Sanyo SA-128S5-A, SA–93AH Technical & Service Manual

TECHNICAL & SERVICE MANUAL
SA–128S5
FILE NO.
REFERENCE NO. SM700338
WINDOW TYPE AIR CONDITIONER
Model No. Product Code No.
SA–128S5
SA-128S5-A 1 851 004 09 General (50Hz) & Europe
IMPORTANT! Please Read Before Starting
This air conditioner meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read the INSTRUCTION MANUAL and INSTALLATION INSTRUCTIONS attached to each air conditioner before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state, and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• All wiring must conform to local electrical codes.
• Each unit must be properly grounded with a ground (or earth) wire or through the supply wiring.
• DO NOT, under any circumstances, cut or remove the third (ground) prong from the power cord plug.
• DO NOT use an adapter Plug or extension cord.
• DO NOT use a damaged power cord, plug, or wall outlet. Replace them immediately.
• DO NOT change the internal wiring or any part of the system.
• DO NOT turn the air conditioner on and off by plugging and unplugging. Use the Operation switch.
When Transporting
Be careful when picking up and moving the air conditioner. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
WARNING
When Installing
Place of Installation
• If possible, install the unit in a shady location. If the site is exposed to the sun, you should provide a sun screen as shown in Fig. a.
• Install it at a spot where optimum cooling circulation can be obtained. No chairs or other obstructions are allowed in front of the air conditioner.
• The back of the air conditioner must extend outside. (Be sure the right and left intake vents are not obstructed by walls or windows.)
• Keep more than 50 cm from any outside obstruction (wall, bush, etc.).
• To provide water drainage, the unit must be tilted at a downward angle 0.5 to 1 cm to the outside.
• While installing the air conditioner, be sure to loosen the
compressor locking nuts to avoid abnormal noise and vibration. (NOTE: Locking nuts are not provided on some models.)
• As a safety measure, it is recommended that two people install the unit: one to hold and balance the unit — the other to lower the window frame to secure the unit.
• Hold the unit securely, and be careful to not drop the cabinet or any parts if the air conditioner is being installed on an upper floor of a multistory building.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of tools have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
Room side
Front grille
OutsideWall
Screen
Enough space from obstacle or wall.
Tilt 0.5 to 1 cm downward to outside.
Support
i
WARNING
CAUTION
Fig. a
HOW TO USE THIS MANUAL
This manual is designed to help service personnel to understand basic functions, operation and possible troubles and their remedies on SANYO window type air conditioners. You can use this manual both as a reference to find specific information about the capacity, construction of the unit, and as a source of information to help you set up and maintain the air conditioner. Please use this manual to make your work easier, keep the air conditioner functioning well, and keep your customer satisfied.
Please read IMPORTANT ! precautional information on the previous page before you start actual work.
SANYO WINDOW TYPE A/C NOMENCLATURE
SANYO window type air conditioner is identified by a model number. Cooling or heating capacity, electrical information and special features included on the air conditioner are indicated on the model number.
ii
Example
SA – 12 8 S 5
Type SA : SANYO window type A/C
Capacity 12 : 12,000 BTU/h class
Design Number
Voltage / Frequency 5 : 220-240V, 50Hz, Single phase
Special Features S : Mechanical Control, Side Air Discharge
NOTE
To identify the correct model number of your air conditioner, you must find the nameplate.
Table of Contents
Page
1. OPERATING RANGE ............................................................................................................................... 1
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 2
2-2. Major Component Specifications.................................................................................................... 3
2-3. Other Component Specifications.................................................................................................... 4
3. DIMENSIONAL DATA............................................................................................................................... 5
4. REFRIGERANT FLOW DIAGRAM .......................................................................................................... 6
5. PERFORMANCE DATA
5-1. Cooling Capacity ........................................................................................................................... 7
6. ELECTRICAL DATA
6-1. Electrical Characteristics ............................................................................................................... 8
6-2. Electric Wiring Diagram.................................................................................................................. 9
7. TROUBLESHOOTING
7-1. Check before and after troubleshooting ........................................................................................ 10
7-2. Air conditioner does not operate .................................................................................................... 11
7-3. Some part of air conditioner does not operate ..............................................................................13
7-4. Air conditioner operates, but abnormalities are observed ............................................................. 15
8. CHECKING ELECTRICAL COMPONENTS
8-1. Measurement of Insulation Resistance.......................................................................................... 16
8-2. Checking Motor Capacitor.............................................................................................................. 17
8-3. Checking Fan Motor Winding......................................................................................................... 17
8-4. Checking Compressor Motor Winding............................................................................................ 17
9. DISASSEMBLY PROCEDURES
9-1. Removing Front Grille .................................................................................................................... 18
9-2. Removing Electrical Component Box ............................................................................................ 19
9-3. Removing Cabinet ......................................................................................................................... 19
9-4. Removing Evaporator .................................................................................................................... 20
9-5. Removing Blower Wheel ............................................................................................................... 20
9-6. Removing Condenser .................................................................................................................... 21
9-7. Removing Propeller Fan ................................................................................................................ 21
9-8. Removing Fan Motor ..................................................................................................................... 21
Unit Display and Control Panel ............................................................................................ 22
APPENDIX
iii
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
2
2. SPECIFICATIONS
2-1. Unit Specifications
Model SA–128S5
Power Source 220–240V Single phase 50Hz Voltage rating 220 / 230 / 240 V Performance Cooling
Capacity kW 3.50
/
3.55
/
3.55
BTU/h 11,900
/
12,100
/
12,100
Air circulation (High)
m3/h 620
Moisture removal (High) Liters/h 2.0
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 6.3
/
6.2
/
6.2
Power input W 1,300
/
1,340
/
1,360
Power factor % 94
/94/
91
C.O.P. W/W 2.69
/
2.65
/
2.61
Starting amperes A 34
Features
Controls / Temperature control Mechanical / Thermostat Control unit — Timer — Fan speeds 2 Airflow direction (Indoor) Horizontal Auto
Vertical Manual Air filter / Air exhaust Washable / Yes Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 780 Refrigerant control Capillary tube Operation sound Indoor : Hi / Lo dB-A 52 / 50
Outdoor : Hi / Lo dB-A 56 / 52 Slide-out chassis Yes Accessories
Dimensions & Weight
Unit dimensions Height mm 375
Width mm 530
Depth mm 620 Package dimensions Height mm 435
Width mm 600
Depth mm 725 Weight Net kg 44.0
Shipping kg 47.0 Shipping volume
m
3
0.19
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35° C D.B. / 24°C W.B.
3
2-2. Major Component Specifications
Model SA–128S5
Controller PCB
Part No. — Controls — Control circuit fuse
Remote Control Unit
Compressor
Type Rotary (Hermetic) Compressor model C-R110H5H 80619445 Source 220–240V Single phase 50Hz Nominal output W 1,100 Compressor oil ... Amount cc SUNISO 4GSD-T ... 550 Coil resistance (Ambient temp. 25°C) C–R : 1.962
C–S : 5.38
Safety devices Type
External protector
Overload relay
MRA98619-9200
Operating temp. Open °C
150±5
Close °C
69±11
Operating amp.(Ambient temp. 25°C )
Trip in 6 to 16 sec. at 22.5A
Run capacitor µF 25.0
VAC 400
Fan & Fan Motor Indoor Outdoor
Type Centrifugal Propeller Dia. / Depth mm ø210 / D96 ø320 / D — Fan motor model ... Q'ty YSK70-4A-661 ... 1 Source 220–240V Single phase 50Hz No. of poles ... rpm (230 V, High) 4 ... 1,010 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT-BRN : 60.0
WHT-YEL : 19.6
YEL-ORG(PNK) : 62.7
Safety devices Type Internal protector
Operating temp. Open °C 130±5
Close °C Automatic reclosing
Run capacitor µF 3.5
VAC 440
Heat Exch. Coil
Coil Evaporator Condenser Rows 2 3 Fin pitch mm 1.4 1.6 Face area
m
2
0.095 0.155
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
4
Model SA–128S5
Auto Deflector Motor M16B
Rating AC 220-240V, 50/60Hz, 3 W, 4.2/5.0 rpm Coil resistance k(at 25°C)
11.15 ± 5%
2-3. Other Component Specification
5
3. DIMENSIONAL DATA
Model SA–128S5
248
530
375
40
248
620
Slits for ventilation
Side view (L) Front view Side view (R)
Power code outlet
Power code outlet
Unit : mm
Dimension with "" mark indicates the maximum allowable wall thickness required for ventilating the unit.
NOTE