Sanyo SAP–KR184GJH, SAP–KR224GJH, SAP–CR224GH, SAP–CR184GH, SAP–KR184GJ Technical & Service Manual

...
TECHNICAL & SERVICE MANUAL
SAP–KR184GJH + SAP–CR184GH SAP–KR224GJH + SAP–CR224GH
FILE NO.
REFERENCE NO. SM700629
Indoor Unit
Outdoor Unit
SPLIT SYSTEM AIR CONDITIONER
SAP–KR184GJH SAP–KR224GJH
SAP–CR184GH SAP–CR224GH
IMPORTANT
These air conditioners employ new refrigerant R410A.
Pay special attention when servicing the unit.
Indoor Model No. Product Code No. SAP–KR184GJH 1 852 094 03 SAP–KR224GJH 1 852 094 02
Outdoor Model No. Product Code No.
SAP–CR184GH 1 852 094 07 SAP–CR224GH 1 852 094 06
Destination: Australia (50Hz)
General area (50Hz)
2
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
Table of Contents
Page
1. OPERATING RANGE .............................................................................................................................. 5
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 6
2-2. Major Component Specifications.................................................................................................... 8
2-3. Other Component Specifications.................................................................................................... 12
3. DIMENSIONAL DATA.............................................................................................................................. 13
4. REFRIGERANT FLOW DIAGRAM ......................................................................................................... 15
5. PERFORMANCE DATA
5-1. Performance charts ....................................................................................................................... 16
5-2. Air Throw Distance Chart .............................................................................................................. 18
5-3. Cooling Capacity ........................................................................................................................... 20
5-4. Heating Capacity ........................................................................................................................... 22
6. ELECTRICAL DATA
6-1. Electrical Characteristics................................................................................................................ 23
6-2. Electric Wiring Diagrams................................................................................................................ 25
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection ............................................................................................................... 27
7-2. Remote Control Unit Installation Position....................................................................................... 29
7-3. Recommended Wire Length and Diameter ................................................................................... 30
7-4. How to Test Run the Air Conditioner ............................................................................................. 31
7-5. Remove the grille to Install the Indoor Unit .................................................................................... 32
8. FUNCTION
8-1. Room Temperature Control ........................................................................................................... 33
8-2. Dry Operation ................................................................................................................................ 35
8-3. Automatic Switching between Cooling and Heating ...................................................................... 36
8-4. Freeze Prevention ......................................................................................................................... 37
8-5. Cold Draft Prevention .................................................................................................................... 38
8-6. Overload Prevention ...................................................................................................................... 39
8-7. Automatic fan speed ...................................................................................................................... 40
8-8. Defrosting Operation ...................................................................................................................... 41
8-9. Outdoor Fan Speed Control .......................................................................................................... 42
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting ........................................................................................ 43
9-2. Air conditioner does not operate .................................................................................................... 44
9-3. Some part of air conditioner does not operate ..............................................................................48
9-4. Air conditioner operates, but abnormalities are observed ............................................................. 50
10. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING THE UNIT
10-1. Characteristics of new refrigerant R410A....................................................................................... 53
10-2. Checklist before serving................................................................................................................. 53
10-3. Tools specifically for R410A........................................................................................................... 55
10-4. Tubing installation procedures........................................................................................................ 55
10-5. In case of compressor malfunction................................................................................................. 56
10-6. In case refrigerant is leaking........................................................................................................... 58
10-7. Charging additional refrigerant....................................................................................................... 59
10-8. Retro-fitting existing systems.......................................................................................................... 59
3
11. CHECKING ELECTRICAL COMPONENTS
11-1. Measurement of Insulation Resistance .......................................................................................... 60
11-2. Checking Continuity of Fuse on PCB Ass'y.................................................................................... 61
11-3. Checking Motor Capacitor ............................................................................................................. 61
12. MAINTENANCE
12-1. Address Setting of the Remote Control Unit .................................................................................. 62
.................................................................................................................................................. 63
APPENDIX
4
5
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Heating
Maximum 27°C D.B. 24°C D.B. / 18°C W.B.
Minimum 16°C D.B. –8°C D.B. / –9°C W.B.
6
2. SPECIFICATIONS
2-1. Unit Specifications
Indoor Unit SAP–KR184GJH Outdoor Unit SAP–CR184GH
Power Source 220–240V Single phase 50Hz Voltage rating 220 / 230 / 240 V Performance Cooling Heating
Capacity kW 5.15 / 5.15 / 5.30 5.70 / 5.70 / 5.70
BTU/h 17,600 / 17,600 / 18,100 19,400 / 19,400 / 19,400
Air circulation (High)
m
3
/h
890 890
Moisture removal (High) Liters/h 2.3
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264
Running amperes A 7.4 / 7.1 / 7.1 7.3 / 7.0 / 6.7
Power input W 1,600 / 1,600 / 1,650 1,580 / 1,580 / 1,580
Power factor % 98 / 98 / 97 98 / 98 / 98
C.O.P. W/W 3.22 / 3.22 / 3.21 3.61 / 3.61 / 3.61
Compressor locked rotor amperes A 28 28
Features
Controls / Temperature control Microprocessor / I.C. thermistor
Control unit Wireless remote controller
Timer ON/OFF 24 hours & Daily program,1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi/Lo)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R410A / 1,600
Refrigerant control Capillary tube
Operation sound Indoor: Hi/Me/Lo/Qt* dB-A 42 / 39 / 3 5 / 32 41 / 38 / 34 / 32
(*Qt=Quiet mode at Lo) Outdoor: Hi dB-A 55 56
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant Narrow tube mm (in.) 6.35(1/4)
tube diameter Wide tube mm (in.) 12.7(1/2)
Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight
Indoor Unit
Outdoor Unit
Unit dimensions Height mm 298 670
Width mm 1,065 880
Depth mm 218 285
Package dimensions Height mm 299 740
Width mm 1,140 1,022
Depth mm 379 400
Weig ht Net kg 12.0 48.0
Shipping kg 15.0 52.0
Shipping volume
m
3
0.129 0.303
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
7
Indoor Unit SAP–KR224GJH Outdoor Unit SAP–CR224GH
Power Source 220–240V Single phase 50Hz Voltage rating 220 / 230 / 240 V Performance Cooling Heating
Capacity kW 6.40 / 6.40 / 6.40 7.20 / 7.20 / 7.20
BTU/h 21,800 / 21,800 / 21,800 24,600 / 24,600 / 24,600
Air circulation (High)
m
3
/h
980 980
Moisture removal (High) Liters/h 3.3
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264
Running amperes A 10.4 / 10.0 / 9.6 10.3 / 9.8 / 9.4
Power input W 2,275 / 2,275 / 2,280 2,240 / 2,240 / 2,240
Power factor % 99 / 99 / 99 99 / 99 / 99
C.O.P. W/W 2.81 / 2.81 / 2.81 3.21 / 3.21 / 3.21
Compressor locked rotor amperes A 49 49
Features
Controls / Temperature control Microprocessor / I.C. thermister
Control unit Wireless remote controller
Timer ON/OFF 24 hours & Daily program,1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi/Lo)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R410A / 1,850
Refrigerant control Capillary tube
Operation sound Indoor: Hi/Me/Lo/Qt* dB-A 45 / 41 / 3 7 / 32 44 / 40 / 36 / 32
(*Qt=Quiet mode at Lo) Outdoor: Hi dB-A 57 58
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 10
Refrigerant Narrow tube mm (in.) 6.35(1/4)
tube diameter Wide tube mm (in.) 15.88(5/8)
Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight
Indoor Unit
Outdoor Unit
Unit dimensions Height mm 298 670
Width mm 1,065 880
Depth mm 218 285
Package dimensions Height mm 299 740
Width mm 1,140 1,022
Depth mm 379 400
Weig ht Net kg 12.0 56.0
Shipping kg 15.0 60.0
Shipping volume
m
3
0.129 0.303
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
8
2-2. Major Component Specifications
2-2-1. Indoor Unit
Indoor Unit SAP–KR184GJH
Controller PCB
Part No. CB-KR184EH (POW-KR184GJH)
Controls Microprocessor
Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-4HPIS4E
Fan & Fan Motor
Type Cross-flow
Q'ty ... Dia. and length mm 1 ... ø94 / L845
Fan motor model ... Q'ty DC Motor SIC-39CVL-D847-2 ... 1
No. of poles ... Rough measure rpm (Cool / Heat) 8 ... 1,200 / 1,200
Nominal output W 30
Coil resistance (Ambient temp. 20°C) ——
——
——
——
——
Safety devices Type Internal controller
Over-current protection Yes
Overheat protection Yes
Run capacitor (on controller PCB) µF
VAC
Flap Motor
Type Stepping motor
Model MP24Z3-12V
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) Each pair of terminals : 400 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area
m
2
0.285
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
9
Indoor Unit SAP–KR224GJH
Controller PCB
Part No. CB-KR224EH (POW-KR184GJH)
Controls Microprocessor
Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-4HPIS4E
Fan & Fan Motor
Type Cross-flow
Q'ty ... Dia. and length mm 1 ... ø94 / L845
Fan motor model ... Q'ty DC Motor SIC-39CVL-D847-2 ... 1
No. of poles ... Rough measure rpm (Cool / Heat) 8 ... 1,300 / 1,300
Nominal output W 30
Coil resistance (Ambient temp. 20°C) ——
——
——
——
——
Safety devices Type Internal controller
Over-current protection Yes
Overheat protection Yes
Run capacitor (on controller PCB) µF
VAC
Flap Motor
Type Stepping motor
Model MP24Z3-12V
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) Each pair of terminals : 400 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area
m
2
0.285
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
10
2-2-2. Outdoor Unit
Outdoor Unit SAP–CR184GH
Controller PCB
Compressor
Type Rotary (Hermetic)
Compressor model 5KS205DAJ21 85204526321
Nominal output W 1,500
Compressor oil ... Amount cc FV50S ... 670
Coil resistance (Ambient temp. 20°C) C–R : 1.780
C–S : 2.175
Safety devices Type Internal protector
Overload relay
Operating temp. Open °C Automatic opening
Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C)
Run capacitor µF 50
VAC 400
Crank case heater
Fan & Fan Motor
Type Propeller
Q'ty ... Dia. 1 ... ø420
Fan motor model ... Q'ty AC motor KFG6S-51E5P ... 1
No. of poles ... Rough measure rpm (Cool / Heat) 6 ... 870 / 850
Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT-BRN : 63.60
WHT-YEL : 58.48
YEL-PNK : 23.36
Safety devices Type Thermal protector
Operating temp. Open °C 130±8
Close Automatic reclosing
Run capacitor µF 4
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.2
Face area
m
2
0.510
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
11
Outdoor Unit SAP–CR224GH
Controller PCB
Compressor
Type Rotary (Hermetic)
Compressor model 5JS270DAA21 85204526322
Nominal output W 1,800
Compressor oil ... Amount cc FV50S ... 1,130
Coil resistance (Ambient temp. 20°C) C–R : 1.166
C–S : 1.534
Safety devices Type Internal protector
Overload relay
Operating temp. Open °C Automatic opening
Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C)
Run capacitor µF 60
VAC 400
Crank case heater
Fan & Fan Motor
Type Propeller
Q'ty ... Dia. 1 ... ø420
Fan motor model ... Q'ty AC motor KFG4S-51C5PB ... 1
No. of poles ... Rough measure rpm (Cool / Heat) 4 ... 980 / 950
Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT-BRN : 53.83
WHT-YEL : 36.32
YEL-PNK : 15.14
Safety devices Type Thermal protector
Operating temp. Open °C 130±8
Close Automatic reclosing
Run capacitor µF 5
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.2
Face area
m
2
0.510
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2-3. Other Component Specifications
12
4-way Valve (Solenoid coil) SHF-7H-34U
Rating AC 220-240 V , 50 / 60 Hz Refrigerant R22, R407C, R410A
Thermostat (Fan Speed Control 23S) MQT5S
Switching temp. °C
high ⇒ LOW 28.5°C ± 1.5 low ⇒ HIGH 31.5°C ± 2
Contact rating AC 220V, 3A
< Only for 224 class >
Magnetic Contactor CLK–25J2
Coil rating 50Hz 220 ~ 240V Coil resistance k(at 20°C) 2.0
< Only for 184 class >
Power Relay (PR) EL1U
Coil rating AC 200–240V, 50/60Hz Contact rating AC 277V, 30A
Outdoor Unit SAP–CR184GH
SAP–CR224GH
Thermistor (Coil / Room sensor) PBM-D41E-S1 (Coil / Room)
Resistance k Coil 0°C 15.0 ± 5% / Room 25°C 5.0 ± 4%
Indoor Unit SAP–KR184GJH
SAP–KR224GJH
13
3. DIMENSIONAL DATA
Indoor Unit SAP–KR184GJH
SAP–KR224GJH
(ø80)
49
5
1055
5
298
1065
50
60 100.5
1055
50
760
(3)218
475 403
60
49 24.5
402.5
95
450
95
212.5
117.5 117.5
1065
298
45
Drain hose ø18
Narrow tube
ø6.35(1/4")
90.5
90.5
307.5450307.5
95
45
95
202.4 202.4
(ø80)
196
46.5
27.4
70
32
133.8
52 23
Wide tube
ø12.70(1/2") 184
ø15.88(5/8") 224
Unit : mm
14
Outdoor Unit SAP–CR184GH
SAP–CR224GH
293
608
880 80
136
12
36
334
310
285
ID:ø
18
2-ID:ø
23.6
670
18
55111
166
2 145
AIR DISCHARGE
AIR INTAKE
AIR INTAKE
Narrow tube service valve
ø6.35(1/4"
)
Wide tube service valve
ø12.70(1/2") 184 ø15.88(5/8") 224
unit:m
Unit : mm
15
4. REFRIGERANT FLOW DIAGRAM
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
CAUTION
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø12.7 mm (1/2 ") 18 class
O.D. ø15.88 mm (5/8 ") 22 class
Compressor
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Heat exchanger
Cooling cycle
Heating cycle
Indoor unit Outdoor unit
Heat exchanger
Muffler
Capillary tubes
(both for heating
and cooling)
Capillary tube
(for heating)
Check valve
or
Strainer
Indoor Unit SAP–KR184GJH
SAP–KR224GJH
Outdoor Unit SAP–CR184GH
SAP–CR224GH
5. PERFORMANCE DATA
5-1. Performance charts
16
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C)
25 30 35 40 45 50
Low pressure at wide tube serveice valve MPa
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
1.8
Outdoor inlet air D.B. temp. (
°C)
–5 0 5 10 15 20 25
High pressure at wide tube serveice valve MPa
4.0
3.8
3.6
3.4
3.2
3.0
2.8
2.6
2.4
2.2
2.0
1.8
< Cooling Characteristics > < Heating Characteristics >
32 27 21
27 20
15
Indoor inlet air
D.B. temp. (°C)
Outdoor fan speed
HighLow
Indoor inlet air
D.B. temp. (°C)
12 11 10
9 8 7 6 5 4
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
13
11 10
9 8 7 6 5 4
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
12
15
27 20 15
32 27 21
Outdoor fan speed
HighLow
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high in heating mode. (Refer to “8-6 Overload prevention”)
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit SAP–KR184GJH Outdoor Unit SAP–CR184GH
17
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C)
25 30 35 40 45 50
Low pressure at wide tube serveice valve MPa
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
1.8
Outdoor inlet air D.B. temp. (
°C)
–5 0 5 10 15 20 25
High pressure at wide tube serveice valve MPa
4.0
3.8
3.6
3.4
3.2
3.0
2.8
2.6
2.4
2.2
2.0
1.8
< Cooling Characteristics > < Heating Characteristics >
32 27 21
27 20
15
Indoor inlet air
D.B. temp. (°C)
Outdoor fan speed
HighLow
Indoor inlet air
D.B. temp. (°C)
15 14 13 12 11 10
9 8 7
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
16
27 20 15
14 13 12 11 10
9 8 7
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
15
16
32 27 21
Outdoor fan speed
HighLow
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high in heating mode. (Refer to “8-6 Overload prevention”)
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit SAP–KR224GJH Outdoor Unit SAP–CR224GH
5-2. Air Throw Distance Chart
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
0
1
2
3
4
0123456789
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
0
1
2
3
4
0123456789
: Flap angle 45° , : Axis air velocity 45° : Flap angle 60° , : Axis air velocity 60°
18
Indoor Unit SAP–KR184GJH
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
0
1
2
3
4
0123456789
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
0
1
2
3
4
0123456789
: Flap angle 45° , : Axis air velocity 45° : Flap angle 60° , : Axis air velocity 60°
19
Indoor Unit SAP–KR224GJH
20
5-3. Cooling Capacity
Indoor Unit SAP–KR184GJH Outdoor Unit SAP–CR184GH
240V Single Phase 50Hz
RATING CAPACITY 5.30 kW
AIR FLOW RATE 890
m3/h
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 30 35 40 43
TC 4.88 4.64 4.36 4.02
CM 1.32 1.41 1.50 1.58
21 SHC 3.43 3.31 3.17 3.01
15 23 SHC 3.88 3.76 3.63 3.46
25 SHC 4.33 4.22 4.08 3.92
27 SHC 4.78 4.64 4.36 4.02
29 SHC 4.88 4.64 4.36 4.02
31 SHC 4.88 4.64 4.36 4.02
TC 5.23 4.98 4.68 4.31
CM 1.35 1.45 1.54 1.62
21 SHC 2.96 2.85 2.71 2.55
17 23 SHC 3.41 3.30 3.16 3.00
25 SHC 3.87 3.75 3.62 3.45
27 SHC 4.32 4.20 4.07 3.90
29 SHC 4.77 4.66 4.52 4.31
31 SHC 5.23 4.98 4.68 4.31
TC 5.57 # 5.30 4.98 4.58
CM 1.40 1.50 1.59 1.67
21 SHC 2.48 2.36 2.23 2.06
19 23 SHC 2.93 2.81 2.68 2.52
25 SHC 3.38 3.27 3.13 2.97
27 SHC 3.83 3.72 3.59 3.42
29 SHC 4.29 4.17 4.04 3.88
31 SHC 4.74 4.63 4.49 4.33
TC 5.90 5.62 5.28 4.86
CM 1.43 1.54 1.63 1.72
23 SHC 2.44 2.33 2.19 2.03
21 25 SHC 2.89 2.78 2.65 2.49
27 SHC 3.34 3.23 3.10 2.94
29 SHC 3.80 3.69 3.55 3.39
31 SHC 4.25 4.14 4.01 3.85
TC 6.25 5.90 5.52 5.14
CM 1.47 1.58 1.68 1.77
23 25 SHC 2.37 2.24 2.11 1.97
27 SHC 2.82 2.70 2.56 2.43
29 SHC 3.28 3.15 3.01 2.88
31 SHC 3.73 3.60 3.47 3.33
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.