Sanyo SAP–K181AHA–S,SAP–C241AHA–S,SAP–K241AHA–S,SAP–C181AHA–S Technical & Service Manual

General (50Hz)General (50/60Hz)
TECHNICAL & SERVICE MANUAL
SAP–K181AHA + SAP–C181AHA SAP–K241AHA + SAP–C241AHA
FILE NO.
REFERENCE NO. SM700463
Indoor Unit
Outdoor Unit
SAP–K181AHA SAP–K241AHA
SAP–C181AHA SAP–C241AHA
Indoor Model No. Product Code No. Destination SAP–K181AHA–S 1 852 070 77 SAP–K241AHA–S 1 852 070 78
Outdoor Model No. Product Code No. Destination
SAP–C181AHA–S 1 852 070 85
Australia
SAP–C241AHA–S 1 852 070 86
Australia
i
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before
beginning.
Follow each installation or repair step exactly as
shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and
tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
ii
Table of Contents
Page
1. OPERATING RANGE .............................................................................................................................. 1
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 2
2-2. Major Component Specifications.................................................................................................... 4
2-3. Other Component Specifications.................................................................................................... 8
3. DIMENSIONAL DATA.............................................................................................................................. 9
4. REFRIGERANT FLOW DIAGRAM ......................................................................................................... 12
5. PERFORMANCE DATA
5-1. Performance charts ....................................................................................................................... 13
5-2. Air Throw Distance Chart .............................................................................................................. 15
5-3. Cooling Capacity ........................................................................................................................... 16
5-4. Heating Capacity ........................................................................................................................... 18
6. ELECTRICAL DATA
6-1. Electrical Characteristics................................................................................................................ 19
6-2. Electric Wiring Diagram.................................................................................................................. 21
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection ............................................................................................................... 24
7-2. Remote Control Unit Installation Position....................................................................................... 26
7-3. Recommended Wire Length and Diameter ................................................................................... 27
8. FUNCTION
8-1. Room Temperature Control ........................................................................................................... 28
8-2. Dry Operation ................................................................................................................................ 30
8-3. Automatic Switching between Cooling and Heating ...................................................................... 30
8-4. Freeze Prevention ......................................................................................................................... 31
8-5. Overload Prevention ...................................................................................................................... 31
8-6. Cold Draft Prevention .................................................................................................................... 32
8-7. Defrosting Operation ..................................................................................................................... 33
8-8. Outdoor Fan Speed Control .......................................................................................................... 34
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting ........................................................................................ 35
9-2. Air conditioner does not operate .................................................................................................... 36
9-3. Some part of air conditioner does not operate .............................................................................. 40
9-4. Air conditioner operates, but abnormalities are observed ............................................................. 42
9-5. If a sensor is defective ................................................................................................................... 44
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance .......................................................................................... 45
10-2. Checking Continuity of Fuse on PCB Ass'y.................................................................................... 46
10-3. Checking Motor Capacitor ............................................................................................................. 46
11. MAINTENANCE
11-1. Changing Address of Remote Control Unit in Indoor Unit ............................................................. 47
INSTRUCTION MANUAL ........................................................................................................ 48
APPENDIX
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Heating
Maximum 27°C D.B. 24°C D.B. / 18°C W.B.
Minimum 16°C D.B. – 8°C D.B. / – 9°C W.B.
2
2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
Power Source 240 V Single phase 50Hz Voltage rating V 240
Cooling Heating
Capacity
kW 4.95 5.70
BTU/h 16,900 19,450
Air circulation (High) m
3
/h 760 760 Moisture removal (High) Liters/h 2.7 — Available voltage range V 216 to 264 Running amperes A 10.6 9.4 Power input W 2,360 2,040 Power factor % 93 90 C.O.P. W/W 2.10 2.79 Compressor locked rotor amperes A 48 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hour ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,330 Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 41 / 38 / 36 41 / 38 / 36
Outdoor – Hi dB-A 53 53 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 810
Depth mm 196 275 Package dimensions Height mm 276 704
Width mm 1,070 953
Depth mm 363 369
Weight Net
kg 12.0 50.0
Shipping
kg 15.0 54.5
Shipping volume m
3
0.11 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAP–K181AHA Outdoor Unit SAP–C181AHA
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
Power Source 240 V Single phase 50Hz Voltage rating V 240
Cooling Heating
Capacity
kW 6.35 7.10
BTU/h 21,700 24,200
Air circulation (High) m
3
/h 830 830 Moisture removal (High) Liters/h 3.3 — Available voltage range V 216 to 264 Running amperes A 13.3 13.3 Power input W 2,980 2,950 Power factor % 93 92 C.O.P. W/W 2.13 2.41 Compressor locked rotor amperes A 73 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hour ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,675 Refrigerant control Capillary tube
Operation sound
Indoor – Hi / Me / Lo dB-A 43 / 41 / 39 43 / 41 / 39
Outdoor – Hi dB-A 55 56 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 10
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 15.88 (5/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 810
Depth mm 196 275 Package dimensions Height mm 276 704
Width mm 1,070 953
Depth mm 363 369
Weight Net
kg 12.0 58.0
Shipping
kg 15.0 61.0
Shipping volume m
3
0.11 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAP–K241AHA Outdoor Unit SAP–C241AHA
4
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K181GJHA Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS–2HS4E
Type Cross-flow Q´ty ... Dia. and length mm 1 ... ø88 / L746 Fan motor model ... Q´ty UF2– 31A5P–S ... 1
No. of poles .... Hi rpm (Cool / Heat) 2 ... 1,335 / 1,215
Nominal output W 30 Coil resistance (Ambient temp. 20°C) WHT – BRN :133.7
WHT – PNK : 168.4
– : – – : – – :
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ±8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440 Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 20°C) k Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m2 0.156
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit SAP–K181AHA
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K241GJHA Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS–2HS4E
Type Cross-flow Q´ty ... Dia. and length mm 1 ... ø88 / L746 Fan motor model ... Q´ty UF2– 31A5P–S ... 1
No. of poles .... Hi rpm (Cool / Heat) 2 ... 1,425 / 1,410
Nominal output W 30 Coil resistance (Ambient temp. 20°C) WHT – BRN :133.7
WHT – PNK : 168.4
– : – – : – – :
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ±8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440 Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 20°C) k Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m2 0.156
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Circuit
Board
Ass´y
Indoor Unit SAP–K241AHA
6
2-2-2. Outdoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Controller PCB POW–C186GH
Type Rotary (Hermetic) Compressor model C–2R170H5T 80827445 Nominal output W 1,700 Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 750 Coil resistance (Ambient temp. 25°C) C – R : 1.35
C – S : 3.42
Type Internal protector
Safety
Overload relay
devices Operating temp. Open °C 170 ± 5
Close °C 105 ± 11
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 40 A
Run capacitor µF 40.0
VAC 400
Crank case heater 240V 30W Type Propeller Q´ty ... Dia. mm 1 ... ø 420 Fan motor model ... Q´ty KFG6S–51A5PA–S ... 1 No. of poles ... rpm (240 V, High) 6 ... 880 Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 67.1
WHT – YEL : 68.1
YEL – PNK : 15.7
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 4.0
VAC 440
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.4 Face area m
2
0.485
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
CompressorFan & Fan Motor
Outdoor Unit SAP–C181AHA
7
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Circuit Board Ass´y POW–C186GH
Type Rotary (Hermetic) Compressor model C–R221H5Q 80687345 Nominal output W 2,200 Compressor oil ... Amount cc 4GSD–T or SAY-56T ... 750 Coil resistance (Ambient temp. 25°C) C – R : 0.78
C – S : 2.41
Type Internal protector External (OLR)
Safety
Overload relay OL–D24
devices Operating temp. Open °C Automatic opening 150 ± 5
Close °C Automatic reclosing 63 ± 11
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 59 A
Run capacitor µF 40.0
VAC 400
Crank case heater 240V 30W Type Propeller Q´ty ... Dia. mm 1 ... ø 420 Fan motor model ... Q´ty KFG4S–51C5P–S ... 1 No. of poles ... rpm (240 V, High) 4 ... 1,010 Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 55.1
WHT – YEL : 37.2
YEL – PNK : 15.5
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 5.0
VAC 440
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.2 Face area m
2
0.497
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
CompressorFan & Fan Motor
Outdoor Unit SAP–C241AHA
2-3. Other Component Specifications
8
4-way Valve (Solenoid coil) LB64012 (Coil), V26-110B (Valve)
Coil rating AC 220-240V, 50/60Hz, 6W Coil resistance (at 20°C) 2,000 ± 7%
Thermostat (Fan Speed Control 23S) MQT5S
Switching temp. °C
high LOW 28.5°C ± 1.5 low HIGH 31.5°C ± 2
Contact rating AC 220V, 3A
Thermostat (Defrost thermo. 23D) TRS02-12MSR
Operating temp. °C ON 12 ± 2
Diff. 8 deg. below
Starting Relay (SR) AMVL300A
Coil rating AC 300V, 50Hz Coil resistance k(at 23°C) 13.3 ± 2% Contact rating 20A AC Operating voltage AC 185 – 217V, 50Hz Return voltage AC 60 – 120V, 50Hz
Power Relay (PR) G4F-1123T-US
Coil rating DC 24V Coil resistance (at 20°C) 640 ± 10% Contact rating AC 240V, 20A
Outdoor Unit SAP–C181AHA
SAP–C241AHA
Thermistor (Room sensor) DTN-TKS142B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ±10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAP–K181AHA
SAP–K241AHA
9
3. DIMENSIONAL DATA
Indoor Unit SAP–K181AHA
SAP–K241AHA
28545
995
45
147.5 147.5
196 (3)
Center of tubing hole (2 places)
Narrow tube ø6.35 (1/4")
Drain hose ø18
Wide tube ø12.7 (1/2") K181 Wide tube ø15.88 (5/8") K241
Remote control unit
172
61 23
Unit : mm
10
Outdoor Unit SAP–C181AHA
810 15
630
22
538
AIR INTAKE
AIR DISCHARGE
136
140
302
325
ø12
5
275
98 45
Narrow tube service valve ø6.35 (1/4")
Wide tube service valve ø12.7 (1/2")
Unit : mm
11
Outdoor Unit : SAP–C241AHA
275
98 45
810 15
630
22
538 136
140
302
325
Narrow tube service valve ø6.35 (1/4")
Wide tube service valve
ø15.88 (5/8")
AIR INTAKE
AIR DISCHARGE
5
Unit : mm
4. REFRIGERANT FLOW DIAGRAM
12
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
CAUTION
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
Indoor Unit SAP–K181AHA Outdoor Unit SAP–C181AHA
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø12.7 mm (1/2 ")
Compressor
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Heat exchanger
Cooling cycle
Heating cycle
Strainer
Strainer
Indoor unit Outdoor unit
Heat exchanger
Capillary
tube
Capillary for liquid injection
Indoor Unit SAP–K241AHA Outdoor Unit SAP–C241AHA
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø15.88 mm (5/8 ")
Compressor
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Cooling cycle
Heating cycle
Strainer
Strainer
Indoor unit Outdoor unit
Heat exchanger
Capillary
tube
Capillary for liquid injection
Muffler
Heat exchanger
5. PERFORMANCE DATA
5-1. Performance charts
Indoor Unit SAP–K181AHA Outdoor Unit SAP–C181AHA
13
Indoor inlet air
D.B. temp. (°C)
Outdoor fan speed
HighLow
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube serveice valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics Heating Characteristics
Indoor inlet air
D.B. temp. (°C)
3.44 (34)
3.24 (32)
2.95 (30)
2.85 (28)
2.65 (26)
2.46 (24)
2.26 (22)
2.06 (20)
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
High pressure at wide tube serveice valve MPa (kgf/cm
2
G)
1.87 (18)
1.67 (16)
1.47 (14) 25
Indoor inlet air
D.B. temp. (°C)
14 13 12 11 10
9 8 7 6
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
15
Indoor inlet air
D.B. temp. (°C)
Outdoor fan speed
HighLow
13 12 11 10
9 8 7 6
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
14
15
32 27 21
27 20 15
27 20 15
32 27 21
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high in heating mode. (Refer to “8-5 Overload prevention”)
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit SAP–K241AHA Outdoor Unit SAP–C241AHA
14
Indoor inlet air
D.B. temp. (°C)
Outdoor fan speed
HighLow
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube serveice valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics Heating Characteristics
27 20 15
Indoor inlet air
D.B. temp. (°C)
3.44 (34)
3.24 (32)
2.95 (30)
2.85 (28)
2.65 (26)
2.46 (24)
2.26 (22)
2.06 (20)
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
High pressure at wide tube serveice valve MPa (kgf/cm
2
G)
1.87 (18)
1.67 (16)
1.47 (14) 25
Indoor inlet air
D.B. temp. (°C)
18 17 16 15 14 13 12 11 10
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
19
Indoor inlet air
D.B. temp. (°C)
Outdoor fan speed
HighLow
27 20 15
17 16 15 14 13 12 11 10
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
18
19
32 27 21
32 27 21
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high in heating mode. (Refer to “8-5 Overload prevention”)
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
5-2. Air Throw Distance Chart
Horizontal distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 45° , : Axis air velocity 45° : Flap angle 60° , : Axis air velocity 60°
15
Indoor Unit SAP–K181AHA
Horizontal distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 45° , : Axis air velocity 45° : Flap angle 60° , : Axis air velocity 60°
16
Indoor Unit SAP–K241AHA
17
5-3. Cooling Capacity
240V Single Phase 50Hz
Indoor Unit SAP–K181AHA Outdoor Unit SAP–C181AHA
RATING CAPACITY 4.95 kW AIR FLOW RATE 760
m3/h
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 30 35 40 43
TC 4.55 4.34 4.07 3.75
CM 1.91 2.05 2.19 2.36
21 SHC 3.04 2.92 2.79 2.62
15 23 SHC 3.39 3.28 3.14 2.98
25 SHC 3.75 3.63 3.50 3.33 27 SHC 4.10 3.99 3.85 3.69 29 SHC 4.46 4.34 4.07 3.75 31 SHC 4.55 4.34 4.07 3.75
TC 4.89 4.65 4.37 4.02
CM 1.96 2.10 2.25 2.42
21 SHC 2.67 2.56 2.42 2.26
17 23 SHC 3.03 2.91 2.78 2.61
25 SHC 3.38 3.27 3.13 2.97 27 SHC 3.74 3.62 3.49 3.32 29 SHC 4.09 3.98 3.84 3.68 31 SHC 4.45 4.33 4.20 4.02
TC 5.20 # 4.95 4.65 4.28
CM 2.02 2.17 2.32 2.49
21 SHC 2.29 2.18 2.04 1.88
19 23 SHC 2.64 2.53 2.40 2.23
25 SHC 3.00 2.89 2.75 2.59 27 SHC 3.35 3.24 3.11 2.94 29 SHC 3.71 3.59 3.46 3.30 31 SHC 4.06 3.95 3.82 3.65
TC 5.51 5.25 4.93 4.54
CM 2.08 2.23 2.39 2.56
23 SHC 2.25 2.14 2.01 1.85
21 25 SHC 2.61 2.50 2.36 2.20
27 SHC 2.96 2.85 2.72 2.56 29 SHC 3.32 3.20 3.07 2.91 31 SHC 3.67 3.56 3.43 3.27
TC 5.84 5.51 5.16 4.80
CM 2.13 2.29 2.45 2.63
23 25 SHC 2.19 2.06 1.93 1.79
27 SHC 2.54 2.42 2.28 2.15 29 SHC 2.90 2.77 2.64 2.50 31 SHC 3.25 3.13 2.99 2.86
TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B. Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
18
240V Single Phase 50Hz
Indoor Unit SAP–K241AHA Outdoor Unit SAP–C241AHA
RATING CAPACITY 6.35 kW AIR FLOW RATE 830
m3/h
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 30 35 40 43
TC 5.84 5.56 5.22 4.81
CM 2.40 2.57 2.75 2.95
21 SHC 3.79 3.63 3.44 3.22
15 23 SHC 4.17 4.01 3.82 3.60
25 SHC 4.55 4.39 4.20 3.98 27 SHC 4.93 4.77 4.58 4.36 29 SHC 5.31 5.15 4.96 4.74 31 SHC 5.69 5.53 5.22 4.81
TC 6.27 5.97 5.61 5.16
CM 2.47 2.65 2.83 3.03
21 SHC 3.41 3.24 3.06 2.83
17 23 SHC 3.79 3.62 3.44 3.21
25 SHC 4.17 4.00 3.82 3.59 27 SHC 4.55 4.39 4.20 3.97 29 SHC 4.93 4.77 4.58 4.35 31 SHC 5.31 5.15 4.96 4.73
TC 6.67 # 6.35 5.97 5.49
CM 2.54 2.73 2.92 3.12
21 SHC 2.99 2.83 2.64 2.42
19 23 SHC 3.37 3.21 3.02 2.80
25 SHC 3.75 3.59 3.40 3.18 27 SHC 4.13 3.97 3.78 3.56 29 SHC 4.51 4.35 4.16 3.94 31 SHC 4.89 4.73 4.54 4.32
TC 7.07 6.73 6.33 5.82
CM 2.61 2.80 3.00 3.20
23 SHC 2.94 2.78 2.60 2.38
21 25 SHC 3.32 3.16 2.98 2.76
27 SHC 3.70 3.54 3.36 3.14 29 SHC 4.08 3.92 3.74 3.52 31 SHC 4.46 4.31 4.12 3.90
TC 7.49 7.07 6.62 6.15
CM 2.68 2.88 3.08 3.29
23 25 SHC 2.86 2.68 2.49 2.31
27 SHC 3.24 3.06 2.87 2.69 29 SHC 3.62 3.44 3.25 3.07 31 SHC 4.00 3.82 3.63 3.45
TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B. Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
5-4. Heating Capacity
Indoor Unit SAP–K181AHA SAP–K241AHA Outdoor Unit SAP–C181AHA SAP–C241AHA
–5 0 5
7
10 15
Outdoor temperature (°C D.B.)
0
10
20
30
40
50
60
70
80
90
100
110
120
Heating capacity ratio (%)
NOTE
1) … Point of Rating condition Black dot in the chart indicate the following rating condition.
Indoor : 20°C D.B. Outdoor : 7°C D.B. / 6°C W.B.
2) Above characteristics indicate instantaneous operation, which does not take into
account defrost operation.
3) Fan speed : High
4) Because this air conditioner heats a room by drawing in the heat of the outside
air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance in conjunction with it.
–8
19
20
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit SAP–K181AHA Outdoor Unit SAP–C181AHA
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 240V Single phase 50Hz Rating Conditions Running Amps. A 0.38 0.50 9.72 10.6
Power Input kW 0.073 0.119 2.168 2.36
Full Load Conditions Running Amps. A 0.38 0.50 11.62 12.5
Power Input kW 0.073 0.119 2.628 2.82
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 240V Single phase 50Hz Rating Conditions Running Amps. A 0.38 0.50 8.52 9.4
Power Input kW 0.073 0.119 1.848 2.04
Full Load Conditions Running Amps. A 0.38 0.50 10.32 11.2
Power Input kW 0.073 0.119 2.238 2.43
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°CD.B. / 18°CW.B.