Wireless Remote Controller (For U, D Type)RCS-BH80AAB.WL
Wireless Remote Controller (For X Type)RCS-SH80AAB.WL
Wireless Remote Controller (For A, T Type)RCS-TRP80AAB.WL
RC Wireless Remote Controller (For K Type)RCS-SH1AAB
Simplified Remote ControllerRCS-KR1AGB
System ControllerSHA-KC64UG
Intelligent ControllerSHA-KT256BA
Communication AdaptorSHA-KA128AAB
Remote SensorART-K45AGB
LonWorks InterfaceSHA-LN16UAB
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page a
2
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an
important part of your job to install or service the system so it
operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum
fins on the air conditioner can cut your fingers.
When Installing…
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical parts
and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously toxic
gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas
water heater, electric room heater or other heat source,
it can cause the generation of poisonous gas.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 2
WARNING
CAUTION
WARNING
CAUTION
2. The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15% or larger than the
respective floor spaces at the top or bottom of the
door).
(3) If an indoor unit is installed in each partitioned room
and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when
mechanical ventilation is installed interlocked with a
gas leakage detector in the smallest room where the
density limit is exceeded, the volume of the next smallest room becomes the object.
3. The minimum indoor floor space compared with the
amount of refrigerant is roughly as follows: (When the
ceiling is 8.8 ft. high)
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set
limit.
The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws imposed to protect the ozone
layer. However, since it contains more than air, it poses the
risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent.
With the recent increase in the number of high density
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its
density does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).
In a room where the density may exceed the limit, create
an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The density is as given below.
Total amount of refrigerant (lbs)
Min. volume of the indoor unit installed room (ft.3)
<
Density limit (oz/ft.3)
The density limit of refrigerant which is used in multi air conditioners is 0.3 oz/ft.
3
(ISO 5149).
1. If there are 2 or more refrigerating systems in a single
refrigerating device, the amount of refrigerant should be
as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B
and C is 353 oz.
The possible amount of leaked refrigerant gas in rooms D, E
and F is 529 oz.
3
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 3
NOTE
Outdoor unit
Refrigerant tubing
Indoor unit
Refrigerant tubing
Outdoor unit
Very
small
room
Small
room
Mechanical ventilation device – Gas leak detector
Medium
room
Large room
Indoor unit
e.g., charged
amount (353 oz)
Indoor unit
Outdoor unit
e.g., charged
amount (529 oz)
Room A Room B Room C Room D Room E Room F
3
ft.
4000
3500
3000
Min. indoor volume
2500
2000
1500
1000
Range below
the density limit of
0.3 oz/ft.
(countermeasuresnot needed)
500
00
0
3
Range above
the density limit of
0.3 oz/ft.
(countermeasuresneeded)
400200600800 1000 1200
Total amount of refrigerant
3
454
398
341
284
227
170
114
57
oz
2
ft.
Min. indoor floor area
(when the ceiling is8.8 ft. high)
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refriger-
ant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the
prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects
in the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refriger-
ant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless
Pipes and Tubes.”
For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints
(optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to
prevent dirt, moisture, or other foreign substances from entering. These substances
can result in system malfunction.
R407C tools
ItemcompatibleRemarks
with R410A?
Manifold gauge Yes No Types of refrigerant, refrigerating machine
oil, and pressure gauge are different.
Charge hoseYesNo To resist higher pressure, material must be changed.
Vacuum pumpYesYesUse a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
Leak detectorYes No Leak detectors for CFC and HCFC that
react to chlorine do not function because
R410A contains no chlorine. Leak detector
for HFC134a can be used for R410A.
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil)
to the flare nuts on the tubing to prevent refrigerant
leakage. For machines that use R407C or R410A, apply
synthetic oil (ether oil) to the flare nuts.
Unit: in. (mm)
Unit: in. (mm)
4
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 4
CAUTION
New
tool?
Manifold gauge
Vacuum pump
Outlet
Inlet
5
3-2. Use R410A exclusive cylinder only.
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
New refrigerant R410A cannot be used for
earlier models
1. Compressor specifications are different.
If recharging a R22 or R407C compressor with
R410A, durability will significantly decrease since
some of the materials used for compressor parts are
different.
2. Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
3. Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it
does not dissolve in R410A. Therefore, refrigerating
machine oil discharged from the compressor can
cause compressor damage.
Please Read Before Starting
Check of Density Limit
Precautions for Installation Using New Refrigerant
New refrigerant R410A cannot be used for earlier models
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
1-5. Tubing Length
1-6. Tubing Size
1-7. Straight Equivalent Length of Joints
1-8. Additional Refrigerant Charge
1-9. System Limitations
1-10. Check of Limit Density
1-11. Installing Distribution Joint
1-12. Optional Distribution Joint Kits
1-13. Example of Tubing Size Selection and
Refrigerant Charge Amount
2. SELECTING THE INSTALLATION SITE . . . . . 19
2-1. Indoor Unit
2-2. Outdoor Unit
2-3. Shield for Horizontal Exhaust Discharge
2-4. Installing the Outdoor Unit in Heavy Snow Areas
2-5. Precautions When Installing in Heavy Snow
Areas
2-6. Dimensions of Wind Ducting
2-7. Dimensions of Snow Ducting
3. HOW TO INSTALL THE INDOOR UNIT . . . . . 24
4-Way Air Discharge Semi-Concealed Type
(X Type)
3-1. Preparation for Suspending
3-2. Suspending the Indoor Unit
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. How to Install the Ceiling Panel
3-7. Special Remarks
1-Way Air Discharge Semi-Concealed Type
(A Type)
3-8. Suspending the Indoor Unit
3-9. Placing the Unit Inside the Ceiling
3-10. Installing the Drain Piping
3-11. Checking the Drainage
3-12. Electrical Power Wiring
3-13. How to Install the Ceiling Panel
Concealed Duct Type (U Type)
3-14. Required Minimum Space for Installation and
Service
3-15. Suspending the Indoor Unit
3-16. Installing the Drain Piping
3-17. Checking the Drainage
3-18. Increasing the Fan Speed
Concealed Duct High-Static Pressure Type
(D Type)
3-19. Required Minimum Space for Installation and
Service
3-20. Suspending the Indoor Unit
3-21. Installing the Drain Piping
3-22. Caution for Ducting Work
3-23. Indoor Fan Performance
Ceiling-Mounted Type (T Type)
3-24. Required Minimum Space for Installation and
Service
3-25. Suspending the Indoor Unit
3-26. Duct for Fresh Air
3-27. Shaping the Tubing
3-28. Installing the Drain Piping
Wall-Mounted Type (K Type)
3-29. Removing the Rear Panel from the Unit
3-30. Selecting and Making a Hole
3-31. Installing the Rear Panel onto the Wall
3-32. Removing the Grille to Install the Indoor Unit
3-33. Preparing the Tubing
3-34. Shaping the Tubing
3-35. Installing the Drain Hose
3-36. When Using Wireless Remote Controller
Instead of Wired Remote Controller
4. HOW TO INSTALL THE OUTDOOR UNIT . . . 55
4-1. Transporting
4-2. Installing the Outdoor Unit
4-3. Routing the Tubing
4-4. Prepare the Tubing
4-5. Connect the Tubing
8-1. Preparing for Test Run
8-2. Test Run Procedure
8-3. Main Outdoor Unit PCB Setting
8-4. Auto Address Setting
8-5. Remote Controller Test Run Settings
8-6. Caution for Pump Down
8-7. Meaning of Alarm Messages
(X Type)
9-2. 1-Way Air Discharge Semi-Concealed Type
(A Type)
9-3. Concealed Duct (High-Static Pressure) Type
(U, D Type)
9-4. Ceiling-Mounted Type (T Type)
9-5. Wall-Mounted Type (K Type)
Page
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 7
8
Table 1-1 Outdoor Unit
1-2. Accessories Supplied
See Tables 1-1 – 1-7.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a
local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 5/16 in.
3. Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring.
Refer to
“
5. ELECTRICAL WIRING” for details.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Check local electrical codes and
regulations before obtaining
wire. Also, check any specified
instructions or limitations.
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for
the outdoor unit and make sure all accessory parts listed are with the system before beginning.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 8
CAUTION
Part name
Connection tubing
Instruction manualpaper
Outer
diameter
ø1-1/8"
Outer
diameter
ø7/8"
Figure
Inner
diameter
ø1"
Inner
diameter
ø3/4"
09053 Model
(10 hp)
0
Q’ty
14053 Model
(16 hp)
1
10
11
(hp = horse power)
9
Table 1-2 (4-Way Air Discharge Semi-Concealed)
Table 1-3 (1-Way Air Discharge Semi-Concealed)
Table 1-4 (Concealed Duct)
Use 3/8" for suspending bolts.
Field supply for suspending bolts and nuts.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 9
Part NameFigure
Full-scale installation diagram
Drain hose
Hose band
Drain insulator
Flare insulator
Insulating tape
Packing
Wiring cover
Screw
Washer
Screw
Part NameFigure
Full-scale installation diagram
Drain hose
White
(heat-resisting)
Q’ty
Printed on container box
1
For securing drain hose
1
For securing drain hose
1
For drain joint
1
For liquid tube
1
For gas tube
1
For gas tube joint
2
For drain joint
1
For covering erectrical wiring
1
For full-scale installation diagram
4
For suspending indoor unit from ceiling
8
For fixing the wiring cover
1
Q’ty
Printed on container box
1
For securing drain hose
1
Remarks
Remarks
Hose band
Drain insulator
Flare insulator
Insulating tape
Packing
Washer
Screw
Bushing
Part NameFigure
Drain hose
Hose band1
Packing1
Drain insulator1
Flare insulator1
Insulating tape
Flare insulator1
White
(heat-resisting)
White
(heat-resisting)
For securing drain hose
1
For drain joint
1
For liquid tube
1
For gas tube
1
For gas tube joint
2
For drain joint
1
For suspending indoor unit from ceiling
8
For full-scale installation diagram
4
For electrical junction box
1
Q’ty
For securing drain hose
1
For securing drain hose
For drain joint
For drain joint
For liquid tube
For gas and liquid tubes flare nuts
2
For gas tube
Remarks
Washer
Sealing putty1
Vinyl clamp8
For suspending indoor unit from ceiling
8
For sealing recessed portion of power supply
For flare and drain insulators
10
Table 1-5 (Concealed Duct High-Static Pressure)
Table 1-6 (Ceiling-Mounted)
Table 1-7 (Wall-Mounted)
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 10
Part NameFigure
Washer
Nut
Flare insulator
Drain socket
Part NameFigure
Full-scale installation diagram1
Washer4
Insulating tape2
Vinyl clamp8
Drain hose1
Hose band2
Drain insulator1
T1/8"
T3/16"
White
(heat-resisting)
L5-1/2"
Q’ty
For suspending indoor unit from ceiling
8
For suspending indoor unit from ceiling
8
Remarks
1For gas tube
For liquid tube
1
For drain pipe connection
1
Q’ty
Remarks
Printed on container box
For temporarily suspending indoor unit from ceiling
2
For gas and liquid tube jointsFlare insulator
2
For gas and liquid tubes flare nuts
For flare and drain insulators
For mainunit and PVC pipe joints
For drain hose connection
For drain hose joint
Gum eyelet1
Part NameFigure
Tappingscrew
Plastic cover
Insulator
5/32" × 1"
For power supply inlet
Q’ty
For fixing the rear panel
10
For improved tubing appearance
1
For insulating flare nut (2452 type only)
1
Remarks
1-5. Tubing Length
Table 1-8 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
1: The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to
the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas
tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 1-9) on the
following page (LA table), and from the table of refrigerant tubing sizes (Table 1-14) on the second following page.)
3: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the
gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.
* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then
change the size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit: 62 lbs
Max. additional charge for 2 outdoor units: 111lbs
11
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 11
1.
2.
The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
3.
4.
H3
L5
B
Balance tubing
(ø1/4
")
Explanation of symbols
Distribution joint
(APR: purchased separately)
Ball valve (field supply)
T- j o i nt (field supply)
Solidly welded shut
(pinch weld)
Main tu
bing length LM = LA + LB … ≤ 262 ft
Main distribution tubes LC – LG are selected according to the capacity after the distribution joint.
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubingsizes on the indoor units.
L1
L2
LM
A
LA
LBLC
LE
Max. 1.3 ft
Max. 1.3 ft
LF
L4
For
extension
LDL3
5
2
For
extension
4
LG
1
40
38
39
H1
R410A distribution joint
APR-CHP680BA (for outdoor unit)
Note: Do not use commercially available T-joints for the liquid tubing and parts.
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor unit connections and tubing branches.
ItemMarkContentsLength (ft.)
L1Max. tubing length
∆L (L2 – L4)
Allowable tubing
length
LMMax. length of main tubing (at max. diameter)262
40
, 2...
112
+
L1+
...
A
+LE+LF+LG
L5
Allowable elevation
difference
H1
H2
Difference between max. length and min.
length from the No.1 distribution joint
Max. length of each distribution tube98
39
+
Total max. tubing length including length of
each distribution tube (only liquid tubing)
Distance between outdoor units
When outdoor unit is installed higher than indoor unit164
When outdoor unit is installed lower than indoor unit131
Max. difference between indoor
Actual length492
Equivalent length574
units49
H3Max. difference between outdoor units
Allowable length of
joint tubing
L = Length, H = Height
L3
T-joint tubing (field-supply); Max. tubing length between
the first T-joint and solidly welded-shut end point
NOTE
>
>
>
>
>
>
>
>
>
>
>
>
131
*3
984
32
13
6.6
12
1-6. Tubing Size
Table 1-9 Main Tubing Size (LA)
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.
However extension is not possible if the resulting tubing size is two ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø1/4".
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the gas
and liquid tubes. (Use field-supply reducers.) (Select from Table 1-9 and Table 1-14.)
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the
gas tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing
size for the total capacity of the outdoor units. (Especially the main tubing segments of LA, LB and LF.)
Table 1-11 Outdoor Unit Tubing Connection Size
Table 1-12 Indoor Unit Tubing Connection Size
Note: Use C1220T-1/2H material for tubing over ø3/4" (ø22.22).
Table 1-10 Main Tubing Size After Distribution (LB, LC...)
Unit: in. (mm)
Unit: in. (mm)
Unit: in. (mm)
Unit: in. (mm)
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 12
BTU/h
(kW)
Total system horsepower
Combined outdoor units
Gas tubing
Liquid tubing
95,500
(28.0)
10
ø7/8"
(ø22.22)
ø3/8"
(ø9.52)
153,600
(45.0)
16
1610
ø1-1/8"
(ø28.58)
ø1/2"
(ø12.7)
191,100
(56.0)
20
10
10
ø5/8"
(ø15.88)
249,100
(73.0)
26
16
10
(ø31.75)
(ø19.05)
307,100
(90.0)
32
16
16
ø1-1/4"
ø3/4"
Total capacity
after distribution
Below BTU/h
Over BTU/h
24,200
(2.5 hp)
–
Gas tubing
Tubing size
Liquid tubing
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
54,600
(6 hp)
24,200
(2.5 hp)
ø5/8"
(ø15.88)
ø3/8"
(ø9.52)
76,800
(8.1 hp)
54,600
(6 hp)
ø3/4"
(ø19.05)
ø3/8"
(ø9.52)
102,400
(11 hp)
76,800
(8.1 hp)
ø7/8"
(ø22.22)
ø3/8"
(ø9.52)
143,300
(15 hp)
102,400
(11 hp)
ø1"
(ø25.4)
ø1/2"
(ø12.7)
178,800
(19 hp)
143,300
(15 hp)
ø1-1/8"
(ø28.58)
ø1/2"
(ø12.7)
238,900
(25 hp)
178,800
(19 hp)
ø1-1/8"
(ø28.58)
ø5/8"
(ø15.88)
hp = horsepower
334,400
(35 hp)
238,900
(25 hp)
ø1-1/4"
(ø31.75)
ø3/4"
(ø19.05)
–
334,400
(35 hp)
ø1-1/2"
(ø38.1)
ø3/4"
(ø19.05)
( A – C)
BTU/h
(kW)
Gas tubing
Liquid tubing
Balance tubing
Indoor unit type7 9 12 18243648
Gas tubing
Liquid tubing
95,500
(28.0)
ø7/8"
(ø22.22)
Brazing connection
ø3/8" (ø9.52)
Flare connection
ø1/4" (ø6.35)
Flare connection
ø1/2" (ø12.7)
153,600
(45.0)
ø1-1/8"
(ø28.58)
ø1/2" (ø12.7)
Balance tube
Liquid tube
ø5/8" (ø15.88)
ø3/8" (ø9.52)ø1/4" (ø6.35)
Gas tube
13
Table 1-16 Refrigerant Charge Amount at Shipment (for outdoor unit)
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 1-15 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing sizeAmount of refrigerant
(in. (mm))charge (oz/ft.)
ø1/4" (ø6.35)0.279
ø3/8" (ø9.52)0.602
ø1/2" (ø12.7)1.38
ø5/8" (ø15.88)1.99
ø3/4" (ø19.05)2.78
ø7/8" (ø22.22)3.93
Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)
* Always charge accurately using a scale for weighing.
* If the existing tubing is used, and the amount of on-site additional
refrigerant charge exceeds the value listed below, then change the
size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit : 62 lbs
Max. additional charge for 2 outdoor units :111 lbs
Max. additional charge for 3 outdoor units :133 lbs
Unit: ft.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 13
Gas tubingsize (in. (mm))
90° elbow
45° elbow0.80.911.21.31.41.71.9
1/2"
(12.7)
5/8"
(15.88)
11.11.41.61.71.92.32.6
3/4"
(19.05)
7/8"
(22.22)1"(25.4)
U-shape tube bent (R2-3/8" – 4" (60 – 100))33.44.14.75.15.66.97.8
Tra p b end
Y-branch distribution jointEquivalent length conversion not n
Ball valve for serviceEquivalent length conversionnot needed.
7.59.210.512.514.115.416.414.0
1-1/8"
(28.58)
eeded.
1-1/4"
(31.8)
1-1/2"
(38.1)
Always check the gas density
limit for the room in which the
unit is installed.
1-10. Check of Limit Density
When installing an air conditioner in a room, it is necessary to
ensure that even if the refrigerant gas accidentally leaks out, its
density does not exceed the limit level for that room.
If the density could exceed the limit level, it is necessary to provide
an opening between the unit and the adjacent room, or to install
mechanical ventilation which is interlocked with a leak detector.
(Total refrigerant charged amount: oz)
(Min. indoor volume where the indoor unit is installed: ft.3)
< Limit density 0.3 (oz/ft.
3
)
The limit density of refrigerant R410A which is used in this unit is
0.3 oz/ft.
3
(ISO 5149).
The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount that is charged in
the field. (For the refrigerant charge amount at shipment, refer to the
unit’s nameplate.)
Minimum indoor volume & floor area as against the amount
of refrigerant is roughly as given in the following table.
Pay special attention to any location,
such as a basement, etc., where leaking refrigerant can accumulate, since
refrigerant gas is heavier than air.
1-11. Installing Distribution Joint
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed
with the optional distribution joint kit
(APR-CHP680BA, APR-CHP1350BA, APR-P160BA,
APR-P680BA, APR-P1350BA).
(2) When creating a branch using a commercially available
T-joint (header joint system), orient the main tubing so that it is
either horizontal (level) or vertical. In order to prevent accumu-
lation of refrigerant oil in stopped units, if the main tubing is
horizontal then each branch tubing length should be at an
angle that is greater than horizontal. If the main tubing is verti-
cal, provide a raised starting portion for each branch.
(3) If there are height differences between indoor units or if branch
tubing that follows a distribution joint is connected to only 1
unit, a trap or ball valve must be added to that
distribution joint. (When adding the ball valve, locate it
within 1.3 ft. of the distribution joint.)
If a trap or ball valve is not added, do not operate the sys-
tem before repairs to a malfunctioning unit are
completed. (The refrigerant oil sent through the tubing to
the malfunctioning unit will accumulate and may damage
(a) : Liquid tubingTotal length of ø7/8" (ft.)(d) : Liquid tubingTotal length of ø1/2" (ft.)
(b) : Liquid tubingTotal length of ø3/4" (ft.)(e) : Liquid tubingTotal length of ø3/8" (ft.)
(c) : Liquid tubingTotal length of ø5/8" (ft.)( f ) : Liquid tubingTotal length of ø1/4" (ft.)
Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the “fully
closed” position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant
from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.
However if only one outdoor unit is installed, a balance tube is not used. Therefore, leave the valves fully closed.)
Charge with R410A refrigerant in liquid form.
With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from
backing up.
After charging is completed, turn all valves to the “fully open” position.
Replace the tubing covers as they were before.
Required additional
refrigerant charge (oz)
1. R410A additional charging absolutely must
be done through liquid charging.
2. The R410A refrigerant cylinder has a gray
base color, and the top part is pink.
3. The R410A refrigerant cylinder includes a
siphon tube. Check that the siphon tube is
present. (This is indicated on the label at the
top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in installation, it is not possible in some cases to use
the same tools for R22 and for R410A.
Example:
Example of each tubing length
Main tubingDistribution joint tubing
LA = 131 ft.Outdoor sideIndoor side
LB = 16 ft.A = 7 ft.1 = 98 ft.
LC = 16 ft.B = 7 ft.2 = 16 ft.
3 = 16 ft.
4 = 65 ft.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 17
CAUTION
Balance tube
Use a flathead screwdriver and
open by turning the part with the screw groove to the right,
from “–” to “|”.
Outdoor unit
09053
model
09053
model
B
A
LA
LB
1 2 3 4
LC
Liquid tube
Use a hex wrench (width 5/32 inch)
and turn to the left to open.
Gas tube
Use a flathead screwdriver and
open by turning the part with the screw groove to the right,
from “–” to “|”.
48 model48 model48 model
36 model
18
Checking of limit density
Density limit is determined on the basis of the size of a room
using an indoor unit of minimum capacity. For instance, when
an indoor unit is used in a room (floor area 161 ft.
2
× ceiling
height 8.8 ft. = room volume 1417 ft.
3
), the graph at right
shows that the minimum room volume should be 2455 ft.
3
(floor area 279 ft.2) for refrigerant of 418 oz.
<Determination by calculation>
Overall refrigerant charge amount for the air conditioner: oz
(Minimum room volume for indoor unit: ft.3)
=
418 (oz)
= 0.29 (oz/ft.
3
) < 0.3 (oz/ft.3)
1417 (ft.
3
)
Therefore, openings such as louvers are not required for this
room.
Obtain liquid tubing size from Tables 1-9, 10, 11, 12 and 15.
Main tubing
LA = ø5/8 (ft.) (Total capacity of indoor unit is 179,400 BTU/h)The longest tubing length in this example
LB = ø1/2 (ft.) (Total capacity of indoor unit is 131,600 BTU/h)(LA = 131 ft.)
LC = ø3/8 (ft.) (Total capacity of indoor unit is 83,800 BTU/h)
Distribution joint tubing
Outdoor side A: ø3/8 (ft.)B: ø3/8 (ft.) (from outdoor unit connection tubing)
Note that the charge amounts per 1 meter are different for each liquid tubing size.
ø5/8 (ft.) → LA: 131 ft. × 1.99 oz/ft. = 261 oz
ø1/2 (ft.) → LB: 16 ft. × 1.38 oz/ft. = 22 oz
ø3/8 (ft.) → LC +A – B +1 – 4: 225 ft. × 0.602 oz/ft. = 135 oz
Total 418 oz
Additional refrigerant charge amount is 418 oz.
Be sure to check the limit density for
the room in which the indoor unit is
installed.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 18
CAUTION
3
ft.
4000
Range below
the density limit of
0.3 oz/ft.
(countermeasuresnot needed)
500
00
0
3
Range above
the density limit of
0.3 oz/ft.
(countermeasuresneeded)
400200600800 1000 1200
Total amount of refrigerant
3
Min. indoor volume
3500
3000
2500
2000
1500
1000
454
398
341
284
227
170
114
57
oz
2
ft.
Min. indoor floor area
(when the ceiling is8.8 ft. high)
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room directly.
This may cause “sweating” on the air discharge ports,
causing them to spray or drip.
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO:
select an appropriate position from which every corner of
the room can be uniformly cooled.
select a location where the ceiling is strong enough to
support the weight of the unit.
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in Table 1-8.
allow room for mounting the remote controller about 3 ft.
off the floor, in an area that is not in direct sunlight nor in
the flow of cool air from the indoor unit.
Air delivery will be degraded if the distance from the floor to
the ceiling is greater than 10 ft.
Fig. 2-1
Fig. 2-2
Fig. 2-3
Fig. 2-4
19
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 19
Ceiling-Mounted Type
Ceiling
Wall
min. 10 in.
Front view
min. 10 in.
NOTE
The rear of the indoor unit can be installed flush
against the wall.
Air
discharge
min. 2 ft.
Side view
Air intake
Max. 10 in.
Obstacle
Concealed Duct (High-Static Pressure) Type
4-Way Air Discharge Semi-Concealed Type
3 ft.
3 ft.
3 ft.
3 ft.
3 ft.
NOTE
1-Way Air Discharge Semi-Concealed Type
Ceiling
min. 2 in.
Air
discharge
min. 3 ft.
Obstacle
Air
intake
min. 2 in.
Wall
Wall
Side view
Wall-Mounted Type
min.
6 in.
min.6 in.
min.
6 in.
Front View
20
Fig. 2-5
Fig. 2-6
Fig. 2-7
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc.
damp, humid or uneven locations
indoors (no-ventilation location)
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance.
Installation Space
Install the outdoor unit where there is enough space for ven-
tilation. Otherwise the unit may not operate properly. Fig. 2-6
shows the minimum space requirement around the outdoor
units when 3 sides are open and only 1 side is shuttered,
with open space above the unit. The mounting base should
be concrete or a similar material that allows for adequate
drainage. Make provisions for anchor bolts, platform height,
and other site-specific installation requirements.
Leave space open above the
unit.
Construct louvers or other
openings in the wall, if necessary, to ensure adequate
ventilation.
Do not do any wiring or tubing within 1 ft. of the front
panel, because this space is needed as a servicing
space for the compressor.
Ensure a base height of 4 in. or more to ensure that
drainage water does not accumulate and freeze
around the bottom of the unit.
If installing a drain pan, install the drain pan prior to
installing the outdoor unit.
* Make sure there is at least 6 in. between the outdoor
unit and the ground.
Also, the direction of the tubing and electrical wiring
should be from the front of the outdoor unit.
Unit: in.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 20
Exhaust fan
Hot air
Heat
Outdoor
unit
source
Example of installation of 2 units
(When wall height is below 6 ft.)
* More than 4 in.
* More than 4 in.
CAUTION
NOTE
More than
2 in.
* More than 4 in.
* However, be sure to ensure a space of 1 ft. or more at
It is necessary to install an air-discharge chamber (field
supply) to direct exhaust from the fan horizontally if it is diffi-
cult to provide a minimum space of 7 ft. between the air-dis-
charge outlet and a nearby obstacle. (Fig. 2-8)
In regions with heavy snowfall,
the outdoor unit should be
provided with a solid, raised plat-
form and snow-proof ducting
(field supply). (Fig. 2-9)
2-4. Installing the Outdoor Unit in Heavy Snow
Areas
In locations where wind-blown snow can be a problem,
snow-proof ducting (field supply) should be fitted to the unit
and direct exposure to the wind should be avoided as much
as possible. (Fig. 2-10) The following problems may occur if
proper countermeasures are not taken:
The fan in the outdoor unit may stop running, causing the
unit to be damaged.
There may be no air flow.
The tubing may freeze and burst.
The condenser pressure may drop because of strong
wind, and the indoor unit may freeze.
2-5. Precautions When Installing in Heavy Snow
Areas
a) The platform should be higher than the maximum snow
depth. (Fig. 2-9)
b) The 2 anchoring feet of the outdoor unit should be used
for the platform, and the platform should be installed
beneath the air-intake side of the outdoor unit.
c) The platform foundation must be solid and the unit must
be secured with anchor bolts.
d) When installing on a roof subject to strong wind, coun-
termeasures must be taken to prevent the unit from
being overturned.
Fig. 2-8
Fig. 2-9
Fig. 2-10
21
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 21
CAUTION
DO
AVOID
Without snowproof ducting
(Without platform)
With snowproof ducting
(High platform)
Fall en snow
2-6. Dimensions of Wind Ducting
Reference diagram for air-discharge chamber (field supply)
2-unit installation
22
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 22
unit: in.
Ceiling panel
33-3/16
35-3/64
(Ceiling panel dimensions)
35-15/64
(Maximum bracket dimensions)
Air direction: Front directionAir direction: Right direction
35-3/64
2-11/6415/16
97-29/32
(Ceiling panel dimensions)
65-53/64(32-5/64)
35-3/64
(Ceiling panel dimensions)
2-11/6415/16
33-3/16
35-3/64
97-29/32
65-53/64(32-5/64)
35-15/64
(Ceiling panel dimensions)
Ceiling panel
(Maximum bracket dimensions)
Front viewFront viewRight side viewRight side view
Note: Can be installed so that the air direction is to the front, right, left or rear direction.
74-7/32
(2-unit installation: maximum dimensions)
5-25/32
33-3/16
31-7/64
33-3/16
31-7/64
(Installation hole pitch)
Top view
unit: in.
36-7/32
7-7/8
(Installation hole pitch)
2-11/6415/16
97-29/32
35-3/64
(Ceiling panel dimensions)
65-53/64(32-5/64)
Front viewRight side view
g
2-7. Dimensions of Snow Ducting
Reference diagram for snow-proof ducting (field supply)
2-unit installation
23
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 23
31-17/32
Air direction:
Front direction
Ceiling panel
53-55/64
31-17/32
31-17/32
31-17/32 (Air intake duct)
9-13/32
45-5/16
(Ceiling panel dimensions)
36-7/64
35-3/64
53-55/64
33-3/16 (Air outlet duct)
9-13/32
1 pc.
4 pc.
9-13/32
(Ceiling panel dimensions)
(32-5/64)
97-29/32
65-53/64
31-17/32
53-55/64
45-5/16
9-13/32
(Ceiling panel dimensions)
35-3/64
35-3/64
32-7/832-7/8
9-13/32
15/1615/16
36-7/64
9-13/32
Air direction:
Right direction
Ceiling panel
35-3/64
53-55/64
9-13/329-13/32
unit: in.
33-3/16 (Air outlet duct)
31-17/32 (Air intake duct)
Front view
Note: Can be installed so that the air direction is to the front, right, left or rear direction.
Installation hole pitch
31-17/32
74-1/64 (Ceiling panel dimensions)
35-3/64
31-7/64
7-7/8
223
3
2
11
3
2
Right side view
35-3/64
3-15/16
31-7/64
70-5/64
2
Ceiling panel dimensions
Top (Before installation of snowfall protection duct)
36-7/32
35-3/64
37-13/32
Installation hole pitchInstallation hole pitch
31-17/32
Ceiling panel
2
Front view
35-3/64
9-29/649-29/64
(Ceiling panel dimensions)
7/82-11/64
1
2
Right side view
unit: in.
45-5/16
36-7/64
92-53/64
Front view
97-29/32
65-53/64
ht side view
Ri
36-7/64
45-5/16
36-7/64
45-5/16
24
X
3. HOW TO INSTALL THE INDOOR UNIT
4-Way Air Discharge Semi-Concealed Type (X Type)
3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to check that the
unit is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using the method
shown in the diagrams (Figs. 3-1 and 3-2), by attaching them to
the ceiling support structure, or by any other method that ensures
that the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the ceiling.
Table 3-1
Unit: in. (mm)
(3) Determine the pitch of the suspension bolts using the supplied
full-scale installation diagram. The diagram and table (Fig. 3-3
and Table 3-2) show the relationship between the positions of the
suspension fitting, unit, and panel.
Table 3-2
Fig. 3-1
Fig. 3-2
Note: For DC Fan Tap Change Procedure
for 4-Way Cassette, see page 30.
Fig. 3-4
3-3. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the supplied
full-scale installation diagram. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
Full-scale installation diagram
(printed on top of container box)
C
B
A
1-3/8 (35)
15/32 – 43/64
(12 – 17)
X
Fig. 3-5
(2) The length of suspension bolts must be appropriate
for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32 in. as shown in
Fig. 3-5.
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as shown
in Fig. 3-5. Use 1 nut and 1 washer for the upper side,
and 2 nuts and 1 washer for the lower side, so that the
unit will not fall off the suspension lugs.
(4) Adjust so that the distance between the unit and the
ceiling bottom is 15/32 to 43/64 in. Tighten the nuts on
the upper side and lower side of the suspension lug.
(5) Remove the protective polyethylene used to protect
the fan parts during transport.
3-4. Installing the Drain Piping
(1) Prepare a standard hard PVC pipe (O.D. 1-1/4 in.) for
the drain and use the supplied drain hose and hose
band to prevent water leaks.
The PVC pipe must be purchased separately. The
unit’s transparent drain port allows you to check
drainage. (Fig. 3-6)
Insert the drain pipe until it contacts the socket, as
shown in Fig. 3-6, then secure it tightly with the
hose band.
Do not use adhesive when connecting the supplied
hose.
Reasons: 1. It may cause water to leak from the
connection. Since the connection is
slippery just after the adhesive has been
applied, the pipe easily slips off.
2. The pipe cannot be removed when
maintenance is needed.
Do not bend the supplied drain hose 90° or more.
The hose may slip off.
Align the hose bands with the end of the hose.
Tighten the hose band firmly. Please make sure
that the bead is not covered by the hose band.
(Fig. 3-6)
(2) After checking the drainage, wrap the supplied packing
and drain pipe insulator around the pipe. (Fig. 3-7)
Make sure the drain pipe has a downward gradient (1/100
or more) and that there are no water traps.
Tighten the hose clamps so
their locking nuts face upward.
(Fig. 3-6)
Do not install an air bleeder
as this may cause water to
spray from the drain pipe
outlet. (Fig. 3-8)
Fig. 3-6
Fig. 3-7
Fig. 3-8
25
Unit: in. (mm)
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 25
Suspension bolt
Nuts and washers
(use for upper and lower)
Double nut
Connection pipe
(drain port)
Hose band
Align the hose
band with the end
of the pipe
Suspension lug
15/32 – 43/64 (12 – 17)
Hard PVC
socket
Supplied
drain hose
VP-25
(Field supply)
Packing
(supplied)
Notch
Hard PVC pipe
VP-25
(Field supply)
PVC adhesive
CAUTION
CAUTION
NOTE
Bead
Drain insulator (supplied)
Air bleeder prohibited
CAUTION
26
X
Fig. 3-9
Fig. 3-10
Fig. 3-11
Fig. 3-12
In cases where it is necessary to raise the height
of the drain piping, the drain piping can be raised
to a maximum height of 33-15/32" above the
bottom surface of the ceiling. Under no
conditions attempt to raise it higher than
33-15/32" above the bottom surface of the ceiling.
Doing so will result in water leakage. (Fig. 3-9)
Do not install the pipe with an upward gradient
from the connection port. This will cause the
drain water to flow backward and leak when the
unit is not operating. (Fig. 3-10)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should
not be allowed to hang unsupported from its
connection to the unit. Fasten the pipe to a wall,
frame, or other support as close to the unit as
possible. (Fig. 3-11)
Provide insulation for any pipes that are run
indoors.
3-5. Checking the Drainage
After wiring and drain piping are completed, use the
following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth to
catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour about 0.3 gal of water into the drain pan
to check drainage. (Fig. 3-12)
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the water
flow through the transparent drain pipe and see if
there is any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover.
Be careful since the fan will
start when you short the pin
on the indoor control board.
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 26
CAUTION
11-3/16 in. or less (as short as possible)
33-15/32 in. or less
0 – 45°
* Length of supplied drain hose = 9-27/32 in.
Upward gradient prohibited
Support
pieces
Drainage check
CAUTION
Over 3-15/16 in.
Water (Approx. 0.3gal)
Plastic container
for water intake
Drain pan outlet
27
X
3-6. How to Install the Ceiling Panel
3-6-1. Before Installing the Ceiling Panel
Checking the unit position
(1) Check that the ceiling hole is within this range:
33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in.
(2) Use the full-scale installation diagram (from the
packaging) that was supplied with the unit to
determine the positioning of the unit on the ceiling
surface. If the positions of the ceiling surface and
unit do not match, air leakage, water leakage, flap
operation failure, or other problems may result.
Never place the panel face-down. Either hang
it vertically or place it on top of a projecting
object. Placing it face-down will damage the
surface.
Do not touch the flap or apply force to it.
(This may cause flap malfunction.)
must be within the range of 15/32 – 43/64 in.
If not within this range, malfunction or other trouble may result.
Fig. 3-13
Fig. 3-14
Fig. 3-15
Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 3-16, 3-17 and 3-18)
a) Remove the 2 screws on the latch of the air-intake
grille. (Fig. 3-16)
b) Slide the air-intake grille catches in the direction
shown by the arrows to open the grille.
(Fig. 3-17)
c) With the air-intake grille opened, remove the grille
hinge from the ceiling panel by sliding it in the direction shown by the arrow . (Fig. 3-18)
Removing the corner cover
a) Slide the corner cover to the direction shown
by the arrow to remove the corner cover.
(Fig. 3-18).
Fig. 3-17
Fig. 3-18
Fig. 3-16
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 27
A
Mainunit
CAUTION
1
A
Ceilingside
Ceiling opening
dimension
Flap
Latch
Screw
2
1
Corner cover
Air-intake grille hinge
Push
Air-intake grille
1
Corner cover
Ceiling panel
1
2
Ceiling panel
1
Strap
28
X
3-6-2. Installing the Ceiling Panel
After completing the wiring process, install the
supplied wiring cover before installing the panel.
It is not possible to install the wiring cover after
installing the panel.
The power must be turned ON in order to change the
flap angle. (Do not attempt to move the flap by hand.
Doing so may damage the flap.)
(1) Insert the temporary fasteners (stainless steel) on
the inside of the ceiling panel into the square holes
on the unit to temporarily fasten the ceiling panel in
place. (Fig. 3-20-1)
The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE
and DRAIN marks on the ceiling panel corner with
the correct positions on the unit.
To remove the ceiling panel, support the ceiling
panel while pressing the temporary fasteners toward
the outside. (Fig. 3-20-1)
(2) Align the panel installation holes and the unit screw
holes.
(3) Tighten the supplied washer head screws at the
4 panel installation locations so that the panel is
attached tightly to the unit. (Fig. 3-20-2)
(4) Check that the panel is attached tightly to the
ceiling.
At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between
the ceiling panel and the ceiling surface. (Fig. 3-21)
If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling. (Fig. 3-21)
Fig. 3-20-1
Fig. 3-20-2
g
Fig. 3-21
Fig. 3-22
If the screws are not sufficiently tight-
ened, trouble such as that shown in
the figure below may occur. Be sure
to tighten the screws securely.
If a gap remains between the ceiling
surface and the ceiling panel even
after the screws are tightened,
adjust the height of the unit again.
The height of the unit can be adjusted from the
ceiling panel corner hole, with the ceiling panel
attached, to an extent that does not affect the
unit levelness, the drain hose, or other elements.
Fig. 3-23
Fig. 3-19-1
Fig. 3-19-2
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 28
Inter-unit control wiring
Screw (supplied)
M4-8 or 5/32" – 5/16"
Push when
you remove
Celling panel
Wiring cover (supplied)Power supply outlet
Square hole in unit
Temporary
fastener
Temporary
fastener
Drain tubing corner
Refrigerant tubing
corner
After completing the
wiring process, install
the supplied wiring cover
before installing the panel.
It is not possible to install
the wiring cover after
installing the panel.
DRAIN mark
CAUTION
Air leakage
Air leakage from
ceilingsurface
Staining
Condensation, water leakage
Ceilin
surface
Adjust so that there are no gaps.
Washer head
screws
Mainunit
Do not allow
Ceiling panel
gaps
REF,PIPE
mark
Panel installation hole
(4 locations)
Insert a wrench
or other tool into
the corner cover
installation hole
and make fine
adjustments to
the unit nut.
29
X
3-6-3. Wiring the Ceiling Panel
(1) Open the cover of the electrical component box.
(2) Connect the 7P wiring connector (red) from the
ceiling panel to the connector in the unit electrical
component box.
If the connectors are not connected, the Auto flap will
not operate. Be sure to connect them securely.
Check that the wiring connector is not caught
between the electrical component box and the cover.
Check that the wiring connector is not caught
between the unit and the ceiling panel.
3-6-4. How to Attach the Corner & Air-Intake Grille
Attaching the corner cover and air-intake grille
A. Attaching the corner cover
(1) Check that the safety cord from the corner cover is
fastened to the ceiling panel pin, as shown in the
figure.
(2) Use the supplied screws to attach the corner cover
to the ceiling panel.
B. Attaching the air-intake grille
To install the air-intake grille, follow the steps for
Removing the grille in the reverse order. By rotating
the air-intake grille, it is possible to attach the grille
onto the ceiling panel from any of 4 directions.
Coordinate the directions of the air-intake grilles
when installing multiple units, and change the
directions according to customer requests.
When attaching the air-intake grille, be careful
that the flap lead wire does not become caught.
Be sure to attach the safety cord that prevents
the air-intake grille from dropping off to the
ceiling panel unit as shown in the figure at right.
With this ceiling panel, the directions of the air-intake
grille lattices when installing multiple units, and the
position of the label showing the company name on
the corner panel, can be changed according to
customer requests, as shown in the figure below.
However, the optional wireless receiver kit can only
be installed at the refrigerant-tubing corner of the
ceiling unit.
g
Fig. 3-24
Fig. 3-25
Fig. 3-26
Fig. 3-27
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 29
(Direction that the unit faces has been changed to
facilitate explanation.)
Electrical component
box cover
Screws
(3 locations)
Ceiling panel side
Ceiling panel
wiring connector
Locations of the air-intake grille catches at
the time the product isshipped.
* The grille can be installed with these
catches facing in any of 4 directions.
Unit drain hose side
Unit electrical component box
Mainsside
Clamp
* Pass the wiring connector through the clamp to fasten it in place,
asshown in the fi
Hole for ceiling panel hook
ure.
Pin
Place the corner cover so that the 3 tabs
fit into the holes in the ceiling panel.
Then fasten it in place with the supplied screws.
Hook that prevents
the grille from dropping
Unit refrigerant tube side
Optional wireless receiver kit
* Can only be installed
in this position.
Can be installed rotated 90˚
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.