Sanyo R410A User Manual

INSTALLATION INSTRUCTIONS
– Split System Air Conditioner –
COOL/DRY Model
In order to protect the environment, this air conditioner uses the new refrigerant R410A.
Contents
Page
IMPORTANT!
Please Read Before Starting.................................. 1
1. GENERAL.......................................................... 2
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Indoor Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Field Wiring 1-6. Additional Materials Required for Installation 1-7. Operating Range
2. INSTALLATION SITE SELECTION................... 3
2-1. Indoor Unit 2-2. Outdoor Unit 2-3. Air Discharge Chamber for Top Discharge 2-4. Wind Shield for “CL” Model
3. HOW TO INSTALL THE INDOOR UNIT ........... 6
3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Remove the Grille to Install the Indoor Unit 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Recommended Wire Length and Diameter 3-8. Wiring Instructions for Inter-unit Connections 3-9. Mounting 3-10. Drain Hose
4. REMOTE CONTROL UNIT INSTALLATION
POSITION ........................................................ 14
4-1. Mounting on a Wall
5. ADDRESS SWITCHES..................................... 15
6. HOW TO INSTALL THE OUTDOOR UNIT....... 16
6-1. Removing the Packaging Skid 6-2. Installing the Outdoor Unit 6-3. Tubing Direction
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Units
KS2462R C2462R
Power supply: 60Hz, single-phase, 208/230V
Units should be installed by a licensed contractor according to local code requirements.
7. ELECTRICAL WIRING ..................................... 17
7-1. General Precautions on Wiring 7-2. Recommended Wire Length and Wire
Diameter for Power Supply System 7-3. Wiring System Diagram 7-4. Examples of Incorrect Wiring
8. HOW TO PROCESS TUBING.......................... 19
8-1. Use of the Flaring Method 8-2. Flaring Procedure with a Flare Tool 8-3. Caution before Connecting Tubes Tightly 8-4. Precautions During Brazing 8-5. Indoor Unit Tubing 8-6. Connecting Tubing between Indoor and
Outdoor Units 8-7. Insulation of Refrigerant Tubing 8-8. Taping the Tubes 8-9. Finishing the Installation
9. AIR PURGING................................................... 22
10. TEST RUN......................................................... 25
10-1. Preparing for Test Run 10-2. Performing Test Run
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS
WHEN INSTALLING UNIT ................................ 28
11-1. Characteristics of New Refrigerant R410A 11-2. Checklist Before Installation 11-3. Tools Specifically for R410A 1 1-4. Charging Additional Refrigerant
Model Combinations
CL2462R
In Canada
SANYO FISHER COMPANY SANYO Canada Inc.
A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent 21605 Plummer Street Concord, Ontario
85464359328000 © SANYO 2002 Chatsworth, CA 91311 U.S.A. L4K 5C7, Canada
IMPORTANT!
WARNING
WARNING
CAUTION
CAUTION
Please Read Before Starting
This air conditioning system meets strict safety and operat­ing standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
When Installing…
…In a Ceiling, Wall or Floor
Make sure the ceiling/wall/floor is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PER­SONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub­ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
1
1. General
Parts Figure Qty Parts Figure Qty
12
1
1
Remote control unit
Parts Figure Qty
12
Tapping screw
Truss-head Phillips 5/32 × 5/8" (
4 × 16 mm)
2
1
AAA alkaline battery
Joint drain
Rawl plug
Remote control holder
NOTE
CAUTION
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Indoor Unit Table 1
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Pipe bending tool (spring bender)
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or A/C workshop.
For rear-left tubing, optional tube connec-
tion (C) (APR-EN46U1B) is necessary. See page 20. Also consult your nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub-
ing as detailed in Table 2. When cutting tubing, add approximately 12 to 16 in.
to each tube length to reduce vibration between the air conditioning units.
2
Table 2
Model
KS2462R
Narrow Tube
Outer Diameter
3/8"
Wide Tube
3/4"
2. Foamed polyethylene insulation for the speci­fied copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16".
1-5. Field Wiring
Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-6. Wiring Instructions for details.
Check local electrical codes and regulations before obtain­ing wire. Also, check any spec­ified instructions or limitations.
1-6. Additional Materials Required for Installation
6 in. min.
6 in. min.
6 in. min.
Front View
INDOOR UNIT
Tubing length (L)
OUTDOOR UNIT
Elevation difference (H)
Indoor unit
Floor level
Wall
Minimum height from floor level
5 ft.
CAUTION
Drain hose
Indoor unit
Outside drainage
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
1-7. Operating Range
Temperature Indoor Air Intake Outdoor Air Intake
Cooling
Maximum 95°F DB, 71°F WB 115°F DB
Minimum 67°F DB, 57°F WB 67°F DB, (0°F DB)*
*CL

2. Installation Site Selection
2-1. Indoor Unit
To prevent abnormal heat genera-
WARNING
AVOID:
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of the room can be uniformly cooled. (High on a wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation difference (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
tion and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.
Fig. 1
Models
Fig. 2
Fig. 3a
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5 ft. from floor level.
Fig. 3b
Table 3
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
C2462R, CL2462R 23 132 50 0.43
*
If total tubing length becomes 23 to 132 ft. (max.), additional refrigerant (R410A) charge of 0.43 oz./ft. is required. No additional charge of compressor oil is necessary.
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
(ft.) (ft.) (ft.) (oz./ft.)
3
*
2-2. Outdoor Unit
Outdoor unit
Hot air
Heat source
Exhaust fan
Min. 1 in.
Min. 1 in.
Min. 2 ft.
Min. 4 inches
Min. 7 ft.
Obstacle above
Ground
Air dis­charge
Air in
Air in
Air discharge
Concrete block 4 in. × 1 ft. 4 in. beams or equal
Anchor bolts (4 pieces)
Min. 6 in.
Air discharge
AVOID:
heat sources, exhaust fans, etc. (Fig. 4a)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 4b)
provide a solid base a minimum of 6 inches above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 4c)
use lug bolts or equal to bolt down unit, to reduce vibration and noise.
2-3. Air Discharge Chamber for Top Discharge
Fig. 4a
Install the air-discharge chamber in the field when:
it is difficult to keep a space of minimum 2 ft. between the air-discharge outlet and an obstacle.
the air-discharge outlet faces a sidewalk and dis­charged hot air may disturb people passing by. Refer to Fig. 5a.
Fig. 4b
Fig. 4c
Fig. 5a
4
2-4. Wind Shield for CL Model
IMPORTANT
Wind shield (air discharge side)
Front
3 - φ1-9/16" hole
6 - φ15/64" hole
9-27/32"21-5/8"15/16"
5-3/16"
22-7/16"1/2"
23-15/32"
21-13/16"
5-5/32"9-27/32"9-27/32"1-1/16"
21-13/16"
It is recommended to use wind shields for CL model (Fig. 5b). CL model is designed to use in low outdoor temperature conditions.
General
When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air tempera­ture in winter), a suitable wind shield must be installed on the outdoor unit.
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
For outer dimensions of the wind shield, see Fig. 5c.
Fig. 5b
Recommended outer dimensions of wind shield (field supply)
CL2462R
Fig. 5c
5
Indoor side
Outdoor side
Set screws for transportation only
Right-rear tubing (recommended)
Right tubing
Left-rear tubling
Center of left-rear tubing hole
Center of right-rear tubing hole
NOTE
3. How to Install the Indoor Unit
NOTE
CAUTION
PVC pipe (locally purchased)
Cut at slight angle
3-1. Remove the Rear Panel from the Unit
Remove and discard the set screws and take off the rear panel. (Fig. 6)
Tubing can be extended in 3 directions as shown in Fig. 7a. Select the direction you need providing the shortest run to the outside unit.
3-2. Make a Hole
(1) Remove the rear panel from the indoor unit and
place it on the wall at the location selected. Make sure the unit is horizontal, using a carpenters level or tape measure to measure down from the ceiling.
(2) Determine which side of the unit you should make
the hole. (Fig. 7b)
(3) Before making a hole, check carefully that no studs
or pipes are directly run behind the spot to be cut.
Fig. 6
Fig. 7a
In case of left-rear or right-rear tubing
Also avoid areas where electri­cal wiring or conduits are located.
The above precautions are also applicable if tubing goes through the wall in any other location.
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and Fig. 8.
Table 4
Hole Dia. (inch)
3-3/16"
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 1/4" shorter than the thickness of the wall. (Fig. 9)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert in the wall. (Fig. 10)
Fig. 7b
Hole should be made at a slight downward slant to the outdoor side.
Fig. 8
Fig. 9
INSIDE
Wall
Plastic cover
(Field supply)
OUTSIDE
PVC pipe
Slight angle
Fig. 10
6
3-3. Install the Rear Panel on the Wall
3/16
"
dia. hole
1-3/16
"
or more
Rawl plug (Field supply)
Air intake grille
Grille
Air intake grille
Be sure to confirm that the wall is strong enough to sus­pend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 10 screws
provided. (Fig. 11) If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use toggle bolts to go through the holes on the panel
or drill 3/16"dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Double check with a ruler or carpenters level that
the panel is level. This is important to install the unit properly. (Fig. 12)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
Fig. 11
Fig. 12
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 13)
3-4. Remove the Grille to Install the Indoor Unit
Basically, these models can be installed and wired with­out removing the grille. If access to any internal part is
needed, follow the steps as given below: How to remove the grille
(1) Set the 2 flaps in the horizontal position. (2) Unscrew the 3 screws. (Fig. 14a) (3) Remove the grille.
(a) Hold both corners of the air intake grille, then pull
out and up to open. (Fig. 14b)
(b) Use a standard screwdriver to push up the 3 tabs
to remove the grille. (Fig. 14b)
(c) Pull the lower part of the grille toward you to
remove. (Fig. 14a)
Fig. 13
Fig. 14a
Fig. 14b
7
How to replace the grille
Frame
Right tubing outlet
Tab
Mounting slot
(1) Close the flaps. (2) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 15a) Insert the tabs in the slots and push the lower part of the grille back into position.
(3) Press at each of the 5 tabs to completely close the
grille. Make sure that the grille and frame are firmly fitted together. (Fig. 15b)
3-5. Shape the Indoor Side Tubing
1) Arrangement of tubing by directions
a) Right tubing
Fig. 15a
The corner of the right frame needs to be cut by a hacksaw or the like. (Fig. 16)
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be cut.
2) To mount the indoor unit on the rear panel:
Hang the 3 mounting slots of the unit on the upper tabs of the rear panel. (Fig. 17)
3-6. Wiring Instructions General precautions on wiring
1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line.
3) To prevent possible hazard due to insulation failure, the unit must be grounded.
Fig. 15b
Fig. 16
Fig. 17
4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
8
3-7. Recommended Wire Length and Diameter
2
4
2
4
11
INDOOR
UNIT
Terminal
OUTDOOR
UNIT
(B)
Terminal
(A)
L2
L1
G
G
G
230V/208V
230V/208V
230V/208V
(Inter-unit) power line
Grounding line
Grounding line
Power supply
Single-phase 230V/208V 60HZ
Disconnect switch
Field supply
WARNING
CAUTION
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regu­lations when carrying out the installation. Table 5 lists recommended wire lengths and diameters for power supply systems. Refer to the wiring system diagram (Fig. 18) for the meaning of “A” and “B” in Table 5.
Table 5
AWG
Model
C2462R,CL2462R 64 (Max.) 132 (Max.) 35A
(A) Power Supply
Wiring Length (ft.)
(#12)
(B) Inter-Unit
Power Line
(#14)
# …AWG (American Wire Gauge)
Fuse or Circuit
Capacity
WARNING
Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
Each wire must be firmly connected.
No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part.
To avoid the risk of electric shock, each air conditioner unit must be grounded.
Be sure to connect the power supply line to the outdoor unit as shown in the wiring dia­gram. The indoor unit draws its power from the outdoor unit.
WIRING SYSTEM DIAGRAM
Fig. 18
9
Loading...
+ 22 hidden pages