1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Indoor Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Field Wiring
1-6. Additional Materials Required for Installation
1-7. Operating Range
2.INSTALLATION SITE SELECTION................... 3
2-1. Indoor Unit
2-2. Outdoor Unit
2-3. Air Discharge Chamber for Top Discharge
2-4. Wind Shield for “CL” Model
3.HOW TO INSTALL THE INDOOR UNIT ........... 6
3-1. Remove the Rear Panel from the Unit
3-2. Make a Hole
3-3. Install the Rear Panel on the Wall
3-4. Remove the Grille to Install the Indoor Unit
3-5. Shape the Indoor Side Tubing
3-6. Wiring Instructions
3-7. Recommended Wire Length and Diameter
3-8. Wiring Instructions for Inter-unit Connections
3-9. Mounting
3-10. Drain Hose
4.REMOTE CONTROL UNIT INSTALLATION
POSITION ........................................................ 14
7-1. General Precautions on Wiring
7-2. Recommended Wire Length and Wire
Diameter for Power Supply System
7-3. Wiring System Diagram
7-4. Examples of Incorrect Wiring
8.HOW TO PROCESS TUBING.......................... 19
8-1. Use of the Flaring Method
8-2. Flaring Procedure with a Flare Tool
8-3. Caution before Connecting Tubes Tightly
8-4. Precautions During Brazing
8-5. Indoor Unit Tubing
8-6. Connecting Tubing between Indoor and
Outdoor Units
8-7. Insulation of Refrigerant Tubing
8-8. Taping the Tubes
8-9. Finishing the Installation
10. TEST RUN......................................................... 25
10-1. Preparing for Test Run
10-2. Performing Test Run
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS
WHEN INSTALLING UNIT ................................ 28
11-1. Characteristics of New Refrigerant R410A
11-2. Checklist Before Installation
11-3. Tools Specifically for R410A
1 1-4. Charging Additional Refrigerant
Model Combinations
CL2462R
In Canada
SANYO FISHER COMPANYSANYO Canada Inc.
A DIVISION OF SANYO NORTH AMERICA CORPORATION300 Applewood Crescent
21605 Plummer StreetConcord, Ontario
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an
important part of your job to install or service the system so
it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
●
Carefully read this instruction booklet before beginning.
●
Follow each installation or repair step exactly as
shown.
●
Observe all local, state, and national electrical codes.
●
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or
death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or product or property damage.
If Necessary, Get Help
When Installing…
…In a Ceiling, Wall or Floor
Make sure the ceiling/wall/floor is strong enough to hold
the unit’s weight. It may be necessary to construct a
strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIAN SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously toxic
gas.
• Confirm upon completing installation that no refrigerant
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other
heat source, it can produce dangerously toxic gas.
1
1. General
PartsFigureQ’tyPartsFigureQ’ty
12
1
1
Remote
control unit
PartsFigureQ’ty
12
Tapping
screw
Truss-head
Phillips
5/32 × 5/8" (
4 × 16 mm)
2
1
AAA alkaline
battery
Joint drain
Rawl plug
Remote control
holder
NOTE
CAUTION
This booklet briefly outlines where and how to install the
air conditioning system. Please read over the entire set
of instructions for the indoor and outdoor units and make
sure all accessory parts listed are with the system before
beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Indoor Unit
Table 1
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Pipe bending tool (spring bender)
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the narrow
and wide tubing, fittings and insulation. Consult your
nearest sales outlet or A/C workshop.
For rear-left tubing, optional tube connec-
tion (C) (APR-EN46U1B) is necessary. See
page 20.
Also consult your nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a
local source, you will need:
1.Deoxidized annealed copper tube for refrigerant tub-
ing as detailed in Table 2.
When cutting tubing, add approximately 12 to 16 in.
to each tube length to reduce vibration between the
air conditioning units.
2
Table 2
Model
KS2462R
Narrow Tube
Outer Diameter
3/8"
Wide Tube
3/4"
2.Foamed polyethylene insulation for the specified copper tubes as required to precise length
of tubing. Wall thickness of the insulation
should be not less than 5/16".
1-5. Field Wiring
Use insulated copper wire for field wiring. Wire
size varies with the total length of wiring. Refer to
3-6. Wiring Instructions for details.
Check local electrical codes
and regulations before obtaining wire. Also, check any specified instructions or limitations.
1-6. Additional Materials Required for Installation
6 in.
min.
6 in.
min.
6 in. min.
Front View
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Elevation
difference (H)
Indoor unit
Floor level
Wall
Minimum height
from floor level
5 ft.
CAUTION
Drain hose
Indoor unit
Outside drainage
1.Refrigeration (armored) tape
2.Insulated staples or clamps for connecting wire
(See local codes)
3.Putty
4.Refrigeration lubricant
5.Clamps or saddles to secure refrigerant tubing
1-7. Operating Range
TemperatureIndoor Air IntakeOutdoor Air Intake
Cooling
Maximum95°F DB, 71°F WB115°F DB
Minimum67°F DB, 57°F WB67°F DB, (0°F DB)*
*CL
2. Installation Site Selection
2-1. Indoor Unit
To prevent abnormal heat genera-
WARNING
AVOID:
●
direct sunlight.
●
nearby heat sources that may affect performance of the
unit.
●
areas where leakage of flammable gas may be expected.
●
places where large amounts of oil mist exist.
DO:
●
select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
●
select a location that will hold the weight of the unit.
●
select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
●
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2)
●
install the unit within the maximum elevation difference
(H) above or below the outdoor unit and within a total
tubing length (L) from the outdoor unit as detailed in
Table 3 and Fig. 3a.
tion and the possibility of fire, do
not place obstacles, enclosures and
grilles in front of or surrounding the
air conditioner in a way that may
block air flow.
Fig. 1
Models
Fig. 2
Fig. 3a
For stable operation of
the air conditioner, do
not install wall-mounted
type indoor units less
than 5 ft. from floor
level.
Fig. 3b
Table 3
ModelLength at ShipmentLength (L)Difference (H)Additional Refrigerant
C2462R, CL2462R23132500.43
*
If total tubing length becomes 23 to 132 ft. (max.), additional refrigerant (R410A) charge of 0.43 oz./ft. is required.
No additional charge of compressor oil is necessary.
Max. Allowable Tubing Limit of TubingLimit of ElevationRequired Amount of
(ft.)(ft.)(ft.)(oz./ft.)
3
*
2-2. Outdoor Unit
Outdoor unit
Hot air
Heat source
Exhaust fan
Min.
1 in.
Min.
1 in.
Min. 2 ft.
Min. 4 inches
Min.
7 ft.
Obstacle above
Ground
Air
discharge
Air in
Air in
Air
discharge
Concrete block
4 in. × 1 ft. 4 in.
beams or equal
Anchor bolts
(4 pieces)
Min. 6 in.
Air discharge
AVOID:
●
heat sources, exhaust fans, etc. (Fig. 4a)
●
damp, humid or uneven locations.
DO:
●
choose a place as cool as possible.
●
choose a place that is well ventilated.
●
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 4b)
●
provide a solid base a minimum of 6 inches above
ground level to reduce humidity and protect the unit
against possible water damage and decreased service
life. (Fig. 4c)
●
use lug bolts or equal to bolt down unit, to reduce
vibration and noise.
2-3. Air Discharge Chamber for Top Discharge
Fig. 4a
Install the air-discharge chamber in the field when:
●
it is difficult to keep a space of minimum 2 ft. between
the air-discharge outlet and an obstacle.
●
the air-discharge outlet faces a sidewalk and discharged hot air may disturb people passing by.
Refer to Fig. 5a.
Fig. 4b
Fig. 4c
Fig. 5a
4
2-4. Wind Shield for “CL” Model
IMPORTANT
Wind shield
(air discharge side)
Front
3 - φ1-9/16" hole
6 - φ15/64" hole
9-27/32"21-5/8"15/16"
5-3/16"
22-7/16"1/2"
23-15/32"
21-13/16"
5-5/32"9-27/32"9-27/32"1-1/16"
21-13/16"
It is recommended to use wind shields for “CL” model
(Fig. 5b). “CL” model is designed to use in low outdoor
temperature conditions.
General
When the outdoor unit is installed in a position exposed
to strong wind (like seasonal winds with low air temperature in winter), a suitable wind shield must be installed
on the outdoor unit.
This unit is designed so that the fan of the outdoor unit
runs at low speed when the air conditioner is operated at
low outdoor air temperatures. When the outdoor unit is
exposed to strong wind, the system pressure drops
because of the freeze protector.
For outer dimensions of the wind shield, see Fig. 5c.
Fig. 5b
Recommended outer dimensions of wind shield
(field supply)
CL2462R
Fig. 5c
5
Indoor
side
Outdoor
side
Set screws for transportation only
Right-rear
tubing
(recommended)
Right tubing
Left-rear tubling
Center of
left-rear
tubing hole
Center of
right-rear
tubing hole
NOTE
3. How to Install the Indoor Unit
NOTE
CAUTION
PVC pipe (locally purchased)
Cut at slight angle
3-1. Remove the Rear Panel from the Unit
Remove and discard the set screws and take off the rear
panel. (Fig. 6)
Tubing can be extended in 3 directions as shown in
Fig. 7a. Select the direction you need providing the
shortest run to the outside unit.
3-2. Make a Hole
(1) Remove the rear panel from the indoor unit and
place it on the wall at the location selected. Make
sure the unit is horizontal, using a carpenter’s level
or tape measure to measure down from the ceiling.
(2) Determine which side of the unit you should make
the hole. (Fig. 7b)
(3) Before making a hole, check carefully that no studs
or pipes are directly run behind the spot to be cut.
Fig. 6
Fig. 7a
In case of left-rear or right-rear tubing
Also avoid areas where electrical wiring or conduits are
located.
The above precautions are also applicable if tubing
goes through the wall in any other location.
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and
Fig. 8.
Table 4
Hole Dia. (inch)
3-3/16"
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a
slight angle 1/4" shorter than the thickness of the
wall. (Fig. 9)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert in the wall. (Fig. 10)
Fig. 7b
Hole should be made at a slight downward slant to the
outdoor side.
Fig. 8
Fig. 9
INSIDE
Wall
Plastic cover
(Field supply)
OUTSIDE
PVC pipe
Slight
angle
Fig. 10
6
3-3. Install the Rear Panel on the Wall
3/16
"
dia. hole
1-3/16
"
or more
Rawl plug
(Field supply)
Air intake grille
Grille
Air intake grille
Be sure to confirm that the wall is strong enough to suspend the unit.
See either Item a) or b) below depending on the wall
type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 10 screws
provided. (Fig. 11)
If you are not able to line up the holes in the rear
panel with the beam locations marked on the wall,
use toggle bolts to go through the holes on the panel
or drill 3/16"dia. holes in the panel over the stud
locations and then mount the rear panel.
(2) Double check with a ruler or carpenter’s level that
the panel is level. This is important to install the unit
properly. (Fig. 12)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and
vibration.
Fig. 11
Fig. 12
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" dia. holes in the wall. Insert rawl plugs for
appropriate mounting screws. (Fig. 13)
3-4. Remove the Grille to Install the Indoor Unit
Basically, these models can be installed and wired without removing the grille. If access to any internal part is
needed, follow the steps as given below:
How to remove the grille
(1) Set the 2 flaps in the horizontal position.
(2) Unscrew the 3 screws. (Fig. 14a)
(3) Remove the grille.
(a) Hold both corners of the air intake grille, then pull
out and up to open. (Fig. 14b)
(b) Use a standard screwdriver to push up the 3 tabs
to remove the grille. (Fig. 14b)
(c) Pull the lower part of the grille toward you to
remove. (Fig. 14a)
Fig. 13
Fig. 14a
Fig. 14b
7
How to replace the grille
Frame
Right tubing
outlet
Tab
Mounting slot
(1) Close the flaps.
(2) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 15a) Insert the tabs
in the slots and push the lower part of the grille back
into position.
(3) Press at each of the 5 tabs to completely close the
grille. Make sure that the grille and frame are firmly
fitted together. (Fig. 15b)
3-5. Shape the Indoor Side Tubing
1) Arrangement of tubing by directions
a) Right tubing
Fig. 15a
The corner of the right frame needs to be cut by a
hacksaw or the like. (Fig. 16)
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be
cut.
2) To mount the indoor unit on the rear panel:
Hang the 3 mounting slots of the unit on the
upper tabs of the rear panel. (Fig. 17)
3-6. Wiring Instructions
General precautions on wiring
1)Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring
closely following the wiring diagram.
2)Provide a power outlet to be used exclusively for
each unit, with a power supply disconnect and circuit
breaker for overcurrent protection provided in the
exclusive line.
3)To prevent possible hazard due to insulation failure,
the unit must be grounded.
Fig. 15b
Fig. 16
Fig. 17
4)Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or become
damaged.
5)Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
6)Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
8
3-7. Recommended Wire Length and Diameter
2
4
2
4
11
INDOOR
UNIT
Terminal
OUTDOOR
UNIT
(B)
Terminal
(A)
L2
L1
G
G
G
230V/208V
230V/208V
230V/208V
(Inter-unit)
power line
Grounding line
Grounding
line
Power supply
Single-phase 230V/208V 60HZ
Disconnect
switch
Field supply
WARNING
CAUTION
Regulations on wiring diameter differ from locality to
locality. For field wiring requirements, please refer to
your local electrical codes. Carefully observe these regulations when carrying out the installation.
Table 5 lists recommended wire lengths and diameters
for power supply systems.
Refer to the wiring system diagram (Fig. 18) for the
meaning of “A” and “B” in Table 5.
Table 5
AWG
Model
C2462R,CL2462R64 (Max.)132 (Max.)35A
(A) Power Supply
Wiring Length (ft.)
(#12)
(B) Inter-Unit
Power Line
(#14)
# …AWG (American Wire Gauge)
Fuse or Circuit
Capacity
WARNING
●
Be sure to comply with local
codes on running the wire
from the indoor unit to the
outdoor unit (size of wire and
wiring method, etc.).
●
Each wire must be firmly
connected.
●
No wire should be allowed to
touch refrigerant tubing, the
compressor, or any moving
part.
To avoid the risk of electric
shock, each air conditioner
unit must be grounded.
Be sure to connect the power
supply line to the outdoor unit
as shown in the wiring diagram. The indoor unit draws its
power from the outdoor unit.
WIRING SYSTEM DIAGRAM
Fig. 18
9
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.