps 2.4 3.2 3.5 Heating Amps 2.4 3.2 3.5 Type Sirocco fan External static pressure-return air Pa 183 (170) 221 (188) 135 (88) External static pressure-supply air Pa 205 (182) 264 (218) 176 (137) Output kW 0.28 (4P)x2 0.35 (4P)x2
Height mm 425 450 Width mm 1785 1903 Depth mm 1000 1120 1220 Liquid (are) mm (inches) 6.35 (1/4) Gas (are) mm (inches) 12.7 (1/2) Drain piping VP-25
The CFR- PHE uses a unique purifying Bioxigen system to produce negative ions this can reduce pollutants by up to 85% whilst improving, signicantly air quality within most environments.
• High eciency heat exchanger & Easy to clean lters
The CFR-PHE unit structure is constructed from Aluzink frame work and galvanised steel with 20 mm thick re resistant acoustic insulation, reducing both weight and sound levels to a minimum. The system is supplied with ducted spigots which can be positioned either at the front or side of the unit to ease
The high eciency low pressure loss total heat exchanger is made of specially treated paper to enable the unit to be as ecient as 76% during normal operation. This allows system to recover both latent and sensible heat.
installation.
Indoor unit specications
Model CFR/ CFR-PHE 33 55 110 175 220
Nominal air ow * m3/hr 300 620 920 1580 1850 External Static Pressure pa 45 55 65 70 77 Sound Pressure ** dB(A) 43 51 50 53 52 Fans Power in Watts 184 340 294 700 700 Absorbed power A 0.75 1.8 2.2 4.4 4.8 Fan speeds no 1 3 Insulation Class F Electrical supply v/ph/htz 230/1/50 Bioxigen Elements (PHE only) Number of elements 2 X C 2 X F Electrical supply v/ph/htz 230/1/50 Power in Watts 8 8 8 8 8 Filter EU3 Paper Heat Exchanger CFR-PHE Temperature Eciency heating *** 76% 74% 72% 68% 73% Temperature Eciency cooling **** 62% 60% 58% 54% 59%
* Nominal air ow ** Sound pressure 1.5 mts from the unit in free eld *** Data referred to -50C 80% RH OAT room condition 200C 50% RH **** Data referred to 320C 50% RH OAT room condition 260C 50% RH
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
11
12
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
13
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
VRF Indoor Unit Range for ECOi and GHP
Wider operation
Comfortable auto -ap control
Model size 7 9 12 16 18 22 25 36 48 60 76 96 Wireless remote control
Capacity kW
Capacity
X Type Semi-Concealed Cassette
XM Type Semi-Concealed
US Type Concealed Duct
U Type Concealed Duct
DR Type Concealed Duct
K Type Wall Mounted Unit
BTU/h
25,48 type
Cooling 2.2 2.8 3.6 4.5 5.6 6.4 7.3 Heating 2.5 3.2 4.2 5.0 6.3 7.0 8.0 Cooling 7,500 9,600 12,000 15,000 19,000 22,000 25,000 Heating 8,500 11,000 14,000 17,000 21,000 24,000 27,000
76,96 type
SPW-X075XH
SPW-XDR74GXH56B
Panel
PNR-XD484GHAB
SPW-XM075XH
Panel
PNR-XM185
SPW-US075XH SPW-US095XH SPW-US125XH SPW-US165XH SPW-US185XH
SPW-U075XH
SPW-UR74GXH56B
SPW-K075XH SPW-K095XH SPW-K125XH
SPW-X095XH
SPW-XDR94GXH56B
Panel
PNR-XD484GHAB
SPW-XM095XH
Panel
PNR-XM185
SPW-U095XH
SPW-UR94GXH56B
SPW-X125XH
SPW-XDR124GXH56B
Panel
PNR-XD484GHAB
SPW-XM125XH
Panel
PNR-XM185
SPW-U125XH
SPW-UR124GXH56B
SPW-X165XH
SPW-XDR164GXH56B
Panel
PNR-XD484GHAB
SPW-XM165XH
Panel
PNR-XM185
SPW-U165XH
SPW-UR164GXH56B
SPW-X185XH
SPW-XDR184GXH56B
Panel
PNR-XD484GHAB
SPW-XM185XH
Panel
PNR-XM185
SPW-U185XH
SPW-UR184GXH56B
SPW-X255XH
SPW-XDR254GXH56B
Panel
PNR-XD484GHAB
SPW-U255XH
SPW-UR254GXH56B
SPW-DR254GXH56B
10.6 14.0 16.0 22.4 28.0
11.4 16.0 18.0 25.0 31.5 36,000 47,800 54,600 76,400 95,500 39,000 54,600 61,500 85,300 107,500
SPW-X365XH
SPW-XDR364GXH56B
Panel
PNR-XD484GHAB
SPW-U365XH
SPW-UR364GXH56B
SPW-DR364GX-
H56B
SPW-X485XH
SPW-XDR484GXH56B
Panel
PNR-XD484GHAB
SPW-U485XH
SPW-UR484GXH56B
SPW-DR484GX-
H56B
Automatic restart function for power failure
SPW-X605XH
SPW-XDR604GXH56B
Panel
PNR-XD484GHAB
SPW-U605XH
SPW-UR604GXH56B
Self-diagnosing function
SPW-DR764GX-
H56B
SPW-DR964GX-
H56B
Built-in infra red
sensor
Automatic fan operation
Separate infra red
sensor
Air Sweep
Mild dry
Built-in drain pump
Functions
KR Type Wall Mounted Unit
T Type Ceiling-
Mounted Unit
FTR Type Floor/Ceiling
Mounted Units
FUR Type
Floor/Ceiling Slim Concealed Duct
FR Type Floor
Standing Unit
FMR Type Concealed Floor
Standing Unit
ADR Type Semi-Concealed Cassette 1-Way Air Discharge
SR Type Semi-Concealed Cassette 2-Way Air Discharge
LDR Type Semi-Concealed Slim Cassette
SPW-KR164GXH56B SPW-KR184GXH56B SPW-KR254GXH56B
SPW-T125XH
SPW-TDR124GXH56B
SPW-FTR74EXH56B SPW-FTR94EXH56B SPW-FTR124EXH56B SPW-FTR164EXH56B SPW-FTR184EXH56B SPW-FTR224EXH56B
SPW-FUR74EXH56B SPW-FUR94EXH56B SPW-FUR124EXH56B SPW-FUR164EXH56B SPW-FUR184EXH56B SPW-FUR224EXH56B
SPW-FR74GXH56B SPW-FR94GXH56B SPW-FR124GXH56B SPW-FR164GXH56B SPW-FR184GXH56B SPW-FR254GXH56B
SPW-FMR74GXH56B SPW-FMR94GXH56B
SPW-ADR74GXH56B
Panel
PNR-AD124GHB
SPW-SR74GXH56B
Panel
PNR-S124GHB
SPW-ADR94GXH56B
Panel
PNR-AD124GHB
SR94GXH56B
Panel
PNR-S124GHB
SPW-LDR94GXH56B
Panel
PNR-LD254GHAB
SPW-FMR124GX-
H56B
SPW-ADR124GX-
H56B Panel
PNR-AD124GHB
SR124GXH56B
Panel
PNR-S124GHB
SPW-LDR124GXH56B
Panel
PNR-LD254GHAB
SPW-T165XH
SPW-TDR164GXH56B
SPW-FMR164GX-
H56B
SR164GXH56B,
Panel
PNR-S124GHB
SPW-LDR164GXH56B
Panel
PNR-LD254GHAB
SPW-T185XH
SPW-TDR184GXH56B
SPW-FMR184GX-
H56B
SR184GXH56B
Panel
PNR-S124GHB
SPW-LDR184GXH56B
Panel
PNR-LD254GHAB
SPW-T225XH
SPW-TDR254GXH56B
SPW-FMR254GX-
H56B
SPW-SR254GXH56B
Panel
PNR-S253GHANB
SPW-LDR254GXH56B
Panel
PNR-LD254GHAB
SPW-T365XH
SPW-TDR364GXH56B
SPW-T485XH
SPW-TDR484GXH56B
GU Type
Total Heat Exchanger
SPW-GU055XH SPW-GU075XH SPW-GU105XH
14
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
15
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
Individual Control Systems Overview
A wide variety of control options to meet the requirements of dierent customers.
Centralised Control Systems Overview
Operation system Individual control systems Timer operation
Requirements
External appearance
Type, model name
Number of indoor units
which can be controlled
Use limitations
Connectable
indoor unit
Function
ON/OFF
Mode setting
Fan speed setting
Temperature setting
Air ow direction
Permit/Prohibit switching - - - -
Weekly programme
*1 Setting is not possible when a remote control unit is present. (Use the remote control for setting.)
Normal
operation
Timer wired
remote controller
RCS-TM80BG
1 group, 8 units 1 group, 8 units 1 group, 8 units
Up to 2 units can be
connected per group.
4 series indoor unit 4 series indoor unit 4 series indoor unit 4 series indoor unit
*1 *1 *1
Operation from
each seat
Wireless remote
controller
RCS-SH80BG.WLB
RCS-TH80BG.WLB
RCS-BH80AG.WLB
RCS-TRP80BG.WLB
RCS-SH1BGB
Up to 2 units can be
connected per group.
- -
Simple operation
Simplied remote
controller
RCS-KR1EG
Up to 2 units can be
connected per group.
weekly programme
Power supply from the
system controller.
When there is no system
controller, connection is
possible to the T10 terminal
Daily and
Schedule timer
SHA-TM64AGB
64 groups,
max. 64 units
of an
indoor unit.
-
-
-
-
-
External appearance
Type, model name
Number of indoor units which
can be controlled
Use limitations
Connectable
indoor unit
Function
ON/OFF
Mode setting
Fan speed setting
Temperature setting
Air ow direction
Permit/Prohibit switching
Weekly programme
Centralised control systems
Operation with various
function from central
station
Only ON/OFF operation
from central station
Simplied charge ratio for each tenant
Touch screen panel
Personal computer
(eld supply)
Web
application
System controller
SHA-KC64AGB
64 groups,
max. 64 units
Up to 10 units can be
connected to one system.
Main unit/sub unit (1
main unit + 1 sub unit)
connection is possible.
Use without remote
controller is possible.
4 series indoor unit 4 series indoor unit 4 series indoor unit 4 series indoor unit
ON/OFF controller
SHA-KC16KAGB
16 groups,
max. 64 units
Up to 8 units (4 main
units + 4 sub units) can be
connected to one system.
Use without remote
controller is impossible.
Intelligent controller
SHA-KT256EG
64 units x 4 systems,
max. 256 units
A communication adaptor
(SHA-KA128AGB) must be
installed for three or more
systems.
Communication adaptor
SHA-KA128AGB
2 systems,
max. 128 units
Maximum 500 indoor
units (128 per communica-
tion adaptor)
*1 *1
-
-
-
-
-
*1
Contact your local SANYO distributor
ELECTRIC VRF COMMERCIAL SPLIT SYSTEMS
ROOM AIR CONDITIONERS
CO
2
ECO HEATING SYSTEM
for brochures on all other ranges of air conditioning and heating solutions
Indicates conformation
with EC Directives
ISO 9001: 2001
Certicate Number: JQ116B
ISO 14001: 2001
Certicate Number: ECOOJ0303-33
SANYO reserves the right to make any variation in specication to the equipment described or to withdraw or replace
products without prior notication or public announcement. All descriptions, illustrations, drawings and specications in
this publication are given in good faith, but are intended to present only general particulars and shall not form any part
of the contract. For full installation details, please contact your SANYO distributor.
Cooling: Indoor temperature 27˚C DB/19˚C WB, Outdoor temperature 35˚C DB/24˚ C WB.
www.sanyoaircon.com
SANYO Air Conditioners. The natural choice.
GHP_VRF_V1_2009
The cooling and heating capacities are based on the following conditions:
Rating Conditions
Heating: Indoor temperature 20˚C DB, Outdoor Temperature 7˚C DB 6˚C WB.
Printed using paper produced from 50% recycled material and 50% from sustainable forestry
Loading...