Sanyo SAP–K92A,SAP–K122A,SAP–K252A,SAP–C182A,SAP–C252A,SAP–C92A,SAP–C122A,SAP–K182A Technical & Service Manual

TECHNICAL & SERVICE MANUAL
SAP–K92A + SAP–C92A SAP–K122A + SAP–C122A SAP–K182A + SAP–C182A SAP–K252A + SAP–C252A
FILE NO.
REFERENCE NO. SM700569
Indoor Unit
Outdoor Unit
SAP–K92A SAP–K122A
SAP–C92A SAP–C122A
Indoor Model No. Product Code No. Destination
SAP–K92A–S 1 852 083 68 SAP–K122A–S 1 852 083 69
Outdoor Model No. Product Code No. Destination
SAP–C92A–S 1 852 084 09 SAP–C122A–S 1 852 084 10 SAP–C182A–S 1 852 084 11
SAP–K182A–S 1 852 083 70
SAP–C182A SAP–C252A
SAP–K182A SAP–K252A
SAP–C252A–S 1 852 084 13SAP–K252A–S 1 852 083 72
Australia Australia
i
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
Table of Contents
Page
1. OPERATING RANGE .............................................................................................................................. 1
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 2
2-2. Major Component Specifications.................................................................................................... 6
2-3. Other Component Specifications.................................................................................................... 14
3. DIMENSIONAL DATA.............................................................................................................................. 16
4. REFRIGERANT FLOW DIAGRAM ......................................................................................................... 20
5. PERFORMANCE DATA
5-1. Performance charts ....................................................................................................................... 22
5-2. Air Throw Distance Chart .............................................................................................................. 24
5-3. Cooling Capacity ........................................................................................................................... 26
6. ELECTRICAL DATA
6-1. Electrical Characteristics................................................................................................................ 30
6-2. Electric Wiring Diagrams................................................................................................................ 32
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection ............................................................................................................... 36
7-2. Remote Control Unit Installation Position....................................................................................... 38
7-3. Recommended Wire Length and Diameter ................................................................................... 39
8. FUNCTION
8-1. Room Temperature Control ........................................................................................................... 40
8-2. Dry Operation ................................................................................................................................ 41
8-3. Freeze Prevention ......................................................................................................................... 41
8-4. Outdoor Fan Speed Control .......................................................................................................... 42
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting ........................................................................................ 43
9-2. Air conditioner does not operate .................................................................................................... 44
9-3. Some part of air conditioner does not operate ..............................................................................48
9-4. Air conditioner operates, but abnormalities are observed ............................................................. 50
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance .......................................................................................... 51
10-2. Checking Continuity of Fuse on PCB Ass'y.................................................................................... 52
10-3. Checking Motor Capacitor ............................................................................................................. 52
11. MAINTENANCE
11-1. Changing Address of Remote Control Unit in Indoor Unit ............................................................. 53
.................................................................................................................................................. 54
APPENDIX
ii
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
2
2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 2.55 / 2.55 / 2.50
BTU/h 8,700 / 8,700 / 8,500 Air circulation (High) m3/h 430 Moisture removal (High) Liters/h 0.80 Available voltage range V 198 to 264 Running amperes A 3.9 / 3.8 / 3.9 Power input W 840 / 860 / 930 Power factor % 98 / 98 / 99 C.O.P. W/W 3.04 / 2.97 / 2.69 Compressor locked rotor amperes A 19 / 20 / 21 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hour ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 850 Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 39 / 37 / 33
Outdoor – Hi dB-A 44 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 9.52 (3/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 250 530
Width mm 790 680
Depth mm 174 225 Package dimensions Height mm 242 580
Width mm 850 812
Depth mm 312 315
Weight Net
kg 7.0 29.0
Shipping
kg 10.0 31.0
Shipping volume m3 0.06 0.15
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAP–K92A Outdoor Unit SAP–C92A
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 3.40 / 3.40 / 3.40
BTU/h 11,600 / 11,600 / 11,600 Air circulation (High) m3/h 470 Moisture removal (High) Liters/h 1.1 Available voltage range V 198 to 264 Running amperes A 5.8 / 5.8 / 5.9 Power input W 1,240 / 1,250 / 1,290 Power factor % 97 / 94 / 91 C.O.P. W/W 2.74 / 2.72 / 2.64 Compressor locked rotor amperes A 32 / 33 / 35 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hour ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi, Lo)
Airflow direction (Indoor )
Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 875 Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 40 / 37 / 34
Outdoor – Hi dB-A 46 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 250 530
Width mm 790 680
Depth mm 174 225 Package dimensions Height mm 242 580
Width mm 850 812
Depth mm 312 315
Weight Net
kg 7.0 32.0
Shipping
kg 10.0 34.0
Shipping volume m3 0.06 0.15
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAP–K122A Outdoor Unit SAP–C122A
4
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 5.15 / 5.15 / 5.00
BTU/h 17,600 / 17,600 / 17,100 Air circulation (High) m3/h 760 Moisture removal (High) Liters/h 2.7 Available voltage range V 198 to 264 Running amperes A 9.5 / 9.5 / 10.1 Power input W 2,000 / 2,030 / 2,130 Power factor % 96 / 93 / 88 C.O.P. W/W 2.58 / 2.54 / 2.35 Compressor locked rotor amperes A 50 / 53 / 55 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hour ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi, Lo)
Airflow direction (Indoor )
Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,350 Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 41 / 38 / 36
Outdoor – Hi dB-A 53 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 810
Depth mm 196 275 Package dimensions Height mm 276 704
Width mm 1,070 953
Depth mm 363 396
Weight Net
kg 12.0 49.0
Shipping
kg 15.0 53.5
Shipping volume m3 0.11 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAP–K182A Outdoor Unit SAP–C182A
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source 220 – 240 V Single phase 50 Hz Voltage rating V 220 / 230 / 240
Cooling
Capacity
kW 7.00 / 7.00 / 7.00
BTU/h 23,900 / 23,900 / 23,900 Air circulation (High) m3/h 840 Moisture removal (High) Liters/h 3.3 Available voltage range V 198 to 264 Running amperes A 13.1 / 13.1 / 13.4 Power input W 2,730 / 2,730 / 2,800 Power factor % 95 / 91 / 87 C.O.P. W/W 2.56 / 2.56 / 2.50 Compressor locked rotor amperes A 67 / 70 / 73 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hour ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi, Lo)
Airflow direction (Indoor )
Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,700 Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 43 / 41 / 39
Outdoor – Hi dB-A 55 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 10
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 15.88 (5/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 810
Depth mm 196 275 Package dimensions Height mm 276 704
Width mm 1,070 953
Depth mm 363 396
Weight Net
kg 12.0 59.0
Shipping
kg 15.0 62.0
Shipping volume m3 0.11 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAP–K252A Outdoor Unit SAP–C252A
6
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K92GJ Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow Number ... Dia. and length mm 1 ... ø97 / L578 Fan motor model ... Number IBH-884-020 ... 1 No. of poles ... rpm (240 V, High) 2 ... 1,290 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT – BRN : 201
WHT – VLT : 261
Safety Type Thermal fuse devices Operating temp. Open °C 130
Close
Run capacitor µF 1.5
VAC 440 Type Stepping motor Model MP24GA3 Rating DC 12 V Coil resistance (Ambient temp. 25°C) A pair of each terminal: 380 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.110
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAP–K92A
7
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K122GJ Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow Number ... Dia. and length mm 1 ... ø97 / L578 Fan motor model ... Number IBH-884-020 ... 1 No. of poles ... rpm (240 V, High) 2 ... 1,350 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT – BRN : 201
WHT – VLT : 261
Safety Type Thermal fuse devices Operating temp. Open °C 130
Close
Run capacitor µF 1.5
VAC 440 Type Stepping motor Model MP24GA3 Rating DC 12 V Coil resistance (Ambient temp. 25°C) A pair of each terminal: 380 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.110
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAP–K122A
8
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K182GJ Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow Number ... Dia. and length mm 1 ... ø88 / L746 Fan motor model ... Number UF2-31A5P-S ... 1 No. of poles ... rpm (240 V, High) 2 ... 1,440 Nominal output W 30 Coil resistance (Ambient temp. 20°C) WHT – BRN : 133.7
WHT – PNK : 168.4
Safety Type Internal protector devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440 Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 25°C) Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m
2
0.156
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAP–K182A
9
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. CB-K252G Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS-3S4E-G
Type Cross–flow Number ... Dia. and length mm 1 ... ø88 / L746 Fan motor model ... Number UF2-31A5P-S ... 1 No. of poles ... rpm (240 V, High) 2 ... 1,440 Nominal output W 30 Coil resistance (Ambient temp. 20°C) WHT – BRN : 133.7
WHT – PNK : 168.4
Safety Type Internal protector devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440 Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 25°C) Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m
2
0.156
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit SAP–K252A
10
2-2-2. Outdoor Unit
Type Rotary (Hermetic) Compressor model C–R81H5Q 80682645–S Nominal output W 800 Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 500 Coil resistance (Ambient temp. 25°C) C – R : 3.38
C – S : 7.49
Type External (OLR A) External (OLR T) Safety Overload relay MRA99109–9201 CS–7C115 devices Operating temp. Open °C 150 ± 5 115 ± 3
Close °C 69 ± 11 95 ± 5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 16 A — Run capacitor µF 22.5
VAC 400 Type Propeller Number ... Dia. mm 1 ... ø 370 Fan motor model ... Number UE6-21AH5PB-S ... 1 No. of poles ... rpm (240 V, High) 6 ... 780 Nominal output W 20
Coil resistance (Ambient temp. 20°C) WHT – BRN : 338.3
WHT – PNK : 389.7
Safety Type Thermal fuse devices Operating temp. Open °C 145 ± 2
Close
Run capacitor µF 1.5
VAC 440 Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m
2
0.333
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAP–C92A
11
Type Rotary (Hermetic) Compressor model C–R112H5X 80616745–S Nominal output W 1,100 Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 550 Coil resistance (Ambient temp. 25°C) C – R : 1.96
C – S : 5.38
Type External (OLR A)
Safety
Overload relay MRA99122–9201
devices Operating temp. Open °C 150 ± 5
Close °C 69 ± 11
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 25 A
Run capacitor µF 25.0
VAC 400 Type Propeller Number ... Dia. mm 1 ... ø 370 Fan motor model ... Number UE6S–21AC5P–S ... 1 No. of poles ... rpm (240 V, High) 6 ... 780 Nominal output W 20
Coil resistance (Ambient temp. 20°C) BRN – WHT : 341.2
WHT – YEL : 212.7
YEL – PNK : 190.0
Safety
Type Thermal fuse
devices Operating temp. Open °C 145 ± 2
Close
Run capacitor µF 1.5
VAC 440 Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.2 Face area m
2
0.329
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAP–C122A
12
Type Rotary (Hermetic) Compressor model 2JS350D5BC02 8520452625100 Nominal output W 1,700 Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 1,130 Coil resistance (Ambient temp. 25°C) C – R : 0.981
C – S : 2.845
Type Internal protector
Safety
Overload relay
devices Operating temp. Open °C Automatic opening
Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C)
Run capacitor µF 45.0
VAC 400 Type Propeller Number ... Dia. mm 1 ... ø 420 Fan motor model ... Number KFG6S–51A5P–S ... 1 No. of poles ... rpm (240 V, High) 6 ... 880 Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 67.09
WHT – YEL : 68.12
YEL – PNK : 15.66
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 4.0
VAC 440 Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m
2
0.506
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAP–C182A
13
Type Rotary (Hermetic) Compressor model C-R221H5S 80687145 Nominal output W 2,200 Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 1,350 Coil resistance (Ambient temp. 25°C) C – R : 0.777
C – S : 2.408
Type Internal protector External (OLR T)
Safety
Overload relay OL–D24
devices Operating temp. Open °C Automatic opening 150 ± 5
Close °C Automatic reclosing 63 ± 11
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 59 A
Run capacitor µF 40.0
VAC 400 Type Propeller Number ... Dia. mm 1 ... ø 420 Fan motor model ... Number KFG4S–51C5PA–S ... 1 No. of poles ... rpm (240 V, High) 4 ... 1,000 Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 55.1
WHT – YEL : 37.2
YEL – PNK : 15.5
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 5.0
VAC 440 Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.2 Face area m
2
0.499
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAP–C252A
2-3. Other Component Specifications
14
<Except SAP-C92>
Thermostat (Fan Speed Control 23S) MQT5S
Switching temp. °C
high LOW 28.5°C ± 1.5 low HIGH 31.5°C ± 2
Contact rating AC 220V, 3A
Power Relay (PR) EL1U
Coil rating AC 200–240V, 50/60Hz Contact rating AC 277V, 30A
Outdoor Unit SAP–C92A
SAP–C122A
Thermistor (Room sensor) DTN-TKS128B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAP–K92A
SAP–K122A
15
Thermostat (Fan Speed Control 23S) MQT5S
Switching temp. °C
high LOW 28.5°C ± 1.5 low HIGH 31.5°C ± 2
Contact rating AC 220V, 3A
Power Relay (PR) EL1U
Coil rating AC 200–240V, 50/60Hz Contact rating AC 277V, 30A
Outdoor Unit SAP–C182A
SAP–C252A
Thermistor (Room sensor) DTN-TKS142B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAP–K182A
SAP–K252A