Sanyo R410A User Manual

Page 1
INSTALLATION INSTRUCTIONS
– Split System Air Conditioner –
COOL/DRY Model
In order to protect the environment, this air conditioner uses the new refrigerant R410A.
Contents
Page
IMPORTANT!
Please Read Before Starting.................................. 1
1. GENERAL.......................................................... 2
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Indoor Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Field Wiring 1-6. Additional Materials Required for Installation 1-7. Operating Range
2. INSTALLATION SITE SELECTION................... 3
2-1. Indoor Unit 2-2. Outdoor Unit 2-3. Air Discharge Chamber for Top Discharge 2-4. Wind Shield for “CL” Model
3. HOW TO INSTALL THE INDOOR UNIT ........... 6
3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Remove the Grille to Install the Indoor Unit 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Recommended Wire Length and Diameter 3-8. Wiring Instructions for Inter-unit Connections 3-9. Mounting 3-10. Drain Hose
4. REMOTE CONTROL UNIT INSTALLATION
POSITION ........................................................ 14
4-1. Mounting on a Wall
5. ADDRESS SWITCHES..................................... 15
6. HOW TO INSTALL THE OUTDOOR UNIT....... 16
6-1. Removing the Packaging Skid 6-2. Installing the Outdoor Unit 6-3. Tubing Direction
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Units
KS2462R C2462R
Power supply: 60Hz, single-phase, 208/230V
Units should be installed by a licensed contractor according to local code requirements.
7. ELECTRICAL WIRING ..................................... 17
7-1. General Precautions on Wiring 7-2. Recommended Wire Length and Wire
Diameter for Power Supply System 7-3. Wiring System Diagram 7-4. Examples of Incorrect Wiring
8. HOW TO PROCESS TUBING.......................... 19
8-1. Use of the Flaring Method 8-2. Flaring Procedure with a Flare Tool 8-3. Caution before Connecting Tubes Tightly 8-4. Precautions During Brazing 8-5. Indoor Unit Tubing 8-6. Connecting Tubing between Indoor and
Outdoor Units 8-7. Insulation of Refrigerant Tubing 8-8. Taping the Tubes 8-9. Finishing the Installation
9. AIR PURGING................................................... 22
10. TEST RUN......................................................... 25
10-1. Preparing for Test Run 10-2. Performing Test Run
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS
WHEN INSTALLING UNIT ................................ 28
11-1. Characteristics of New Refrigerant R410A 11-2. Checklist Before Installation 11-3. Tools Specifically for R410A 1 1-4. Charging Additional Refrigerant
Model Combinations
CL2462R
In Canada
SANYO FISHER COMPANY SANYO Canada Inc.
A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent 21605 Plummer Street Concord, Ontario
85464359328000 © SANYO 2002 Chatsworth, CA 91311 U.S.A. L4K 5C7, Canada
Page 2
IMPORTANT!
WARNING
WARNING
CAUTION
CAUTION
Please Read Before Starting
This air conditioning system meets strict safety and operat­ing standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
When Installing…
…In a Ceiling, Wall or Floor
Make sure the ceiling/wall/floor is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PER­SONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub­ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
1
Page 3
1. General
Parts Figure Qty Parts Figure Qty
12
1
1
Remote control unit
Parts Figure Qty
12
Tapping screw
Truss-head Phillips 5/32 × 5/8" (
4 × 16 mm)
2
1
AAA alkaline battery
Joint drain
Rawl plug
Remote control holder
NOTE
CAUTION
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Indoor Unit Table 1
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Pipe bending tool (spring bender)
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or A/C workshop.
For rear-left tubing, optional tube connec-
tion (C) (APR-EN46U1B) is necessary. See page 20. Also consult your nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub-
ing as detailed in Table 2. When cutting tubing, add approximately 12 to 16 in.
to each tube length to reduce vibration between the air conditioning units.
2
Table 2
Model
KS2462R
Narrow Tube
Outer Diameter
3/8"
Wide Tube
3/4"
2. Foamed polyethylene insulation for the speci­fied copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16".
1-5. Field Wiring
Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-6. Wiring Instructions for details.
Check local electrical codes and regulations before obtain­ing wire. Also, check any spec­ified instructions or limitations.
Page 4
1-6. Additional Materials Required for Installation
6 in. min.
6 in. min.
6 in. min.
Front View
INDOOR UNIT
Tubing length (L)
OUTDOOR UNIT
Elevation difference (H)
Indoor unit
Floor level
Wall
Minimum height from floor level
5 ft.
CAUTION
Drain hose
Indoor unit
Outside drainage
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
1-7. Operating Range
Temperature Indoor Air Intake Outdoor Air Intake
Cooling
Maximum 95°F DB, 71°F WB 115°F DB
Minimum 67°F DB, 57°F WB 67°F DB, (0°F DB)*
*CL

2. Installation Site Selection
2-1. Indoor Unit
To prevent abnormal heat genera-
WARNING
AVOID:
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of the room can be uniformly cooled. (High on a wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation difference (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
tion and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.
Fig. 1
Models
Fig. 2
Fig. 3a
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5 ft. from floor level.
Fig. 3b
Table 3
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
C2462R, CL2462R 23 132 50 0.43
*
If total tubing length becomes 23 to 132 ft. (max.), additional refrigerant (R410A) charge of 0.43 oz./ft. is required. No additional charge of compressor oil is necessary.
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
(ft.) (ft.) (ft.) (oz./ft.)
3
*
Page 5
2-2. Outdoor Unit
Outdoor unit
Hot air
Heat source
Exhaust fan
Min. 1 in.
Min. 1 in.
Min. 2 ft.
Min. 4 inches
Min. 7 ft.
Obstacle above
Ground
Air dis­charge
Air in
Air in
Air discharge
Concrete block 4 in. × 1 ft. 4 in. beams or equal
Anchor bolts (4 pieces)
Min. 6 in.
Air discharge
AVOID:
heat sources, exhaust fans, etc. (Fig. 4a)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 4b)
provide a solid base a minimum of 6 inches above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 4c)
use lug bolts or equal to bolt down unit, to reduce vibration and noise.
2-3. Air Discharge Chamber for Top Discharge
Fig. 4a
Install the air-discharge chamber in the field when:
it is difficult to keep a space of minimum 2 ft. between the air-discharge outlet and an obstacle.
the air-discharge outlet faces a sidewalk and dis­charged hot air may disturb people passing by. Refer to Fig. 5a.
Fig. 4b
Fig. 4c
Fig. 5a
4
Page 6
2-4. Wind Shield for CL Model
IMPORTANT
Wind shield (air discharge side)
Front
3 - φ1-9/16" hole
6 - φ15/64" hole
9-27/32"21-5/8"15/16"
5-3/16"
22-7/16"1/2"
23-15/32"
21-13/16"
5-5/32"9-27/32"9-27/32"1-1/16"
21-13/16"
It is recommended to use wind shields for CL model (Fig. 5b). CL model is designed to use in low outdoor temperature conditions.
General
When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air tempera­ture in winter), a suitable wind shield must be installed on the outdoor unit.
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
For outer dimensions of the wind shield, see Fig. 5c.
Fig. 5b
Recommended outer dimensions of wind shield (field supply)
CL2462R
Fig. 5c
5
Page 7
Indoor side
Outdoor side
Set screws for transportation only
Right-rear tubing (recommended)
Right tubing
Left-rear tubling
Center of left-rear tubing hole
Center of right-rear tubing hole
NOTE
3. How to Install the Indoor Unit
NOTE
CAUTION
PVC pipe (locally purchased)
Cut at slight angle
3-1. Remove the Rear Panel from the Unit
Remove and discard the set screws and take off the rear panel. (Fig. 6)
Tubing can be extended in 3 directions as shown in Fig. 7a. Select the direction you need providing the shortest run to the outside unit.
3-2. Make a Hole
(1) Remove the rear panel from the indoor unit and
place it on the wall at the location selected. Make sure the unit is horizontal, using a carpenters level or tape measure to measure down from the ceiling.
(2) Determine which side of the unit you should make
the hole. (Fig. 7b)
(3) Before making a hole, check carefully that no studs
or pipes are directly run behind the spot to be cut.
Fig. 6
Fig. 7a
In case of left-rear or right-rear tubing
Also avoid areas where electri­cal wiring or conduits are located.
The above precautions are also applicable if tubing goes through the wall in any other location.
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and Fig. 8.
Table 4
Hole Dia. (inch)
3-3/16"
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 1/4" shorter than the thickness of the wall. (Fig. 9)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert in the wall. (Fig. 10)
Fig. 7b
Hole should be made at a slight downward slant to the outdoor side.
Fig. 8
Fig. 9
INSIDE
Wall
Plastic cover
(Field supply)
OUTSIDE
PVC pipe
Slight angle
Fig. 10
6
Page 8
3-3. Install the Rear Panel on the Wall
3/16
"
dia. hole
1-3/16
"
or more
Rawl plug (Field supply)
Air intake grille
Grille
Air intake grille
Be sure to confirm that the wall is strong enough to sus­pend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 10 screws
provided. (Fig. 11) If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use toggle bolts to go through the holes on the panel
or drill 3/16"dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Double check with a ruler or carpenters level that
the panel is level. This is important to install the unit properly. (Fig. 12)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
Fig. 11
Fig. 12
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 13)
3-4. Remove the Grille to Install the Indoor Unit
Basically, these models can be installed and wired with­out removing the grille. If access to any internal part is
needed, follow the steps as given below: How to remove the grille
(1) Set the 2 flaps in the horizontal position. (2) Unscrew the 3 screws. (Fig. 14a) (3) Remove the grille.
(a) Hold both corners of the air intake grille, then pull
out and up to open. (Fig. 14b)
(b) Use a standard screwdriver to push up the 3 tabs
to remove the grille. (Fig. 14b)
(c) Pull the lower part of the grille toward you to
remove. (Fig. 14a)
Fig. 13
Fig. 14a
Fig. 14b
7
Page 9
How to replace the grille
Frame
Right tubing outlet
Tab
Mounting slot
(1) Close the flaps. (2) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 15a) Insert the tabs in the slots and push the lower part of the grille back into position.
(3) Press at each of the 5 tabs to completely close the
grille. Make sure that the grille and frame are firmly fitted together. (Fig. 15b)
3-5. Shape the Indoor Side Tubing
1) Arrangement of tubing by directions
a) Right tubing
Fig. 15a
The corner of the right frame needs to be cut by a hacksaw or the like. (Fig. 16)
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be cut.
2) To mount the indoor unit on the rear panel:
Hang the 3 mounting slots of the unit on the upper tabs of the rear panel. (Fig. 17)
3-6. Wiring Instructions General precautions on wiring
1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line.
3) To prevent possible hazard due to insulation failure, the unit must be grounded.
Fig. 15b
Fig. 16
Fig. 17
4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
8
Page 10
3-7. Recommended Wire Length and Diameter
2
4
2
4
11
INDOOR
UNIT
Terminal
OUTDOOR
UNIT
(B)
Terminal
(A)
L2
L1
G
G
G
230V/208V
230V/208V
230V/208V
(Inter-unit) power line
Grounding line
Grounding line
Power supply
Single-phase 230V/208V 60HZ
Disconnect switch
Field supply
WARNING
CAUTION
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regu­lations when carrying out the installation. Table 5 lists recommended wire lengths and diameters for power supply systems. Refer to the wiring system diagram (Fig. 18) for the meaning of “A” and “B” in Table 5.
Table 5
AWG
Model
C2462R,CL2462R 64 (Max.) 132 (Max.) 35A
(A) Power Supply
Wiring Length (ft.)
(#12)
(B) Inter-Unit
Power Line
(#14)
# …AWG (American Wire Gauge)
Fuse or Circuit
Capacity
WARNING
Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
Each wire must be firmly connected.
No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part.
To avoid the risk of electric shock, each air conditioner unit must be grounded.
Be sure to connect the power supply line to the outdoor unit as shown in the wiring dia­gram. The indoor unit draws its power from the outdoor unit.
WIRING SYSTEM DIAGRAM
Fig. 18
9
Page 11
3-8. Wiring Instructions for Inter-unit Connections
Rear panel
Wiring
Wall
10 in.
Plastic cover
Terminal plate
Cover plate
Lock nut
Top of conduit connector
Inter-unit control line
wiring Earth plate
(1) Insert the inter-unit wiring (according to local codes)
into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 10 inches to extend from the wall face. (Fig. 19)
(2) Route the inter-unit wiring from the back of the
indoor unit and pull it toward the front for connection. (Figs. 20a and 20b)
(3) Connect the inter-unit wiring to the corresponding
terminals on the terminal plate (Figs. 20a and 20b) while referring to the wiring diagram.
(4) Be sure to secure the wiring with the provided
clamp.
How to remove the cover plate
To access the terminal plate inside the indoor unit, follow these steps.
(1) Using a Phillips screwdriver, remove the screw on
the cover plate. (Figs. 20a and 20b)
(2) Remove the cover plate.
Fig. 19
Fig. 20a
Fig. 20b
10
Page 12
NOTE
Solid wire
Loop
Insulation
Strip 1 inch
Stranded wire
Ring connector
Strip 3/8 inch
Screw with special washer
Ring connector
Terminal plate
Wire
Screw with special washer
Ring connector
Wire
WARNING
Loose wiring may cause the
Twist wire ends
terminal to overheat or result in unit malfunction. A fire haz­ard may also exist. Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow the instructions How to connect wiring to the terminal and fasten the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
For solid core wiring (or F-cable)
Fig. 21a
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 1 in. (Fig. 21a)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi­nal screw using a screwdriver.
For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip
the insulation to expose the stranded wiring about 3/8 in. and tightly twist the wire ends. (Figs. 21b and 21c)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connector. (Fig. 21b)
(4) Place the ring connector wire, and replace and tight-
en the removed terminal screw using a screwdriver. (Fig. 22)
Fig. 21b
Fig. 21c
Fig. 22
Being careful not to cut the wire, strip off the plastic insu­lation using a wire cutter or pliers. (Fig. 23)
Fig. 23
11
Page 13
3-9. Mounting
Cover
Refrigerant tubing
Drain hose
Inter-unit wiring
Pipe bending tool
a
b
b / a = 0.7 or more
Insulation (Field supply)
Refrigerant tubing
Drain hose
Conduit
Inter-unit wiring
CAUTION
CAUTION
Right-side tubing
(1) Shape the refrigerant tubing so that it can easily go
into the wall hole. (Fig. 24)
If using a stepladder, be careful to keep your balance and not fall off. To prevent the unit from damage and avoid per­sonal injury, ask for someone’s help when feeding the tubing through the hole because the unit is heavy and difficult to hold in place.
(2) Push the wiring, refrigerant tubing, and drain hose
through the hole in the wall. Adjust the indoor unit so it is securely seated on the rear panel.
(3) Carefully bend the tubing (if necessary) to run along
the wall in the direction of the outdoor unit and then tape as far as the fittings.
Fig. 24
Fig. 25
The air conditioners perfor­mance will be deteriorated if a tube is crushed. To prevent crushing of tubing, avoid sharp bends. Use a pipe bending tool to bend tubes. (Fig. 25)
(4) Connect the refrigerant tubing to the outdoor unit.
(After performing a leak test on the connecting part, insulate it with tubing insulation. (Fig. 26)) Also, refer to Section 4-3. Connecting Tubing between Indoor and Outdoor Units.
(5) Assemble the refrigerant tubing, drain hose, and
inter-unit wiring as shown in Fig. 27.
Fig. 26
Fig. 27
12
Page 14
3-10. Drain Hose
Slant
Drain hose
Indoor unit
Condensation
Insulation material (locally purchased) must be used.
a) The drain hose should be slanted downward to the
outdoors. (Fig. 28) b) Never form a trap in the course of the hose. c) If the drain hose will run in the room, insulate the
hose with insulation*so that chilled condensation
will not damage furniture or floors. (Fig. 29)
*
Foamed polyethylene or its equivalent is recom­mended.
Fig. 28
WARNING
Do not supply power to the unit or operate it until all tub­ing and wiring to the outside unit are completed.
Risk of Electric Shock
Fig. 29
13
Page 15
4. Remote Control Unit Installation Position
Truss-head tapping screw 5/32 × 5/8" (4 × 16 mm supplied)
Remote control unit holder
Holder
Holder
Truss-head tapping screw 5/32 × 5/8" (4 × 16 mm supplied)
The remote control unit can be operated from either a non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places:
In direct sunlight
Behind a curtain or other place where it is covered
More than 26 ft. (8 m) away from the air conditioner
In the path of the air conditioners airstream
Where it may become extremely hot or cold
Where it may be subject to electrical or magnetic interference
4-1. Mounting on a Wall
1) Confirm the indoor unit beeps when the ON/OFF button is pressed at the wall location where the remote control unit is to be attached, then attach the holder to the wall. (Fig. 30)
2) When taking out the remote control unit, grasp and pull it from the holder.
When using the remote control unit
Point the transmission portion of the remote con­trol unit at the receiver area of the indoor unit to control the air conditioner.
Do not place objects that may block the transmit­ted signals between the receiver and the remote control unit.
When mounting the remote control unit to prevent theft or loss
1) Mount the holder to the wall with one of the screws (using only the hole in the top of the holder) (Fig. 31).
2) Remove the cover of the remote control unit and take out the batteries. Next, place the remote control unit in the holder.
3) Fasten both the remote control unit and holder to the wall with the remaining screw (using the hole in the bottom of the holder).
4) Install the batteries in the remote control unit and close the cover.
Fig. 30
Fig. 31
14
Page 16
5. Address Switches
JP11
Change the address switch to prevent mixing of sig­nals from remote control units when 2 Sanyo air con­ditioners are installed next to each other. Normally, the address switch is set to A. To change the address to B, break tab Aof the remote control address switch and cut the jumper cable (JP11) on the indoor unit board. (Figs. 32 and 33) If you need more information, contact your air condi­tioning system dealer.
Normally, the tabs on the remote control unit should not be broken.
Address switch (tab A)
NOTE
The illustration above pictures the remote control unit after the cover has been lowered and removed.
Fig. 32
Fig. 33
15
Page 17
6. How to Install the Outdoor Unit
Access panel
Front
Tubing outlets
Down
Right
Rear
Inter-unit wiring outlets
Power supply wiring outlets
Power supply line
Inter-unit power line
Power supply line Inter unit power line
1/2"
1/2"
6-1. Removing the Packing Skid
Remove the packing skid from the bottom. (Fig. 34) Place the unit on a level concrete pad, block or equal
and anchor.
Compressor
Refer to Section 2. Installation Site Selection.
6-2. Installing the Outdoor Unit
(1) Install blocks or a solid platform under the outdoor
unit which provides a minimum height of 6 in. from ground level. (Fig. 35)
(2) The outdoor unit must be bolted down tightly to the
blocks or platform with 4 anchor bolts.
6-3. Tubing Direction
Tubing can be extended in 4 different directions as shown in Fig. 36.
Service valves are housed inside the unit. To access them, remove the access panel by removing the 3 attaching screws, then slide the panel downward and pull it toward you. If either rear, right or front tubing is needed, punch out the knockout holes with a hammer and punch or similar tool.
Packing
skid
Fig. 34
13-3/8
6-11/16 26 4-21/64
Anchor bolts (not supplied)
1-3/16 1-3/16
15-3/4
14-31/32
After punching out the knockout holes, mount plastic protectors on the tubing outlets. There accessories are packed inside the unit and can be accessed through the access panel.
Use tube benders to extend refrigerant tubing to the outside.
Fig. 36
Height : Min: 6 in.
Unit: inch
Fig. 35
16
Page 18
7. Electrical Wiring
NOTE
7-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provid­ed in the exclusive line.
(3) To prevent possible hazards from insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done in accordance
with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused
by electrical noise, care must be taken when wiring as follows:
The inter-unit control wiring and the remote con­trol wiring (option) should be wired apart from the inter-unit power wiring.
It is recommended that shielded wires or twisted­pair wires be used for the remote control and the inter-unit control wiring if the air conditioner is installed where it is exposed to the influence of electrical and/or electro-magnetic noise.
7-2. Recommended Wire Length and Wire Diameter for Power Supply System
(B)
*1
Inter-unit
Wiring
Models
*1
Power Supply
(A)
AGW #14
C2462R, CL2462R 64 ft. (AWG #12) 35 A
132 ft.
Time Delay Fuse or Circuit Capacity
*1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of “A” and B.
AWG = American Wire Gauge
Disconnect SW (Field supply)
To access the electrical component box, open the air intake grille and remove the electrical component box cover.
7-3. Wiring System Diagram
Outdoor Unit: “C”, CL models Single-phase
Indoor Unit Outdoor Unit
(B)
1 2
G
Ground
4
60 Hz, 208/230 V
L1
1 2 G 4
(A)
17
L2
G
Ground
Page 19
CAUTION
7-4. Examples of Incorrect Wiring
Problem 1
Short circuit will occur after approx. 3 minutes.
Problem 2
Air conditioner will not operate.
Problem 3
Compressor will not start; only indoor unit will operate.
1
4
2
G G
Indoor unit Outdoor unit
1
4
2
G G
1
4
2
Indoor unit Outdoor unit
1
4
2
G G
1
4
2
Indoor unit Outdoor unit
1 2
4
G G
1
4
2
Indoor unit Outdoor unit
1 2
4
G G
1
4
2
Indoor unit Outdoor unit
1 2
4
The following are examples of improper wiring that result in system misoperation. You should confirm that you have wired the units correctly before beginning the Test Run described on page 25.
18
Page 20
Deburring
Before
After
Reamer
Copper tubing
Flare tool
Flare nut
Copper tubing
Apply refrigerant lubricant here and here
8. How to Process Tubing
NOTE
NOTE
0 to
0.5 mm
(See 11. REFRIGERANT R410A: SPECIAL PRECAUTIONS)
The narrow tubing side is connected by a flare nut, and the wide tubing side is connected by brazing.
8-1. Use of the Flaring Method
Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
8-2. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a tube
cutter. It is recommended to cut approx. 12 to 16 in. longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a tube
reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 37)
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 38a)
Fig. 37
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
tool.*(Fig. 38b) (*Use RIGID
®
or equivalent.)
(5) Use the special flare tool for R410A for making a flare.
If the conventional flare tool (for R22) is used, the flared portion of the tubing should protrude 1.0 to
1.5 mm. (Fig. 38c)
A good flare should have the following characteristics:
inside surface is glossy and smooth.
edge is smooth.
tapered sides are of uniform length.
8-3. Caution before Connecting Tubes Tightly
(1) Apply a sealing cap or water-proof tape to prevent dust
or water from entering the tubes before they are used.
(2) Apply refrigerant lubricant to the matching surfaces
of the flare and union before connecting them together. This helps to reduce gas leaks. (Fig. 39a)
When R410A flare tool is used
Fig. 38a
Fig. 38b
When conventional flare tool is used (clutching method)
1.0 1.5 mm
Flare the tubing by 1.0 to 1.5 mm.
Fig. 38c
Fig. 39a
19
Page 21
(3) For proper connection, align the union tube and flare tube
B'
B
A'
2. Mount the rear panel
A
Rear View
Wide tube
Optional tube connection (C) 1/2" (Optional part)
1. Cut hole in wall
3. Cut
4. Flare
5. Connect
4-1/8"
4. Flare wide tube
3. Cut wide tube
5. Connect tube assy
Optional tube connection (C) 1/2" (Optional part)
Narrow tube 3/8"
6. Connect wide tube 3/4"
7. Connect
narrow tube 3/8"
NOTE
Flare nut
Union
with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 39b)
Adjust the shape of the narrow and wide tubes using a tube bender at the installation site and connect them to the each tubing side valve using a flare nut.
8-4. Precautions During Brazing
Replace air inside the tube with nitrogen gas to prevent cop­per oxide film from forming during the brazing process.
Do not allow the tubing to get too hot during the brazing process. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool between brazings.
8-5. Indoor Unit Tubing
Rear-left tubing
For rear-left tubing, optional tube connection (C) (APR­EN46U1B) is necessary. Please consult your nearest
sales outlet or A/C workshop.
Fig. 39b
1. Make a 3-3/16" hole in the wall, centered on the crossing point between the triangle marks (A and B) on the rear panel. (Fig. 40a)
2. Set the rear panel at its original position where it was installed with screws.
3. Cut the wide tube at a point 4-1/8" from the triangle mark.
4. Remove the 1/2" flare nut from the optional tube connec­tion (C), place it on the cut wide tube, and then flare the wide tube. (Fig. 40b)
5. Connect the optional tube connection (C) to the wide tube.
6. Connect the 3/4" tube to the connected optional tube con­nection.
7. Connect the 3/8" tube to the narrow tube.
8. Cover the narrow and wide tubes with insulation material.
Rear-right tubing
9. Make a 3-3/16" hole in the wall, centered on the crossing point between the triangle marks (A' and B') on the rear panel. (Fig. 40a)
10. Connect the 3/4" tube to the wide tube.
11. Connect the 3/8" tube to the narrow tube.
12. Cover the narrow and wide tubes with insulation material.
Fig. 40a
Fig. 40b
20
Page 22
Apply putty here
Tubing
Clamp
Insulated tubes
Insulation
Min. 5/16"
Thickness: min. 5/16"
8-6. Connecting Tubing between Indoor and
NOTE
IMPORTANT
Indoor unit
Outdoor unit
Spanner
Torque wrench
Insulation (Field supply)
Outdoor Units
a) Tightly connect the indoor side refrigerant tubing
extended from the wall with the outdoor side tubing. (Fig. 41)
b) To fasten the flare nuts, apply specified torque as:
Table 6
Tube Dia. Tightening Torque
3/8" Approx. 300 – 340 lbs..in (35 – 40 N.m) 3/4" Approx. 870 – 1,040 lbs..in (100 – 120 N.m)
8-7. Insulation of Refrigerant Tubing
(For C2462R and CL2462R)
Fig. 41
To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insu­lation should be a minimum 5/16" (Fig. 43)
8-8. Taping the Tubes
CAUTION
After a tube has been insulated, never try to bend it into a nar­row curve, as this may cause the tube to break or crack.
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the out-
door unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 44)
(3) Clamp the tubing bundle to the wall, using 1 clamp
approx. every 4 ft.
Fig. 42
Fig. 43
Fig. 44
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also be sure the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.
8-9. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. Fig. 45 shows refrigerant tubing taped separately from the drain hose.
Fig. 45
21
Page 23
9. Air Purging
CAUTION
Manifold valve
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.
pressure in the system rises
operating current rises
cooling (or heating) efficiency drops
moisture in the air may freeze and block capillary tub­ing
water may lead to corrosion of parts in the refrigerant system
Air Purging with a Vacuum Pump (for Test Run)
Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been proper­ly connected and all wiring for the test run has been completed. Remove the valve caps from both the wide and narrow service valves on the outdoor unit. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.
Leak test
(1) With the service valves on the outdoor unit closed,
remove the 1/4". flare nut and its bonnet on the wide tube service valve. (Save them for reuse.)
Pressure gauge
Lo Hi
Charge hose
Nitrogen gas cylinder (In vertical standing position)
Outdoor unit
Service valve
Wide tubeNarrow
tube
(2) Attach a manifold valve (with pressure gauges) and
dry nitrogen gas cylinder to this service port with charge hoses.
Use a manifold valve for air purging. If it is not available, use a stop valve for this pur­pose. The Hi knob of the manifold valve must always be kept closed.
(3) Pressurize the system to no more than 150 P.S.I.G.
with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 150 P.S.I.G. Then, test for leaks with liquid soap.
Pressure gauge
Indoor unit
Fig. 46
Manifold valve
Lo Hi
Cap
Nitrogen gas cylinder
Narrow tube
Wide tube
Fig. 47
22
Page 24
Manifold valve
CAUTION
NOTE
To prevent nitrogen from enter the refrigerant system in the liquid state, the top of the cylinder must be higher than the bottom when you pres­surize the system. Usually, the cylinder is used in a vertical standing position. (Refer to the previous page.)
(4) Do a leak test of all joints of the tubing (both
indoor and outdoor) and both wide and narrow service valves. Bubbles indicate a leak. Wipe off the soap with a clean cloth after the leak test.
(5) After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Evacuation
(1) Attach the charge hose end described in the
preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm that the Lo knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with the tubing length and capacity of the pump. The following table shows the amount of time for evacuation:
The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.
(2) When the desired vacuum is reached, close the
Lo knob of the manifold valve and turn off the vacuum pump.
If tubing length is
less than 50 ft.
45 minutes or more
If tubing length is
longer than 50 ft.
90 minutes or more
Required time for evacuation
when 30 gal/h vacuum pump is used
Vacuum pump
Cap
Narrow tube
Wide tube
Manifold valve
Vacuum gauge
Lo
Hi
Pressure gauge
Lo Hi
Vacuum pump
Outdoor unit
Service valve
Wide tubeNarrow
tube
Indoor unit
Fig. 48
Fig. 49
23
Page 25
Charging additional refrigerant
CAUTION
CAUTION
CAUTION
Use a charging cylinder designed for use with R410A.
Calculate the required amount of additional refrigerant according to narrow tube length (see P. 3, Table 3). (Fig. 50)
Use a balance (scale) to measure the refrigerant accu­rately.
When charging R410A, due to the high pressure be sure to careful­ly open the charging cylinder valve a little at a time.
After the required vacuum level is reached, charge liquid refrigerant from the charge opening of the liquid-side valve. Valves must be closed at this time.
Note: If the additional refrigerant charge amount cannot all
be charged at once, charge the remaining refrigerant in gas form by using the wide tube service valve with the system in Cooling mode at the time of test run.
When the charging is completed, all valves must be fully opened.
Outdoor unit
Hex wrench
Max. allowable tubing length at shipment
Narrow tube
Wide tube
Narrow tube
132 ft.
Fig. 50
Wide tube
Fig. 51
Indoor unit
Required additional charge
CLOSE OPEN
Finishing the job
(1) With a hex wrench, turn the narrow tube service valve
stem counter-clockwise to fully open the valve. (Fig. 51)
(2) With a screwdriver, turn the wide tube service valve
stem counter-clockwise to fully open the valve. (Fig. 51)
To avoid gas from leaking when removing the charge hose, make sure the stem of the wide tube is turned all the way out (“BACK SEA T” position).
(3) Loosen the charge hose connected to the wide tube
service port (1/4".) slightly to release the pressure, then remove the hose.
(4) Replace the 1/4". flare nut and its bonnet on the wide
tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. This process is very important to prevent gas from leaking from the system.
(5) Replace the valve caps at both wide and narrow ser-
vice valves and fasten them securely.
This completes air purging with a vacuum pump. The air conditioner is now ready for a test run.
24
Page 26
10. Test Run
IMPORTANT
CAUTION
10-1. Preparing for Test Run Before starting the air conditioner, check the follow-
ing:
(1) Remove all loose matter from the cabinet especially
metal filings, bits of wire, and clips.
(2) Connect the control wiring correctly and tighten all elec-
trical connections.
(3) For CL models only:
Connect the power to the unit for at least 5 hours before starting the compressor. The bottom of the com­pressor should be warm to the touch and the crankcase heater around the feet of the compressor should be hot to the touch.
(4) Open both the wide and narrow tube service valves
after an air purge.
(5) Remove the transportation cardboard protection for the
indoor fan.
10-2. Performing Test Run
Be careful since the fan will start when performing Test Run.
(1) Locate the Operation Selector (on right side) by open-
ing the air discharge grille on the indoor unit. (Fig. 52)
(2) Set the Operation Selector to the Test position. The
air conditioner will start running.
(3) Let the unit run for about 30 minutes and check that
the unit operates normally.
(4) After the Test Run, be sure to reset the Operation
Selector to the ON position for normal operation. The air conditioner continues to run.
(5) Referring to the Operatiing Instructions, select the
Cooling mode and press the ON / OFF operation but­ton on the remote control unit, to confirm remote con­trol unit operation.
INDOOR UNIT
Fig. 52
ON OFF TEST
Operation Selector
Set the Operation Selector to the ON position. Otherwise the unit will stop or will not run correctly.
25
Page 27
Basic Functions of the Service Valves
Action
Shipping and air purging
Operating and test running the air conditioner
Narrow Tube Service
Wide Tube Service
Valve (3-Way) Valve (Ball Valve)
CLOSED CLOSED
O-ring
Stem
Fully Fully OPEN OPEN
Narrow tube service valve Wide tube service valve
Valve cap
O-ring
Service port (B)
Stem
3-Way Valve
C2462R CL2462R
26
Page 28
CAUTION
Pump Down
Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing any of the gas. Pump down is used when the unit is to be moved or before servicing the refrigerant circuit.
Pump down procedure
Be sure to carry out pump down with the unit in Cooling mode.
(1) Connect the low pressure side (wide tube valve ser-
vice port) charging hose of the manifold valve to the service port (B) on the wide tube service valve.
(2) Using a hex wrench, turn the narrow tube service
valve clockwise all the way to close the service valve.
(3) Press the operation button and start cooling opera-
tion.
(4) When the low pressure gauge reading falls to 1 to
2
0.5 kg/cm
(14.2 to 7.1 psi), fully close the wide tube valve stem with a standard screwdriver. Then quickly stop the unit. When the pressure becomes 0.5 kg/cm2or less, the compressor stops by operation of the low-pressure switch. Recover the remaining refrigerant using refrig­erant recovery equipment to protect the compressor.
(5) Disconnect all gauges and hoses, and replace the
bonnets and the valve caps as they were previously.
(6) When the unit is transferred, after recovering the
refrigerant in the unit, charge the specified amount of refrigerant.
27
Page 29
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN INSTALLING UNIT
CAUTION
11-1. Characteristics of New Refrigerant R410A 11-1-1. What is New Refrigerant R410A?
R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture which do not adversely affect the earths ozone layer. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22.
11-1-2. Components (mixing proportions)
HFC32 (50%) / HFC125 (50%)
11-1-3. Characteristics
Less toxic, more chemically stable refrigerant
The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase).
When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state.
Thus, always charge the refrigerant while it is in liquid phase.
Ether-type oil is used for compressor oil for R410A-type units, which is different from the mineral oil used for R22. Thus more attention to moisture prevention and faster replacement work compared with conventional models are required.
11-2. Checklist Before Installation
Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ between these two tools. Where a conventional flare tool is used, make sure to observe ASpecification (amount of protrusion).
Diameter of tube (ø) D
ø6.35 (1/4") 0 0.5 mm 1.0 1.5 mm
ø19.05 (3/4") 0 0.5 mm 1.0 1.5 mm
Size of flare
Flare tool for R410A Conventional flare tool (for R22)
D
A Specification
A
D
A
Flare tool for R410A
Flare nut: Because the new refrigerant R410A operates at 1.6 times higher pressure than the conventional
Conventional flare tool (R22)
refrigerant R22, the flare nuts that came with the unit must be used.
28
Page 30
Tubing precautions
Refrigerant R410A is more easily affected by dust or moisture compared to R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation.
Never use 0.7mm-thick copper tubing or tubing which is less than 0.8mm in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C.
Outer diameter: mm (inch) Tubing wall thickness: mm (inch)
Narrow tube ø6.35 (1/4") 0.8 (0.032) Wide tube ø19.05 (3/4") 1.0 (0.042)
No addition of compressor oil for R410A
No additional charge of compressor oil is required.
No use of refrigerant other than R410A
Never use a refrigerant other than R410A.
If refrigerant R410A is exposed to fire
Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure to provide ample ventilation during installation work.
Caution in case of R410A leak
Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room, immediately provide thorough ventilation.
29
Page 31
11-3. Tools Specifically for R410A
CAUTION
For servicing, use the following tools for R410A
Tool Distinction Tool Name
Gauge manifold
Charging hose
Gas leak detector
Refrigerant cylinder
Charging cylinder
Refrigerant recovery unit
Tools specifically for R410A
Vacuum pump with anti-reverse flow (*1)
(Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.)
Vacuum pump (*2) can be used if the following adapter is attached.
Vacuum pump adapter (reverse-flow prevention adapter) (*3).
(Solenoid valve-installed adapter attached to a conventional vacuum pump.)
Electronic scale for charging refrigerant
Flare tool
Bender
Tools which can be com­monly used for R22, R407C, and R410A
Torque wrench
Cutter, reamer
Welding machine, nitrogen gas cylinder
The above tools specifically for R410A must not be used for R22 and R407C. Doing so will cause malfunction of the unit.
For the above vacuum pump (*1, *2) and vacuum pump adapter (*3), those for R22-type units can be used for R407C-type. However, they must be used exclu­sively for R410A and never alternately with R22 and R407C.
To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, sizes of the service ports and flare nuts of the narrow tube service valve and wide tube service valve have been altered.
30
Page 32
11-4. Charging Additional Refrigerant
CAUTION
11-4-1. When Tubes are Extended
Observe the proper amount of refrigerant as stated in the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only.
Never charge additional refrigerant if refrigerant is leaking from the unit.
11-5. Retro-Fitting Existing Systems 11-5-1. Use of Existing Units
Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to operate improperly and may result in a hazardous condition.
11-5-2. Use of Existing Tubing
If replacing an older unit that used refrigerant R22 with a R410A unit, do not use its existing tubing. Instead, com­pletely new tubing must be used.
31
Loading...