Sanyo SAP–K91A,SAP–CM1821A,SAP–K91A-S,SAP–CM1821A-S Technical & Service Manual

TECHNICAL & SERVICE MANUAL
SAP–K91A (2) + SAP–CM1821A
FILE NO.
REFERENCE NO. SM700428
Indoor Unit
Outdoor Unit
MULTI-SPLIT SYSTEM AIR CONDITIONER
SAP–K91A (2)
Indoor Model No Product Code No.
SAP–K91A–S 1 852 063 35
Outdoor Model No. Product Code No.
SAP–CM1821A–S 1 852 068 10
Destination : Australia
i
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operat­ing standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub­ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause
accidental
injury or death.
• Ground the unit
following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This pre­vents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refriger­ant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
WARNING
WARNING
CAUTION
CAUTION
Table of Contents
Page
Unit Combination.................................................................................................................................... iii
1. OPERATING RANGE .............................................................................................................................. 1
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 2
2-2. Major Component Specifications.................................................................................................... 3
2-3. Other Component Specifications.................................................................................................... 5
3. DIMENSIONAL DATA.............................................................................................................................. 6
4. COOLING CAPACITY ............................................................................................................................. 8
5. AIR THROW DISTANCE CHART ........................................................................................................... 10
6. REFRIGERANT FLOW DIAGRAM ......................................................................................................... 11
7. ELECTRICAL DATA
7-1. Electrical Characteristics................................................................................................................ 12
7-2. Electric Wiring Diagrams................................................................................................................ 13
8. INSTALLATION INSTRUCTIONS
8-1. Installation Site Selection............................................................................................................... 15
8-2. Remote Control Unit Installation Position....................................................................................... 17
8-3. Recommended Wire Length and Diameter ................................................................................... 18
9. FUNCTION
9-1. Room Temperature Control ........................................................................................................... 19
9-2. Dry Operation ................................................................................................................................ 20
9-3. Freeze Prevention ......................................................................................................................... 20
10. TROUBLESHOOTING
10-1. Check before and after troubleshooting ........................................................................................ 21
10-2. Air conditioner does not operate .................................................................................................... 22
10-3. Some part of air conditioner does not operate .............................................................................. 27
10-4. Air conditioner operates, but abnormalities are observed ............................................................. 29
10-5. If a sensor is defective ................................................................................................................... 30
11. ARRANGEMENT OF ELECTRICAL COMPONENT .............................................................................. 31
12. CHECKING ELECTRICAL COMPONENTS
12-1. Measurement of Insulation Resistance.......................................................................................... 32
12-2. Checking Continuity of Fuse on PCB Ass'y.................................................................................... 33
12-3. Checking Motor Capacitor ............................................................................................................. 33
INSTRUCTION MANUAL ........................................................................................................ 34
APPENDIX
ii
iii
Unit Combination
Combine indoor and outdoor units only as listed below.
Indoor Unit
Outdoor Unit
A
B
Fig.1
Refer toOutdoor Unit
Symbol of
Indoor Unit
Indoor Unit
SAP–CM1821A
K91A A
Fig.1
K91A B
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
No. of indoor units. 1-unit 2-units Power Source 240V Single phase 50 Hz
Cooling
Capacity kW 2.50 5.00
BTU/h 8,500 17,100
Air circulation (High) m3/h 430 430
2
Moisture removal (High) Liters/h 0.85 0.85
2 Voltage rating V 240 Available voltage range V 216 to 264 Running amperes A 5.0 9.3 Power input W 1,110 2,120 Power factor % 93 95 C.O.P. W/W 2.30 2.41 Compressor locked rotor amperes A 24 48 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hour ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti–Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,260 (630
2) Refrigerant control Capillary tube Operation sound Indoor – Hi / Me / Lo dB-A 39 / 37 / 33
Outdoor – Hi dB-A 53 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 9.52 (3/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 250 630
Width mm 790 810
Depth mm 174 275 Package dimensions Height mm 242 704
Width mm 850 953
Depth mm 312 369 Weight Net kg 7.0 48.0
Shipping kg 10.0 52.5 Shipping volume m
3
0.06 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAP–K91A Outdoor Unit SAP–CM1821A
2
2-2. Major Component Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K91G Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS–7S3E
Type Cross–flow Number ... Dia. and length mm 1 ... ø95 / L578 Fan motor model ... Number UF4Q–21H5P–S ... 1 No. of poles ... rpm (240 V, High) 4 ... 1,290 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT – BRN :449.4
WHT – VLT : 126.4 VLT – ORG : 92.4 ORG – YEL : 136.1
YEL – PNK : 92.5
Safety
Type Internal fuse
devices Operating temp. Open °C 145 ± 2
Close
Run capacitor µF 1.0
VAC 440 Type Stepping motor Model MP24S2–12V Rating DC 12 V Coil resistance (Ambient temp. 25°C) A pair of each terminal : 380 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.110
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
3
Indoor Unit SAP–K91A
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Type Rotary (Hermetic) Compressor model ... Number C–1R80H5K ... 2 / 80603345–S ... 2 Nominal output W 800 Compressor oil ... Amount cc SUNISO 4GSD–T ... 320
2
Coil resistance (Ambient temp. 25°C) C – R : 3.65
C – S : 5.38
Type External protector (OLR 1, 3) External protector (OLR 2, 4)
Safety
Overload relay ... Number MRA99109-9201 ... 2 CS-7C115 ... 2
devices Operating temp. Open °C 150 ± 5 115 ± 3
Close °C 69 ± 11 95 ± 5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 16A
Run capacitor ... Number µF 30.0 ... 2
VAC 400 ... 2
Type Propeller Number ... Dia. mm 1 ... ø420 Fan motor model ... Number KFG6–51C5P–S ... 1 No. of poles ... rpm (240 V) 6 ... 870 Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 67.1
WHT – PNK : 83.8
Safety
Type Internal protector
devices Operating temp. Open °C 130 ± 5
Close Automatic reclosing
Run capacitor µF 4.0
VAC 440
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m
2
0.506
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
Outdoor Unit SAP–CM1821A
4
5
2-3. Other Component Specifications
Power Relay (PR) G7L-2A-TUB-55
Coil rating AC 200–240V, 50/60Hz Coil resistance (at 23°C) 21 ± 15% Contact rating AC 220V, 25A
Outdoor Unit SAP–CM1821A
Thermistor (Room sensor) DTN-TKS128B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAP–K91A
6
3. DIMENSIONAL DATA
Indoor Unit SAP–K91A
790
250
174 (3)
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8")
Drain hose ø18
58.5
132
41.0
41.0
Center of tubing hole (2 places)
18.5
57
161
Remote control unit
Unit : mm
7
Outdoor Unit SAP–CM1821A
810 15
538
AIR INTAKE
AIR DISCHARGE
136
140
302
630
22
5
275
98 45 45 45
325
Narrow tube service valve ø6.35 (1/4")
Wide tube service valve ø9.52 (3/8")
2
1
1
2
Unit : mm
4. COOLING CAPACITY
1 - indoor unit in operation
240V Single phase 50Hz
RATING CAPACITY 2.50 kW
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 20 25 30 35 40 43
TC 2.52 2.41 2.30 2.19 2.06 1.89
CM 0.72 0.78 0.84 0.90 0.95 1.00
21 SHC 1.71 1.65 1.59 1.54 1.47 1.40
15 23 SHC 1.92 1.86 1.80 1.75 1.68 1.61
25 SHC 2.13 2.07 2.01 1.96 1.89 1.82 27 SHC 2.34 2.28 2.22 2.17 2.06 1.89 29 SHC 2.52 2.41 2.30 2.19 2.06 1.89 31 SHC 2.52 2.41 2.30 2.19 2.06 1.89
TC 2.70 2.59 2.47 2.35 2.21 2.03
CM 0.74 0.80 0.86 0.92 0.98 1.03
21 SHC 1.49 1.43 1.38 1.32 1.26 1.18
17 23 SHC 1.70 1.64 1.59 1.53 1.47 1.39
25 SHC 1.91 1.85 1.80 1.74 1.68 1.60 27 SHC 2.12 2.06 2.01 1.95 1.89 1.81 29 SHC 2.33 2.27 2.22 2.16 2.10 2.02 31 SHC 2.54 2.48 2.43 2.35 2.21 2.03
TC 2.88 2.75 2.63 # 2.50 2.35 2.16
CM 0.77 0.83 0.89 0.95 1.01 1.06
21 SHC 1.26 1.21 1.15 1.10 1.03 0.96
19 23 SHC 1.47 1.42 1.36 1.31 1.24 1.17
25 SHC 1.68 1.63 1.57 1.52 1.45 1.38 27 SHC 1.89 1.84 1.78 1.73 1.66 1.59 29 SHC 2.10 2.05 1.99 1.94 1.87 1.80 31 SHC 2.31 2.26 2.20 2.15 2.08 2.01
TC 3.05 2.92 2.78 2.65 2.49 2.29
CM 0.79 0.85 0.91 0.98 1.04 1.09
23 SHC 1.24 1.19 1.13 1.08 1.02 0.94
21 25 SHC 1.45 1.40 1.34 1.29 1.23 1.15
27 SHC 1.66 1.61 1.55 1.50 1.44 1.36 29 SHC 1.87 1.82 1.76 1.71 1.65 1.57 31 SHC 2.08 2.03 1.97 1.92 1.86 1.78
TC 3.23 3.09 2.95 2.78 2.60 2.42
CM 0.80 0.87 0.93 1.00 1.06 1.12
23 25 SHC 1.21 1.16 1.10 1.04 0.98 0.91
27 SHC 1.42 1.37 1.31 1.25 1.19 1.12 29 SHC 1.63 1.58 1.52 1.46 1.40 1.33
31 SHC 1.84 1.79 1.73 1.67 1.61 1.54 TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B. Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
Indoor Unit SAP–K91A (✕1) Outdoor Unit SAP–CM1821A
8
2 - indoor units in operation
240V Single phase 50Hz
RATING CAPACITY 5.00 kW
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 20 25 30 35 40 43
TC 5.04 4.82 4.60 4.38 4.11 3.79
CM 1.46 1.58 1.69 1.81 1.91 2.02
21 SHC 3.41 3.30 3.19 3.08 2.95 2.79
15 23 SHC 3.83 3.72 3.61 3.50 3.37 3.21
25 SHC 4.25 4.14 4.03 3.92 3.79 3.63
27 SHC 4.67 4.56 4.45 4.34 4.11 3.79
29 SHC 5.04 4.82 4.60 4.38 4.11 3.79
31 SHC 5.04 4.82 4.60 4.38 4.11 3.79
TC 5.41 5.17 4.94 4.70 4.42 4.07
CM 1.50 1.62 1.74 1.86 1.97 2.08
21 SHC 2.98 2.87 2.76 2.65 2.52 2.36
17 23 SHC 3.40 3.29 3.18 3.07 2.94 2.78
25 SHC 3.82 3.71 3.60 3.49 3.36 3.20
27 SHC 4.24 4.13 4.02 3.91 3.78 3.62
29 SHC 4.66 4.55 4.44 4.33 4.20 4.04
31 SHC 5.08 4.97 4.85 4.70 4.42 4.07
TC 5.75 5.50 5.25 # 5.00 4.70 4.33
CM 1.55 1.67 1.79 1.92 2.03 2.14
21 SHC 2.53 2.42 2.31 2.20 2.07 1.91
19 23 SHC 2.95 2.84 2.73 2.62 2.49 2.33
25 SHC 3.37 3.26 3.14 3.04 2.91 2.75
27 SHC 3.79 3.67 3.56 3.46 3.33 3.17
29 SHC 4.21 4.09 3.98 3.88 3.75 3.59
31 SHC 4.63 4.51 4.40 4.29 4.17 4.01
TC 6.10 5.83 5.57 5.30 4.98 4.58
CM 1.59 1.72 1.84 1.97 2.09 2.20
23 SHC 2.49 2.38 2.27 2.16 2.04 1.88
21 25 SHC 2.91 2.80 2.69 2.58 2.46 2.30
27 SHC 3.33 3.22 3.11 3.00 2.88 2.72
29 SHC 3.75 3.64 3.53 3.42 3.29 3.14
31 SHC 4.17 4.06 3.95 3.84 3.71 3.56
TC 6.47 6.19 5.90 5.57 5.21 4.85
CM 1.62 1.76 1.89 2.03 2.14 2.26
23 25 SHC 2.42 2.31 2.20 2.08 1.95 1.82
27 SHC 2.84 2.73 2.62 2.50 2.37 2.24
29 SHC 3.26 3.15 3.04 2.92 2.79 2.66
31 SHC 3.68 3.57 3.46 3.34 3.21 3.08 TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B. Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
Indoor Unit SAP–K91A (✕2) Outdoor Unit SAP–CM1821A
9
5. AIR THROW DISTANCE CHART
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
10
Indoor Unit SAP–K91A
6. REFRIGERANT FLOW DIAGRAM
11
Indoor Unit SAP–K91A Outdoor Unit SAP–CM1821A
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensa­tion, both tubes must be well insulated with a proper insula­tion material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
CAUTION
Outdoor Unit
Wide tube
O.D. ø9.52mm (3/8 ")
Narrow tube
O.D. ø6.35 mm (1/4")
Condenser
Wide tube service valve
Compressor A
Accumulator
Compressor B
B
A
A
Narrow tube service valve
Capillary tube
B
Accumulator
Evaporator
Indoor Unit A
Evaporator
Indoor Unit B
7. ELECTRICAL DATA
7-1. Electrical Characteristics
1 - indoor unit in operation
2 - indoor units in operation
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 240V Single phase 50Hz Rating Conditions Running Amps. A 0.36 0.50 8.44 9.3
Power Input kW 0.080 0.119 1.921 2.12
Full Load Conditions Running Amps. A 0.36 0.50 10.04 10.9
Power Input kW 0.080 0.119 2.261 2.46
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAP–K91A (✕2) Outdoor Unit SAP–CM1821A
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 240V Single phase 50Hz Rating Conditions Running Amps. A 0.18 0.50 4.32 5.0
Power Input kW 0.040 0.119 0.951 1.11
Full Load Conditions Running Amps. A 0.18 0.50 5.12 5.8
Power Input kW 0.040 0.119 1.121 1.28
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAP–K91A (✕1) Outdoor Unit SAP–CM1821A
12
13
7-2. Electric Wiring Diagram
Indoor Unit SAP–K91A
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
WARNING
14
Outdoor Unit SAP–CM1821A
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
WARNING