Sanyo PW-UMR184EXH56, SPW-UMR94EXH56, SPW-UMR74EXH56, SPW-UMR224EXH56, SPW-UMR124EXH56 User Manual

...
Page 1
– ECO-i System Air Conditioner –
INSTALLATION AND OPERATION MANUAL
R410A Models
Indoor Units
Outdoor Units
SPW-UMR74EXH56 SPW-UMR94EXH56 SPW-UMR124EXH56 SPW-UMR164EXH56 SPW-UMR184EXH56 SPW-UMR224EXH56
C
DC Inverter Main Unit SPW-CR604GDXH8, SPW-CR704GDXH8, SPW-CR904GDXH8, SPW-CR1154GDXH8
Constant Speed (Sub) Unit SPW-CR704GDCH8, SPW-CR904GDCH8, SPW-CR1154GDCH8
Optional Controllers
Remote Controller RCS-SH80AG
RC Wireless Remote Controller RCS-BH80AG.WL
Simplified Remote Controller RCS-KR1AG
for Refrigerant R410A
SANYO Airconditioners Europe S.r.l.
Via Bisceglie, No. 76
20152 Milano, Italy
37.4196.054.0 ©SANYO 2005
Page 2
2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operat­ing standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
This product is intended for professional use. Permission from the power supplier is required when installing an outdoor unit that is connected to a 16 A distribution network.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including fail­ure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this sys­tem. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inad­equate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is speci­fied as either “narrow” or “wide” than as “liquid” or “gas.”
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm after installation that no refrigerant gas is leak­ing. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
NOTE
WARNING
CAUTION
WARNING
CAUTION
Page 3
3
2. The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adja-
cent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when mechanical ventilation is installed inter­locked with a gas leakage detector in the smallest room where the density limit is exceeded, the vol­ume of the next smallest room becomes the object.
3. The minimum indoor floor space compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7 m high)
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air condi­tioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to pro­tect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, how­ever, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant com­pared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant acci­dentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the density may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The density is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
Density limit (kg/m
3
)
The density limit of refrigerant which is used in multi air con­ditioners is 0.3 kg/m
3
(ISO 5149).
1. If there are 2 or more refrigerating systems in a sin­gle refrigerating device, the amount of refrigerant should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
Outdoor unit
Refrigerant tubing
Indoor unit
Refrigerant tubing
NOTE
e.g., charged amount (10 kg)
Indoor unit
Room A Room B Room C Room D Room E Room F
Outdoor unit
e.g., charged amount (15 kg)
Outdoor unit
Very small room
Small room
Mechanical ventilation device – Gas leak detector
Medium room
Large room
Indoor unit
40
Range below the
2
35
m
density limit of 0.3 kg/m
30
(countermeasures not needed)
25
20
15
10
5
Min. indoor floor space
0
3
10 20 30
Total amount of refrigerant
Range above the density limit of 0.3 kg/m (countermeasures needed)
3
kg
Page 4
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor unit and make sure all accessory parts listed are with the system before beginning.
1-2. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately
from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant
tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness
of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire
size varies with the total length of wiring. Refer to
4. Electrical Wiring for details.
1-3. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
4
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Please Read Before Starting
Check of Density Limit
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-1. Tools Required for Installation (not supplied) 1-2. Type of Copper Tube and Insulation Material 1-3. Additional Materials Required for Installation
2. HOW TO INSTALL THE UNIT . . . . . . . . . . . . . .5
2-1. Duct for fresh air
3. TEST OF THE SYSTEM AND CONTROL OF THE
AIR VOLUME TO THE OUTLET GRILLES . . . .7
CONTENTS
Page
Page
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenters level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
4. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . .8
4-1. General Precautions on Wiring 4-2. Recommended Wire Length and Wire Diame-
ter for Power Supply System
4-3. Wiring System Diagrams
5. HOW TO PROCESS TUBING . . . . . . . . . . . . . .12
5-1. Connecting the Refrigerant Tubing 5-2. Connecting Tubing between Indoor and Out-
door Units 5-3. Insulating the Refrigerant Tubing 5-4. Taping the Tubes 5-5. Finishing the Installation
6 APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
CAUTION
Page 5
5
2. HOW TO INSTALL THE UNIT
Fig. 2-1
Minimum operation and maintenance area. (fig. 2-1)
Fig. 2-2
Fig. 2-4
Find the space for the installation of the return air grille and mark the opening to do. Cut the falseceiling. (fig. 2-2)
Use rawl plug suitable to the ceiling consistence and four M10 threaded bars of suitable length (not supplied). (fig. 2-
3)
Mark on the ceiling the holes for the hanging rods, verify the distance of the centres. The value included in the brackets is referred to the model X18. (fig. 2-4) Drill a 80 mm diameter hole, for the passage of refrigeration
pipework, condensate pipework and electrical cable. Insert a PVC pipe in the wall. (fig. 2-5)
Secure the unit in position with locknuts and washers, level the unit, keeping the right distance from the falseceiling for the installation of return air grille. (fig. 2-6)
Foresee a removable panel of the falseceiling for servicing. (fig. 2-7)
The unit is supplied with PVC hose from the condensate pump. Maximum pump lift is 250 mm over the unit. Convoy the condensate with a positive slope (min. 1:100) to the out­side. The highest point in the condensate pipework should be as close to the unit as possible. This prevents a large volume of water draining back into the unit when it is switched off. (fig. 2-8)
Convoy the condensate to the outside with a positive slope, from a trap at the end if necessary. (fig. 2-9)
300
Fig. 2-3
Fig. 2-5
Fig. 2-6
Fig. 2-7
Fig. 2-8
Fig. 2-9
7/9/12 1500 1100 16/18/22 1700 1100
AB
Page 6
6
Intake coduct
False ceiling
Air intake
Outlet conduct
On the front and rear side of the unit a rectangular port (with flange) helps during duct mounting. (fig. 2-10)
Rear and front flange for the air intake. The value included in the brackets is referred to the model X18. (fig. 2-11)
Discarge air duct (optional accessory). Contact the After Sale Service. (fig. 2-12)
Remove the filter and pour, inside the condensate drain pan, 0.5 liter of water. Start the unit checking for proper drain pump operation. (fig. 2-13)
Fig. 2-10
Fig. 2-11
Fig. 2-12
Fig. 2-13
2
1
There is a duct connection port for drawing in fresh air. The supplementary fan motor for outside air intake has to be supplied separately and controlled by a bipolar ON-OFF switch with safety fuses. Fresh air flow must be about 10% of the total air flow to avoid operating problems and noise.
Open the knock-out hole , fix a 120 mm flange on the unit and connect the thermically insulated duct.
Install an outside grille with filter inspection port to prevent dust and leaves from entering and fouling the indoor unit heat exchanger.
2-1 Duct for fresh air
Page 7
7
3. TEST OF THE SYSTEM AND CONTROL OF THE AIR VOLUME TO THE OUTLET GRILLES
The unit is prearranged to supply an external static pressure of about 5 mm. Too high resistances in the air distribution system can cause an exceedingly small air volume to the outlet grilles. This trouble can be solved by increasing the fan speed as follows:
Open the cover of the electrical junction box. Take out the booster cable clamped in the box. (fig. 3-1)
Disconnect the fan motor plug in the electrical box and insert the booster cable as a cable extension between the motor plug and the socket from the PCB. The external static pres­sure will increase to 7 mm w.g. Check static pressure and air flow rate on the fan performance graph. (fig. 3-2)
Fan motor
Fan motor
Booster cable
Booster cable
Connector motor cable (at the supply)
Fig. 3-1
Fig. 3-2
0
2
4
6
8
10
200 400 600 800 1000
H
HH
M
L
7/9/12
16/18/22
m3/h
m
3
/h
EXTERNAL STATIC PRESSURE (mmW.G.)
EXTERNAL STATIC PRESSURE (mmW.G.)
H = High fan speed L = Low fan speed HH = Very high fan speed M = Middle fan speed
H: Standard supplied unit. Available fan speeds: Low-Midd-
le-High (L - M - H). Max. static pressure: about 5 mm
HH: Unit with cable extension of the fan motor (booster
cable). Available fan speeds: Middle-High-Very high (M ­H - HH). Max. static pressure: about 7 mm
10
8
6
4
2
0
300 500 700 900 1100 1300 1500
M
L
HH
H
Page 8
8
4. ELECTRICAL WIRING
4-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and cir­cuit breaker for overcurrent protection should be provided in the exclusive line.
(3) To prevent possible hazards from insulation fail-
ure, the unit must be grounded.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before begin­ning.
You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control
wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring
between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is dam-
aged, it must be replaced by a repair shop appointed by the manufacture, because special purpose tools are required.
4-2. Recommended Wire Length and Wire Diameter for Power Supply System
* With ring-type wire terminal.
Outdoor unit
(A) Power supply
Wire size Max. length
2
SPW-CR604GDXH8 113 m 15 A SPW-CR704GDXH8 74 m 30 A SPW-CR904GDXH8 60 m 35 A SPW-CR1154GDXH8 55 m 40 A SPW-CR704GDCH8 47 m 35 A SPW-CR904GDCH8 46 m 40 A SPW-CR1154GDCH8
4 mm 6 mm 6 mm 6 mm 6 mm 6 mm 6 mm
2
2
2
2
2
2
39 m 50 A
Time delay fuse or circuit capacity
Indoor unit
(B) Power supply
2.5 mm
Max. 130 m
Time delay fuse or
2
circuit capacity
10 ~ 16A
Control wiring
(C) Inter-unit (between outdoor and
(D) Remote control wiring (E) Control wiring for group control
indoor units) control wiring
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Use shielded wiring* Use shielded wiring Use shielded wiring
Max. 1,000 m
Max. 500 m
or
(A) Power supply
Wire size Max. length
2.5 mm 6 mm 6 mm
10 mm
6 mm
10 mm 10 mm
2
70 m
2
74 m
2
60 m
2
91 m
2
47 m
2
77 m
2
65 m
0.75 mm
2
(AWG #18)
Max. 500 m (Total)
Time delay fuse or circuit capacity
16A 35A 35A 50A 35A 50A 50A
NOTE
(F) Inter-outdoor unit control wiring
2
0.75 mm
(AWG #18)
Use shielded wiring
Max. 500 m
Page 9
9
4-3. Wiring System Diagrams
(1) Refer to Section 5-2. Recommended Wire Length
and Wire Diameter for Power Supply System for the explanation of A,” “B,” “C,” “D, and E, in the above diagrams.
(2) The basic connection diagram of the indoor unit
shows the 7P terminal board, so the terminal boards in your equipment may differ from the dia­gram.
(3) Refrigerant Circuit (R.C.) address should be set
before turning the power on.
7P terminal board
1(L) power supply
2(N) U1 U2
Inter-unit
control
wiring
R1 R2
Remote
controller
Power supply 220-240V 50Hz
Remote controller
WHT BLK
Power supply 220-240V 50Hz
Remote controller
WHT BLK
Group control:
Power supply 220-240V 50Hz
L N
Ground
B
D
1
1
2
2
L N
Ground
B
D
1
1
2
2
L N
Ground
B
E
Indoor unit (No. 1)
1
2
U1
U2
R1
R2
Indoor unit (No. 2)
1
2
U1
U2
R1
R2
Indoor unit (No. 3)
1
2
U1
U2
R1
R2
Outdoor unit
C
Ground
Ground
C
U1
U2
3
4
INV unit
A
1
2
3
4
5
L1 L2 L3 N
Ground
Power supply 380-415V-3N 50Hz
Ground
F
Inter-outdoor-unit control wiring
Outdoor unit CS unit
Ground
C
3
4
A
1
2
3
4
5
L1 L2 L3 N
Ground
Power supply 380-415V-3N 50Hz
Ground
C
Indoor
Power supply 220-240V 50Hz
Remote controller
1
WHT BLK
1
2
2
L N
Ground
D
unit (No. n)
B
1
2
U1
U2
R1
R2
Ground
NOTE
Page 10
10
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no con­nection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-1)
Fig. 4-1
Fig. 4-2
Fig. 4-3
CAUTION
(3) Do not install inter-unit control wiring such as star
branch wiring. Star branch wiring causes mis-address setting.
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 1 m are not included in the total branch number.) (Fig. 4-3)
Outdoor unit Outdoor unit Outdoor unit
Prohibited
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
NO
Outdoor unit Indoor unit Indoor unit Indoor unit
NO
Indoor unit Indoor unit Indoor unit
Branch point
Prohibited
Outdoor unit
Indoor unit
Branch point
16 or fewer
Outdoor unit Outdoor unit Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit
more than 1 m
Indoor unit
more than 1 m
Indoor unit
less than 1 m
Indoor unit
Indoor unit Indoor unit Indoor unit
Page 11
11
Fig. 4-4
Fig. 4-5
Fig. 4-6
(5) Use shielded wires for inter-unit control wiring
(c) and ground the shield on both sides, other­wise misoperation from noise may occur. (Fig. 4-4) Connect wiring as shown in Section 4-3. Wiring System Diagrams.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, fol­low the instructions on How to connect wiring to the terminal and fasten the wire securely with the fixing screw of the terminal plate.
How to connect wiring to the terminal
For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Fig. 4-5)
(2) Using a Phillips head screwdriver, remove the ter-
minal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screw­driver. (Fig. 4-6)
WARNING
Special washer
Wire
Ground
Strip 10 mm
Screw
Ring pressure terminal
Terminal plate
Shielded wire
Ground
Stranded wire
Ring pressure terminal
Screw and Special washer
Ring pressure terminal
Wire
Page 12
12
5. HOW TO PROCESS TUBING
The narrow tubing side is connected by a flare nut, and the wide tubing side is connected by brazing.
5-1. Connecting the Refrigerant Tubing
Use of the Flaring Method
Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 30 – 50 cm longer than the tubing length you esti­mate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 5-1)
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 5-2)
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a
flare tool.* (Fig. 5-3)
(*Use RIGID
®
or equivalent.)
A good flare should have the following characteristics:
inside surface is glossy and smooth
edge is smooth
tapered sides are of uniform length
NOTE
NOTE
Fig. 5-1
Fig. 5-2
Fig. 5-3
Before
Deburring
After
Copper tubing
Reamer
Flare nut
Copper tubing
Flare tool
Page 13
13
Caution Before Connecting Tubes Tightly
(1) Apply a sealing cap or water-proof tape to prevent
dust or water from entering the tubes before they are used.
(2) Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connect­ing them together. This is effective for reducing gas leaks. (Fig. 5-4)
(3) For proper connection, align the union tube and
flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 5-5)
Adjust the shape of the narrow tube (liquid tube)
using a tube bender at the installation site and connect it to the narrow tubing side (liquid tubing side) valve using a flare.
Cautions During Brazing
Replace air inside the tube with nitrogen gas to
prevent copper oxide film from forming during the brazing process. (Oxygen, carbon dioxide and Freon are not acceptable.)
Do not allow the tubing to get too hot during
brazing. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool when brazing.
Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the for-
mation of oxide film. These agents adversely affect the refrigerant and refrigerant oil, and may cause damage or malfunctions.
5-2. Connecting Tubing Between Indoor and Out-
door Units
(1) Tightly connect the indoor-side refrigerant tubing
extended from the wall with the outdoor-side tub­ing.
(2) To fasten the flare nuts, apply specified torque as
at right:
When removing the flare nuts from the tubing con-
nections, or when tightening them after connecting the tubing, be sure to use 2 monkey wrenches or spanners as shown. (Fig. 5-6) If the flare nuts are over-tightened, the flare may be damaged, which could result refrigerant leakage and cause in injury or asphyxiation to room occu­pants.
For the flare nuts at tubing connections, be sure to
use the flare nuts that were supplied with the unit, or else flare nuts for R410A (type 2). The refriger­ant tubing that is used must be of the correct wall thickness as shown in the table at right.
Fig. 5-4
Fig. 5-5
Fig. 5-6
Because the pressure is approximately 1.6 times higher than conventional refrigerant pressure, the use of ordinary flare nuts (type 1) or thin-walled tubes may result in tube rupture, injury, or asphyxi­ation caused by refrigerant leakage.
In order to prevent damage to the flare caused by
over-tightening of the flare nuts, use the table above as a guide when tightening.
When tightening the flare nut on the narrow tube,
use a monkey wrench with a nominal handle length of 200 mm.
Indoor unit
Tube diameter
φ
6.35 (1/4")
φ
9.52 (3/8")
φ
12.7 (1/2")
φ
15.88 (5/8")
Apply refrigerant lubricant here and here
Union
Flare nut
Torque wrench
Outdoor unit
Tightening torque, approximate
14 – 18 N
(140 – 180 kgf
34 – 42 N
(340 – 420 kgf
49 – 61 N
(490 – 610 kgf
68 – 82 N
(680 – 820 kgf
m
·
cm)
·
m
·
cm)
·
m
·
cm)
·
m
·
cm)
·
Spanner
Tube thickness
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Page 14
14
Fig. 5-8
Fig. 5-7
Fig. 5-9
5-3. Insulating the Refrigerant Tubing
Tubing Insulation
Thermal insulation must be applied to all unit tub-
ing, including distribution joint (purchased sepa­rately).
* For gas tubing, the insulation material must be
heat resistant to 120°C or above. For other tubing, it must be heat resistant to 80°C or above.
Insulation material thickness must be 10 mm or greater.
If the conditions inside the ceiling exceed DB 30°C and RH 70%, increase the thickness of the gas tubing insulation material by 1 step.
Taping the flare nuts
Wind the white insulation tape around the flare nuts at the wide tube connections. Then cover up the tubing connections with the flare insulator, and fill the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the sup­plied vinyl clamps. (Fig. 5-8)
Insulation material
The material used for insulation must have good insu­lation characteristics, be easy to use, be age resis­tant, and must not easily absorb moisture.
After a tube has been insu­lated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
Never grasp the drain or refrigerant connecting outlets when moving the unit.
y
Three tubes arranged together
Two tubes arranged together
If the exterior of the outdoor unit valves has been finished with a square duct covering, make sure you allow suffi­cient space to use the valves and to allow the panels to be attached and removed.
CAUTION
Narrow tubing
Sealer (supplied)
Unit side insulator
Flare nut
Narrow tubing
Insulation
Cosmetic (finishing) tape
Insulation
Insulation tape (white)
(supplied)
Vin
Wide tubing
Wide tubing
Balance tubing
Flare insulator (supplied)
Tube insulator (not supplied) Heat resistant 120°C or above
l clamps (supplied)
CAUTION
Refrigerant tubing and insulator
Drain insulator and clamp. Large (supplied)
Packing clamp. Small hose band (supplied)
(not supplied)
Drain pipe and insulator (not supplied)
Insulation tape
Vinyl
Flare
clamp
insulator
Seal
The procedure used for installing the insulator for both wide and narrow tubes is the same.
Page 15
15
Fig. 5-10
Fig. 5-11
5-4. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical
wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To pre­vent the condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the
outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1
clamp approx. each meter. (Fig. 5-10)
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also ensure that the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.
5-5. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to pre­vent rain and draft from entering. (Fig. 5-11)
NOTE
g
Insulated tubes
Clamp
Drain hose
Apply putty here
Tubin
Page 16
6. APPENDIX
1. 2.
Name of Parts (Indoor Unit)
Air outlet
Water drain
Air filter
Care and Cleaning
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before
WARNING
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them
(Indoor unit) with a clean, soft cloth.
cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo­nents and cause an electric shock hazard.
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic
CAUTION
parts using very hot water.
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be cleaned every year. Consult your dealer or service center.
Air filter
The air filter collects dust and other particles from the air and should be cleaned at regular intervals as indicated in the table below or when the filter indication ( ) on the display of the remote control unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air conditioner drops greatly.
Type Period
UMR Six months
NOTE
The frequency with which the filter should be cleaned depends on the environment in which the unit is used.
<How to clean the filter>
1. Remove the air filter from the air intake grille.
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the
filter in lukewarm, soapy water, rinse it in clean water, and dry it.
16
Page 17
Care: After a prolonged idle period
Care: Before a prolonged idle period
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a blockage, remove it.
Operate the fan for half a day to dry out the inside.
Disconnect the power supply and also turn off the circuit breaker.
Clean the air filter and replace it in its original position.
Outdoor unit internal components must be checked and cleaned periodically. Con-
tact your local dealer for this service.
CAUTION
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled improperly; special care should be taken when you clean these parts.
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt or soot.
3. The internal coil and other components of the outdoor unit must also be cleaned periodi­cally. Consult your dealer or service center.
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center.
Tips for Energy Saving
Avoid
Do
Do not block the air intake and outlet of the unit. If either is obstructed, the unit
will not work well, and may be damaged.
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls and ceiling of the room are warmed by the sun, it will take longer to cool the room.
Always try to keep the air filter clean. (Refer to Care and Cleaning.) A clogged filter will impair the performance of the unit.
To prevent conditioned air from escaping, keep windows, doors and any other open­ings closed.
Should the power fail while the unit is running
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is restored using the same settings before the power was interrupted.
Trouble
Air conditioner does not run at all
1. Power failure.
2. Leakage circuit breaker has
3. Line voltage is too low.
4. Operation button is turned off.
5. The wired remote control unit or
Compressor runs but soon stops Poor cooling (or heating)
performance
1. Obstr uction in front of condenser
1. Dirty or clogged air filter.
2. Heat source or many people in
3. Doors and/or windows are open.
4. Obstacle near air intake or air
5. Thermostat is set too high for
6. (Defrosting system does not work.)
Possible Cause
tripped.
malfunctioning. (
The inspection mark and the
H, L, P in
on
(or too low for heating).
combination with numbers
the LCD of the wired
heat pump is
letters E, F,
appear
remote control unit.)
coil
room.
discharge port. cooling
After a power outage, press ON/
1.
on the
2. Contact service center.
3. Consult your electrician or dealer.
4. Press the button again.
5. Consult your dealer.
1. Remove obstruction
1. Clean air filter to improve the
2. Eliminate heat source if possible.
3. Shut them to keep the heat (or
4. Remove it to ensure good airflow.
5. Set the temperature lower (or
6. (Consult your dealer.)
wired remote control unit.
Remedy
OFF operation
airflow.
cold) out.
higher).
button
NOTE
17
Page 18
Nom des pièces (unité intérieure)
1. 2.
Sortie díair
Drain
Entretien et nettoyage
1. Pour toute sécurité, éteignez le climatiseur et débranchez-le de la prise secteur.
AVERTISSEMENT
2. Ne versez pas deau sur lunité intérieure pour la nettoyer. Cela pourrait abîmer les com­posants internes et provoquer des décharges électriques.
Filtre à air
Larrivée dair et la sortie dair
(unité intérieure)
1. Ne utilisez jamais de dissolvants ni de produits chimiques puissants lorsque lunité
ATTENTION
2. Certains bords métalliques et les ailettes étant coupants, ils doivent être manipulés avec
3. La bobine interne et les autres composants de lunité extérieure doivent être nettoyés
Filtre à air
Le filtre à air recueille la poussière et les particules se trouvant dans lair et doit être nettoyé à inter­valles réguliers comme indiqué dans le tableau cidessous ou lorsque le symbole du filtre ( ) affiché sur la télécommande (avec fil) indique que le filtre doit être nettoyé. Si le filtre est bloqué, lefficacité du climatiseur diminue nettement.
Type Période
UMR Six mois
Nettoyez larrivée dair et la sortie de lunité intérieure avec la brosse dun aspirateur ou les essuyer avec un chiffon propre et doux.
intérieure est nettoyée. Nessuyez pas les pièces en plastique avec de leau très chaude.
précaution lors du nettoyage sous peine de provoquer des blessures.
tous les ans. Consultez le concessionnaire ou un service après-vente.
REMARQUE
La fréquence de nettoyage du filtre dépend de lenvironnement dans lequel lunité est utilisée.
<Comment nettoyer le filtre>
1. Retirez le filtre à air de la grille de larrivée dair.
2. Se servir dun aspirateur pour enlever la poussière légère. Si de la poussière adhère au
filtre, lavez celui-ci dans de leau tiède et savonneuse, puis rincez-le dans de leau propre et séchez-le.
18
Page 19
Entretien : après une période dinactivité
prolongée
Entretien : avant une période d’inactivité
prolongée
Vérifiez larrivée dair et la sortie dair des unités intérieure et extérieure et assurez-vous quelles ne sont pas obstruées ; si elles sont obstruées, remédiez
à ce problème.
Faites fonctionner le ventilateur pendant une demi-journée pour faire sécher lintérieur de lunité.
Débranchez lalimentation et mettez le disjoncteur en position arrêt.
Nettoyez le filtre à air et remettez-le dans sa position initiale.
Les éléments internes de lunité extérieur doivent être vérifiés et nettoyés
régulièrement. Contactez votre distributeur le plus proche pour effectuer ces opérations.
ATTENTION
1. Certains bords métalliques et les ailettes du condensateur étant coupants, ils doivent être manipulés avec précaution lors du nettoyage sous peine de provoquer des blessures.
2. Vérifiez régulièrement que la sortie et larrivée dair ne soient pas obstruées par de la poussière ou de la suie.
3. La bobine interne et les autres composants de lunité extérieure doivent être nettoyés régulièrement. Consultez le concessionnaire ou un service après-vente.
19
Page 20
Guide de dépannage
Si le climatiseur ne fonctionne pas correctement, effectuez les vérifications suivantes avant de faire appel à un réparateur. Si le problème persiste, prenez contact avec votre concessionnaire ou avec un service après-vente.
Panne Cause possible Remède
Le climatiseur ne fonctionne pas du tout.
Le compresseur se met en marche mais il sarrÍte aussitôt.
Refroidissement (ou chauffage) insuffisant.
1. Coupure de courant. 1. Après une panne de courant,
2. Le disjoncteur a fonctionné. 2. Prenez contact avec un service
3. Tension de ligne trop basse. 3. Consultez un électricien ou le
4. Le bouton de fonctionnement est en position Off.
5. La télécommande avec fil ou la pompe thermique ne fonctionne pas correctement. (La marque díinspection et les lettres E, F, H, L, P ainsi que des numéros apparaissent sur laffichage à cristaux liquides de la télécommande avec fil.)
1. Il y a un obstacle dev ant la bobine du condensateur.
1. Filtre à air sale ou obstrué. 1. Nettoyez le filtre à air afin
2. Source de chaleur ou trop de monde dans la pièce.
3. Portes et/ou fenÍtres ouv ertes. 3. Fermez-les pour empÍcher la
4. Obstacle devant larrivée ou la sortie dair.
5. Le thermostat est réglé sur une température trop élevée pour le refroidissement (ou trop basse pour le chauffage).
6. (Le dégivrage du système ne fonctionne pas.)
appuyez sur le bouton de marche/ arrêt de fonctionnement de la télécommande avec fil.
après-vente.
concessionnaire.
4. Appuyez à nouveau sur le bouton.
5. Consultez le concessionnaire.
1. Retirez ce qui fait obstruction.
díaméliorer la circulation díair.
2. Si possible, éliminez la source de chaleur.
pénétration dair chaud (ou froid).
4. Retirez líobstacle pour assurer une bonne circulation dair.
5. Réglez la température plus bas (ou plus haut).
6. (Consultez le concessionnaire
.)
Conseils pour économiser l’énergie
Obstruer les arrivées et les sorties dair de lappareil. Si elles sont bouchées,
lappareil ne fonctionnera pas de façon satisfaisante et il risque d’être endom­magé.
Laisser le soleil pénétrer directement dans la pièce. Utiliser des persiennes ou des rideaux. Si les murs et le plafond de la pièce sont chauds sous laction du soleil, il faudra plus longtemps pour refroidir la pièce.
Toujours maintenir le filtre à air propre. (Voir Entretien et nettoyage) Un filtre obstrué risque daffecter le fonctionnement de lunité.
Pour éviter que lair refroidi ne s’échappe, maintenir toutes les fenêtres, portes et autres ouvertures fermées.
REMARQUE
À éviter
Choses à faire
Si une panne de courant se produit lorsque lunité fonctionne
Si lalimentation de cette unité est temporairement arrêtée, lunité se remettra en marche, après rétablissement de lalimentation, avec les mêmes réglages quavant la panne de courant.
20
Page 21
Bezeichnungen der Teile
Luftauslass
Care and Cleaning
Pflege und Reinigung
1. Aus Sicherheitsgründen darauf achten, das Gerät vor dem Reinigen auszuschalten und
WARNUNG
es außerdem vom Netz zu trennen.
2. Kein Wasser auf die Inneneinheit schütten, um diese zu reinigen. Dadurch werden die inneren Bauteile beschädigt, und es besteht Stromschlaggefahr.
Wasserablass
Luftfilter
Lufteinlass- und -auslassseite
(Inneneinheit)
1. Verwenden Sie niemals Lösungsmittel oder starke Chemikalien, um die Inneneinheit zu
VORSICHT
2. Gewisse Metallkanten und die Kondensatorrippen sind scharf und können Verletzungen
3. Die innere Wärmeaustauscherschlange und andere Bauteile der Außeneinheit müssen
Luftfilter
Der Luftfilter sammelt Staub und andere Teilchen aus der Luft und sollte in regelmäßigen Abständen gereinigt werden, wie in der Tabelle unten angezeigt, bzw. wenn die Filteranzeige ( ) auf dem Dis-
play der (verdrahteten) Fernbedienung anzeigt, dass der Filter gereinigt werden sollt. Falls der Filter verstopft ist, nimmt der Wirkungsgrad des Klimageräts stark sb.
Typ Zeitraum
UMR Sechs Monate
Reinigen Sie die Lufteinlass- und -auslassseite der Inneneinheit mit einer Staubsauger­bürste bzw. wischen Sie sie mit einem sauberen weichen Tuch ab.
reinigen. Wischen Sie die Plastikteile nicht mehr sehr heißem Wasser ab.
verursachen, wenn sie nicht richtig gehandhabt werden; beim Reinigen dieser Teile besonders vorsichtig sein.
einmal im Jahr gereinigt werden. Wenden Sie sich dazu bitte an Ihren Fachhändler oder an eine Kundendienststelle.
ZUR BEACHTUNG
Die Häufigkeit der Luftfilterreinigung hängt von der Umgebung, in der der Luftfilter verwendet wird, ab.
<Reinigen des Luftfilters>
1. Nehmen Sie den Luftfilter aus dem Lufteinlassgitter.
2. Einen Staubsauger verwenden, um leichten Staub zu entfernen. Wenn klebriger Staub
am Filter anhaftet, diesen in lauwarmer Seifenlauge auswaschen, mit sauberem Wasser abspülen und trocknen lassen.
21
Page 22
Pflege: Wenn das Gerät über längere
Zeit nicht verwendet wurde
Pflege: Wenn das Gerät über längere
Zeit nicht verwendet werden soll
Überprüfen Sie Lufteinlässe und -auslässe der Innen- und der Außeneinheit auf Verstopfung; ist eine Verstopfung vorhanden, entfernen Sie sie.
Lassen Sie das Getriebe einen halben Tag lang laufen, um das Innere des Geräts zu trocknen.
Schalten Sie die Stromversorgung des Geräts aus; schalten Sie dann auch den Trennschalter aus.
Reinigen Sie den Luftfilter und setzen Sie ihn dann erneut an seiner Aus­gangsposition ein.
Die Innenbauteile der Außeneinheit müssen regelmäßig überprüft und gere­inigt werden. Lassen Sie diese Arbeiten von Ihrem Fachhändler durchführen.
1. Gewisse Metallkanten und die Kondensatorrippen sind scharf und können Verletzungen verursachen, wenn Sie nicht richtig gehandhabt werden. Seien Sie daher beim Reinigen dieser Teile besonders vorsichtig.
2. Überprüfen Sie die Außeneinheit regelmäßig, um zu sehen, ob Luftauslass oder Luftein­lass mit Staub oder Ruß verstopft sind.
3. Die innere Wärmeaustauscherschlange und andere Bauteile der Außeneinheit müssen ebenfalls regelmäßig gereinigt werden. Wenden Sie sich dazu bitte an Ihren Fachhändler oder an eine Kundendienststelle.
VORSICHT
1. 2.
22
Page 23
Fehlersuche
Wenn Ihr Klimagerät nicht richtig funktioniert, zuerst die folgenden Punkte überprüfen, bevor ein Kundendiensttechniker ange­fordert wird. Läßt sich die Störung nicht beheben, so wenden Sie sich bitte an Ihren Fachhändler oder an eine Kundendienst­stelle.
Störung Mögliche Ursache Abhilfe
Das Klimagerät läuft überhaupt nicht.
1. Keine Stromzufuhr. 1.
2. Der Fehlerstromschutzschalter wurde ausgelöst.
3. Netzspannung ist zu niedrig. 3. Lassen Sie sich von Ihrem Elektriker
4. Die Betriebstaste ist ausgeschaltet. 4. Die Taste erneut drücken.
5. Fehlfunktion der verdrahtete Fernbedienung oder der Wärmepumpe. (
Das Überprüfungszeichen und die Buchstaben E, F , H, L, P zusammen mit Zahlen werden auf der LCD-Anzeige der verdrahtete Fernbedienung angezeigt.)
Kompressor läuft, kommt jedoch bald zum Stillstand.
Schlechte Kühl- oder Heizleistung 1. Luftfilter ist schmutzig oder
1. Ein Hindernis befindet sich vor der Kondensatorschlange.
zugesetzt.
2. Eine Wärmequelle oder viele Leute befinden sich im Raum.
3. Türen und/oder Fenster sind geöffnet.
4.
Ein Hindernis befindet sich in der Nähe von Lufteinlass oder Luftauslass.
5. Der Thermostat ist zu hoch zum Kühlen eingestellt (bzw. zu niedrig zum Heizen).
6. (Abtausystem funktioniert nicht.) 6. (Lassen Sie sich von Ihrem
Drücken Sie nach einem Stromausfall die Betriebstaste (ON/OFF) auf der verdrahteten Fernbedienung.
2. Wenden Sie sich an eine Kundendienststelle.
oder Fachhändler beraten.
5. Lassen Sie sich von Ihrem Fachhändler beraten.
1. Hindernis entfernen.
1. Luftfilter reinigen, um den Luftstrom zu verbessern.
2. Die Wärmequelle möglichst abschalten.
3. Diese schlieen, damit keine Wärme (bzw. Kälte) von auflen eindringt.
4. Hindernis entfernen, um einen unbehinderten Luftstrom zu gewährleisten.
5. Temperatur niedriger (bzw. höher) einstellen.
Fac
hhändler beraten.)
Nützliche Hinweise für Energieeinsparung
Zu vermeiden
ZUR BEACHTUNG
Bei einem Stromausfall während des Betriebs des Geräts
Wird die Stromversorgung dieses Geräts vorübergehend unterbrochen, setzt das Gerät den Betrieb nach erneuter Stromversorgung automatisch mit denselben Einstellungen wie vor der Unterbrechung der Stromversorgung fort.
Blockieren Sie den Lufteinlass und -auslass des Gerätes nicht. Falls der Ein- oder
Auslass blockiert wird, funktioniert das Gerät nicht richtig und kann sogar beschädigt werden.
Setzen Sie den Raum nicht direkter Sonnenbestrahlung aus. Markisen, Jalousien oder Vorhänge verwenden. Wenn die Wände und Decke des Raumes Strahlungswärme von der Sonne aufnehmen, dauert es länger, den Raum zu kühlen.
Ja
Den Luftfilter stets sauber halten. (Siehe den Abschnitt Pflege und Reinigung.) Ein ver­stopfter Filter beeinträchtigt die Leistung des Gerätes.
Um zu verhindern, dass klimatisierte Luft entweicht, Fenster, Türen und andere Öffnungen außer für Lüftungszwecke geschlossen halten.
23
Page 24
Nome delle parti (Unità interna)
1. 2.
Uscita d’aria
Scarico dell’acqua
Cura e manutenzione
1. Per motivi di sicurezza, accertare che il condizionatore daria sia spento e che la spina
AVVERTIMENTO
del cavo di alimentazione sia staccata dalla presa di corrente prima di procedere con le operazioni di pulizia.
2. Non versare acqua sullunità interna per pulirla. Ciò può danneggiare i componenti interni e causare il pericolo di scosse.
Filtro aria
Lato presa daria e uscita
daria (unità interna)
1. Per pulire lunità interna, non si devono usare solventi o sostanze chimiche aggressive.
PRECAUZIONE
2. Alcuni bordi metallici e le alette sono taglienti e possono causare ferite se maneggiati in
3. La serpentina interna e gli altri componenti dellunità esterna devono essere puliti una
Filtro dellaria
Il filtro dellaria raccoglie le particelle di polvere e sporco dallaria e dovrebbe essere pulito a intervalli regolari, come indicato nella tabella seguente, oppure quando lindicazione del filtro ( ) sul display
del telecomando (tipo cablato) non segnala che occorre pulire il filtro. Se il filtro si ostruisce, leffi­cienza del condizionatore daria ne risulta notevolmente compromessa.
Tipo Periodo
UMR Sei mesi
Pulire il lato della presa daria e delluscita daria dellunità interna con una spazzola aspi­rapolvere o con un panno pulito e morbido.
Non pulire i componenti in plastica con acqua molto calda.
modo incorretto. Prestare perciò la dovuta attenzione nel pulire tali parti.
volta allanno. Rivolgersi al proprio rivenditore o centro di assistenza.
NOTA
La frequenza alla quale occorre pulire il filtro dipende dallambiente in cui viene utilizzata lunità.
<Pulizia del filtro>
1. Rimuovere il filtro dellaria dalla griglia della presa daria.
2. Rimuovere la polvere leggera servendosi di un aspirapolvere. Se la polvere resta attaccata al fil-
tro, lavarlo con acqua saponata tiepida, sciacquarlo con acqua pulita ed asciugarlo.
24
Page 25
Cura: dopo un periodo di
inattività prolungato
Cura: prima di periodo di
inattività prolungato
Controllare le prese daria e le uscite daria delle unità interna ed esterna, verificando che non siano ostruite; eliminare eventuali ostruzioni.
Azionare la ventola per mezza giornata per far asciugare linterno.
Scollegare lalimentazione elettrica e disinserire linterruttore automatico.
Pulire il filtro dellaria e rimetterlo nella sua posizione originale.
I componenti interni dellunità esterna vanno controllati e puliti periodicamente. A questo
scopo rivolgersi al proprio rivenditore locale.
1. Alcuni bordi metallici e le alette del condensatore sono taglienti e possono causare ferite se maneggiati in modo incorretto; occorre pertanto prestare particolare attenzione nel pulire tali componenti.
2. Controllare periodicamente lunità esterna, accertando che luscita daria e la presa daria non siano ostruite da sporco o fuliggine.
3. Anche la bobina interna e altri componenti dellunità esterna richiedono una pulizia peri­odica. Rivolgersi al proprio rivenditore o centro di assistenza.
PRECAUZIONE
25
Page 26
Prima di chiamare il tecnico
Se il condizionatore daria non funziona correttamente, prima di chiamare il tecnico per la riparazione controllare quanto segue. Se ciò non consente di eliminare il problema, rivolgersi al proprio rivenditore o centro di assistenza.
Problema Causa probabile Rimedio
Il condizionatore daria non funziona.
Il compressore funziona, ma si arresta subito.
Le prestazioni di raffreddamento (o di riscaldamento) sono scarse.
1. Si è verificata una mancanza di corrente. 1.
2. Il salvavita è scattato. 2. Rivolgersi al centro di assistenza.
3. La tensione di rete è insufficiente. 3. Rivolgersi ad un elettricista o al
4. Il pulsante di accensione/spegnimento è spento.
5. Il telecomando cablato o la pompa di calore non funziona correttamente. (Sullo schermo LCD del telecomando cablato vengono visualizzati il segno di ispezione e le lettere E, F, H, L, P, in combinazione con dei numeri).
1. Presenza di unostruzione davanti alla serpentina del condensatore.
1. Il filtro dellíaria è sporco o intasato. 1. Pulire il filtro dellaria per
2. Nella stanza ci sono una fonte di calore o molte persone.
3. Ci sono porte o finestre aperte. 3. Chiuderle per mantenere il caldo
4. C’è un ostacolo vicino alla presa daria o all’uscita dell’aria.
5. Il termostato è impostato ad un valore troppo alto per il raffreddamento (o troppo basso per il riscaldamento).
6. (Il sistema di sbrinamento non funziona). 6. (Rivolgersi al proprio rivenditore
Dopo una mancanza di corrente, premere il pulsante di accensione/spegnimento (ON/ OFF) del telecomando cablato.
proprio rivenditore.
4. Premere nuovamente il pulsante.
5. Rivolgersi al proprio rivenditore.
1. Rimuovere lostruzione.
migliorare il getto dell’aria.
2. Se possibile, eliminate la fonte di calore.
(o il freddo) allesterno.
4. Rimuoverlo in modo da assicurare un buon getto daria.
5. Impostare la temperatura a un livello più basso (o più alto).
.)
Suggerimenti per risparmiare energia
Non ostruire la presa d’aria e luscita daria dellunità. In caso di ostruzione,
lunità non funziona correttamente e può subire dei danni.
Non lasciar entrare la luce solare diretta nella stanza. A tale scopo utilizzare parasole, tende o persiane. Se le pareti e il soffitto vengono riscaldati dal sole, il raffreddamento della stanza richiede più tempo.
Mantenete sempre pulito il filtro dellaria (fare riferimento a Cura e manutenzione). Un filtro ostruito compromette il rendimento dellunità.
Per evitare fughe daria condizionata, tenete chiuse finestre, porte ed altre aperture.
NOTA
Da evitare
Cose da fare
Mancanza di corrente durante il funzionamento dellunità
In caso di una temporanea mancanza di corrente, lunità riprende automaticamente a funzionare, al ripristino della corrente, con le stesse impostazioni che aveva prima dellinterruzione.
26
Page 27
Nomenclatura das peças (unidade interior)
Saída de ar
Drenagem de água
Cuidados e limpeza
1. Por motivos de segurança desligue o aparelho de ar condicionado e desligue-o também
ADVERTÊNCIA
da rede antes de proceder à sua limpeza.
2. Não verta água sobre a unidade interior para a limpar. Poderá danificar os componentes internos e causar descargas eléctricas.
Filtro de ar
Lado de entrada e saída de ar
(unidade interior)
1. Nunca utilize solventes ou produtos químicos fortes para limpar a unidade interior. Não
PRECAUÇÃO
2. Algumas bordas metálicas e as pás do condensador são pontiagudas e podem causar
3. A serpentina interna e outros componentes da unidade exterior devem ser limpos todos
Filtro de ar
O filtro de ar recolhe a poeira e outras partículas do ar. Deve ser limpo em intervalos regulares como indicado na tabela abaixo ou quando a indicação de filtro ( ) aparece no visor da unidade de con­trolo remoto (com fios) indicando que o filtro deve ser limpo. Se o filtro ficar bloqueado, a eficiência do ar condicionado diminui bastante.
Tipo Período
UMR Seis meses
Limpe o lado de entrada e saída de ar da unidade interior com um aspirador ou com um pano macio e limpo.
limpe as peças plásticas com água muito quente.
ferimentos se não forem manuseadas com cuidado; tenha especial cuidado ao limpar estas partes.
os anos. Contacte o seu concessionário ou centro de reparações.
NOTA
A frequência de limpeza do filtro depende do ambiente de utilização da unidade.
<Como limpar o filtro>
1. Remova o filtro de ar da grelha de entrada de ar.
2. Utilize um aspirador para retirar poeira ligeira. Se houver poeira peganhosa no filtro, lave o filtro
com água morna com sabão, passe-o por água limpa e seque-o.
27
Page 28
Atenção: após um período de
inactividade prolongado
Atenção: antes de um período de
inactividade prolongado
Verifique se as entradas e saídas de ar da unidade exterior estão bloqueadas. Se estiverem bloqueadas, limpe-as.
Utilize o ventilador durante meio dia para secar o interior da unidade.
Desligue a unidade da corrente eléctrica e do disjuntor.
Limpe o filtro de ar e volte a colocá-lo na posição original.
Os componentes internos da unidade exterior devem ser verificados e limpos periodicamente. Contacte o revendedor local para efectuar esta operação.
1. Algumas bordas metálicas e as pás do condensador são pontiagudas e podem causar ferimentos se não forem manuseadas com cuidado; tenha especial cuidado ao limpar estas peças.
2. Inspeccione periodicamente a unidade exterior para verificar se a entrada ou a saída de ar estão bloqueadas com sujidade ou fuligem.
3. A serpentina interna e outros componentes da unidade exterior também devem ser limpos periodicamente. Contacte o seu concessionário ou centro de reparações.
PRECAUÇÃO
1. 2.
28
Page 29
Resolução de problemas
Se o seu aparelho de ar condicionado não funciona correctamente, verifique primeiro os seguintes pontos antes de solicitar assistência. Se não conseguir solucionar o problema, contacte o seu concessionário ou o serviço de assistência.
Avaria Causa possível Solução
O aparelho de ar condicionado não funciona de maneira nenhuma.
O compressor começa a funcionar mas pára pouco depois.
Rendimento de arrefecimento (ou aquecimento) deficiente.
1. Falha de alimentação. 1.
Após uma falha de corrente eléctrica, pressione o bot operaç
ão ON/OFF na unidade
ão de
de controlo remoto com fios.
2. O disjuntor de fugas foi activado. 2. Contacte o serviço de assistência.
3. Tensão de rede demasiado baixa. 3. Consulte um electricista ou o seu
4. O botão de operação está desactivado.
5. A unidade de controlo remoto com fios ou a bomba de calor não está a funcionar correctamente. (A marca de inspecção e as letras E, F, H, L, P associadas a n˙meros aparecem no LCD da unidade de controlo remoto com fios.)
1. Obstrução em frente da serpentina do compressor.
1. Filtro de ar sujo ou obstr uído. 1. Limpe o filtro de ar para melhorar a
2. Fonte de calor ou demasiadas pessoas na habitação.
3. Portas e/ou janelas abertas. 3. Feche-as para evitar a entrada de
4. Obstáculos perto da entrada ou saída de ar.
5. O termóstato est·á ajustado muito alto para arrefecimento (ou muito baixo para aquecimento).
6. (O sistema de descongelação não funciona.)
concessionário.
4. Pressione novamente o botão.
5. Consulte o seu concessionário.
1. Retire a obstrução.
circulação do ar.
2. Elimine a fonte de calor se for possível.
calor (ou frio).
4. Retire os obstáculos para assegurar uma boa circulação de ar.
5. Coloque a temperatura mais baixa (ou mais alta).
6. (Consulte o seu concessionário
.)
Sugestões para poupar energia
Bloquear a entrada e saída de ar do aparelho. Se estiverem obstruídas, o aparelho
não funcionará adequadamente e poderá ficar danificado.
SDeixar a luz solar incidir directamente na sala. Use cortinas, venezianas, etc. Se as paredes e o tecto da habitação forem aquecidos pelo sol levará mais tempo para arrefe­cer a habitação.
Procure manter o filtro de ar sempre limpo. (Consulte Cuidados e limpeza.) Um filtro obstruído prejudica o rendimento do aparelho.
Para evitar a saída do ar condicionado, mantenha janelas, portas e outras aberturas fechadas.
NOTA
Evite
Faça
Se ocorrer uma falha de energia com a unidade a funcionar
Se a corrente eléctrica for cortada temporariamente, a unidade retoma a operação automaticamente após a reposição da corrente eléctrica utilizando os mesmos ajustes programados.
29
Page 30
UMR
Air outlet
Water drain
Air filter
30
Page 31
1. 2.
31
Page 32
32
Page 33
Nombres de las partes (unidad interior)
1. 2.
Salida de aire
Drenaje de agua
Cuidados y limpieza
1. Por motivos de seguridad, asegúrese de apagar el acondicionador de aire, y desconec-
ADVERTENCIA
tarlo también de la red eléctrica antes de realizar su limpieza.
2. No vierta agua sobre la unidad interior para limpiarla. El agua podría estropear los com­ponentes internos y producir una descarga eléctrica.
Filtro de aire
Lados de entrada y salida de
aire (Unidad interior)
1. No utilice nunca disolventes o productos químicos ásperos cuando limpie la unidad interi-
PRECAUCIÓN
or. No limpie las partes de plástico con agua muy caliente.
2. Algunos bordes metálicos y las aletas, al ser puntiagudos, pueden causar heridas si no se manejan con cuidado. Tenga mucho cuidado al limpiar estas piezas.
3. El serpentín interno y otros componentes de la unidad exterior deberán limpiarse todos los años. Póngase en contacto con su concesionario o centro de reparaciones.
Filtro de aire
El filtro de aire recoge polvo y otras partículas del aire y deberá ser limpiado a intervalos regulares como se indica en la tabla de abajo o cuando la indicación de filtro ( ) del visualizador de la
unidad del mando a distancia (tipo alámbrica) muestre que el filtro necesita ser limpiado. Si se blo­quea el filtro, la eficacia del acondicionador de aire disminuirá enormemente.
Tipo Periodo
UMR Seis meses
Limpie los lados de entrada y salida de aire de la unidad interior con el cepillo de una aspi­radora, o límpielos con un paño limpio y suave.
NOTA
La frecuencia con que deberá ser limpiado el filtro de aire dependerá del entorno en el que se utilice la unidad.
<Cómo limpiar el filtro>
1. Extraiga el filtro de aire de la rejilla de entrada de aire.
2. Utilice una aspiradora para quitar el polvo ligero. Si en el filtro hay polvo pegado, lave el filtro con
agua enjabonada templada, enjuáguelo en agua limpia y séquelo.
33
Page 34
Cuidado: después de un
periodo de inactividad
prolongado
Cuidado: antes de un
periodo de inactividad
prolongado
Compruebe las entradas y salidas de aire de la unidad exterior para ver si están obstruidas; si hay una obstrucción, quítela.
Haga funcionar el ventilador durante medio día para secar el interior.
Desconecte el suministro eléctrico y desactive también el disyuntor.
Limpie el filtro de aire y vuelva a ponerlo en su posición original.
Los componentes internos de la unidad exterior deberán ser comprobados y limpiados per- iódicamente. Póngase en contacto con su distribuidor local para este servicio.
1. Algunos bordes metálicos y las aletas del condensador son agudos y podrán ocasionar heridas si se manejan incorrectamente; cuando limpie estas partes deberá tener cuidado especial.
2. Compruebe periódicamente la unidad exterior para ver si la salida de aire o enterada de aire está obstruida con suciedad u hollín.
3. El serpentín interno y otros componentes de la unidad exterior deberán también ser limpiados periódicamente. Póngase en contacto con su concesionario o centro de reparaciones.
PRECAUCIÓN
34
Page 35
Localización de averías
Si su acondicionador de aire no funciona correctamente, compruebe primero la lista de abajo antes de llamar al servicio de reparaciones. Si no puede solucionar el problema, póngase en contacto con su concesionario o centro de reparaciones.
Avería Causa posible Remedio
El acondicionador de aire no funciona en absoluto.
El compresor se pone en funcionamiento pero se para pronto.
Mal enfriamiento (o calefacción). 1. Filtro de aire sucio u obstruido. 1. Limpie el filtro de aire para mejorar
1. Corte de alimentación eléctrica. 1.
Después de una interrupción del suministro eléctrico, pulse el bot
ón de operación ON/OFF en
la unidad de mando a distancia alámbrica.
2. Ha saltado el ruptor de fugas. 2. Póngase en contacto con el centro
3. La tensión de la línea es demasiado baja.
4. El botón de operación está desactivado.
5. La unidad de mando a distancia alámbrica o la bomba de calor está funcionando mal. (En el LCD de la unidad de mando a distancia alámbrica aparece la marca de inspección y las letras E, F, H, L, P en combinación con números.)
1. Obstrucción delante del serpentín del condensador.
2. Fuente de calor o muchas personas en la sala.
3. Puertas y/o ventanas abiertas. 3. Ciérrelas para que no entre el calor
4. Obstáculos cerca de la entrada o salida de aire.
5. El termostato está ajustado demasiado alto para enfriamiento (o demasiado bajo para calefacción).
6. (El sistema de descongelación no funciona.)
de reparaciones.
3. Póngase en contacto con un electricista o con su concesionario.
4. Pulse el botón otra vez.
5. Consulte a su distribuidor.
1. Retire la obstrucción.
la circulación del aire.
2. Elimine la fuente de calor si fuese posible.
(o el frío).
4. Quite los obstáculos para asegurar una buena circulación del aire.
5. Fije una temperatura m·s baja (o más alta).
6. (Consulte a su distribuidor
.)
Sugerencias para ahorrar energía
No bloquee la entrada y salida de aire de la unidad. Si cualquiera de ellas está
obstruida, la unidad no funcionará bien, y podrá dañarse.
No deje que entre luz solar directa en la habitación. Utilice parasoles, persianas o corti­nas. Si el sol calienta las paredes y el techo de la sala, se tardará más tiempo en enfri­arla.
Sí
Mantenga siempre limpio el filtro de aire. (Refer to Cuidados y limpieza.) Un filtro obstruido reducirá el rendimiento de la unidad..
Para evitar que escape el aire acondicionado, cierre las ventanas, las puertas y otras aberturas.
NOTA
Evite
Si ocurre un corte del suministro eléctrico mientras está funcionando la unidad
Si el suministro eléctrico de esta unidad se interrumpe temporalmente, la unidad reanudará automáticamente la operación una vez restablecido el suministro utilizando los mismos ajustes que los de antes de cortarse el suministro eléctrico.
35
Page 36
Loading...